Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹3.7 CrAdmitted-Finance 880 1 SC ROAD BATOR HOWRAH 711104 | HOWRAH | HOWRAH | WEST BENGAL | 711104 | ₹3.7 Cr | L1 | Admitted-Finance |
| 2 | L2₹3.1 CrAdmitted-Finance | ₹3.1 Cr | L2 | Admitted-Finance |
| 3 | L3₹4.0 CrAdmitted-Finance | ₹4.0 Cr | L3 | Admitted-Finance |
| 4 | L4₹3.5 CrAdmitted-Finance | ₹3.5 Cr | L4 | Admitted-Finance |
| 5 | L5₹4.2 CrAdmitted-Finance AT PO PS NEAR INDIAN OIL PETROL PUMP WARD NO 03 CHANDRASEKHARPUR BHUBANESWAR MC DIST KHURDA ODISHA | BHUBANESWAR | KHURDA | ODISHA | ₹4.2 Cr | L5 | Admitted-Finance |
| Sl No | Description | Qty | Unit | Textel Technologies Private Limited L5 | HINDUSTAN CONSTRUCTION CORPORATION L7 | M/S KAY BEE SALES & SERVICES L2 | SHUBH ENGINEERS L3 | National Construction L8 | EVOLUTION TECH and INFRA PVT LTD L10 | Lyra Engineering Services L4 | Discern Engineering Private Limited L1 | VKS PROJECTS L9 | DOUSE FIRE SYSTEMS PRIVATE LIMITED L6 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1.00PART Note to Bidders: All statutory approval related to this work from State authority/CFO/govt. body designated for the purpose shall be obtained by the contractor. No additional payment will be made for the same. | |||||||||||||
| 2.00 | PART-A: Fire fighting & Domestic pumps & associated piping (SoCS Building) | 1 | Nos | 2,80,94,303 ₹2.8 Cr | 2,64,33,550 ₹2.6 Cr | 2,06,61,445 ₹2.1 Cr | 2,71,42,070 ₹2.7 Cr | 2,37,16,050 ₹2.4 Cr | 2,15,80,050 ₹2.2 Cr | 2,59,48,865 ₹2.6 Cr | 2,67,78,907 ₹2.7 Cr | 2,72,11,630 ₹2.7 Cr | 3,58,73,166 ₹3.6 Cr |
| 3.00 | PART-B : Electrical Works (SoCS Building) | 1 | Nos | 45,24,422 ₹45.2 L | 38,67,700 ₹38.7 L | 30,84,350 ₹30.8 L | 26,41,250 ₹26.4 L | 21,94,000 ₹21.9 L | 35,62,350 ₹35.6 L | 19,41,400 ₹19.4 L | 17,55,805 ₹17.6 L | 30,74,227 ₹30.7 L | 9,68,573 ₹9.7 L |
| 4.00 | Part -C: FA System for SoCS & SoMS Buildings : | 1 | Nos | 61,47,632 ₹61.5 L | 60,42,000 ₹60.4 L | 48,07,725 ₹48.1 L | 62,74,990 ₹62.7 L | 66,25,000 ₹66.3 L | 70,67,250 ₹70.7 L | 36,22,000 ₹36.2 L | 52,29,151 ₹52.3 L | 63,12,867 ₹63.1 L | 69,92,333 ₹69.9 L |
| 5.00 | Part-D: PA System for SoCS & SoMS Buildings | 1 | Nos | 5,83,123 ₹5.8 L | 16,88,000 ₹16.9 L | 4,06,450 ₹4.1 L | 20,20,250 ₹20.2 L | 14,91,250 ₹14.9 L | 8,83,250 ₹8.8 L | 10,38,000 ₹10.4 L | 10,46,186 ₹10.5 L | 21,31,821 ₹21.3 L | 14,90,290 ₹14.9 L |
| 6.00 | Part E - Miscllaneous: | 1 | Nos | 29,84,540 ₹29.8 L | 39,05,500 ₹39.1 L | 22,08,600 ₹22.1 L | 22,35,900 ₹22.4 L | 42,44,500 ₹42.4 L | 54,09,750 ₹54.1 L | 23,83,400 ₹23.8 L | 21,42,732 ₹21.4 L | 47,56,105 ₹47.6 L | 35,78,525 ₹35.8 L |
Updated dates
Tender Value
₹4.5 Cr
EMD Value
₹9.0 L
Closing Date
6 Jan 2026, 5:00 pmClosed
Chief Engineer (ESG)
DCSEM, 3rd Floor, V.S. Bhavan, Anushaktinagar, Mumbai - 400094.
Supply, Installation, Testing and Commissioning of Firefighting, Fire Alarm and Public Address System for School of Computer and Mathematical Science Buildings at NISER, Bhubaneswar, Orissa.
2025_DCSEM_888058_1
DCSEM/CQD/QSC/NISER-FF /NIT/12/25-26 dtd 01.12.2025
Open Tender
Job Works
300 days
Bhubaneshwar, Orissa
Please refer Tender documents.
8 documents required · 8 mandatory
₹0
₹9.0 L
9 Mar 2026
2 Dec 2025
8 Jan 2026
2 Dec 2025
6 Jan 2026
2 Dec 2025
2 Dec 2025 - 15 Dec 2025
Tender Inviting Authority:
Name of Work: Sq.Mtr
NIT No: 3 C x 120 sq.mm Cu. stranded cable (on Wall/Trench/ Cable tray)
1) Bidders are requested to note that they should necessarily submit their financial bids in the format provided and no other format is acceptable. If the price bid has been given as a standard BoQ format with the tender document, then the same is to be downloaded and to be filled by all the bidders. Bidders are required to download the BoQ file, open it and complete the BLUE coloured (unprotected) cells with their respective financial quotes and other details (such as name of the bidder). No other cells should be changed. Once the details have been completed, the bidder should save it and submit it online, without changing the filename. If the BoQ file is found to be modified by the bidder, the bid will be rejected.
2) Bidders are advised to download this BOQ as it is and quote their offer/rates in the permitted column and upload the same in the commercial bid. Bidder shall not tamper/modify downloaded price bid template in any manner. In case if the same is found to be tempered/modified in any manner, tender will be completely rejected and EMD would be forefeited and tenderer is liable to be banned from doing business.
3) All the documents being submitted by the bidders would be encrypted using PKI encryption techniques to ensure the secrecy of the data. The data entered cannot be viewed by unauthorized persons until the time of bid opening. The confidentiality of the bids is maintained using the secured Socket Layer 128 bit encryption technology. Data storage encryption of sensitive fields is done. Any bid document that is uploaded to the server is subjected to symmetric encryption using a system generated symmetric key. Further this key is subjected to asymmetric encryption using buyers/bid opener’s public keys. Overall, the uploaded tender documents become readable only after the tender opening by the authorized bid openers.
Important Notes
I 1) The proposed work has to be carried out at School of Computer & Mathematical Science Buildings at NISER, Bhubaneswar, Orissa.
2) The tenderers are advised to visit the site to acquaint themselves regarding site conditions about the level of sub-soil water, drainage facility for dewatering, accessibility to the site etc., and quote the rates accordingly.
3) Vehicular movement shall abide by the regulations imposed by the concerned authorities. The contractor shall abide by the security rules & regulations of the Department. The approach roads should be kept clean & free from obstruction for smooth functioning.
4) The following security regulation shall be followed strictly while movement of labourers/workers/ contractor's personnel etc.
(i) The contractor shall issue I-Cards to his workers deployed on regular basis.
(ii) The supervisor of the contractor having photo pass can bring daily wage workers/ casual workers inside School of Computer & Mathematical Science Buildings at NISER, Bhubaneswar, Orissa for work. He should prepare list of such workers in duplicate. The original copy shall be handed over to the representative of the Engineer in Charge at the gate and endorsement obtained on the duplicate, on daily basis.
(iii) Contractor shall arrange for Police Verification Certificate (PVC) for permanent labour and supervisors on the work as required by Local Authorities.
(v) The daily wage workers/ casual workers employed by the contractor must wear florescence High-Visibility wear without fail during their presence inside School of Computer & Mathematical Science Buildings at NISER, Bhubaneswar, Orissa.
5) The contractor shall follow strictly the DAE safety rules .
6) The drawings issued for tender purpose are preliminary and indicative only. The working drawing shall be issued in phased manner at the time of execution. Nothing extra shall been entertained towards revision in drawings.
7) The contractor shall arrange water for construction purpose of his own.
8) Please refer pre bid query reply, if any.
9) Tenderers to quote rates inclusive of all taxes, duties, GST etc. as applicale.
3C x 120 Sq.mm Cu. conductor cable 3C x 4 Sq.mm Cu. conductor cable
Tender Inviting Authority:
Name of Work: Sq.Mtr
NIT No: 3 C x 120 sq.mm Cu. stranded cable (on Wall/Trench/ Cable tray)
PART-B : Electrical Works (SoCS Building)
300 mm (W) x 100 mm (D) x 2 mm (T)
M.V Panel:Supply, installation, testing & commissioning of Electrical switchboards, powder coated floor mounting,front operated front
access cubicle type, totally enclosed, with IP-42 protection with hinged and lockabale doors. It shall be fabricated from 2 mm thick CRCA sheets including interconnections, tinned copper crimping lugs, bonding to earth, suitable for use at 415 V, 3 phase 4 wire 50 Hertz system, and suitable for a fault level of 35 KA symmetrical at 415 V complete as per specifications, instructions & approval of EIC and as below : All switchboards shall have provision for entry of cables from the top/bottom as required. All live accessible parts shall be shrouded and all equipment shall be finger touch proof. The bus bars insulation shall be with heat shrinkable sleeves. SMC/DMC shrouds and busbar supports shall be used. Notes: 1) All G.A. & fabrication drawings shall be got approved from the E.I.C. Necessary touch up painting may be done at site, incase if required. The scope includes all tests as specified in department's specification, relevant I.S. and as required by E.I.C, shall have to be performed at factory & at installation site and shall be included in the quoted rate. 2) The equipment shall be designed to ensure complete safety during operation inspection, connection of cables etc. 3) Control wires shall be of 1.1 KV 1.5 sq.mm FRLS copper wires and neatly bunched separately and adequately supported so as to prevent sagging and strain on termination. 4) A minimum of 10% spare terminals shall be provided on each terminal block for future requirement. 5) All metallic parts of the equipment not carrying current shall be earthed with copper material 6) All concealed hinged doors and covers shall be provided with suitable flexible earthing connections. 7) The size of the earth bus chosen shall be to withstand full fault current of 35KA 8) Earth bus bar shall be supported at suitable intervals. 9) All the current transformers shall be resin cast type class-I only. 10) Name of fabricator, G.A. & detailed fabrication drawing and short circuit forces and temp rise calculation for panel shall be submitted for dept's approval. 11) Bimetallic washers shall be used for all aluminium to copper joints & it shall be of approved make & quality. 12) Indication lamps shall be heavy duty cluster type LED. 13) All Outgoing feeders shall have 'ON' indication lamps. 14) All neutrals shall be isolatable type. 15) Power cabling between motor and starter shall be measured separately. Control cabling between panel and tank shall be measured separtaely. However, any other control / power wiring / cabling, if required is in the scope of this item.
Select, Excess (+), Less (-) Less (-)
Tender Inviting Authority: Chief Engineer (ESG)
Earthing System: Supply, installation, testing & commissioning of earthing system & associated accessories, etc. complete all as per layout drawing & standard drawing CSG/EM/STD/12, specifications & as per the instructions of E.I.C. Note: 1) Measurements of resistance of each earth station & resistance of complete scheme of earthing layout must be measured recorded & got approved by E.I.C. 2) Jointing of the earth strip shall be with brass nuts bolts and also with solder joints. 3) Jointing of the earth wire shall be with solder joints with tinned cable sockets. Strip/wire fixed to wall/side of trench/ slab/column/beam/shaft with 5mm thick G.I spacers & GI saddles or on existing cable tray with saddles or in ground at 750 mm below including excavation in all types of soil with protective baked bricks, refilling & removal of excess earth within a radius of 500 m temporary reinstatement & back filling of trench, interconnections of earth strip/wire with brass nuts, bolts & washers and solder jointing, painting with two coats of black bituminous compound for earth wire/strip in ground & green enamel paint for earth wire/strip on surface, etc.
Name of the Bidder/ Bidding Firm / Company :
Sl. No. Item Description Item Code / Make Quantity Units Estimated Rate in Rs. P Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency BASIC RATE In Figures To be entered by the Bidder in Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT in Rs. P TOTAL AMOUNT With Taxes TOTAL AMOUNT In Words
1 Control Cable: Supply, installation, testing & commissioning of 1.1 KV grade multicore copper solid / stranded conductor of following sizes, PVC insulated, FRLS PVC outer sheathed armoured cable between various sensors and starter etc. on existing cable tray/surface on 5mm thick M.S. flat /GI spacer/angle/support fixed with coach screws/grouted in wall/anchor fasteners 2mm thick G.I. Fabricated saddle, all fixing accessories, etc complete including painting of M.S spacers/angles and saddles etc. providing brass cable number tag as per enclosed detailed specifications, drawings & as per instructions of the E-I-C .The scope also includes end connections at both ends with glands etc. as required.. Note: 1) End joint of cable is also included in the scope of work with all required acceseries.
2 PART-A: Fire fighting & Domestic pumps & associated piping (SoCS Building) 1 Nos Excess(+) Full Conversion INR
3 PART-B : Electrical Works (SoCS Building) 1 Nos Excess(+) Full Conversion INR
4 Part -C: FA System for SoCS & SoMS Buildings : 1 Nos Excess(+) Full Conversion INR
5 Part-D: PA System for SoCS & SoMS Buildings 1 Nos Excess(+) Full Conversion INR
6 Part E - Miscllaneous: 1 Nos Excess(+) Full Conversion INR
Total in Figures
Quoted Rate in Figures Select
Quoted Rate in Words
Select, Excess (+), Less (-) Less (-)
Tender Inviting Authority: Chief Engineer (ESG)
Earthing System: Supply, installation, testing & commissioning of earthing system & associated accessories, etc. complete all as per layout drawing & standard drawing CSG/EM/STD/12, specifications & as per the instructions of E.I.C. Note: 1) Measurements of resistance of each earth station & resistance of complete scheme of earthing layout must be measured recorded & got approved by E.I.C. 2) Jointing of the earth strip shall be with brass nuts bolts and also with solder joints. 3) Jointing of the earth wire shall be with solder joints with tinned cable sockets. Strip/wire fixed to wall/side of trench/ slab/column/beam/shaft with 5mm thick G.I spacers & GI saddles or on existing cable tray with saddles or in ground at 750 mm below including excavation in all types of soil with protective baked bricks, refilling & removal of excess earth within a radius of 500 m temporary reinstatement & back filling of trench, interconnections of earth strip/wire with brass nuts, bolts & washers and solder jointing, painting with two coats of black bituminous compound for earth wire/strip in ground & green enamel paint for earth wire/strip on surface, etc.
Name of the Bidder/ Bidding Firm / Company :
EXCAVATION OF EARTH: Earth work excavation over areas for foundation of tank, trenches, pits etc. in all soils, soft and hard rocks, upto depth 1.5 m including shoring and dewatering if necessary, dressing the sides, trimming and preparing the bed for foundation and refilling all round the foundation / tank (after testing) with selected excavated earth in layers not exceeding 250 mm thick, watering, consolidation and disposing off the surplus earth within a distance of 50 m etc, complete as per specifications & drawings, including spreading, leveling the surplus disposed earth in required grade / profile as directed by EIC.
Sl. No. Item Description Item Code / Make Quantity Units Estimated Rate in Rs. P Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency RATE In Figures To be entered by the Bidder in Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT in Rs. P TOTAL AMOUNT TOTAL AMOUNT In Words
1 MOTOR DRIVEN FIRE FIGHTING PUMPS: Design, supply, installation, testing & commissioning of Motor driven Centrifugal Horizontal split case Pump Set for fire fighting system with a flow capacity of 2400 LPM and total head of 88 m, with CI casing, standard fittings, bronze impeller, mechanical seal, along with all accessories, suitably rated TEFC squirrel cage energy efficient induction motor (IE - 3 as per IS 12615 : 2011) as electrical drive with synchronous speed not exceeding 1500 rpm, Class-F insulation, IP-55 rated to operate at 415 V+/- 10% , 50 Hz+/- 3% , 3 phase AC Supply, including supply of MS common base plate frame and installing pump and motor on it along with foundation bolts, coupling guard,anti vibration pads and other accessories etc complete as per specifications, drawings and instructions of E-I-C. The pump offered shall be of fire fighting duty and its characteristics shall be as per TAC and also as per IS 12469-1988 or its latest edition. Cost of all the items, accessories, tools and tackles, packing etc required to put pumping system into service. 2 sets Excess(+) Full Conversion INR
2 Terrace Fire Pump: Supply, installation, testing & commissioning of Motor driven Centrifugal Horizontal Pump Set for fire fighting system of following capacity & head along with all accessories with CI casing, Stainless Steel shaft, standard fittings, bronze impeller, suitable coupling to the electrical driven TEFC,squirrel cage induction motor suitably rated, with synchronous speed not exceeding 3000 rpm, Class-F insulation, IP-55, rated to operate at 415 V+/-10%, 50 Hz +/- 5%, 3 phase AC supply, including supply of of MS common base plate frame and installing pump set on it , foundation bolts, coupling guard, anti vibration pads and other accessories & connecting and jointing with suction & delivery piping with necessary reducers, enlargers, flanges etc, complete as per specifications, drawings and as instructed by Engineer-In-Charge. Providing weather proof hood fabricated from 5 mm. thick UV stabilised FRP above pump & motor to protect it from weather as instructed by Engineer-In-Charge.
2.1 i) 450 LPM at 40 m head NB: 1) The cost of all the items mentioned above are to be included under this item and no extra payment shall be made. 2) The sketch/ drg of weather proof cover is to be got approved by E-I-C before fabrication of the same. 1 set Excess(+) Full Conversion INR
3 JOCKEY PUMP: Design, Supply, installation, testing & commissioning of Motor driven Centrifugal horizontal split case / End suction Jockey Pump Set for fire fighting system with a flow capacity of 180 lpm and total head of 88 m, with CI casing, standard fittings, bronze impeller, along with all accessories, suitably rated squirrel cage induction motor energy efficient (IE - 3 as per IS 12615 : 2011) as electrical drive with synchronous speed not exceeding 3000 rpm, Class-F insulation, IP-55 rated to operate at 415 V+/- 10% , 50 Hz+/- 3% , 3 phase AC supply, including supply of MS common base plate frame and installing pump and motor on it, alongwith foundation bolts, coupling guard,anti vibration pads and other accessories etc complete as per specifications, drawings and instructions of E-I-C.The pump offered shall be of fire fighting duty and its characteristics shall be as per TAC and also as per IS 12469-1988 or its latest edition. Cost of all the items, accessories, tools and tackles, packing etc required to put pumping system into service shall also be included in rates quoted by the bidders. 2 set Excess(+) Full Conversion INR
4 DIESEL ENGINE DRIVEN MAIN FF PUMPS: Design, supply, installation, testing & of commissioning of Diesel Engine driven Centrifugal horizontal split case Pump Set for fire fighting system with a flow capacity of 2400 LPM and total head of 88 m, with CI casing, standard fittings, bronze impeller, mechanical seal, along with all accessories, suitably rated water cooled Deisel Engine with radiator and fan, having aprox. speed of 1500 rpm, along with starting batteries, including supply of MS common base plate frame and installing pump and engine on it along with foundation bolts, coupling guard, anti vibration pads, standard diesel tank fabricated out of 3 mm thick MS CRCA sheets of capacity 990 litres with proper MS frame supports and heavy class GI fuel pipe (approximately 30 m) laid upto engine, exhaust piping and cladding including supply of bends based on site requirement. Supply of the required first charge of lubricants, fuel, distilled water for battery and other consumables related to diesel engine shall be included. The pump offered shall be of fire fighting duty and its characteristics shall be as per TAC and also as per IS 12469-1988 or its latest edition. The entire job shall be carried out as per relevant standards, specifications and drawings, site conditions and as per instructions of E-I-C. Cost of all the items accessories, tools and tackles, packings etc requiredto put pumping system into service shall also be included in rates quoted by the bidders. 1 set Excess(+) Full Conversion INR
5 SUBMERSIBLE DEWATERING PUMP : Design, supply, installation, testing & commissioning of Submersible dewatering Pump Set to give a discharge of 50 Lpm and total head of 9.5 m & 3 phase, 415 v, AC, continuous rated squirrel cage induction motor with class-B insulation, with 40 mm dia outlet GM gate valve, with necessary fittings, flanges, jointing, supports & painting etc. complete in all respects and as directed by EIC. 1 set Excess(+) Full Conversion INR
6 AIR CUSHION TANK: Design, Supply and erection of air cushion tank (material IS 2062/2002) with air release valve, drain valve, gate valve, provision for pressure switches, pressure guages etc. inside the pump house including making inlet and outlet connection with MS pipe of required length from discharge header to air cushion tank, fixing properly and securing the same to the base etc. complete in all respect having painting including two coats of approved paint over a coat of primer. The tank shall be fabricated out of 8 mm thick M.S. sheet, shall be of cylindrical shape with 300 mm dia. and 1.5 m height. The tank shall be installed on suitable vertical legs. The legs shall be provided with M.S. plate of size 75 mm x 75 mm x 5 mm at the bottom. The legs shall be grouted in cement concrete foundation. Flange connection shall be provided for connection with discharge header. The fabrication drawings of the tank shall be submitted to EIC and got approved by the department before fabrication. 2 set Excess(+) Full Conversion INR
7 M.S. Seamless Pipes: Supply, Installation of MS seamless pipe of following nominal sizes and wall thickness and conforming to ASTM A-106 Grade-B and testing at site with clean & potable water a pressure of 1.5 times of operating pressure for 120 minute duration and rectification of leaky joints after laying at site with all necessary specials/fittings, Mechanical/ flanged/ welded joints, Flanged/welded joints with various GI Pipes, elbows, Tees, Bends, Reducers, Collars, Nut & Bolts, jointing including painting with two coats of anti corrosion post office red paints over two coats of red oxide primer (for laying above ground) and including wrapping with 4 mm thick PYPKOTE insulation with adhesive coat in an approved manner as per the specifications and to correct alignment and levels including all hardware in including the testing the specials/ joints hydraulically for the pressure & duration and rectification of leaky joints as specified all as per drawings, specifications and instruction of E.I.C. Cost of all the items, accessories, fittings, tools and tackles, packing etc required to put pumping system into service shall also be included in rates quoted by bidders.
7.1 200 mm dia. (Above Ground) 30 m Excess(+) Full Conversion INR
7.2 150 mm dia. (Above Ground) 100 m Excess(+) Full Conversion INR
7.3 150 mm dia.(Below Ground) 2000 m Excess(+) Full Conversion INR
7.4 80 mm dia.(Above Ground) 15 m Excess(+) Full Conversion INR
7.5 80 mm dia.(Below Ground) 20 m Excess(+) Full Conversion INR
7.6 65 mm dia.(Above Ground) 40 m Excess(+) Full Conversion INR
8 G.I. Pipes: Supply, installation, testing and commissioning of Heavy Duty, "C" Class GI pipes of following sizes confirming to IS-1239 along with all necessary fittings, flanges, jointing (screwed / welded / flanged etc.) and required supports with two coats of paint as per color code of the piping systems over two coats of red oxide primer, including all hardware, complete in all respects as per specifications and as instructed by Engineer-In-Charge. NB : 1) The pipe line shall be measured along the centre line. NB: 2) Any Core cut if required for laying the pipes shall be included in above cost, no extra payment will be made for the same.
8.1 150 mm dia. 80 m Excess(+) Full Conversion INR
8.2 100 mm dia. 200 m Excess(+) Full Conversion INR
8.3 80 mm dia. 180 m Excess(+) Full Conversion INR
8.4 65 mm dia. 280 m Excess(+) Full Conversion INR
8.5 50 mm dia. 1200 m Excess(+) Full Conversion INR
8.6 40 mm dia. 300 m Excess(+) Full Conversion INR
8.7 32 mm dia. 400 m Excess(+) Full Conversion INR
8.8 25 mm dia. 200 m Excess(+) Full Conversion INR
9 CI Gate Valves: Supply, installation, testing and commissioning of double flanged CI/Cast Steel Gate Valve of required sizes of ratings PN 1.6 with non rising stem conforming to IS-14846 with all necessary fittings like flanges, neoprene gaskets, nut bolts, hardware, flanges, neoprene gaskets, nut bolts, hardware, flange joint etc. as shown in the drawings and as per specifications and as instructed by Engineer-In-Charge.
9.1 200 mm dia. 1 Gun Metal Ball Valve: Supply, installation, testing and commissioning of heavy pattern screw down Gun Metal Gate Valves of following sizes confirming to relevent IS with hand wheels at top including testing for a pressure of 16 kg/sq.cm. for two hours, all as per specification, drawings and as instructed by Engineer-In-Charge as per Technical Specification. Excess(+) Full Conversion INR
9.2 150 mm dia. 17 Gun Metal Ball Valve: Supply, installation, testing and commissioning of heavy pattern screw down Gun Metal Gate Valves of following sizes confirming to relevent IS with hand wheels at top including testing for a pressure of 16 kg/sq.cm. for two hours, all as per specification, drawings and as instructed by Engineer-In-Charge as per Technical Specification. Excess(+) Full Conversion INR
9.3 100 mm dia. 23 Gun Metal Ball Valve: Supply, installation, testing and commissioning of heavy pattern screw down Gun Metal Gate Valves of following sizes confirming to relevent IS with hand wheels at top including testing for a pressure of 16 kg/sq.cm. for two hours, all as per specification, drawings and as instructed by Engineer-In-Charge as per Technical Specification. Excess(+) Full Conversion INR
9.4 80 mm dia. 12 Gun Metal Ball Valve: Supply, installation, testing and commissioning of heavy pattern screw down Gun Metal Gate Valves of following sizes confirming to relevent IS with hand wheels at top including testing for a pressure of 16 kg/sq.cm. for two hours, all as per specification, drawings and as instructed by Engineer-In-Charge as per Technical Specification. Excess(+) Full Conversion INR
9.5 65 mm dia. 4 Gun Metal Ball Valve: Supply, installation, testing and commissioning of heavy pattern screw down Gun Metal Gate Valves of following sizes confirming to relevent IS with hand wheels at top including testing for a pressure of 16 kg/sq.cm. for two hours, all as per specification, drawings and as instructed by Engineer-In-Charge as per Technical Specification. Excess(+) Full Conversion INR
10 Gun Metal Gate Valve: Supply, installation, testing and commissioning of heavy pattern screw down Gun Metal Gate Valves of following sizes confirming to Class 2 of IS : 778 with hand wheels at top
10.1 50 mm dia. 19 Gun Metal Ball Valve: Supply, installation, testing and commissioning of heavy pattern screw down Gun Metal Gate Valves of following sizes confirming to relevent IS with hand wheels at top including testing for a pressure of 16 kg/sq.cm. for two hours, all as per specification, drawings and as instructed by Engineer-In-Charge as per Technical Specification. Excess(+) Full Conversion INR
11 including testing for a pressure of 16 kg/sq.cm. for two hours, all as per specification, drawings and as instructed by Engineer-In-Charge.
11.1 200 mm dia. 1 Gun Metal Ball Valve: Supply, installation, testing and commissioning of heavy pattern screw down Gun Metal Gate Valves of following sizes confirming to relevent IS with hand wheels at top including testing for a pressure of 16 kg/sq.cm. for two hours, all as per specification, drawings and as instructed by Engineer-In-Charge as per Technical Specification. Excess(+) Full Conversion INR
11.2 150 mm dia. 9 Gun Metal Ball Valve: Supply, installation, testing and commissioning of heavy pattern screw down Gun Metal Gate Valves of following sizes confirming to relevent IS with hand wheels at top including testing for a pressure of 16 kg/sq.cm. for two hours, all as per specification, drawings and as instructed by Engineer-In-Charge as per Technical Specification. Excess(+) Full Conversion INR
11.3 100 mm dia. 4 Gun Metal Ball Valve: Supply, installation, testing and commissioning of heavy pattern screw down Gun Metal Gate Valves of following sizes confirming to relevent IS with hand wheels at top including testing for a pressure of 16 kg/sq.cm. for two hours, all as per specification, drawings and as instructed by Engineer-In-Charge as per Technical Specification. Excess(+) Full Conversion INR
11.4 65 mm dia. 2 Gun Metal Ball Valve: Supply, installation, testing and commissioning of heavy pattern screw down Gun Metal Gate Valves of following sizes confirming to relevent IS with hand wheels at top including testing for a pressure of 16 kg/sq.cm. for two hours, all as per specification, drawings and as instructed by Engineer-In-Charge as per Technical Specification. Excess(+) Full Conversion INR
12 Non Return Valve(Check Valve): Supply, installation, testing and commissioning of double flanged CI/ Cast Steel non return valves of following sizes of ratings PN 1.6 inline with relevant IS(flap/ball type) with gun metal working parts & CI body and including all necessary fittings flanges, neoprene gaskets, nuts bolts for fixing with pipe, hardware, joints etc. as per drawings, specifications and as instructed by Engineer-In-Charge. 5 nos. Excess(+) Full Conversion INR
13 PRESSURE SWITCHES: Supply, installation, testing & commissioning of suitable Pressure switches on air cushion tank, with a range of 2-14 Kg/sqcm with low & high set points conforming to relevant IS, specifications, complete in all respects as required & as per instructions of EIC. 2 nos. Excess(+) Full Conversion INR
14 PRESSURE RELEASE VALVES: Supply, installation and testing of suitable Pressure release valve of 50 mm dia, of CI body, with pressure setting range 7-15 kg/sqcm, on top of Air Vessel, complete in all respect as required & as per instructions of EIC. 3 Gun Metal Ball Valve: Supply, installation, testing and commissioning of heavy pattern screw down Gun Metal Gate Valves of following sizes confirming to relevent IS with hand wheels at top including testing for a pressure of 16 kg/sq.cm. for two hours, all as per specification, drawings and as instructed by Engineer-In-Charge as per Technical Specification. Excess(+) Full Conversion INR
15 Alarm Valve: Supplying, erecting and fixing in position 150mm dia Fire sprinkler Alarm valve HD / TYCO make with inlet and outlet connections pressure gauges etc complete as per the given drawings, specifications or instruction of the EIC. 12 Gun Metal Ball Valve: Supply, installation, testing and commissioning of heavy pattern screw down Gun Metal Gate Valves of following sizes confirming to relevent IS with hand wheels at top including testing for a pressure of 16 kg/sq.cm. for two hours, all as per specification, drawings and as instructed by Engineer-In-Charge as per Technical Specification. Excess(+) Full Conversion INR
16 Hydrant Landing Valve: Supply, installation, testing & commissioning of Single outlet SS hydrant landing valve conforming to IS 5290 having 80 mm diameter flanged inlet 63 mm diameter instantaneous type female outlet with SS hand wheel, blank cap & GI chain conforming to IS 901, twist release type plug including nuts, bolts, washers, gaskets with necessary fittings like Tees, elbows etc. including providing 80 mm diameter GI pipe heavy class conforming to IS 1239 of suitable length to extend the hydrant from downcomer making flanged/welded joints, testing the unit, painting the hydrant valve and the exposed portion of GI pipe with 2 coats of signal red paint of approved make over a coat of approved make of primer, all as per specification and as instructed by Engineer-In-Charge. 10 Gun Metal Ball Valve: Supply, installation, testing and commissioning of heavy pattern screw down Gun Metal Gate Valves of following sizes confirming to relevent IS with hand wheels at top including testing for a pressure of 16 kg/sq.cm. for two hours, all as per specification, drawings and as instructed by Engineer-In-Charge as per Technical Specification. Excess(+) Full Conversion INR
17 External Hydrant:Supply, Installation, testing & commisioning of Single Outlet Hydrant valve of oblique Morris pattern Stainless Steel (SS-304) landing valve with C.I./ S.S. hand wheel, SS blank cap, detachable stainless steel female coupling, confirming to IS-5290/5041 having instantaneous coupling having 63 mm dia. SS blank cap and chain confirming to IS 901 to suit the hosepipes, including nuts, bolts, washers, gaskets, with necessary fittings like tee, bend etc, testing the unit, painting the Hydrant valve with 2 coats of red paint over a coat of Zinc reached primer, all as per specifications and as directed by E-I-C.
17.1 Siamese Connections: 3 Gun Metal Ball Valve: Supply, installation, testing and commissioning of heavy pattern screw down Gun Metal Gate Valves of following sizes confirming to relevent IS with hand wheels at top including testing for a pressure of 16 kg/sq.cm. for two hours, all as per specification, drawings and as instructed by Engineer-In-Charge as per Technical Specification. Excess(+) Full Conversion INR
18 2-Way Siamese Connection: Supply, installation, testing & commissioning of Siamese connections having two numbers of 63 mm diameter G.M/SS inlet (instantaneous male coupling) along with one number 100 mm diameter C.I. double flange non return valve of rating PN 1.6 conforming to IS 5312 with G,.M working parts, and fittings all connected to 100 mm diameter GI pipe with necessary fittings including blank caps, flanges and joints, welding etc. and supplying and fixing of inlet housing box made out of 14 gauge M.S Sheet with angle and frame of suitable size and painting with two coats of synthetic enamel paint over a coat of approved primer over pipes and housing box and white enamel paint inside housing box complete in all respects as per specification and as instructed by Engineer-in-Charge. 12 set Excess(+) Full Conversion INR
19 Hose Reel With Drum: Providing & fixing rubber hose reel of 19 mm diameter x 36 m along with swinging drum along with high pressure braided rubber hose conforming to IS 884 including 8 mm diameter SS cut off nozzle on one end, wall mounting type, necessary brackets suitable suitable for wall mounting, fixing on downcomer including connecting the other end to the downcomer by providing necessary connecting nipple/coupling, nuts, bolts etc. and providing & fixing 20 mm dia G.M. peet valve of approved make all complete including painting (the drum and brackets shall be painted with two coats of signal red enamel paint from outside and white enamel paint from inside) & as shown and as instructed by Engineer-In-Charge. 22 Gun Metal Ball Valve: Supply, installation, testing and commissioning of heavy pattern screw down Gun Metal Gate Valves of following sizes confirming to relevent IS with hand wheels at top including testing for a pressure of 16 kg/sq.cm. for two hours, all as per specification, drawings and as instructed by Engineer-In-Charge as per Technical Specification. Excess(+) Full Conversion INR
20 Hose Cabinet: Supply, installation & commissioning of 1.6 mm thick MS sheet metal hose cabinet of size 750x650x250 mm or appropriate for accomodating 02 nos. of hose pipes (measured & paid seperately under relevent SOQ item) and SS-304 branch pipe with nozzle. The box shall have front glass door lock with angle iron frame. The hose pipe box shall be fixed with Hilti make Anchor Fastner on the wall or nut bolts (in case of stand in open space) as shown in the drawing and as directed by EIC. The MS box shall be painted with two coats of signal red enamel paint from outside and white enamel paint from inside. The scope also includes supplying of gun metal /stainless steel branch pipe of 63 mm dia. fitted with detachable hexagonal nozzle of 19 mm dia. conforming to IS : 903 or universal pattern as per IS :2871. The branch pipe with detachable nozzle shall be placed in the hose cabinet complete in all respect as instructed by Engineer-In-Charge. 22 set Excess(+) Full Conversion INR
21 Hose Pipe: Supply and installation of Unlined Flax Canvas (hose pipe) for fire fighting conforming to RRL fire hose type A or Synthetic Fibre Woven-Jacket (SFWJ) Elastomeric fire hose type B conforming to IS:636 all with ISI marks as required and of approved make and of 63 mm dia & 15 mtrs length, fitted with male and female SS coupling confirming to IS:903, ISI marks with guaranteed bursting pressure of 35.7 kg/sq.cm and complete as per the technical specifications and as instructed by Engineer-In-Charge. Each set shall comprise of 2 hose pipes 16 Gun Metal Ball Valve: Supply, installation, testing and commissioning of heavy pattern screw down Gun Metal Gate Valves of following sizes confirming to relevent IS with hand wheels at top including testing for a pressure of 16 kg/sq.cm. for two hours, all as per specification, drawings and as instructed by Engineer-In-Charge as per Technical Specification. Excess(+) Full Conversion INR
22 Pressure Guages: Supply, installation testing and commisioning of pressure gauges of SS material with dial not less than 150 mm dia of appropriate range and complete in all respects with shut off gauge, cocks , all fittings etc, duly calibrated before installation in MKS and FPS units and duly tested after installation as per drawing and as instructed by Engineer-In-Charge. 6 Gun Metal Ball Valve: Supply, installation, testing and commissioning of heavy pattern screw down Gun Metal Gate Valves of following sizes confirming to relevent IS with hand wheels at top including testing for a pressure of 16 kg/sq.cm. for two hours, all as per specification, drawings and as instructed by Engineer-In-Charge as per Technical Specification. Excess(+) Full Conversion INR
23 Air Release Valve: Providing and fixing 20/25/40/50 mm dia (dia shall be as applicable as per relevant IS code) (PN - 1.6, Type-S1, Flanged, ISI marked) air release valve conforming to IS - 14845 : 2000 with isolating valve (pressure rating PN 1.6) including making necessary flanged joints and providing all fitting materials nuts, bolts etc. and providing T on the pipeline for its installation at site all as per technical specification, drawings and as instructed by Engineer-In-Charge. 22 Gun Metal Ball Valve: Supply, installation, testing and commissioning of heavy pattern screw down Gun Metal Gate Valves of following sizes confirming to relevent IS with hand wheels at top including testing for a pressure of 16 kg/sq.cm. for two hours, all as per specification, drawings and as instructed by Engineer-In-Charge as per Technical Specification. Excess(+) Full Conversion INR
24 Orifice Plate: Design, supply and fixing stainless steel orifice plate of not less than 6 mm thick having suitable bore for reducing the pressure at the fire hydrant outlet as per fire brigade requirement and to restrict the operating pressure within 3.5 kg/sq.cm. at the fire hydrant outlet. The orifice plate shall be fixed in position & it shall be fitted between the flanges. The orifice plates shall have test certificate and calibrated to give the required pressure, complete all as per specification, drawings & as directed by E.I.C.
24.1 Fire Extinguisher: 50 Gun Metal Ball Valve: Supply, installation, testing and commissioning of heavy pattern screw down Gun Metal Gate Valves of following sizes confirming to relevent IS with hand wheels at top including testing for a pressure of 16 kg/sq.cm. for two hours, all as per specification, drawings and as instructed by Engineer-In-Charge as per Technical Specification. Excess(+) Full Conversion INR
24.2 Proividing & fixing of Dry Chemical Powder (ABC) type fire extinguisher of 06 Kg capacity either portable or trolley mounted as per approved make fitted with pressure indicating gauge, internal tube, squeeze lever type valve fully charged with ABC powder (Mono Ammonium Phosphate) pressured by Nitrogen complete in all respects including wall suspension bracket and conforming to IS 15683-2006. The Fire extinguisher shall be supplied and placed without any damage, scratches and loss of accessories as per specifications and as instructed by Engineer-In-Charge. 7 Gun Metal Ball Valve: Supply, installation, testing and commissioning of heavy pattern screw down Gun Metal Gate Valves of following sizes confirming to relevent IS with hand wheels at top including testing for a pressure of 16 kg/sq.cm. for two hours, all as per specification, drawings and as instructed by Engineer-In-Charge as per Technical Specification. Excess(+) Full Conversion INR
24.3 Providing & fixing of, CO2 type fire extinguisher of 4.5 Kg capacity either portable or trolley mounted, highly effective against B & C class of fire, having ISI certification mark, 8 Gun Metal Ball Valve: Supply, installation, testing and commissioning of heavy pattern screw down Gun Metal Gate Valves of following sizes confirming to relevent IS with hand wheels at top including testing for a pressure of 16 kg/sq.cm. for two hours, all as per specification, drawings and as instructed by Engineer-In-Charge as per Technical Specification. Excess(+) Full Conversion INR
25 having flat base including valve, discharge hose & complete in all respects including initial fill with CO2 gas conforming to IS 15683:2006, wall suspension bracket as required & as per instructions of Engineer In Charge. The Fire extinguisher shall be supplied and placed without any damage, scratches and loss of accessories as per specifications and as instructed by Engineer-In-Charge. 4 Gun Metal Ball Valve: Supply, installation, testing and commissioning of heavy pattern screw down Gun Metal Gate Valves of following sizes confirming to relevent IS with hand wheels at top including testing for a pressure of 16 kg/sq.cm. for two hours, all as per specification, drawings and as instructed by Engineer-In-Charge as per Technical Specification. Excess(+) Full Conversion INR
26 Fire Bucket: Supply and placing of fire sand bucket filled with dry and clean sand to be kept on floor or wall hook confirming to IS 2546. The fire bucket shall be galvanized mild steel of 9 litres capacity. The bucket shall be provided and placed as per instruction of EIC. 2500 kg Excess(+) Full Conversion INR
27.1 Bucket Stand: Providing floor mounting stand for keeping 2 Nos. of FIRE buckets of 1000mm in length, 900mm in height, frame made out of 30x30x4 mm M.S. angle, rectangular bottom frame with cross supports for legs, suitable G.I. pipe shall be welded on the top end of of legs with 2 hooks on GI pipe for sand buckets and duly painted with one coat of red oxide and two coats of black paint all complete as per the given drawing, specifications or instruction of Engineer-In-Charge (E.I.C.) 1230 25 mm dia Excess(+) Full Conversion INR
27.2 M.S. Supports / Structure: Supply, cutting, fabrication, welding, erecting & fixing in position of M.S. support/structure (angle, channel, beam, plate, chequered plate etc.) for steps and other purpose (not applicable for items for which supports are already included in the item) including painting with two coats of synthetic enamel paint of approved make & shade over a coat of approved steel primer all as instructed by Engineer-In-Charge. Material shall conform to IS-2062. 185 25 mm dia Excess(+) Full Conversion INR
27.3 Ordinary soil 110 25 mm dia Excess(+) Full Conversion INR
28.1 Hard Rock 6 Gun Metal Ball Valve: Supply, installation, testing and commissioning of heavy pattern screw down Gun Metal Gate Valves of following sizes confirming to relevent IS with hand wheels at top including testing for a pressure of 16 kg/sq.cm. for two hours, all as per specification, drawings and as instructed by Engineer-In-Charge as per Technical Specification. Excess(+) Full Conversion INR
29 Valve Chamber: Construction of brick masonary valve chambers of following sizes comprising of 230 mm thick brick masonry in cement mortar 1:4 over a bed of 150 mm thick cement concrete of grade M-15 for foundation with 150 mm offset all round, including providing and fixing C.I. steps / foot rests / rungs each weighing not less than 5 Kg. first step at 450 mm from top of cover, remaining @ 300 mm centre to centre staggered with 380 mm spacing, painting etc. racking out joints & plastering in cement mortar 1:3, 20 mm thick both on internal and external surfaces, internal surfaces finished smooth with a floating coat of neat cement, providing 100 mm thick RCC slab casted in M.S. angle box frame (Galvanised) of 25 mm x 25 mm x 4 mm size in three equal pieces with reinforcement weighing not less than 100 kg/cu.m, fabricated M.S. angle all around & M.S. galvanised flat stiffners including formwork as per drawing etc. complete with lifting hooks at top, providing and fixing C.I. circular surface box weighing not less than 14 kg. over the RCC slab for key rod operation, painting all as per specifications and directions of EIC including dewatering the pit, if required till completion of the work. 70 each Excess(+) Full Conversion INR
30 1.2 m width x 1.2 m length x 1.2 m depth 20 cum Excess(+) Full Conversion INR
31 PCC Pedestals: Providing PCC pedestals /thrust /anchor block of required sizes for underground pipes, fire hose box etc. and specials with cement concrete 1:2:4 at required intervals including form work, curing, finishing etc. complete in all respect as as per standard specifications and as instructed by Engineer-In-Charge. 6 each Excess(+) Full Conversion INR
32 ROAD CUTTING & RE-SURFACING: Cutting the existing asphalt road and demolishing WBM or BBM including rubble soling if any for providing services and making good the same after the work is satisfactorily completed, including relaying of soling doing water bound macadam, bituminous bound macadam road providing and laying 50 mm thick asphaltic layer etc, complete as directed by EIC. 700 Gun Metal Ball Valve: Supply, installation, testing and commissioning of heavy pattern screw down Gun Metal Gate Valves of following sizes confirming to relevent IS with hand wheels at top including testing for a pressure of 16 kg/sq.cm. for two hours, all as per specification, drawings and as instructed by Engineer-In-Charge as per Technical Specification. Excess(+) Full Conversion INR
33 Foundation For Pump: Providing and laying Design-Mix Reinforced Cement Concrete foundation (design and drawing to be provided by contractor) for fire fighting pump of M-20 by weight batching using graded stone aggregate of 20 mm finishing, curing etc. as specified and also including dewatering, if any, cost of form work, shuttering & steel reinforcement, including nozing all around by 50 x 50 x 5 mm angle, all complete as per specifications, drawings and as directd by EIC. 700 Gun Metal Ball Valve: Supply, installation, testing and commissioning of heavy pattern screw down Gun Metal Gate Valves of following sizes confirming to relevent IS with hand wheels at top including testing for a pressure of 16 kg/sq.cm. for two hours, all as per specification, drawings and as instructed by Engineer-In-Charge as per Technical Specification. Excess(+) Full Conversion INR
34 Sprinklers:- Supply, installation, testing & commissioning of 15 mm dia recessed sprinkler with quartzoid bulb and set to operate at 68 deg Celsius, with rosette plate [Pendent type Sprinkler (K-80), FM & UL approved] with all assembly complete in all respects as directed by EIC.
34.1 Flexi Drops: Supply, installation, testing & commissioning of Sprinkler Flexible drop pipes made of Corruggated SS Tubing to with stand 16 Bar pressure with welded reducer on one end to directly accomadate sprinkler & female checknut on the other end to connect to the branch pipe with supports complete [Length 1.5 mtr, FM & UL approved]
34.11 High Velocity Water Spray System: Design, supply, fabrication, erection,testing and comissioning of High Velocity water Spray system for Two Nos. of out door transformers. (connecting water pipe line for HVWS system from nearest suitable point from underground external fire hydrant pipe) 2 set Excess(+) Full Conversion INR
34.2 Deluge Valves (DV): Supply, Installation, testing & commissioning of Deluge valves assembly along with all accessories complete in all respect as per drawing, as directed by EIC and as per Technical Specification. It should also include all required accessories such as six way manifold, water inlet & outlet position is perpendicular to each other, valves, NRVs, Emergency Release Box, restriction nozzles, pressure gauges, stop valve, Drip valve, check valve, etc.
34.21 100 mm dia 55 Nos Excess(+) Full Conversion INR
34.3 H. V. Nozzles: Supply, Installation, testing & commissioning of H.V. Nozzles all as per drawing, as directed by EIC and as per Technical Specification.
34.31 15 mm dia 55 Nos Excess(+) Full Conversion INR
34.4 Quartzoid Bulb Detectors : Supply, Installation, testing & commissioning of Bulb detectors all as per drawing, as directed by EIC and as per Technical Specification.
34.41 High Velocity Water Spray System: Design, supply, fabrication, erection,testing and comissioning of High Velocity water Spray system for Two Nos. of out door transformers. (connecting water pipe line for HVWS system from nearest suitable point from underground external fire hydrant pipe) 2 Nos Excess(+) Full Conversion INR
34.51 Y Strainer : 'Supply, installation and testing of 'Y' strainer of following sizes made out of cast iron, with perforated brass filter fixed, in position, to flange or pipe with nut bolts, gaskets, washers etc. in an apporved manner, complete in all respect as per drawing, as directed by EIC. 12 Nos Excess(+) Full Conversion INR 3 Supplying, Conveying and fixing spls. Including ea item4 10 Nos
Total in Figures 4 Construction of chamber for 100mm sluice plates item5 10 Nos
Quoted Rate in Figures Select
Quoted Rate in Words
Select, Excess (+), Less (-) Less (-)
Tender Inviting Authority: Chief Engineer (ESG)
Earthing System: Supply, installation, testing & commissioning of earthing system & associated accessories, etc. complete all as per layout drawing & standard drawing CSG/EM/STD/12, specifications & as per the instructions of E.I.C. Note: 1) Measurements of resistance of each earth station & resistance of complete scheme of earthing layout must be measured recorded & got approved by E.I.C. 2) Jointing of the earth strip shall be with brass nuts bolts and also with solder joints. 3) Jointing of the earth wire shall be with solder joints with tinned cable sockets. Strip/wire fixed to wall/side of trench/ slab/column/beam/shaft with 5mm thick G.I spacers & GI saddles or on existing cable tray with saddles or in ground at 750 mm below including excavation in all types of soil with protective baked bricks, refilling & removal of excess earth within a radius of 500 m temporary reinstatement & back filling of trench, interconnections of earth strip/wire with brass nuts, bolts & washers and solder jointing, painting with two coats of black bituminous compound for earth wire/strip in ground & green enamel paint for earth wire/strip on surface, etc.
Name of the Bidder/ Bidding Firm / Company :
Sl. No. Item Description Item Code / Make Quantity Units Estimated Rate in Rs. P Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency RATE In Figures To be entered by the Bidder in Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT in Rs. P TOTAL AMOUNT TOTAL AMOUNT In Words
1.1 GI strip/wire fixed to wall/side of trench/ slab/column/beam/shaft with 5mm thick G.I spacers & GI saddles or on existing cable tray with saddles or in ground at 750 mm below including excavation in all types of soil with protective baked bricks, refilling & removal of excess earth within a radius of 500 m temporary reinstatement & back filling of trench, interconnections of earth strip/wire with brass nuts, bolts & washers and solder jointing, painting with two coats of black bituminous compound for earth wire/strip in ground & green enamel paint for earth wire/strip on surface , etc. 1 set Excess(+) Full Conversion INR
1.2 M.V Panel (Main Fire panel): Incomer a) 1 No. 630 A ,36 KA FP MCCB & complete with microprocessor based over current, short circuit & earth fault release. b) 1 set of RYB indication lamp with HRC protection fuses c) 3 nos 630/5 A ratio, class-I 15 VA burden cast resin current transformer d)1 No. 96 sqmm, 0-500V voltmeter with 3 way & off selector switch and HRC protection fuses. e) 1 no.0-630A , 96 sqmm ammeter with three way & off selector switch f) 1 No. Intelligent panel meter, indicating V, I, W, Var, MD, PF, etc. g) 1 No. water level control relay with 3 nos. stainless steel probes similar to M/s Minilec make cat no. WLC D1.The 3 Nos stainless steel probes with required lengths of PVC wires & connectors shall be mounted on underground water tank & the MS supporting arrangement shall be measured seperately - 3 sets (02 for fire tanks and 01 for sump) h) 6 window Annunciation for fault indication of pumps, low water level in UG tank etc. Bus bar: 630 A TPN tinned copper bus bar having maximum current density of 800 A/sq.inch to withstand symmetrical fault level of 35 KA at 415 V. The neutral bus bar shall have 100% capacity 1 set Excess(+) Full Conversion INR
1.3 Outgoings: A) Starter for Main Electric fire Pump & main electric sprinkler pump:- 2 sets Suitable automatic star/delta starter with MCCB fuseless backup protection (Type-II co-ordinated as per IS 13947-4-1) for 2400 lpm @ 120 m head for main fire pump & main sprinkler pump with overload protection, current sensing type single phase preventor complete with all accessories and internal wiring required for automatic & manual operation, etc. complete as required. (Capacity of motor shall be as per IS 12469-1988 considering efficiency of pumps as indicated elsewhere in SOQ Specifications) The scope also includes providing following: 1) 1 no.0-300 A , 96 sqmm ammeter with three way & off selector switch - 1 set 2) 3 nos 300/5 A ratio,class-I 5 VA burden cast resin current transformer for current monitoring. - 1 set 3) 1 No. 240V contactor for water level control relay contact multiplication. The contacts shall be used for control of motor and Diesel engine operated main FF pumps & jockey pump. - 1 set 4) ON-OFF indication lamp - 1 set 5) ON-OFF push button - 1 set 6) Auto mannual selector switch - 1 no. B) Starter for main Jockey pump & Sprinkler jockey pump: 2 sets a) Suitable automatic star/delta starter with MCCB fuseless backup protection for 180 lpm @ 120 m head (appox. 20 hp) for main jockey pump & sprinkler jockey pump with overload protection, current sensing type single phase preventor complete with all accessories and internal wiring required for automatic & manual operation, complete as required. (Capacity of motor shall be as per IS 12469-1988 considering efficiency of pumps as indicated elsewhere in SOQ Specifications) The scope also includes providing following: 1) 1 no.0-40 A , 96 sqmm ammeter with three way & off selector switch - 1 set 2) 3 nos 40/5 A ratio,class-I 5 VA burden cast resin current transformer for current monitoring. - 1 set 3) 1 No. 240V contactor for water level control relay contact multiplication. 4) ON-OFF indication lamp - 1 set 5) ON-OFF push button - 1 set 6) Auto manual selector switch - 1 no. 4 set Excess(+) Full Conversion INR
2 C) Diesel Engine Control for Diesel Engine driven main fire fighting pump comprising of: 1) 3 attempt starting device, timers and relays as required, push buttons, start/stop in manual mode. 2) Indication lamp for high/low lub oil pressure, High water temperature and Engine ON indication. 3) Battery charger suitable for 12V DC with boost & trickle selector switch, 0-30V DC voltmeter, 0-20A DC ammeter. 4) All standard relays and accessories for automatic operation of diesel engine. 5) Engine should trip in case of low water level in underground tank. 6) The auto manual indication and switch shall be provided in the Panel. 7) Indication windows for fault indication of pumps, low water level in UG tank etc. D) Starter for submersible dewatering pump : 1 set Suitable automatic DOL starter with MPCB fuseless backup protection for approximately 1.0 HP motor of submersible dewatering pump with overload protection, current sensing type single phase preventor complete with all accessories and internal wiring required for automatic & manual operation, complete as required. The scope also includes providing followings : 1) 1 no.0-10 A , 96 sqmm ammeter with three way & off selector switch - 1 set 2) 3 nos 10/5 A ratio,class-I 5 VA burden cast resin current transformer for current monitoring. - 1 set 3) ON-OFF indication lamp - 1 set 4) ON-OFF push button - 1 set 5) Auto mannual selector switch - 1 set E) TPN, 415V, 63/40A MCCB with microprocessor based overcurrent, short circuit & earth fault release & 1 set of indication lamps - 2 Nos. F) 2P, 415V, 32A MCCB with microprocessor based overcurrent, short circuit & earth fault release - 2 Nos. G) 1 No 40 A FP MCCB with microprocessor based overcurrent, short circuit & earth fault release- 2 sets (01 for DB1 and 01 for DB 2)
2.1 Terrace Pump Starter : Supply, installation, testing and commissioning of 14 SWG MS CRCA sheet starter enclosure, IP 55 wall mounting type, powder coated with RAL-7032 shade complete with suitable automatic star-delta starter with HRC back up protection (Type-II co-ordinated as per IS 13947-4-1) for 900 LPM @ 35 m head booster pump (approximately 8 HP) with overload protection, current sensing type single phase preventor complete with all accessories and internal wiring required for manual operation, c 200 25 x 6 mm GI Strip Excess(+) Full Conversion INR
2.2 Mtrs 250 8 SWG GI. wire Excess(+) Full Conversion INR
3 omplete as required. The scope also includes providing following: 1) 1 no.0-20 A , ammeter with three way & off selector switch - 1 set 2) 3 nos 20/5 A ratio,class-I 5 VA burden cast resin current transformer for current monitoring. - 1 set 3) ON-OFF-TRIP indication lamp - 1 set 4) ON-OFF push button - 1 set 5) 1 No. 240 V auxiliary contactor 6) Water Level Controller with 3 no. probes - 1 set
3.1 m safety tests to confirm isolation and restore the wall or surface to its original finish. Note : Scope includes Shutdown coordination, permits, safe disconnection and removal of batteries (as per regulations), cable tagging, dismantling, transportation/removal from site, temporary terminations, minor surface patching/finishing. Shutdown coordination, permits, safe disconnection and removal of batteries (as per regulations), cable tagging, dismantling, transportation/removal from site, temporary terminations, minor surface patching/finishing. 12 Gun Metal Ball Valve: Supply, installation, testing and commissioning of heavy pattern screw down Gun Metal Gate Valves of following sizes confirming to relevent IS with hand wheels at top including testing for a pressure of 16 kg/sq.cm. for two hours, all as per specification, drawings and as instructed by Engineer-In-Charge as per Technical Specification. Excess(+) Full Conversion INR
3.2 Removal of Concealed Manual Call Points (MCPs) and Hooters in SoMS Building : Carefully locate and remove concealed MCPs and hooters (sounders) from back-boxed or flush-mounted installations. Disconnect wiring, remove back boxes if necessary, and safely store or hand over removed devices. After removal, restore the opening or recessed area to the original finish using plaster and paint so that no visible damage remains. If devices are to be relocated or replaced, make good as instructed. Perform isolation testing to ensure no live circuits remain open. Note: Scope includes Safe disconnection, removal of device and back box, plastering/patching, touch-up painting, disposal of damaged parts, isolation testing. 8 Item No.1.1 Excess(+) Full Conversion INR
4 Core Cutting in RCC/Concrete for Services – 100 mm Diameter : Perform wet core cutting in reinforced concrete slabs, walls, or beams using diamond core drilling machines to form 100 mm diameter openings for services. Remove core plug, manage slurry/water, dispose debris, and protect reinforcement. Coordinate with structural engineer as required. After services are installed, provide suitable sleeve/pipe and seal the annular gap using non-shrink grout or approved fire-rated sealant to restore original fire rating and/or waterproofing. Provide temporary supports and safety barriers during cutting. Note: Scope includes providing Core cutting labour and machine, water/slurry management, debris removal, supply of sleeve (if specified), sealing with grout/fire-rated sealant, reinstatement of fire rating (if required).
4.1 Remote ON / OFF P.B. Station: Supply, installation, testing and commissioning of 14 SWG MS CRCA sheet, remote ON/OFF push button enclosure, with ON / OFF indication lamps, IP 42, wall mounting type, powder coated with RAL 7032 shade complete with internal wiring with 1.5 sq.mm copper PVC FRLS wires etc. Note: 1) ON - OFF indication lamps shall be heavy duty LED type, 240V, 50 Hz. 2) PB station shall be lockable type to prevent unauthorize operation of booster pump. 500 25 x 6 mm GI Strip Excess(+) Full Conversion INR
5 M.V Panel (Main Fire panel): Incomer a) 1 No. 630 A ,36 KA FP MCCB & complete with microprocessor based over current, short circuit & earth fault release. b) 1 set of RYB indication lamp with HRC protection fuses c) 3 nos 630/5 A ratio, class-I 15 VA burden cast resin current transformer d)1 No. 96 sqmm, 0-500V voltmeter with 3 way & off selector switch and HRC protection fuses. e) 1 no.0-630A , 96 sqmm ammeter with three way & off selector switch f) 1 No. Intelligent panel meter, indicating V, I, W, Var, MD, PF, etc. g) 1 No. water level control relay with 3 nos. stainless steel probes similar to M/s Minilec make cat no. WLC D1.The 3 Nos stainless steel probes with required lengths of PVC wires & connectors shall be mounted on underground water tank & the MS supporting arrangement shall be measured seperately - 3 sets (02 for fire tanks and 01 for sump) h) 6 window Annunciation for fault indication of pumps, low water level in UG tank etc. Bus bar: 630 A TPN tinned copper bus bar having maximum current density of 800 A/sq.inch to withstand symmetrical fault level of 35 KA at 415 V. The neutral bus bar shall have 100% capacity. c. "For more item description please refer additional sheet of Inportnat notes."
5.1 M.V.Cables: Supply, installation, testing & commissioning of 1.1 KV grade XLPE insulated, inner sheath PVC , extruded FRLS PVC outer sheath, GI strip / wire armoured, multistranded Aluminium / copper conductor power cable confirming to IS : 1554 part I/IS 7098 part-1 with upto date amendments, fixed on wall/column/slab/false ceiling or in existing hume pipe/trench/ shaft/pit/ on 5mm thick M.S. flat /GI spacer/angle/ support fixed with coach screws/grouted in wall/anchor fasteners 2mm. thick G.I. Fabricated saddle, all fixing accessories, etc complete including painting of M.S spacers/angles and saddles all complete as per enclosed detailed specifications, drawings & as per instructions of the E-I-C & of the following sizes. The space between the two support shall be 600mm. approx. 15 m Excess(+) Full Conversion INR
6.1 3C x 4 Sq.mm Cu. conductor cable (On Wall / Trench / Cable tray)
6.11 End Joints: End jointing of following sizes of cable by crimping with supply of all jointing materials like solderless tinned copper cable socket, cable glands, gland earthing, insulation tape, flux, duplicate interconnection between gland earthing strip & to the nearest earthing bus terminals as per the drawings, specifications and as per the instructions of the Engineer-in-charge. 300 m Excess(+) Full Conversion INR
6.12 6 C x 2.5 sq.mm copper conductor cable (On Wall / Trench / Cable tray) 300 25 x 6 mm GI Strip Excess(+) Full Conversion INR 3 Supplying, Conveying and fixing spls. Including ea item4 10 Nos
Total in Figures 4 Construction of chamber for 100mm sluice plates item5 10 Nos
Quoted Rate in Figures Select
Quoted Rate in Words
Select, Excess (+), Less (-) Less (-)
Tender Inviting Authority: Chief Engineer (ESG)
Earthing System: Supply, installation, testing & commissioning of earthing system & associated accessories, etc. complete all as per layout drawing & standard drawing CSG/EM/STD/12, specifications & as per the instructions of E.I.C. Note: 1) Measurements of resistance of each earth station & resistance of complete scheme of earthing layout must be measured recorded & got approved by E.I.C. 2) Jointing of the earth strip shall be with brass nuts bolts and also with solder joints. 3) Jointing of the earth wire shall be with solder joints with tinned cable sockets. Strip/wire fixed to wall/side of trench/ slab/column/beam/shaft with 5mm thick G.I spacers & GI saddles or on existing cable tray with saddles or in ground at 750 mm below including excavation in all types of soil with protective baked bricks, refilling & removal of excess earth within a radius of 500 m temporary reinstatement & back filling of trench, interconnections of earth strip/wire with brass nuts, bolts & washers and solder jointing, painting with two coats of black bituminous compound for earth wire/strip in ground & green enamel paint for earth wire/strip on surface, etc.
Name of the Bidder/ Bidding Firm / Company :
Sl. No. Item Description Item Code / Make Quantity Units Estimated Rate in Rs. P Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency RATE In Figures To be entered by the Bidder in Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT in Rs. P TOTAL AMOUNT TOTAL AMOUNT In Words
1 m 1 Construction of chamber for 100mm sluices valve item1 10 1 Nos
1.01 NOS 1 Each Excess(+) Full Conversion INR
1.02 Cable Tray: Supply & fixing of following sizes of ladder type GI cable trays similar to M/s Indiana make with vertical sides on both ends and suitable MS supports including concrete bolts, hold fast etc. The scope includes supply of readymade bends, reducers,Tee, covers etc. as required as per instructions of EIC. 1 Each Excess(+) Full Conversion INR
1.04 FACP Components 930 Each Excess(+) Full Conversion INR
1.05 Main FACP: Supply, installation, testing and commissioning of Vds approved microprocessor based Hot Redundant TCP/IP networkable, LCD color touch screen , Intelligent Addressable Fire Alarm Control panel with 16 loop with battery back up with hot redundancy in cpu/master control unit, hot redundancy in all loop cards, relay and interface card etc. complete with necesary mounting arrangement for wall mounting, Licensced software for panel operation (if any) , backup batteries etc. all as per tender specification & as directed by Engineer in-charge. Note: Scope of work includes Integration of system by addressing, programming of all the devices in the system, commisioning & performance testing all as per tender specification & as directed by Engineer in-charge. 15 Each Excess(+) Full Conversion INR
1.06 Active Repeater Panel: Supply, installation, testing and commissioning of Vds approved Active Repeater Panel equipped with an in built buzzer/hooter, LCD display for indicating all system states, just mimic of the main panel, having push buttons for Silence/Mute, Acknowledge, Reset etc. complete with necesary mounting arrangement for wall mounting . all as per tender specification & as directed by Engineer in-charge. Note: i.) Scope of work includes Integration of Reapeater panel with main FACP. Required accessories for communication between FACP and Repeater panel i.e. communication card etc. shall be the part of this item & the rate shall be quoted accordingly. ii.) The repeater panel power supply shall be drawn from the main FACP & cabling for this shall be the part of this item & the rate shall be quoted accordingly. iii.) Communication cable & power supply cable shall be as per manufacturer standards. iv.) Cabling between repeater panel & main FACP shall be done in existing conduit & laying of conduit (if required) shall be measured under item no.-3 of Part-C. v.) If the communication between repeater panels & main FA panel is through loop cable, then the cabling shall be measured under the item no.-1 of Part-C. If the communication between repeater panels & main FA panel is through Cat5/Cat6 cable or any other means, then the same shall be included under the scope of Item no.1.2 of Part-A. 54 Each Excess(+) Full Conversion INR
1.07 Passive Repeater Panel: Supply, installation, testing and commissioning of Vds approved Passive Repeater Panel , equipped with LCD display for indicating all system states as indicated on main panel. complete with necesary mounting arrangement for wall mounting all as per tender specification & as directed by Engineer in-charge. Note: 1.) Scope of work includes Integration of Reapeater panel with main FACP. Required accessories for communication between FACP and Repeater panel i.e. communication card etc. shall be the part of this item & the rate shall be quoted accordingly. 2.) The repeater panel power supply shall be drawn from the main FACP & cabling for this shall be the part of this item & the rate shall be quoted accordingly. 3.) Scope of work also includes removal of existing repeater panel (Floor panel), by breaking the wall, cutting the existing conduits if required, & placing the new panel at same location, filling the leftover gaps in wall with cement, mortar & bricks etc. finishing by 36 Each Excess(+) Full Conversion INR
1.08 applying white cement & touch up painting of that area by roller/brush etc. 4.) Communication cable & power supply cable shall be as per manufacturer standards. 5.) Cabling between repeater panel & main FACP shall be done in existing conduit & laying of conduit (if required) shall be measured under item no.-3 of Part-C. 6.) If the communication between repeater panels & main FA panel is through loop cable, then the cabling shall be measured under the item no.-1 of Part-C. If the communication between repeater panels & main FA panel is through Cat5/Cat6 cable or any other means, then the same shall be included under the scope of Item no.1.3 of Part-A. 2 Each Excess(+) Full Conversion INR
1.09 Intelligent Addressable Multi sensor Detector : Supply, installation, testing and commissioning of Vds approved Intelligent Addressable type multisensor detector with base for use as heat or smoke or combined both having integrated fault isolators, capability of soft addressing from panel & detecting all types of fires from TF-1 to TF-8 & all classes of heat as per EN-5,7 & 29 etc. all as per tender specification & as directed by Engineer in-charge. 720 Each Excess(+) Full Conversion INR
1.1 Rate of Rise Heat Detectors (Thermal Detectors): Supply ,installation,testing & commissioning of Analog Addressable Heat Detectors with solid state design with sensing element combination of fixed type and rate of riseof temperature indicating LED, mounting base etc. as per detailed Specification. 4 Each Excess(+) Full Conversion INR 2 Construction of chamber for 100mm sluices valve item3 10 Nos
Total in Figures 4 Construction of chamber for 100mm sluice plates item5 10 Nos
Quoted Rate in Figures Select
Quoted Rate in Words
Select, Excess (+), Less (-) Less (-)
Tender Inviting Authority: Chief Engineer (ESG)
Earthing System: Supply, installation, testing & commissioning of earthing system & associated accessories, etc. complete all as per layout drawing & standard drawing CSG/EM/STD/12, specifications & as per the instructions of E.I.C. Note: 1) Measurements of resistance of each earth station & resistance of complete scheme of earthing layout must be measured recorded & got approved by E.I.C. 2) Jointing of the earth strip shall be with brass nuts bolts and also with solder joints. 3) Jointing of the earth wire shall be with solder joints with tinned cable sockets. Strip/wire fixed to wall/side of trench/ slab/column/beam/shaft with 5mm thick G.I spacers & GI saddles or on existing cable tray with saddles or in ground at 750 mm below including excavation in all types of soil with protective baked bricks, refilling & removal of excess earth within a radius of 500 m temporary reinstatement & back filling of trench, interconnections of earth strip/wire with brass nuts, bolts & washers and solder jointing, painting with two coats of black bituminous compound for earth wire/strip in ground & green enamel paint for earth wire/strip on surface, etc.
Name of the Bidder/ Bidding Firm / Company :
Call station: SITC of EN54-16 certified Digital call station, designed in a modern and robust chassis with built-in numerical keypad, having gooseneck microphone , suitable for extension upto min. 2 remote call station extensions, each with atleast 20 free customizable functions and selection push buttons (14 for zones & atleast 6 for other functions) with atleast two LEDs per button , menu/function keys (pre-programmed) , suitable for connection with controller via network cable up to 500 meter etc. all as per specification & as directed by Engineer in-charge. Note: i. The quoted rate shall be inclusive of DC power unit (if required) , all connecting accesories & interconnecting cable betwen Call Stations & Network Controller . ii. Cabling between call station & network controller shall be done with network cable on surface in HMS PVC conduit & laying of conduit on surface shall be measured under item no.-3 of Part-C. The distance of call stations from network controller will be around 100 mtr. For exact measurements, agencies are requested to visit the site.
Sl. No. Item Description Item Code / Make Quantity Units Estimated Rate in Rs. P Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency RATE In Figures To be entered by the Bidder in Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT in Rs. P TOTAL AMOUNT TOTAL AMOUNT In Words
1 Addressable Manual call point: Supply, installation, testing and commissioning of flush mounted Vds approved Addressable Manual call point , Double action - break glass type with Push Button, Loop powered , comprise of an electronic circuit in-built to provide addressing capability, having inbuilt fault isolators etc. all as per tender specification & as directed by Engineer in-charge. Note: i.) Scope of work includes breaking the wall, cutting the existing conduits if required, & placing the MCP at the location instructed by EIC, filling the leftover gaps in wall with cement, mortar & bricks etc. finishing by applying white cement & touch up painting of that area by roller/brush etc. ii.) if additional GI box is required for flush mounting of MCP then it shall also be considered accordingly under the scope. 1 Each Excess(+) Full Conversion INR 1 Construction of chamber for 100mm sluices valve item1 10 1 Nos
2 Addressable loop powered Sounder : Supply, installation, testing and commissioning of Vds approved Addressable Loop Powered multi tone sounder with integrated fault isolators , having a sound pressure level of atleast 89dB at 1 meter distance, tone & volume adjustable from panel etc. all as per tender specification & as directed by Engineer in-charge. 2 Each Excess(+) Full Conversion INR
3 Addressable loop powered Flasher : Supply, installation, testing and commissioning of Vds approved Addressable loop powered Flasher with inbuilt fault isolators having configurable flash rate adjustable from FACP etc. all as per tender specification & as directed by Engineer in-charge. 1 Each Excess(+) Full Conversion INR
4 Remote Indicator: Supply, installation, testing and commissioning of Remote indicator having 360° view, for both wall mount and ceiling mount, controlled and powered directly via the alarm output of the fire detector or a suitable loop module etc. all as per tender specification & as directed by Engineer in-charge. 45 Each Excess(+) Full Conversion INR
5 Addressable Control/Output module: Supply, installation, testing and commissioning of Vds approved Addressable Control/Output module containing atleast four relay outputs, each containing a potential-free contact with a fail-safe , in-built fault isolators etc. all as per tender specification & as directed by Engineer in-charge. 1 Each Excess(+) Full Conversion INR
6 Network Controller: SITC of EN54-16 certified IP based Digital Voice Evacuation cum public address system for min. 4 Zones with expandable upto min. 2 call stations and up to min. 10 loudspeaker circuits, completely digital audio and control data transmission, Speaker line supervision in each zone for short circuit fault, discontinuity, ground fault and speaker fault, automatic isolation incase of short circuit. - Input module for atleast 4 audio - Possible to send same message simultaneously to several zones, - Built in message manager to store emergency- or business-calls - Gain adjustment in the inputs and outputs - Priority for emergency voice alert like fire or any other emergency services -Zone status LED's ,system status LED's etc. The controller shall supervised cabling to the amplifier, survillance of each amplifier, surveillance of the entire signal path, survillance of individual module in the system & overall fault indication all as required, as per specification & as directed by Engineer in-charge. Note: i.) Scope of work also includes Integration with Fire Alarm System with necessary cabling. Integration of PA System with FA system shall be soft integration via network cable as per manufacturere standards. ii.) If additional hardware devices like router, zone controllers, EOL/Line supervision set for each speaker line etc. are needed, then their rate shall be included in the quoted rate. iii.) Quoted rate shall also include rate of DC power unit (if required). 1 Each Excess(+) Full Conversion INR 2 Construction of chamber for 100mm sluices valve item3 10 Nos
Total in Figures 4 Construction of chamber for 100mm sluice plates item5 10 Nos
Quoted Rate in Figures Select
Quoted Rate in Words
Select, Excess (+), Less (-) Less (-)
Tender Inviting Authority: Chief Engineer (ESG)
Earthing System: Supply, installation, testing & commissioning of earthing system & associated accessories, etc. complete all as per layout drawing & standard drawing CSG/EM/STD/12, specifications & as per the instructions of E.I.C. Note: 1) Measurements of resistance of each earth station & resistance of complete scheme of earthing layout must be measured recorded & got approved by E.I.C. 2) Jointing of the earth strip shall be with brass nuts bolts and also with solder joints. 3) Jointing of the earth wire shall be with solder joints with tinned cable sockets. Strip/wire fixed to wall/side of trench/ slab/column/beam/shaft with 5mm thick G.I spacers & GI saddles or on existing cable tray with saddles or in ground at 750 mm below including excavation in all types of soil with protective baked bricks, refilling & removal of excess earth within a radius of 500 m temporary reinstatement & back filling of trench, interconnections of earth strip/wire with brass nuts, bolts & washers and solder jointing, painting with two coats of black bituminous compound for earth wire/strip in ground & green enamel paint for earth wire/strip on surface, etc.
Name of the Bidder/ Bidding Firm / Company :
Amplifier SITC of Digital 2x500 W ( 1000W Total) Class D, high efficiency Power Amplifier/Amplifiers EN54-16 certified system device with Short Circuit & Overload Protection, permanently monitored by the system controller having special standby provision for saving energy during the time the amplifier is not is use , 4 channel input, LED indication for the status etc. all as per specification & as directed by Engineer in-charge & shall have following features: -240W RMS per Channel -Amplifier Output voltage 100V -Supply input AC 230 +/- 10% - 50/60Hz -Short Circuit, Power, Tempreature, Overload & Short circuit Protection, Automatic Standby etc. Note: The design of amplifier shall be modular & the rating of individual amplifiers shall be as per the reccomendation of manufacturer .
Sl. No. Item Description Item Code / Make Quantity Units Estimated Rate in Rs. P Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency RATE In Figures To be entered by the Bidder in Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT in Rs. P TOTAL AMOUNT TOTAL AMOUNT In Words
1 Speaker: Supply, Installation, Testing & Comissioning of EN54-24 certified 100V, 6W wall mounted cabinet speaker having tappings at 6W / 3W/1.5W complete with necessary mounting hardware & accessories all as per specification & as directed by Engineer in-charge. 1 Construction of chamber for 100mm sluices valve item1 10 1 Nos
1.1 Supply, Installation, Testing & Comissioning of CD/DVD player for background music (Sony or Equivalent) all as per tender specification & as directed by Engineer in-charge. 6300 25 x 6 mm GI Strip Excess(+) Full Conversion INR
1.2 Equipment Rack, Made of MS for housing of all above equipment , front lockable glass door, Fan tray for cooling, Indivdual FUSE power supply unit, including all internal wiring/ interconnection as required all as per tender specification & as directed by Engineer in-charge. 1350 Surface HMS PVC conduit Supply, installation, testing and commissioning of 25mm dia. FRLS HMS PVC conduit fixed on the surface of wall / slab / column / beam with 2 mm thick hot dip GI saddle & 4-5 mm thick hot dip GI Spacer (3 nos. per meter) complete with necessary accessories like coupler, elbow, tee, bends, circular boxes etc. all as per specification & as instructed by EIC. Excess(+) Full Conversion INR
2 Cabling: 75 PVC coated flexible steel Conduit Supply, installation, testing & commissioning of 25mm liquid tight, FRLS , PVC coated Flexible Galvanised Steel conduit made up of helical coil of self interlocked ribbed stripes of Galvanised steel complete with necessary accessories like coupler, elbow, tee, bends, circular boxes etc. fixed on the surface of wall / slab / column / beam with 2mm thick hot dip GI saddle & 4-5 mm thick hot dip GI Spaceras per specification & as instructed by EIC. Excess(+) Full Conversion INR
3 Shielded Flexible Cable in existing concealed conduit : Supply, installation, testing and commissioning of 1100 V grade, 2 C x 1.5 Sq.mm Multistranded Copper conductor , PVC insulated, overall Al. mylar tape shielded twisted pair with drain wire of ATC copper, Extruded FRLS PVC Type 'ST3' sheathed Flexible cable confirming to relevant IS standards in existing concealed conduit including termination with suitable copper lugs at Device base/Loop module boxes/Junction boxes/Speakers, ferruling on both sides etc. all as per tender specification & as directed by Engineer in-charge.
3.1 Shielded Armoured cable on Surface : Supply, installation, testing and commissioning of 300 /500 V grade, 2C x 1.5 Sq.mm Multistranded Copper conductor, PVC insulated , overall Al. mylar tape shielded twisted pair with drain wire of ATC copper, FR PVC inner sheathed, G.I round wire Armoured, FRLS PVC outer sheathed confirming to relevant IS standards fixed on existing wall/column/slab/ shaft/pit/ on 4-5mm thick hot dip galvanized spacers fixed with coach screws & nylon plugs, 2mm thick hot dip GI saddles with all necessary fixing accessories etc. all as per site requirement, tender specification & as directed by Engineer in-charge. Note: Scope of work also includes making necessary holes on wall wherever required for wall crossing, filling of leftover gaps with cement mortar, finishing by applying white cement, etc. all as instructed by EIC. 900 Removal and Reinstatement of False Ceiling for Fire Alarm Detectors / Cabling Work : Provide labour, tools, materials and supervision for the careful removal of existing false ceiling panels/tiles (gypsum, mineral fibre, GRC or as applicable) in areas required for installation of fire alarm detectors, fire alarm cabling, junction boxes, etc. Work includes providing access and cut-outs, safe stacking and labelling of removed panels, temporary supports/bracing, and protection of surrounding finishes. After completion of installation works, reinstate and refix all ceiling panels to their original position, align joints, finish cut edges, and carry out touch-up painting to match the existing finish. Includes cleaning, debris removal to contractor’s vehicle, and a 6-month reinstatement warranty. Note: Scope Includes Careful removal, labelling/storing of panels, temporary supports, minor framework repair, joint alignment, touch-up painting, cleaning, disposal of damaged/broken tiles/panels during the work & replacement with new tile/panels etc. Excess(+) Full Conversion INR
3.2 Unshielded Flexible Cable in existing concealed conduit : Supply, installation, testing and commissioning of 1100 V grade, 2 C x 1.5 Sq.mm Multistranded Copper conductor , PVC insulated, Extruded FRLS PVC Type 'ST3' sheathed Flexible cable confirming to relevant IS standards in existing concealed conduit including termination with suitable copper lugs at Device base/Loop module boxes/Junction boxes/Speakers, ferruling on both sides etc. all as per tender specification & as directed by Engineer in-charge. 600 Removal and Reinstatement of False Ceiling for Fire Alarm Detectors / Cabling Work : Provide labour, tools, materials and supervision for the careful removal of existing false ceiling panels/tiles (gypsum, mineral fibre, GRC or as applicable) in areas required for installation of fire alarm detectors, fire alarm cabling, junction boxes, etc. Work includes providing access and cut-outs, safe stacking and labelling of removed panels, temporary supports/bracing, and protection of surrounding finishes. After completion of installation works, reinstate and refix all ceiling panels to their original position, align joints, finish cut edges, and carry out touch-up painting to match the existing finish. Includes cleaning, debris removal to contractor’s vehicle, and a 6-month reinstatement warranty. Note: Scope Includes Careful removal, labelling/storing of panels, temporary supports, minor framework repair, joint alignment, touch-up painting, cleaning, disposal of damaged/broken tiles/panels during the work & replacement with new tile/panels etc. Excess(+) Full Conversion INR
3.3 Unshielded Armoured cable on Surface : Supply, installation, testing and commissioning of 1100 V grade, 2C x 1.5 Sq.mm Multistranded Copper conductor, XLPE insulated , FR PVC inner sheathed, G.I round wire Armoured, FRLS PVC Type-ST2 outer sheathed confirming to relevant IS standards fixed on existing wall/column/slab/ shaft/ pit/ on on 4-5mm thick hot dip galvanized spacers fixed with coach screws & nylon plugs, 2mm thick hot dip GI saddles with all necessary fixing accessories , etc. all as per site requirement, tender specification & as directed by Engineer in-charge. 525 Removal and Reinstatement of False Ceiling for Fire Alarm Detectors / Cabling Work : Provide labour, tools, materials and supervision for the careful removal of existing false ceiling panels/tiles (gypsum, mineral fibre, GRC or as applicable) in areas required for installation of fire alarm detectors, fire alarm cabling, junction boxes, etc. Work includes providing access and cut-outs, safe stacking and labelling of removed panels, temporary supports/bracing, and protection of surrounding finishes. After completion of installation works, reinstate and refix all ceiling panels to their original position, align joints, finish cut edges, and carry out touch-up painting to match the existing finish. Includes cleaning, debris removal to contractor’s vehicle, and a 6-month reinstatement warranty. Note: Scope Includes Careful removal, labelling/storing of panels, temporary supports, minor framework repair, joint alignment, touch-up painting, cleaning, disposal of damaged/broken tiles/panels during the work & replacement with new tile/panels etc. Excess(+) Full Conversion INR
4 End Termination for surface cable: Providing end joints of 2Cx1.5sq.mm cable at Device base/Loop module boxes/Junction boxes/Speakers etc. by crimping with all jointing materials like solder less copper lugs, brass gland, PVC insulated tape etc. all as required & instructed by the Engineer-in-charge 650 Dismantling and Removal of Existing Fire Alarm (FA) Panel of SoMS Building: Disconnect, isolate, and make safe the existing fire alarm control panel(s), including batteries, power isolators, communication links, and field wiring, in accordance with site electrical isolation permit procedures. Tag and label all cables before disconnection. Dismantle the panel and associated mounting hardware; remove the panel, batteries and redundant accessories from site or hand over to client as directed. Provide temporary rerouting or termination of essential alarm circuits if required until the new panel is installed. Perfor Excess(+) Full Conversion INR
5 Boxes: Fabricated , Supply, installation, testing and commissioning of surface type metal boxes/ junction boxes made out of 16 SWG MS CRCA sheet powder coated with suitable cutouts for cable entry having dimensions suitable for mounting the Detector/Sounder/Speaker all as required & as directed by Engineer in-charge. 1 Job Excess(+) Full Conversion INR
6 Conduits 50 Each Excess(+) Full Conversion INR
7 Concealed HMS PVC conduit Supply, installation, testing and commissioning of 25mm dia. FRLS HMS PVC conduit in wall/ column/slab/beam/ground, complete with necessary bends, tees, and accessories, fix conduit in alignment, pull/fish cables if required, and seal conduit ends with sleeves etc. Note: Scope of work also includes chiseling & cutting in wall/ column/slab/ground, removal of existing conduit (if required), filling the leftover gaps with cement, mortar , finishing by applying white cement & necessary touch up painting etc. as per site conditions & as instructed by EIC. 30 Each Excess(+) Full Conversion INR 2 Construction of chamber for 100mm sluices valve item3 10 Nos
Total in Figures 4 Construction of chamber for 100mm sluice plates item5 10 Nos
Quoted Rate in Figures Select
Quoted Rate in Words
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.05 MB
Tendernotice_1.pdf
PDF • 1.02 MB
DetailedNITforNISERFF.pdf
Tender Documents • 1.00 MB
TechBidSGFforNISERFF.pdf
Tender Documents • 1.78 MB
03Drawing3051.pdf
Tender Documents • 0.20 MB
04Drawing3054.pdf
Tender Documents • 0.18 MB
05Drawing3053.pdf
Tender Documents • 0.19 MB
06Drawin3055.pdf
Tender Documents • 0.15 MB
07Drawing3056.pdf
Tender Documents • 0.18 MB
08Drawing3003.pdf
Tender Documents • 0.41 MB
09Drawing3003A.pdf
Tender Documents • 0.39 MB
TechdatasheetNISERFF.xls
Tender Documents • 0.08 MB
01Drawing3049.pdf
Tender Documents • 0.29 MB
02Drawing3050.pdf
Tender Documents • 0.32 MB
BOQ_933418.xls
BOQ • 0.50 MB
Download all tender documents and submit your bid