REPAIR/MAINT OF POWER/DISTRIBUTION, OCBs/LT OVER HEAD LINES HT/LT SWITCH GEAR CONTROL PANEL, APFC PANELS INSTALLED AT VARIOUS VCBs, ISOLATION TRANSFORMERS, VOLTAGE STABILISERS INSTALLED AT VARIOUS LOCATIONS AT DRDL/ASL AREA UNDER GE(I) RND KBAGH HYD
2021_MES_447414_1
GE I KBAGH TOKEN 23 OF 2021 2022
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
Hyderabad
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
Yes
GE I R and D Kanchanbagh
₹98,000
Yes
3 Jul 2021
1 Jun 2021
30 Jun 2021
1 Jun 2021
28 Jun 2021
15 Jun 2021
1 Jun 2021 - 7 Jun 2021
Amount
Disconnecting electrically and mechanically indoor/outdoor transformers indoor/ourdoor upto 2500 KVA capacity, carefully for major/minor repairs complete all as specified and directed.
M&L for draining out complete transformers oil from the transformers upto 800 KVA capacity at site which found major repair and storing the oil in suitable container (container to be provided by the contractor to keep aside for re -use (after repair) and lifting of core assembly by opening of top cover and other items for checking of faults/repair and lowering and refixing the same in its original position after inspection to make it ready for transportation to carry out rewinding work in workshop including transportation to workshop ( rate is deemed to be inclusive of transportation , T&P and man power ) complete all as specified and directed. Note: Winding shall be measured and paid seperately
All as per item No. 02 above, but for transformer capacity 1000 to 5000 KVA.
Supply and winding rectungular copper conductor of size and thickness as per the OEM specification to obtain the rated impedance values and KVA rating as specified by the OEM for various transformer capacities step down 33/11 KV & 11/0.433 KV for making HV/LV coils including the class 'A' insulation paper, IEC standard, high density laminated board confirming IEC 60763 of required thickness quality all as specified and directed.
Disconnecting and removing of the unserviceable silica gel breather supply and fixing new silica gel breather with silica gel for following capacities of transformers as per existing model and size all as directed.
200 to 400 KVA transformer
500 to 1000 KVA transformer
1600 to 2500 KVA transformer Make:- ETE/SUPER FAB
Supply and fixing HV bushes complete with brass stud and nuts, check nuts, cups etc., complete for transformers up to 500 KVA, 11/0.433 KV and removing burnt out/unserviceable item complete all as specified directed. Note. The rates quoted is deemed to be included the cost of necessary labour charges for draining out & re-filling transformer oil, opening of top cover by unscrewing nut, bolts washers and connections.
All as per item No. 06 above, but for transformer capacity 630 to 2500 KVA.
Dehydration and filtration of transformer oil in transformers/OCB of indoor/outdoor/ isolation type at different location with centrifusing machine electrically operated and achieve die electric strength 60 KV including carrying out oil testing before and after the dehydration process for each transformer complete all as specified and directed. Note : Transformer oil for topping up will be mesured and paid separately under relevant item of schedule.
Supply and topping up of new transformer oil as per IS :335, die electric strength not less than 60 KV with the help of Filtration including draining out old oil plant complete all as specified and directed. Make :- Power Oil/Electrol
Supply and fixing LV bushes with nuts, check nuts etc complete for transformers up to 500 KVA, 11/0.433 KV and removing burnt out/unserviceable item complete all as specified directed. Note.The rates quoted is deemed to be included the cost of necessary labour charges for draining out & re-filling transforer oil, opening of top cover by unscrewing nut, bolts washers and connections.
All as per item No. 10 above, but for transformer capacity 630 to 800 KVA.
All as per item No. 10 above, but for transformer capacity 1000 to 2500 KVA.
All as per item No. 10 above, but for transformer capacity 5000 KVA for 33/11 KV
Supply and fixing in replacement LT studs made out of brass with nuts and washers etc as per existing size and shape complete after removing the unserviceable studs of following capacity of transformer all as specified and directed. Note.The rates quoted is deemed to be included the cost of necessary labour charges for draining out & re-filling transformer oil, opening of top cover by unscrewing nut, bolts washers and connections.
Up to 400 KVA
500 to 750 KVA
1000 to 5000 KVA
Disconnecting the transformer of any capacity and any make, out door/indoor type from platform / two pole structure by opening HT/LT side connection, earth connections etc and shifting it to another location by crane and putting it in proper position including connecting all collections on HT/LT side and earthing strip to neutral and body and testing complete all as specified and directed. Note:- This work shall be carried out as and when required during break downs.
Opening top cover of transformer decanning of complete transformer oil and keeping it in cleaning and dry container taking out complete core with windings and segregating of HT/LT leg coils, dismantling and reassembling of core after thorough cleaning including assembling and jointing connection HT/LT coil in core complete with all insulating material making new star delta connection proper alignment including keeping owen chamber of 100 degree C. temperature to remove the moisture fixing of upper yoke lamination checking tightening of nuts, bolts etc and making good any deficient item testing and putting inside transformer tank after duly cleaning with suitable cleaning media filling of transformer oil closing the top cover properly and testing for capacity up to 400 KVA, 11/0.433 KV complete all as specified and directed.
All as per item No. 16 above, but for capacity 500 to 800 KVA.
All as per item No. 16 above, but for capacity 1000 to1600 KVA.
All as per item No. 16 above, but for capacity 2500 KVA.
All as per item No. 16 above, but for capacity 5000 KVA for 33/11 KV.
Supply and Fix male and female contacts copper/brass as per existing type for RYB phases suitable for 11 KV SF6 circuit breaker complete set and testing including removing worn out contacts from the breaker complete all as specified and directed.
Supply and Fix indicator lamps LED type (R/Y/B) 110 Volts for HT/LT panels/breakers including removing of the unserviceable complete all as specified and directed. Make :- L&T/Alstom/Siemens
Material and labour for XLPE cable end joint, out door cold shrinkable type of 11KV (earthed) grade cable , 120 to 185 sqmm; 3 core complete with jointing material and accessories including removing the unserviceable joint all as specified.
All as per item No: 25 above but indoor type
All as per item No: 25 above but of size 50 to 95 sqmm indoor type
All as per item No: 25 above but of size 50 to 95 sqmm outdoor type Make for item No. 25 to 28 : Raychem/3M/Densons
S&F Cable jointing kit for 11 KV (Earthed) grade cable for straight through cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm.
All as per item No. 29 above but of size 120 sqmm to 185 sqmm
Supply & Fix 110 Volts Power Pack for 11KV Vaccum circuit breaker of any capacity and any type including removing old unserviceable one and all as directed and specified.
Supply and Fix battery of nominal voltage 2V-200 AH @ C10 to 1.75 ECV complete including inter connecting strip of size 120 x 25 x 2 mm complete including testing all as specified and directed. Make :- Amaron model No. AR 200 PC (PSBO200) or equivalent approved in Exide express.
Supply and laying electrical including rubber matt confirming IEC 61111 ISI marked of 30 KV grade, 4 mm thick, 1.0 mtr width, blue coloured anti skid taxture finish ROHS/PAH complete including fixing on ground using necessary chemical adhesive liquid all as specified and directed.
Earthing complete with copper plate electrode 600x 600x 3 mm thick buried directly in ground vertically to a depth not less than 2.25 mtr deep below normal ground level with top edge of earth plate, not less than 1.5 mtr below normal ground level connected to copper strip earth lead of size 20 x 3 mm by means of bolts, nuts/check nuts and washers etc of galvanised iron, protected by galvanised iron pipe light grade 32mm dia upto a length of 4 mtr away from earth electrode and connected to main switch/control board including necessary excavation earth work in any type of soil and PCC 1:3:6 type C1 for earth chamber, 40 mm thick RCC cover slab 1:2:4 type B1 with 6 mm dia TMT Bars at 140 mm cc both ways, watering pipe 20 mm dia light grade GI, funnel, wire mesh, lugs, charcoal and salt etc complete all as shown in Electrical plate No. 3 SSR Part I and testing complete including removing unserviceable earthing all as specified and directed.
Material and labour for Earthing complete with galvanised steel earth plate electrode 600 x 600 x 6 mm thick buried directly in ground vertically to a depth of not less than 2.25 mtrs below ground level with the top edge of earth plate at a depth of not less than 1.5 mtrs below normal ground level, connected to and including galvanised iron earth strip of size 32x6 mm with GI medium grade protection pipe of 40 mm dia for earth electrode upto test point or upto 7.5 mtr whichever is less, by means bolts, nuts, check nuts and washers of galvanised iron including necessary excavation earth work in any type of soil, PCC pit (1:3:6) type C1 and RCC cover (1:2:4) type B1 of 40 mm, watering pipe 20 mm dia GI pipe, wire mesh, funnel, lugs, charcoal, salt etc complete all as per electrical plate No. 3 or SSR Part-I complete all as specified and directed. Note : GI strip and GI pipe 40 mm dia beyond 7.5 metres per earth will be measured and paid separately.
Supply and Fix galvanised iron strip of size 32x6 mm burried in ground/on wall as earth continuity conductor and all as specified and directed.
Supply, Fix and connect earth continuity conductor of copper strip size 20 x 3 mm on wall/trench/floor etc., And through GI pipe complete all as specified and directed.
Supply and Fix GI tubing 40 mm dia light grade for protection of earth conductor and all as specified and directed. Make : Jindal/Prakash/Oswal
Supply, install, test and commissioning LT Panel board, factory made cubical type, outdoor type made out of 3.15 mm thick CRCA sheet totally enclosed with necessary ventilations, weather, dust and vermin proof suitable for working 415 volts, 3 phase, 50 Hz having aluminium bus bars of capacity 400 Amps and half neutral duly colour coaded sleeves and supported with DMC/SMC insulators complete with Digital type multifunction meter V,A KVA, KVAR, PF, KWAH with class 1 accuracy including suitable range of CT's : ASS, VSS, set of three LED phase indicating lamps duly prewired with suitable size of copper conductor cables and shall be mounted in PCC foundation in PCC 1:2:4 type B1, with MS channels, nuts, bolts, washers etc the panel board shall be fabricated as per IEC-60439-1&2 firm as approved by GE and powder coated the panel board with RAL -7032 shade shall be suitable to accommodate and including cost of the following switch gear items including removing unserviceable item complete all as specified and directed :- (a) MCCB 250 Amps, 4 pole, 36 KA thermal magnetic adjustable over load & short circuit ratings, Icu with suitable rotary handles = 100% Ics - 01 No. (I/C) (b) MCCB 100 Amps, 4 pole, 25 KA thermal magnetic adjustable over load & short circuit ratings, Icu = 100% Ics - 01 Nos. (out going) (d) MCCB 63 Amps, 4 pole, 16 KA thermal magnetic adjustable over load & short circuit ratings, Icu = 100% Ics - 03 Nos. (out going)
Ditto all as per Item No: 39 above but out door type made out of 3.15 mm thick CRCA sheet with aluminium bus bar of capacity 600 Amps, including fixing of the following items :- (a) MCCB 400 Amps, 4 pole, 36 KA thermal magnetic adjustable over load & short circuit ratings, Icu = 100% Ics - 01 No. (I/C) (b) MCCB 200 Amps, 4 pole, 25 KA thermal magnetic adjustable over load & short circuit ratings, Icu = 100% Ics - 02 Nos. (out going) (c) MCCB 100 Amps, 4 pole, 16 KA thermal magnetic adjustable over load & short circuit ratings, Icu = 100% Ics - 02 Nos. (out going). Make for Ser 39 & 40 - POWER SWITCH GEAR & CONTROL, HYDERABAD / JAI HIND ELECTRICAL, AMBEGAON PUNE / VIDYT TECHNOLOGIES INDIA PVT LTD HYDERABAD.
Supply & Fix in repairs cable glands of size 300 to 400 sqmm complete all as specified and directed.
Supply & Fix in repairs cable glands of size 185 to 240 sqmm complete all as specified and directed.
Supply & Fix in repairs cable glands of size 120 to 150 sqmm complete all as specified and directed.
Supply & Fix in repairs cable glands of size 70 to 90 sqmm complete all as specified and directed.
Supply & Fix in repairs cable glands of size 35 to 50 sqmm complete all as specified and directed.
Supply & Fix in repairs cable glands of size 16 to 25 sqmm complete all as specified and directed.
Supply & Fix in repairs cable lugs of size 300 to 400 sqmm complete all as specified and directed.
Supply & Fix in repairs cable lugs of size 185 to 240 sqmm complete all as specified and directed.
Supply & Fix in repairs cable lugs of size 120 to 150 sqmm complete all as specified and directed.
Supply & Fix in repairs cable lugs of size 70 to 90 sqmm complete all as specified and directed.
Supply & Fix in repairs cable lugs of size 35 to 50 sqmm complete all as specified and directed.
Supply & Fix in repairs cable lugs of size 16 to 25 sqmm complete all as specified and directed.
M&L for disconnect the existing cable from LT panel and aligning properly and connect in LT panel using lugs of existing size complete all as specified and directed.
M&L for CRCA sheet of thickness 3.15mm out door type enclouser fabricating to a shape required to enclose the out door bus bars providing intermediate openable doors throught out length with SS locks, canopy on top through out the duct as required at site including providing air vents duct, powder coated the enclouser and canopy with not less than 50 micron, fixing the enclouser using necessary angle iron supports, nitrle rubber insulators including removing old bus duct enclouser, screwing bus bars during replacement as required at site. Note : The drawing of enclouser fabrication to be submitted in prior for scrutiny of Engr-in-Charge.
M&L for CRCA sheet of thickness 3.15mm out door type fabricating openable door/canopy for the existing out door type LT Panel with all hinges , door locks and providing air vents as suitable including replacing the old damaged doors and fixing with necessary hinges/welding to the panel, duly powder coated of RAL 7032 coloured not less than 50 micron thickness all as specified and directed.
Material and labour for spray painting of transformer in its position after preparing the surfaces, removing rust, grease, coating and any other surfaces with two coats of synthetic enamel paint (grey color) make smooth finish transformers 11/0.433 KV of following capacities all as specified and directed. Make of paint : Asian/Nerolac/Berger Benz
400 KVA to 500 KVA
630 KVA to 750 KVA
1000 KVA to 2500 KVA
M&L for fabricating feeder distribution layout board on acrylic sheet of thickness 3mm and size as required at site designing the layout as per the sketch provided by the Engr-in-charge using ecosolvent print including lamination and fixing to the wall using necessary fixing nuts, bolts and spares as required at site. The job includes removing of old layout board from its position complete all as specified and directed.
S&F in replacmenet MCCB with rating of 100Amps,415Volts 4pole with 25KA breaking capacity,thermal magnetic adjustable of overload & short circuit release as per IS-13947 & IEC 60947-2 & the service short circuit breaking capacity (Ics) should be 100% of ultimate breaking capcity(Icu) including suitable spreader links & connectors as required at sire for fixing. MCCB should be with suitable spreaders and phase barriers for each terminals with all accessories all as specified and directed.
All As per item No :59 above but 125Amps, 4 pole, 25KA
All As per item No :59 above but 200Amps, 4 pole, 35/36KA
All As per item No :59 above but 250Amps, 4 pole, 35/36KA
All As per item No :59 above but 400Amps, 4 pole, 35/36KA
All As per item No :59 above but 630Amps, 4 pole, 50KA Make for item No. 59 to 63 : L&T/Legrand/C&S
Supply & Fix 25 KVAR power capacitor, type MPP, 415/440V,50HZ, 3ph including removing unserviceable power capacitor complete all as specified
All as per Item No: 65 above but of capacity 20 KVAR
All as per Item No: 65 above but of capacity 15 KVAR
All as per Item No: 65 above but of capacity 10 KVAR
Ditto as per Item No: 65 above but of capacity 05 KVAR Make for Item No: 65 to 69 : L&T/ Havells/Neptune
Supply & Fix Capacitor duty type Contactors, 415 volts Suitable for 25 KVAR capacitor including removing the old unserviceable item all as specified and directed.
All as per Item No. 70 above but suitable to 20KVAR Capacitor
All as per Item No 70 above but suitable to 15KVAR Capacitor
All as per Item No 70 above but suitable to 10KVAR Capacitor
All as per Item No 70 above but suitable to 05KVAR Capacitor
Supply & Fix Control relay (Auxilary contactor), 4amps, 415 volts complete including removing unserviceable item all as specidied and directed.
Supply & Fix Auxilary Contact bolck (1NO + 1NC) for contactor complete including removing unserviceable item all as speicified and directed.
Supply & Fix HRC fuse Link 20 amps complete including removing unserviceable item all as speicified and directed.
Supply & Fix Cylindrical fuse 415 volts 6 amps
Supply & Fix APFC Relay 12 stage type complete with testing inlcuding removing the unserviceable item. Make : L&T/EPCOS/ Havells/ Neptune
Supply & Fix Digital type Power factor meter 3Phase (multi function meter) suitable to existing size and modifications to existing panel complete with testing including removing the unserviceable item. Make : L&T/EPCOS/ Havells/ Neptune
Supply & Fix current transformer 400/5A to 800/5A Class 1, VA 15 50Hz complete including removing unserviceable item all as specified and directed. Make : Kappa/L&T/C&S
M&L Programming the existing APFC relay 8 stage and testing control wiring, capacitors, contactors, MCB complete capacitor bank panel all as specified and directed.
M&L for LT Panel board , fabricating, brazing/welding , hinges, locking arrangenent supports, of any size as directed including nuts, bolts, washers welding, bending, cold or hot, drilling holes for bolts in any shape or size as directed.
M&L for alteration of existing LT panel MCCB slots suitable for accommodating new MCCB as per site requirement complete all as specified and directed.
ELEVATORS MAINTENANCE ENGINEER WORKS
S.S.ENGINEERING CORPORATION
stage.html
html • 0.05 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .