Electrical work connection to (i) Construction of S&T Goomti under work Provision of Second goods shed common running line of CSL-730m at Pharia (ii) Provision of modular Sewage Treatment Plant at NGT nominated stations Belthara Road (BLTR) & Khorshan Road(KRND) Stations.
E-Tender-L-14-26-27
E-Tender-L-14-26-27
Open
4 Months
Unknown (Unspecified Location)
₹0
₹22,500
15 May 2026
15 May 2026
27 May 2026
IS:9537/Part III/ 1983 (Latest Version) with accessories, junction box etc. including clamping etc. as per site requirement.
Description:- Supply, recessing and fixing of PVC conduit pipe 25 mm (Medium) dia conforming to
making chase, plastering/ clamping etc. and making the wall good in and original condition with white washing/ colouring etc. as per site requirement.
Description:- Supply and wiring of 1.5 sq.mm PVC insulated multi stranded copper conductor
(recessed/surface) PVC conduit pipe for wiring of point wiring/circuit wiring/ sub main/ main as required including connection ,testing and commissioning as required.
Description:- Supply and wiring of 2.5 sq.mm PVC insulated multi stranded copper conductor
(recessed/surface) PVC conduit pipe for wiring of point wiring/circuit wiring/ sub main/ main as required including connection ,testing and commissioning as required.
Description:- Supply and wiring of 4.0 sq.mm PVC insulated multi stranded copper conductor
(recessed/surface) PVC conduit pipe for wiring of point wiring/circuit wiring/ sub main/ main as required including connection ,testing and commissioning as required.
VARANASI DIVISION-ELECTRICAL/NORTH EASTERN RLY
single core FR cable conforming to IS:694/1990 (Latest version) and drawing in laid (recessed/surface) PVC conduit pipe for wiring of point wiring/circuit wiring/ sub main/ main as required including connection ,testing and commissioning as required.
Description:- Supply of PVC insulated multi stranded copper conductor single core 1.0 sq.mm PVC
IS:694/1990 (Latest version) and for earthing and drawing in already laid PVC conduit pipe for wiring / sub main/ main as required including connection, testing and commissioning as per site required.
junction box of laid conduit including connections, testing and commissioning as required.
Description:- Supply and erection of Modular Metal boxes concealed Boards suitable for white
regulators. Metal board boxes are to be concealed in wall of size suitable 3 modules. G.I Metal boxes confirming to IS14772:2000 or latest.
suitable 3 modules suitable for mounting of Modular type switches/plug socket, fan regulator and connection to wiring.
cover plate 6 module white and flush metal box size 8"x 3",6 module.
Description:- Supply and erection of Modular Metal boxes concealed Boards suitable for white
regulators. Metal board boxes are to be concealed in wall of size suitable 8 modules. G.I Metal boxes confirming to IS14772:2000 or latest.
suitable 8 modules suitable for mounting of Modular type switches/plug socket, fan regulator and connection to wiring.
finish single mounting cover plate with frame and Modular type piano switches/plug Socket, fan regulators. Metal board boxes are to be concealed in wall of suitable 12 module.
suitable 12 module suitable for mounting of Modular type piano switches /plug socket, fan regulator and connection to wiring.
way) complete in all respect. Switches confirming to IS3854:1997 or latest.
outlet 3/5 Pin 10A complete in all respect. Socket confirming to IS1293:2005 or latest.
(1-way) complete in all respect. Switches confirming to IS3854:1997 or latest.
3/5 Pin 16/20A with shutter complete in all respect. Socket confirming to IS1293:2005 or latest.
MCB 25 Amps for AC Unit complete in all respect.
electronic Regulator complete in all respect. Regulators confirming to IS11037:1984 or latest.
22 VARANASI DIVISION-ELECTRICAL/NORTH EASTERN RLY 22 Description:- Supply, installation, testing & commissioning of 2+4 ways single door, sheet steel, phosphatised, powder painted MCB DBs with Bus bar, neutral link, earth bar and din rail fitted with 63A isolator and 4 Nos 6-16 A , MCB, 10KA, 240/415 50 Hz with enclosure as req, MCB DB conforming to ISI 3032, IS 8623, BS 5486 and MCB conforming to IS 8828:1996, IEC 60898:2002.
Description:- Supply, Installation, Testing and Commissioning of SPN MCB Distribution Board 8 Way
No. MCB 02 Pole 40 Amp 10 KA 230V as incoming and 06 Nos. MCB of 6-20 Amp single pole 10 KA
Description:- Supply of LED Tube light with fitting power rating (in watt): 24, Lamp Efficacy (Lumen/watt) minimum :100 Colour Temperature (in K): 6500, Ingress protection in IP: IP 20,
100-300, Power factor: >/= 0.9, Warranty for free replacement (Years): 1 year, installation, connection with twin core PVC insulated flexible copper conductor cable of size 14/0.193 mm. including testing and commissioning.
Description:- Supply, installation, testing and commissioning of Ceiling fan 1200 mm sweep, Motor: Brushless DC, power consumption (W): 25-30, Winding: Copper, Speed control: 5 step with Remote,
340, Service Value >/= 7.5, conforming to IS:374/1979 and IS:374/2019 or latest, Conformity to Safety Standard IS: 302/1979 connection with twin core PVC insulated flexible copper conductor cable of size 14/0.193 mm including earthing.
Description:- Supply, installation, testing, commissioning of ISI Marked Exhaust fan, sweep
conforming to Indian Standard: IS 2312 (latest), suitable for single phase, 50Hz, AC, connection with 2.5 sq.mm copper conductor and fixing/grouting the nut and bolts of suitable size & including making the hole on wall in original condition i.e. colouring etc as per site requrirement.
Description:- Provision of Earth pit with supply and fixing of GI earth pipe medium class 4.5 mts
earth electrode. And Supply & laying of 6 SWG GI wire as conductor electrode in 15mm dia GI pipe including soldering etc connection should be done as per drawing attached and as per attached Specification.
Description:- Supply & Making Maintenance free Earthing arrangement for HV system. Earth electrode Length = 3000 mm. O Shell dia = 50 mm,O Shell thickness = 3.25 mm, Inner Shell dia 25
CEE/Maintenance Free Earthing/July 2009 Amendment No 1.All material will be supplied by Contractor.
Description:- Supply , testing and commissioning of sheet steel clad dust and vermin proof floor mounted type Junction box of dimension at least (Length-0.75Mtr, Height-0.60 Mtr, Width-0.50 Mtr) with 14 SWG CR sheet for main supporting frame and 16 SWG CR sheet for doors & covers including
and other hardware as required with RYB led indicator, Danger board, end termination of existing cables in junction box with lugs, glands and hardware, cleaning and painting of synthetic enamel spray paint (Double coating) including Making Plinth (Brick work) of size 0.8x0.6x0.6 Mtr for Junction box as per direction of Engineer In-charge at site.
Description:- Supply, fabrication, and erection of fabricated structure angle iron 35x35x5mm
arrangement of different equipment complete with clamp, nut bolt etc complete in all respect as per site requirement.
arrangement. Cable laying work shall be governed by IS :1255/1983.(cable supplied by Railway).
VARANASI DIVISION-ELECTRICAL/NORTH EASTERN RLY
exceeding 400 sqmm direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as req. Cable laying work shall be governed by IS :1255/1983. (cable supplied by Railway). (I) This method involves digging a trench in the ground and laying cable(s) on a bedding of minimum 75 mm riddled soil or sand at the bottom of the trench, and covering it with additional riddled soil or sand of minimum 75 mm and protecting it by means of tiles, bricks or slabs. (II) Depth - The desired minimum depth of laying from ground surface to the top of cable is as follows: Low voltage and control cables -0.75 m, Cables at road crossings 1.00 m, Cables at railway level crossings (measured from bottom of sleepers to the top of pipe)- 1.00 m
Description:- Laying of one number additional XLPE cable of 1100V grade of size exceeding 25
formation including excavation, sand cushioning, protective covering and refilling the trench etc as req. Cable laying work shall be governed by IS :1255/1983.(cable supplied by Railway).
Description:- All work pertaining to Horizontal Directional drilling (HDD/ Boring and trenchless cable it includes supply transportation and insertion of self lubricated HDPE/ CI pipe and laying of cable in
be crossed. The depth of horizontal boring should be minimum 1.64 mtr. from rail flange/ road level. HDPE Pipe of IS: 4984/1995. Note: By using self lubricated HDPE pipe of 117 mm inner dia and 125 mm outer dia in the bore and the laying of cable in the bore under the track/road as per direction of Engineer in charge.
Amp TPN conforming to IS:13947 part III/1983 including hardware and insulators as required.
2x32Amp MCB DP 10 KA as outgoing(For MCCB's Ics= 100% Icu) ) .
bracket complete with two nos clamp nuts, bolts etc. suitable for mounting of LED street light fitting on tubular poles including bending the pipe to the required shape.
Description:- Supply, fixing, testing & commissioning of hot dip galvanized octagonal pole 5 mtr.
concert foundation (1:2:4) etc. The pole shall be complete with holes, anchor bolts, bottom plate etc. As per Tech spec/site requirement IS/IE rules of following type. Weight of the pole should not be less than 40 Kg Single arm type with 1.5 to 2.0 feet long(Weight 5.5 Kg).
Description:- Supply, Erection, testing & commissioning of energy efficient LED street light luminary 60-70 Watt capacity with luminous efficacy greater than equal to 100 made from pressure die cast aluminum housing, toughened front glass cover, fitted with secondary optics, heat sink and integrated electronic driver for long life with IP 65/66 Protection suitable for working on 240 Volt, 50
pole/truss/ roof/ wall by fabrication by suitable clamp/ bracket made/pipe from G.I. flat of 40 x 6 mm approx. duly painted with nut, bolts and washers of 12 mm diameter as per site requirement. The connection shall be carried out through ISI marked, PVC insulated, flexible three-core copper wire from the existing ceiling rose /catenaries/ junction box as per site conditions. The connection cord shall be protected by suitable size of heavy duty flexible PVC conduit.
complete with all accessories. (LED luminaires should conform to min IP:66) including erection, testing, fixing & commissioning of LED street light fitting on pole/wall/structure.
Description:- Supply, Installation, Testing and Commissioning of 70 W High Bay Light Fitting with Pressure die cast aluminium alloy ACD12 housing (Heat sink) for effective thermal management, sturdiness & excellent corrosion resistant, Epoxy powder coated after phosphochromate treatment in metallic grey finish with high efficiency long life SMD LEDs with lumen efficacy of > 130 lm/W with wide beam optics to ensure better uniformity of light distribution. Operating temperature -10 degree
L70B50: 50000 hours, Integral Electronic driver with APFC, lower THD, Output Short Circuit Protection, Surge Voltage Protection, Over voltage protection & other safety test as per IS:15885 Part 2/Sec 13, CCT 5700 K, THD < 10, PF > 0.95 complete in all respect as required. NOTE - Fittings shall be inspected at manufacturer's premises by the RITES. Cost for the inspection shall be borne by the contractor. VARANASI DIVISION-ELECTRICAL/NORTH EASTERN RLY
42 Description:- Installation Testing & commissioning of 1.5 Ton, Split AC(AC supplied by Railway)
mounted Voltage Stabilizer, 220V, input Voltage 140V-260V, single phase complete and conforming to IS :11260/1985 or latest.
Mounting Bracket
Description:- Supply, installation, testing & commissioning of Automatic changeover wall mounted
two any type of Air-Conditioner. Each AC can be kept ON from 1 hour to 24 hours. Complete in all aspect.
Description:- Supply, installation, testing and commissioning of 30 A plug- sockets boards enclosure with 30A PN &E Metal plug & socket along with 25A SP MCB. Sheet steel enclosure shall
MCB shall confirm to IS/IEC -60898-1-2002 (latest version), ISI Marked, with visible coloured contact position indicator and Degree of protection IP20. Provision shall be in conformity with IS :732/1989 (Latest version), IS : 4648/1968 (Latest Version).
TI/SPC/PSI/CLS/0020(12/02) with A &C slip no-1 to 4 or latest.
with erected pole or wall as per technical specification for passing cable of different size.
capacity 10kA with enclosure complete. MCB Conforming to IS :60898 or (Latest version) and enclosure conforming to IS:8623-1 & 3.
capacity 25 kA at 415 V,50Hz, complete with enclosure as required, conforming to IS/IEC:60947(Pt.- II)/2003 or latest.
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
TenderDocument.pdf
ATTACHMENT
Explanatorynote.pdf
ATTACHMENT
Advancecorrectionslipno.11.pdf Advance correction slip no11
ATTACHMENT
Advancecorrectionslipno.11.pdf
ATTACHMENT
Download all tender documents and submit your bid