Executive Engineer
Electric Division JPDCL Udhampur
i.Creation of 25 KVA Sub Station alongwith HT.LT network at New BDC Building ser Pyt. Jaganoo Block Jaganoo ii.Electric poles at different pyts. of Block Majalta under BDC Grants
2024_PDD_259932_1
ED/Udh/13A of 2024-25 dt. 14-10-2024
Open Tender
Electrical Works
Turn-key
365 days
In Village Majalta
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,000
Executive Enginer Electric DivisionJPDCL
₹24,000
7 Nov 2024
14 Oct 2024
5 Nov 2024
14 Oct 2024
4 Nov 2024
14 Oct 2024
14 Oct 2024 - 22 Oct 2024
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Erection of 11 KV line on 9 mtr. long ST poles, 30mm² ACSR Conductor Creation of 25 KVA Sub Station alongwith HT/LT network at New BDC Building ser Pyt. Jaganoo Block Jaganoo
9 mtr. Long ST Pole (ST-410 SP-33)
GI V Cross -arm with top Bracket including clamps
GI Channel X-arm including clamps and Angle for braces
30mm² ACSR Weasel Conductor
11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm.
11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75KV Positive and 80 KV Negative, creepage distance 320mm with fitting
Galvanized Nuts and Bolts
Danger Plates with Clamps
Anti climbing device with clamps
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm
Painting of 9 mtr ST poles with two coats of Aluminium paint.
Cement bottoming 1:2:4 mix as per REC standard 0.5 cum per pole
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Creation of 25 KVA Sub Station alongwith HT/LT network at New BDC Building ser Pyt. Jaganoo Block Jaganoo
11/0.433 KV, 3-phase distribution Transformer 25 KVA with Bimetallic Terminal Connectors Energy Level-2 Aluminium Wound, & with LV Cable box having detachable Aluminium Gland plate
Gapless surge Arrestor, 9 kv, 10 KA , LA with polymer housing stn. Type
11 KV GO AB Switch 3 phase, 3 pole, 200 Amp, vertical
11 KV Horn gap fuse set 3 phase 200 A
70 mm² 1.1 KV Grade, PVC insulated stranded conductor FRLS Type
9 mtr. Long ST pole (ST-410 SP-33)
11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75 Positive and 80 KV Negative, creepage distance 320mm with fitting
GI Channel /Angle/flat of sizes including clamps
Galvanized Nuts and Bolts.
Cement bottoming 1:2:4 mix as per REC standard 0.5 cum per pole
Earthing of sub stn. Excavation of earth pit of dia 650mm & depth 3000mm installation of earthing pipe of 40mm Nominal bore & 4mm wall thickness & length 2.5 mtr. Long as per IS 1239. G.I Strip for neutral earthing of size 25mmx3mm for connection of transforemr body, GO Set & lightening arrestor as per IS 2629/85, GI Nuts & bolts refilled with earth enhancement materials and earth chamber with RCC Slab cover
3-phase 4-wire Prodigy meter with box
LT Fuse Switch made of angle Iron 50X50X6, with aluminium Bus Bar strip 50X6mm fixed on Bus Bar Insualtor including clamps for fixing of switch
Survey, supply, Transportation, Carriage, Erection, Testing and Commissioning for Erection of 3 Phase 4 Wire LT line on 8 mtr. ST poles Creation of 25 KVA Sub Station alongwith HT/LT network at New BDC Building ser Pyt. Jaganoo Block Jaganoo .
8 mtr. Long ST poles (ST-410 SP15)
GI M Clamps for shackle insulator
30mm² ACSR Weasel Conductor
Shackle insulator
Galvanized Nuts and Bolts.
Danger Plates with Clamps
Anti climbing device with clamps
Earthing complete by GI Rod 20mm 2.5 mtr. Long through GI Strip
Painting of 8 mtr ST poles with one coat of Red Oxide
Painting of 8 mtr ST poles with two coat of Aluminium Paint
Cement bottoming 1:2:4 mix as per REC standard 0.5 cum per pole
Survey, supply, Transportation, Carriage, Erection, Testing and Commissioning for Erection of 1 Phase 2 Wire LT line on 8 mtr. PCC poles for Electric poles at different pyts. of Block Majalta under
8 mtr. Long PCC poles (Wl-PCC 200kg_)
8 mtr. Long ST Pole (ST-410 SP-15)
GI M Clamps for shackle insulator
GI U Clamps for shackle insulator
30mm² ACSR Weasel Conductor
Shackle insulator
Galvanized Nuts and Bolts.
Earthing complete by GI Rod 20mm 2.5 mtr. Long through GI Strip
Painting of 8 mtr ST poles with two coat of Aluminium Paint
Cement bottoming 1:2:4 mix as per REC standard 0.5 cum per pole
VEENA CONSTRUCTION CO. (BID ID -2196598)
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .