Loading…
Loading…
Tender Value
₹45.0 L
EMD Value
₹90,000
Closing Date
20 Apr 2026, 3:00 pmClosed
No
No
Single Packet System
Normal Tender
No
Not Applicable
Lowest to Highest
60 days
Expenditure
Capital (Works)
Above/Below/Par
ELECTRICAL
12 conditions · 1 needing a document upload
Technical Eligibility Criteria
I/we the tenderer (s) am/are signing this document after carefully reading the contents.
I/We the tenderer(s) also accept all the conditions of the tender and have signed all the pages in confirmation thereof.
I/we hereby declare that I/we have downloaded the tender documents from Indian Railway website www.ireps.gov.in . I/we have verified the content of the document from the website and there is no addition, no deletion or no alteration to the content of the tender document. In case of any discrepancy noticed at any stage i.e. evaluation of tenders, execution of work or final payment of the contract, the master copy available with the railway Administration shall be final and binding upon me/us.
I/we declare and certify that I/we have not made any misleading or false representation in the forms, statements and attachments in proof of the qualification requirements.
I/We also understand that my/our offer will be evaluated based on the documents/credentials submitted along with the offer and same shall be binding upon me/us.
I/We declare that the information and documents submitted along with the tender by me/us are correct and I/we are fully responsible for the correctness of the information and documents, submitted by us.
I/we certify that I/we the tenderer(s) is/are not blacklisted or debarred by Railways or any other Ministry / Department of Govt. of India from participation in tender on the date of submission of bids, either in individual capacity or as a HUF/ member of the partnership firm/LLP/JV/Society/Trust.
I/we understand that if the contents of the certificate submitted by us are found to be forged/false at any time during process for evaluation of tenders, it shall lead to forfeiture of the Bid Security and may also lead to any other action provided in the contract including banning of business for a period of upto two year. Further, I/we and all my/our constituents understand that my/our offer shall be summarily rejected.
I/we also understand that if the contents of the certificate submitted by us are found to be false/forged at any time after the award of the contract, it will lead to termination of the contract, along with forfeiture of Bid Security/Security Deposit and Performance guarantee and may also lead to any other action provided in the contract including banning of business for a period of upto two year.
I/We have read the clause regarding restriction on procurement from a bidder of a country which shares a land border with India and certify that I am/We are not from such a country or, if from such a country, have been registered with the competent Authority. I/We hereby certify that I/we fulfil all the requirements in this regard and am/are eligible to be considered (evidence of valid registration by the competent authority is enclosed)
43 conditions · 9 needing a document upload
Please furnish documents in support of your claim to fulfil the eligibility criteria as mentioned in tender documents. Each page of copy of documents/ certificates in support of credential, submitted by you shall be self attested/digitally signed by the you or authorized representative of your firm. Only those documents which are declared explicitly by you as "documents supporting the claim of qualifying the laid down eligibility criteria" will be considered for evaluating the offer or otherwise available in the offer.
No deviation shall be accepted, in case of deviation in any term and condition in tender documents offer will summarily be rejected.
Requisite documents proving technical eligibility criteria and technical eligibility criteria have been uploaded along with those required as per explanation given in clause 10 of IRGCC-2022 (Works matter).
All requisite valid documents regarding constitution of business of the bidding firm should be submitted along with the tender as per clause 14 of IRGCC-2022 (Works matter), otherwise their offer will be considered incomplete and shall not be considered.
The tenderer whether sole proprietor / a company or a partnership firm / joint venture (JV) / registered society / registered trust / HUF / LLP etc if they want to act through agent or individual partner(s), should submit along with the tender, a copy of power of attorney duly stamped and authenticated by a Notary Public or by Magistrate in favour of the specific person whether he/they be partner(s) of the firm or any other person, specifically authorizing him/them to sign the tender, submit the tender and further to deal with the Tender/ Contract up to the stage of signing the agreement except in case where such specific person is authorized for above purposes through a provision made in the partnership deed / Memorandum of Understanding / Article of Association /Board resolution, failing which tender shall be summarily rejected. A separate power of attorney duly stamped and authenticated by a Notary Public or by Magistrate in favour of the specific person whether he/they be partner(s) of the firm or any other person, shall be submitted after award of work, specifically authorizing him/them to deal with all other contractual activities subsequent to signing of agreement, if required. Note: A Power of Attorney executed and issued overseas, the document will also have to be legalized by the Indian Embassy and notarized in the jurisdiction where the Power of Attorney is being issued. However, the Power of Attorney provided by Bidders from countries that have signed the Hague Legislation Convention 1961 are not required to be legalized by the Indian Embassy if it carries a conforming Appostille certificate. Reference: para 15 of IRGCC-2022 (Works matter),otherwise their offer will be considered incomplete and shall not be considered.
Partnership firm, if applicable in the instant tender, should submit all valid requisite documents and full fill the stipulations as per clause 18 of IRGCC-2022 (works matter), otherwise their offer will be considered incomplete and shall not be considered.
Please enter the percentage of local content in the material being offered. Please enter 0 for fully imported items, and 100 for fully indigenous items. The definition and calculation of local content shall be in accordance with the Make in India policy as incorporated in the tender conditions.
Please submit your Bank details of the firm /individual/JV/partnership etc. i.e. Name of the Bank along with Bank Branch code, account No., IFSC Code, PAN Number and other necessary & relevant documents.
Tenderers are advised to visit the site of work to ascertain all aspects of the site conditions viz accessibility, availability of approach road, nature of the soil, availability of material, availability of labour etc. that may be encountered in course of execution of work.
Tenderer should see the website for the corrigendum/addendum to the NIT/tender document, if any that may be uploaded prior to tender opening (inclusive) as there will not be any separate communication for that.
The tenderer for carrying any construction work in Uttar Pradesh must get themselves registered from the registering Officer under Section - 7 of the Building and Other Construction Workers Act, 1996 and rules made there-to by the Uttar Pradesh Govt. and submit certificate of Registration (Labour Department). For enactment of this Act, the tenderer shall be required to pay cess @ 1% of cost of construction work to be deducted from each bill.
The contractor(s) shall observe all the formalities, perform all the acts and abide by all the provisions contained in the Contract Labour Act-1970 and Contract Labour Central Rules, 1971 which in addition to other stipulations provides that the contractor(s) shall obtain license(s) from appropriate licensing officer of the area before commencement of the work and shall produce a copy thereof along with the original to the Railway office, which will be returned to the contractor after verification.
If any complaint is received against the contractor regarding violation of contract laws, (exposing Principal Employer to the risk of legal proceedings under labour laws), the guilty contractor will be black listed and their contract shall be terminated following the due procedure, apart from initiating criminal proceedings against him with the help of Labour department officials. (Authority: RB letter no.2008/E (LI)/AT/CNR/3, dated 24.01.2018).
The tenderer has to submit necessary documents in compliance of clause 10 to 18 (Part-I) of IRGCC 2022 (Works matter) mandatorily, otherwise offer will be considered as Incomplete Offer and accordingly shall not be considered.
It is the responsibility of the tenderer to see corrigendum, if any, to tender notice up to the date of tender opening. IRGCC-2022 (works matter) is for reference only. Any correction issued by competent authority up to date of opening will be applicable. Tenderer should quote accordingly.
Railways reserves the right to accept or reject any or all the tenders and to award the work in whole or in part without assigning the reason for any such action.
It is to be noted that tenderer digital signature on the E-Tender form will be considered as confirmation that tenderer have read and accepted all the conditions laid down in the documents as well as related specification of items, schedule & quantity of items in the tender, consisting of techno-commercial offer form (including special conditions attached to E-Tender) and Financial offer form.
The quantities shown in the attached Schedule are given as a guide and are approximate only and are as a guide to give the tenderer(s) an idea of quantum of work involved. Quantities are subject to variation according to the needs of the Railway. The Railway does not guarantee work under each item of the Schedule. The Railway reserves the right to increase/ decrease and/or delete or include any of the quantities given above and no extra rate will be allowed on this account.
In case of any information submitted by tenderer is found to be false forged or incorrect at any time during process for evaluation of tenders, it shall lead to forfeiture of the tender Earnest Money Deposit besides banning of business for a period of upto five years. In case of any information submitted by tenderer is found to be false forged or incorrect after the award of contract, the contract shall be terminated. Earnest Money Deposit (EMD), Performance Guarantee and Security Deposit available with the railway shall be forfeited. In addition, other dues of the contractor, if any, under this contract shall be forfeited and agency shall be banned for doing business for a period of upto five years.
Opening of e-tender online:- The e-tenders will be opened online using the IREPS portal. No representative is required to be present for opening of tender and taking notes of rates quoted and ranking as the complete details of rates etc. of all the bidders shall be available to the bidders in the website after the opening of the tender.
In case the date of closing mentioned in the Notice Inviting Tender is declared a holiday/bandh/strike etc. on any account, the date of closing tender online will not be changed as the application in the website of IREPS does not permit submission of any offer after closing date and time of the tender. However, opening of tenders online will be on any convenient day after the closing date/time of tenders.
All the bidders / tenderers should ensure that they are GST compliant and their quoted tax structure / rates are as per GST Law ( Ref - Railway Board letter No.2008/RS(G)/777/1 Dated - 29/5/2017 )
GCC 2022 for works Contract
The Bid Security shall be deposited either in cash through e- payment gateway or submitted as Bank Guarantee bond from a scheduled commercial bank of India or as mentioned in tender documents. The Bank Guarantee bond shall be as per Annexure- VIA and shall be valid for a period of 90days beyond the bid validity period. In case, submission of Bid Security in the form of Bank Guarantee, following shall be ensured: i. A scanned copy of the Bank Guarantee shall be uploaded on e-Procurement Portal (IREPS) while applying to the tender. ii. The original Bank Guarantee should be delivered in person to the official nominated as indicated in the tender document within 5 working days of deadline of submission of bids. iii. Non submission of scanned copy of Bank Guarantee with the bid on e-tendering portal (IREPS) and/or non submission of original Bank Guarantee within the specified period shall lead to summary rejection of bid. iv. The Tender Security shall remain valid for a period of 90 days beyond the validity period for the Tender. v. The details of the BG, physically submitted should match with the details available in the scanned copy and the data entered during bid submission time, failing which the bid will be rejected. vi. The Bank Guarantee shall be placed in an envelope, which shall be sealed. The envelope shall clearly bear the identification "Bid for the ***** Project" and shall clearly indicate the name and address of the Bidder. In addition, the Bid Due Date should be indicated on the right hand top corner of the envelope. vii. The envelope shall be addressed to Sr.DEE/G/PRYJ, DRM office Nawab Yusuf Road, Prayagraj-211001. viii. If the envelope is not sealed and marked as instructed above, the Railway assumes no responsibility for the misplacement or premature opening of the contents of the Bid submitted and consequent losses, if any, suffered by the Bidder.
Electrical work in connection with the work of "Prayagraj-Improvement to DRM Office building & campus".
ELG-159-2526
ELG-159-2526
Open
Works - General
6 Months
Prayagraj, Uttar Pradesh
₹0
₹90,000
20 Apr 2026
27 Mar 2026
6 Apr 2026
56 items across 1 schedule · ₹45,01,255.89 total
| # | Description | Unit | Qty | Rate | Amount |
|---|---|---|---|---|---|
| 1 | Supply and recessing/fixing of PVC Conduit pipe 25 mm (Medium) conforming to IS 9537/ Part III/1983 (Latest version) with accessories,junction box, etc including making chase, plastering/ clamping etc as per technical specifications. Inspection by- Consignee. | Metre | 2500.00 | 47.22 | 1,18,050 |
| 2 | Supply of PVC insulated multi stranded copper conductor single core FRLSH cable 2.5 Sq. mm conforming to IS: 694 (latest version), and drawing in laid (recessed /surface) PVC conduit pipe for wiring of point wiring/ circuit wiring/sub main/ Main as required as per technical specification including connections, testing and commissioning. Inspection by- Consignee. | Metre | 2500.00 | 23.55 | 58,875 |
| 3 | Supply of PVC insulated multi stranded copper conductor single core FRLSH cable 4.0 Sq. mm conforming to IS: 694(latest version), and drawing in laid (recessed /surface) PVC conduit pipe for wiring of point wiring/ circuit wiring/sub main/ Main as required as per technical specification including connections, testing and commissioning. Inspection by- Consignee. | Metre | 2000.00 | 36.37 | 72,740 |
| 4 | Supply of PVC insulated multi stranded copper conductor single core FRLSH cable 6.0 Sq. mm conforming to IS: 694 (latest version), and drawing in laid (recessed /surface) PVC conduit pipe for wiring of point wiring/ circuit wiring/sub main/ Main as required as per technical specification including connections, testing and commissioning. Inspection by- Consignee. | Metre | 1000.00 | 50.19 | 50,190 |
| 5 | Supply of PVC insulated multi stranded copper conductor single core HRFR cable 1.5 Sq. mm conforming to IS: 694 (latest version), and drawing in laid (recessed /surface) PVC conduit pipe for Earth wire as required as per technical specification including connections, testing and commissioning. Inspection by- Consignee. | Metre | 3000.00 | 15.22 | 45,660 |
| 6 | Supply, Erection, Testing and Commissioning of following Modular Type switch 10 A (1-way) complete in all respect. Inspection by- Consignee. | Numbers | 150.00 | 64.99 | 9,748.5 |
| 7 | Supply, Erection, Testing and Commissioning of following Modular type Plug socket outlet 2/3 Pin 10 A complete in all respect. Inspection by- Consignee. | Numbers | 36.00 | 107.45 | 3,868.2 |
| 8 | Supply, Erection, Testing and Commissioning of following Modular Type switch 20 A (1-way) complete in all respect.Inspection by- Consignee. | Numbers | 60.00 | 132.59 | 7,955.4 |
| 9 | Supply, Erection, Testing and Commissioning of following Modular type Plug socket outlet 5/3 Pin 20 A complete in all respect. Inspection by- Consignee. | Numbers | 60.00 | 153.37 | 9,202.2 |
| 10 | Supply and Erection of Modular type switch blanking set to fill the blank space White finished mounting cover plate complete in all respect.Inspection by- Consignee. | Numbers | 20.00 | 7.86 | 157.2 |
| 11 | Supply and Erection of Junction Box cover POP type complete in all respect including hardware material for fixing. Inspection by- Consignee. | Numbers | 200.00 | 5.23 | 1,046 |
| 12 | Supply and Erection of white finish single mounting cover plate with base frame suitable 3 module suitable for mounting of Modular type piano switches/ plug Socket, fan regulator and connection to wiring. Inspection by- Consignee. | Numbers | 40.00 | 69.33 | 2,773.2 |
| 13 | Supply and Erection of white finish single mounting cover plate with base frame suitable 8 module suitable for mounting of Modular type piano switches/ plug Socket, fan regulator and connection to wiring. Inspection by- Consignee. | Numbers | 60.00 | 146.45 | 8,787 |
| 14 | Supply and Erection of white finish single mounting cover plate with base frame suitable 12 module suitable for mounting of Modular type piano switches/ plug Socket, fan regulator and connection to wiring. Inspection by- Consignee. | Numbers | 40.00 | 211.44 | 8,457.6 |
| 15 | Supply and Erection of Modular Metal boxes concealed Boards suitable for mounting of 3 module white finish single mounting cover plate with Frame and Modular type piano switches/ plug Socket, fan regulators. Metal board boxes are to be concealed in wall. Inspection by- Consignee. | Numbers | 80.00 | 45.48 | 3,638.4 |
| 16 | Supply and Erection of Modular Metal boxes concealed Boards suitable for mounting of 8 module white finish single mounting cover plate with Frame and Modular type piano switches/ plug Socket, fan regulators. Metal board boxes are to be concealed in wall. Inspection by- Consignee. | Numbers | 120.00 | 79.73 | 9,567.6 |
| 17 | Supply and Erection of Modular Metal boxes concealed Boards suitable for mounting of 12 module white finish single mounting cover plate with Frame and Modular type piano switches/ plug Socket, fan regulators. Metal board boxes are to be concealed in wall. Inspection by- Consignee. | Numbers | 80.00 | 128.24 | 10,259.2 |
| 18 | Supply and Installation of Ceiling rose 3 plate as per IS No. 371/1999 (Latest Version) including connections, Testing and commissioning as per Tech. Specification. Inspection by- Consignee. | Numbers | 400.00 | 15.12 | 6,048 |
| 19 | Supply and recessing/fixing on surface of 6 SWG GI wire conforming to IS: 280/2006 (Latest Version) for loop earthing as required for earthing of installation as per IE Rule. Inspection by- Consignee. | Metre | 3000.00 | 9.54 | 28,620 |
| 20 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CM/M/W) minimum 6.00, Air delivery minimum 210 Cum/Min , 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. Inspection by- Consignee. | Numbers | 40.00 | 2,208.91 | 88,356.4 |
| 21 | Termination of LT XLPE cables of various sizes (One Job means all 4 cores of cables). Inspection by- Consignee. | Numbers | 25.00 | 116.96 | 2,924 |
| 22 | Supply and laying of B class, 50 mm dia, GI pipe of for cable riser/road crossing as required and as per relevant technical specification. Inspection by- Consignee. | Metre | 100.00 | 121.37 | 12,137 |
| 23 | Collecting, Transporting from SSE/PS/ store to site, laying, testing, and commissioning of above LT cable . Laying direct in ground (Including excavation, sand cushioning, protection brick covering and refilling the trench etc.), direct in RCC/Metal pipes in rod/track crossings and on surface/required in wall/in concrete floor by cutting recessed and finished originally as required as per relevant technical specifications. | Metre | 1000.00 | 63.91 | 63,910 |
| 24 | Supply, replacement, fixing, testing, connecting and commissioning of 120 Watt or above LED flood light fittings as per IS:10322. LED Luminaries:-(1) Acomplete LED lighting unit consisting of a light source and Potted driver to gether with parts of distribute lights,to position and protect the light source,and to connect the light source to a branch circuit.The light source itself may be an LED array and LED module,or an LED lamp.(2):-Supplied LED luminaries shall confirm to IS:16101(2012) IS :16106(2012).Light Source(LED) in the Luminaries should be of make:-(1):-NICHIA/ CREE/OSRAM/ SEOUL/PHILIPS/ LUMILEDS /LEDNIUM. (2):-LEDs to IS:16105 (2012). IS:16108(2012), IEC:62471. Type LED:- High power LED, SMD (Surface Mounting device)/COB (Clip on board). 1.Input operating voltage :-105-295 V AC.2:- Normal Voltage-220VAC,3.Driver type: constant current driver with short circuit protection. 4.LED life:- >50000 burning hours. 5.Depreciation:- 30% max. after 50000 burning hours. 6.Control of distribution:-Full cut off. 7.Surge protection: 4KV. 8.Drive component:Industrial grade only. 9.Efficiency of driver electronic: > 85%. 10.Beam angle:>=140 degree along with road and >=80 degree across theroad. 11.Colour temperature:5000-6500K. 12.Colour rendering index(CRI):>=75. 13.Ingress protection:IP- 66.14.Lumen output: >120 lumens/watt. 15.Power factor:->0.95. 16.Total harmonics distortion (THD):-<15%. 17. Lamp cover: Toughened glass or UV stabilsed polycarbonate. 18.Finishing: Power coated/Anodized. 19.Secondry optics:poly carbonate reflector/ poly carbonates lens. 20.Construction of housing: extruded aluminum/CRCA/Pressure diecast aluminum. 21.Mounting:Suitable for existing pole/Truss/Lantern mounted. 22.Certificate:Firm tosubmit LM80 (In respect of LED used) & LM79 (Inrespect of luminaire used) test certificate from National/International accredited Laboratory and OEM certificate for compliance of BIS/IEC. 23.Warranty:Firm to submit warranty certificate for five year along with the supply. Allfittings shall be fitted with new suitable bend/elbow with clamp and proper nut and bolt and connection with twisted twin flexible cord of minimum size 16/1mm copper conductor as per relevant technicalspecification. Materials paraMtrs.s must remain unchanged during entire warranty period. Inspection by- Consignee. | Numbers | 25.00 | 6,128.43 | 1,53,210.75 |
| 25 | Supply, fixing, testing, connecting and commissioning of 300 mm sweep Exhaust Fan suitable for 230 volts, 50 Hz AC supply, 1400 RPM heavy duty with wiring and flexible PVC pipe as required. Inspection by- Consignee. | Numbers | 20.00 | 1,565.53 | 31,310.6 |
| 26 | Supply, replacement, fixing, testing, connecting and commissioning of energy efficient luminaries complete with all accessries of capacity 18/20 watt, 4 feet length, T8 LED lamps with sutable current control driver circuit ,suitable for surface/recessed mounting.LED Luminaries:-(1) A complete LED lighting unit consisting of a light source and potted driver together with parts of distribute light,to position and protect the light source,and to connect the light source to a branch circuit.The light source itself may be an LED array and LED module, or an LED lamp. (2):- Supplied LED luminaries shall confirm to IS:16101(2012) IS :16106(2012) .Light Source (LED) in the Luminaries should be of make:- (1):- NICHIA/ CREE/OSRAM/ SEOUL/ PHILIPS/LUMILEDS /LEDNIUM. (2):-LEDs to IS: 16105(2012). IS:16108(2012), IEC:62471.1.Input operating voltage :-105-295 V AC. 2:-Normal Voltage-220V AC.3.Driver type: constant current driver with short circuit protection(For tube light). 4.Control of distribution:-Full cut off. 5.Drive component :Industrial grade only .6.Efficiency of driver electronic: > 85% (For tube light).7.Colour temperature:5000-6500K(For tube light). 8.Colour rendering index(CRI):>75(For tube light). 9.Ingress protection :IP-20. 10.Lumen output: >100 lumens/[email protected] drive current(For tube light). 11.Power factor:- >0.90(For tube light). 12.Total hormonics distrotion(THD):-<20% (For tube light). 13. Lamp cover :Acrylic cover which does not result in loss of lumens. 14. Finishing:Power coated /Anodized. 15.Secondry optics:poly corbonate reflector/ poly carbonate lens. 16. Construction of housing: extruded aluminum/CRCA/Pressure die cast aluminum. 17.Mounting :Suitable for surface mounting/recessed mounting. 18. Certificate: Firm to submit LM80(In respect of LED used) & LM79 (In respect of luminare used) test certificate from National/International accredited Laboratory and OEM certificate for complience of BIS/IEC. 19.Warranty:Firm to submit warranty certificate for five year along with the supply.All fittings shall be fitted as surface mounting/recessed mounting with twisted twin flexible cord of minimum size 16/0.2 mm copper conductor as per relevant technical specification. Materials praMtrs.s must remain unchanged during entire warranty period. 1x18/20 watt. Inspection by- Consignee. | Numbers | 100.00 | 313.49 | 31,349 |
| 27 | Supply, erection, testing and commissioning of One phase distribution board comprising of one no. 32/40 amps DP MCB with 40 A ELCB/RCCB as incoming and 4 nos. 10 amps SP MCB , 4 nos. 20 A SP MCB as outgoing complete with copper bus bars, neutral link and other accessories housed in CRCA sheet enclosure with double door type. Inspection by- Consignee. | Numbers | 10.00 | 3,335.24 | 33,352.4 |
| 28 | Supply, replacement, fixing, testing, connecting and commissioning of 72 Watt or above LED street lights fittings as per IS:10322. LED Luminaries:-(1) A complete LED lighting unit consisting of a light source and potted driver together with parts of distribute lights,to position and protect the light source,and to connect the light source to a branch circuit. The light source itself may be an LED array and LED module, or an LED lamp.(2):-Supplied LED luminaries shall confirm to IS:16101 (2012) IS :16106(2012). Light Source(LED) in the Luminaries should be of make:- (1):-NICHIA/ CREE/OSRAM/ SEOUL/ PHILIPS/LUMILEDS /LEDNIUM. (2):-LEDs to IS:16105(2012). IS:16108(2012), IEC:62471. Type LED:- High power LED,SMD(Surface Mounting device)/COB(Clip on board). 1.Input operating voltage :-105-295 V AC.2:- Normal Voltage-220V AC,3.Driver type: constant current driver with short circuit protection. 4.LED life:- >50000 burning hours. 5.Depreciation:- 30% max.after 50000 burning hours.6.Control of distribution:-Full cut off. 7.Surge protection:4KV. 8.Drive component :Industrial grade only.9.Efficiency of driver electronic: > 85%.10.Beam angle:>=140 degree along with road and >=80 degree across the road.11.Colour temperature:5000-6500K. 12.Colour rendering index(CRI):>=75. 13.Ingress protection :IP-66.14.Lumen output: >120 lumens/watt.15.Power factor:->0.95. 16.Total harmonics distortion(THD):- <15%.17.Lamp cover :Toughened glass or UV stabilised poly carbonate. 18.Finishing:Power coated/Anodized. 19.Secondry optics:poly carbonate reflector/ poly carbonates lens. 20.Construction of housing: extruded aluminum/ CRCA/Pressure die cast aluminum. 21.Mounting :Suitable for existing pole/ Truss/ Lantern mounted. 22.Certificate:Firm to submit LM 80(In respect of LED used) & LM79 (In respect of luminare used) test certificate from National/ International accredited Laboratory and OEM certificate for compliance of BIS/IEC. 23.Warranty:Firm to submit warranty certificate for five year along with the supply. All fittings shall be fitted with new suitable bend/elbow with clamp and proper nut and bolt and connection with twisted twin flexible cord of minimum size 16/1 mm copper conductor as per relevant technical specification. Material paraMtrs.s must remain unchanged during entire warranty period. Inspection by- Consignee. | Numbers | 40.00 | 2,556.58 | 1,02,263.2 |
| 29 | Supply and erection of 6 Mtr. Galvanized (as per BS EN ISO 1461) octagonal pole with base plate 220x220x12mm, top 70mm and bottom 130mm of 3mm thick sheet suitable for maximum wind speed upto 160 Km/Hr. including foundation bolts and foundation with M 20 grade RCC and FE 415 grade reinforcement (450x450x800 mm deep ) (foundation should be as per design approved by pole manufacturer) GI base plate G.I. anchor plate etc.as required including supplying and fixing of double arm hot dipped galvanized bracket suitable for street light fittings and supplying and drawing of 3x2.5Sq.mm FRLS copper conductor single core cable from junction box with two Nos 6/10AMP MCB to luminaire complete including termination with copper lugs as required. Inspection by- Consignee. | Numbers | 20.00 | 8,936.17 | 1,78,723.4 |
| 30 | Supply and instalation of 1-phase 5KVA, 120/96Volt DC input UPS with Battery Bank of 12V, 10 Nos tubular battereies of Okaya or any superior approved make each of 150AH for Emergency Supply of Metring system and sub- station lightings .After completion of the works all materials to be deposited to the concern SSEs stores. Inspection by- Consignee. | Numbers | 1.00 | 1,52,850.67 | 1,52,850.67 |
| 31 | Supply of heavy duty aluminium stool type folding ladder having "C" shapes section of size 16"x12" on top suitable for height upto 12 feet complete similar to Sumer make design no. AL- 201/8818 (heavy duty) or equivalent. Inspection by- Consignee. | Numbers | 2.00 | 10,869.09 | 21,738.18 |
| 32 | Supply, laying, fixing, testing and commissioning of 10.0 sq mm FRLS, PVC insulated multi stranded copper conductor single core cable 1100 Volts confirming to IS-694 (latest version) of approved make in the existing PVC conduit for wiring of point wiring/circuit wiring/sub main/main as per Tech Spec-I attached, IS & IE rules. | Numbers | 1000.00 | 70.63 | 70,630 |
| 33 | Electric Pole cutting (Pole to be deposited in Consigence's office.) | Numbers | 10.00 | 583.58 | 5,835.8 |
| 34 | Design, Manufacturing, Supply, Erection,testing andcommissioning of LT switchgearpanel board of 02mm Tk. Dia pressed CRSsteel sheet panel shall betreated for anticorrosion treatment and finishedwithsmoke gray paint as per technicalspecificationno. Sr.DEE/G/ALD/Panel- 94/113 Comprising withasunder:-........MCCB of 400 A, 36 kAStandardbreaking capacity, 415 volt, 3Phase 4 Pole currentrating 400Amp. | Numbers | 1.00 | 19,742.88 | 19,742.88 |
| 35 | MCCB of 250 A, 36 kA Standard breakingcapacity,415 volt, 3 Phase 4 Pole currentrating 250 Amp. | Numbers | 5.00 | 10,779.46 | 53,897.3 |
| 36 | MCCB of 125A, 36 kA Standard breakingcapacity,415 volt, 3 Phase 4 Polecurrentrating 125 Amp. | Numbers | 8.00 | 6,568.96 | 52,551.68 |
| 37 | MCCB of 63A, 36 kA Standard breakingcapacity,415 volt, 3 Phase 4 Pole currentrating 63 Amp. | Numbers | 5.00 | 3,184.81 | 15,924.05 |
| 38 | Manual Changeover Switch 400A 4 Pole as perrelevant spec. | Numbers | 1.00 | 27,659.26 | 27,659.26 |
| 39 | "Supply, fixing, testing, connectingandcommissioning of Outgoing/FeederPanelMounted Multi-function Mtrs. withAccuracyClass 1 as per IEC 62053-21 or Class0.5,0.5S as per IEC 62053-22.LED Mtrs. Cl 1withRS485: Mtrs. should have followingfeatures built-inLED • Flush mounting 96 x96 mm • True RMSmeasurement •Password protection provision forsecurity •Site selectable for 3 Phase 4 wire, 3Phase3 wire, 1 Phase, CT Secondary1A/5A,Universal Auxiliary Supply 80- 300VAC/DC,Input Voltage Measurement 50- 500VAC,64 samples/ cycle The Mtrs. should be abletoread/display following paraMtrs.sInstantaneousParaMtrs.s (V1, V2, V3,V12, V23, V31, Avg (VLN, VLL), A1, A2,A3, Aavg, F, PF-1, PF-2, PF-3, PF(Avg) W1,W2, W3, W (total) VA1, VA2, VA3,VA(total) Cumulative ParaMtrs.s (Import Wh,ImportVah, Import load hours, Reset (old)CumulativeparaMtrs.s (Import Wh, Importload hours,Communication (RS485 ModusRTU).complete withallaccessories. 56" | Numbers | 18.00 | 2,557.48 | 46,034.64 |
| 40 | Supply of Indicator lamps with suitable holder. | Numbers | 57.00 | 81.28 | 4,632.96 |
| 41 | Fabrication works and insulated Aluminumbus barsof 800A capacity for phases &800A capacity forneutral Bus bar shall besuitably insulated with heatshrinkablesleeves/ epoxy coating/insulating taptowithstand the test voltage of 2.5 KVCopper stripfor connection outgoing aswell as incoming withsuitable size beprovided.Inspection by- Consignee for item no 34 to 41 due to LT panel. | Numbers | 1.00 | 45,718.92 | 45,718.92 |
| 42 | Supply erection, testing & commissioning of basic Earthing Kit 1set as per RDSO spec. No RDSO/PE/SPEC /PS/0109(REV.0)-2008, Amendment '1' or latest specification. Inspection by- Consignee. | Numbers | 10.00 | 12,665.01 | 1,26,650.1 |
| 43 | Supply, fixing, testing and commissioning of wall mounted/recessed LT Double door 4Way distribution board made up of steel sheet, phosphatised powder painted complete with neutral link, earth point, Din rail and prewired with following items to be fixed in distribution board and site requirement. Inspection by- Consignee. | Numbers | 5.00 | 329.86 | 1,649.3 |
| 44 | Supply, fixing, testing and commissioning of wall mounted/recessed LT Double door 6Way distribution board made up of steel sheet, phosphatised powder painted complete with neutral link, earth point, Din rail and prewired with following items to be fixed in distribution board and site requirement. Inspection by- Consignee. | Numbers | 5.00 | 498.08 | 2,490.4 |
| 45 | Supply, fixing, testing and commissioning of DP RCBO's 10 (2P, 30 mA) Amp outgoing confirming to IS: 12640-2,IEC-61009-1 or latest. Inspection by-Consignee. | Numbers | 30.00 | 2,520.12 | 75,603.6 |
| 46 | Supply, fixing, testing and commissioning of DP RCBO's 16 (2P, 30 mA) Amp outgoing confirming to IS: 12640-2,IEC-61009-1 or latest. Inspection by-Consignee. | Numbers | 25.00 | 2,520.12 | 63,003 |
| 47 | Supply, fixing, testing and commissioning of DP RCBO's 20 (2P, 30 mA) Amp outgoing confirming to IS: 12640-2, IEC-61009-1 or latest. Inspection by-Consignee. | Numbers | 23.00 | 2,520.12 | 57,962.76 |
| 48 | Supply, fixing, testing and commissioning of DP RCBO's 25 (2P, 30 mA) Amp outgoing confirming to IS: 12640-2, IEC-61009-1 or latest. Inspection by-Consignee. | Numbers | 20.00 | 2,520.12 | 50,402.4 |
| 49 | Supply, erection, testing & commissioning of High Mast tower 12 mtr long alongwith 4 tros 200 W LED fittings complete with all accessories as per specification no. CEE/C/TKJ/NR-14. Inspection by- RITES. | Numbers | 2.00 | 5,59,219.5 | 11,18,439 |
| 50 | Supply, fixing, testing and commissioning of BLDC Wall Bracket Fan of sweep size - 400mm, suitable for operation in 1 Ph,230V, 50Hz supply system including all accessories. Inspection by- Consignee. | Numbers | 80.00 | 4,703.17 | 3,76,253.6 |
| 51 | Supply, fixing, testing & commissioning of Ventilating fan 15 watt. Inspection by- Consignee. | Numbers | 20.00 | 5,212.49 | 1,04,249.8 |
| 52 | Supply and commissioning of PVC Pipe 25 mm. Inspection by-Consignee. | Numbers | 20.00 | 82.33 | 1,646.6 |
| 53 | Supply, fixing, testing and commissioning of 250 mm sweep fresh air fan complete and conforming to Explanatory Note. Inspection by- Consignee. | Numbers | 27.00 | 1,041.12 | 28,110.24 |
| 54 | Supply, fixing, testing & commissioning of 18 Watt LED Octane + LED Panel Square Light, 6500 K Slim, Compact, Aluminum die cast edge lit panel, Recess mounted square fixture with opal diffuser and separate electronic driver. Ceiling cutout (210 X 210) mm, Height 23 mm +-1 mm. Inspection by-Consignee. | Numbers | 100.00 | 1,410 | 1,41,000 |
| 55 | Supply, fixing, testing and commissioning of LED down lighter, housing aluminum die cast, white powder coated and PMMA diffuser having system wattage equal to 15-18 Watt complete with all mounting arrangement, accessories complete of make Phillips, Bajaj, Havells or similar conforming to CEE/NR's spec. No. CEE/NR/121- lect/PS/2018 (Rev- '3') or latest at Tech Spec-III attached & PCEE/NR's spec. No. PCEE/NR/121- Elect/PS/2019 (Rev- '4') at Tech Spec-IV attached or latest. Inspection by- Consignee. | Numbers | 150.00 | 623.59 | 93,538.5 |
| 56 | Supply, fixing, testing, connecting and commissioning of 24/36 watt 2x2 LED lights fittings as per IS:10322 , recess LED Fitting 24/36 watt, suitable for surface/ recessed mounting. LED Luminaries:-(1) A complete LED lighting unit consisting of a light source and driver together with parts of distribute light, to position and protect the light source, and to connect the light source to a branch circuit.The light source it self may be an LED array and LED module, or an LED lamp.(2):-Supplied LED luminaries shall confirm to IS:16101(2012) IS :16106 (2012). Light Source (LED) in the Luminaries should be of make:- (1):- NICHIA/CREE/ OSRAM/ SEOUL /PHILIPS / LUMILEDS /LEDNIUM. (2):-LEDs to IS:16105(2012). IS: 16108(2012), IEC:62471. 1. Input operating voltage :-105-295 V AC.2:- Normal Voltage-220 VAC. 3. Driver type: constant current driver with short circuit protection. 4.Control of distribution:- Full cut off. 5. Lumens-2880/4320 . 6. Efficiency of driver electronic: > 85%. 7. Colour temperature:4000K. 8.Colour rendering index (CRI):>75. 9. Ingress protection : IP-20. 10.Lumen output: >=120 lumens/ watt @ Max. 350 mA drive current. 11. Power factor:->0.97. 12. Total harmonics distortion (THD):-<20%. 13.Lamp cover :Acrylic cover whichdoes not result in loss of lumens. 14. Finishing: Power coated/Anodized. 15. Secondry optics: poly carbonate reflector/ poly carbonate lens. 16. Construction of housing: extruded aluminum/ CRCA/Pressure die cast aluminum. 17. Mounting: Suitable for surface mounting/ recessed mounting. 18. Certificate:Firm to submit LM80 (In respect of LED used) & LM79 (In respect of luminare used) test certificate from National/International accredited Laboratory and OEM certificate for complience of BIS/IEC. 19. Warranty: Firm to submit warranty certificate for five year along with the supply. All fittings shall be fitted as surface mounting/recessed mounting with twisted twin flexible cord of minimum size 16/0.2 mm copper conductor as per relevant technical specification. Material parameters must remain unchanged during entire warranty period. Inspection by-Consignee. | Numbers | 400.00 | 1,474.65 | 5,89,860 |
| Schedule total | ₹45,01,255.89 | ||||
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
Tenderdocument_1.pdf
ATTACHMENT
GCCACS2022CORRECTION.pdf
ATTACHMENT
GCC_April-2022_2022__27_04_227.pdf
ATTACHMENT
Annexure-VA.pdf
ATTACHMENT
AnnxVIB.pdf
ATTACHMENT
2022_12_13RBCE_CE-I-CTIndianRailwaysStandardGeneralConditionsofContractApril2022ACSNo_21.pdf
ATTACHMENT
2023_04_26RBCE_CE-I-CTIndianRailwaysStandardGeneralConditionsofContractApril-2022AdvanceCorrectionSlipNo_3ACS-31.pdf
ATTACHMENT
2023_08_07RBCE_CE-I-CTIndianRailwayStandardGeneralConditionsofContractApril-2022AdvanceCorrectionSlipNo_4ACS-4_1.pdf
ATTACHMENT
2023_10_20RBCE_CE-I-CTIndianRailwayStandardGeneralConditionsofContractApril-2022AdvanceCorrectionSlipNo_5ACS-5_1.pdf
ATTACHMENT
2023_12_21IndianRailwaysStandardGeneralConditionsofContractApril-2022AdvanceCorrectionSlipNo_6ACS-6_1.pdf
ATTACHMENT
Likelysourceofsupply.pdf
ATTACHMENT
ACS_7to10.pdf
ATTACHMENT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .