17 conditions · 5 needing a document upload
Financial Eligibility Criteria: (Ref: RB letter No. 2022/CE- I/CT/GCC2022/POLICY : Advance Correction Slip No.-1 dt 14.07.2022) The tenderer must have minimum average annual contractual turnover of V/N or 'V' whichever is less; where V= Advertised value of the tender in crores of Rupees N= Number of years prescribed for completion of work for which bids have been invited. The average annual contractual turnover shall be calculated as an average of "total contractual payments" in the previous three financial years, as per the audited balance sheet. However, in case balance sheet of the previous year is yet to be prepared/ audited, the audited balance sheet of the fourth previous year shall be considered for calculating average annual contractual turnover. The tenderers shall submit requisite information as per Annexure-VIIB, along with copies of Audited Balance Sheets duly certified by the Chartered Accountant/ Certificate from Chartered Accountant duly supported by Audited Balance Sheet.
The intending tenderers should possess a valid electrical contractor license at the time of opening of tender, issued by any state government & same should be submitted along with tender documents by all bidders including working contractors of this unit otherwise offer shall be summarily rejected....... IT SHOULD BE NOTED BY THE TENDERER THAT ELECTRICAL LICENSE UNDER RENEWAL AT THE TIME OF TENDER OPENING WILL NOT BE CONSIDERED AND OFFER WILL BE SUMMARILY REJECTED. IT IS THE RESPONSIBILITY OF TENDERER TO UPLOAD VALID ELECTRICAL CONTRACTOR LICENSE ON THE DATE OF TENDER OPENING.
All requisite documents mentioned in clause 3.7 of tender document attached pertaining to constitution of firm/concern. (As applicable).
41 conditions · 4 needing a document upload
The rate to be quoted by tenderer shall be inclusive of all state/central taxes including GST. THE TENDERER SHOULD UPLOAD VALID GST REGISTRATION CERTIFICATE ALONG WITH THE OFFER.
The tender shall comply with General Condition of contract (GCC),2022 of Indian Railways (file attached). and its latest amendment, if any. The tenderer shall submit the offer after duly satisfying himself/herself with the GCC,2022 in general.
Tenderers are required to upload the Bank details as per Annexure-XII (Real Time Gross Saving (RTGS)/National Electronic Fund Transfer (NEFT) Model Mandate Form)of tender document.
Tenderers are required to upload requisite details as per Annexure-VIIB (DETAILS OF CONTRACTUAL PAYMENT RECEIVED IN LAST THREE FINANCIAL YEARS AND CURRENT FINANCIAL YEAR) without which the offer is liable to be rejected.
Tenderers are compulsorily required to upload Affidavit as per Annexure-XXIV along with tender document, without which the offer will be considered incomplete and will be rejected summarily.
All requisite documents/credentials mentioned in clause 3.5 of tender document attached pertaining to his/their technical and financial eligibility. (As applicable).
All requisite documents mentioned in clause 3.7 of tender document attached pertaining to constitution of firm/concern. (As applicable).
Please enter the percentage of local content in the material being offered. Please enter 0 for fully imported items, and 100 for fully indigenous items. The definition and calculation of local content shall be in accordance with the Make in India policy as incorporated in the tender conditions.
Tender involves rewiring of mainly occupied staff quarters. Therefore, availability of quarters for re-wiring will be limited in numbers and in gradual manner. Contractor cannot demand availability of all staff quarters (proportional to tendered qty) simultaneously and cannot claim any type of relaxation on this account.
The plastering work after cutting of grooves shall be finished properly in the level of original wall with painting/white wash to the satisfaction of Railways.
The contractor has to submit drawing/plan showing route diagram to consignee for signature of concerned SSEs of other departments. It required geological survey to be conducted at his own cost to avoid damage of any other cable/Pipe etc.
No post tender correspondence for submission of additional documents shall be entertained after opening of the Technical & Commercial offers. Even suo-moto post tender letters of the tenderer/s shall be treated as Null & Void.
No post tender correspondence for submission of additional documents shall be entertained after opening of the Technical & Commercial offers. Even suo-moto post tender letters of the tenderer/s shall be treated as Null & Void.
The rate to be quoted by tenderer shall be inclusive of all state/central taxes including GST. tenderer shall submit GST certificate along with the offer.
This tender complies with Public Procurement Policy (Make in India) Order 2017, dated 15/06/2017, issued by Department of Industrial Promotion and Policy, Ministry of Commerce, circulated vide Railway Board letter no. 2015/RS(G)/779/5 dated 03/08/2017 and 27/12/2017.
IF ANY DISCREPANCY IS FOUND IN THE TENDER DOCUMENT, NAMELY SOR ITEM DESCRIPTION, SPECIAL TENDER CONDITION ETC., CLARIFICATION CAN BE SOUGHT FROM THE OFFICE OF SRDEE/G/DLI, DRM OFFICE, STATE ENTRY ROAD, NEW DELHI.
This tender complies with Railway Board instructions for Startups (recognized by Department of Industrial Policy and Promotion, Ministry of Commerce and Industry) for exemption from payment of Bid Security as detailed in GCC 2022 as amended from time to time. Such Startup firms may note that no other exemption is applicable to them in this particular tender.
On account payment, contractor shall submitted indemnity bond with validity up to the completion/extended period in the prescribed format (please refer Annexure-XXVIII) at the contractor's cost, vesting the ownership of such material with the railways.
This tender shall also complies with "Indian Railways Standard General Conditions of Contract, April 2022 (Advance Correction Slip No. 11)" vide Railway Board letter No. 2022/CE-I/CT/GCC- 2022/POLICY/Pt.I (E-3320424), dated:13.03.2026 (attached)
All disputes or differences of any kind whatsoever arising out of or in connection with this contract, whether during its execution or after completion, termination, or breach thereof, shall be subject to the exclusive jurisdiction of the competent courts at New Delhi only.
The issues not covered under the tender document shall be governed by General conditions of Contract (GCC) 2022 or its latest amendments if any during entire period of contract. If any contradiction in Tender Document and GCC is observed then GCC shall prevail.
Before energization /commissioning, the contractor shall carry out all pre-commissioning tests (like, Continuity resistance of conductors, Insulation resistance test, Polarity test, Verification of automatic disconnection of supply (ADS), Phase sequence test, Functional tests, Voltage drop verification, Earth electrode resistance test, Earth Continuity test, Load test, Verification of additional protection (RCDs/RCCBs/RCBOs) etc.) and submit the corresponding test reports as specified in the Chapter 16 (Verification of Installation) of CPWD General Specifications for Electrical Works, Part-I (Internal), 2023 or latest. The rates quoted in the NIT schedule are inclusive of all the aforementioned tests and no additional payment will be made and contractor shall submit the required test report for the same.
All test instruments used for carrying out the pre-commissioning tests shall be of reputed make (like Megger, Fluke etc. ) and shall be properly calibrated, with valid calibration certificates available for verification whenever required.
Rewiring of Railway Quarters in the jurisdiction of SSE/PS/HNZM.
93-R1-SRDEE-G-DLI-2026-27
93-R1-SRDEE-G-DLI-2026-27
Open
Works - General
12 Months
Delhi, Delhi
₹0
₹1.8 L
18 Aug 2026
27 Jul 2026
4 Aug 2026
69 items across 1 schedule
| # | Description | Unit | Qty | Rate | Amount |
|---|---|---|---|---|---|
| — | — | — | Above/ 8780764.00 Below/P | ||
| — | 1368.00 | — | — | ||
| Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLSH/HFFR PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLSH PVC insulated copper conductor single core cable etc. as required and conforming to IS 732:2019 (reviewed 2024) & CPWD General Specifications for Electrical Works Part-I Internal - 2023 and CPWD DSR (E&M) 2025 & as per explanatory note. Group A | — | — | — | 9,68,544 | |
| — | 10800.00 | — | — | ||
| Supply and recessing/fixing of PVC conduit pipe of 25mm size conforming to IS 9537 Part-III 1987/IEC 60614-2-2 (or Latest version) with accessories junction box, bends etc. including making chase, plastering/clamping etc. as per site requirement & as per explanatory note. | — | — | — | 3,56,400 | |
| — | 11520.00 | — | — | ||
| Supply of following sizes FRLSH PVC insulated multi stranded annealed copper conductor single core cable conforming to IS 694 (or Latest Version), and drawing in Laid (recessed /surface) PVC conduit pipe for wiring of circuit wiring / sub main / main as required as per technical specification including connections, testing and commissioning & as per explanatory note. 1x2.5 sq.mm | — | — | — | 4,95,360 | |
| — | 25200.00 | — | — | ||
| Supply of following sizes FRLSH PVC insulated multi stranded annealed copper conductor single core cable conforming to IS 694 (or Latest Version), and drawing in Laid (recessed /surface) PVC conduit pipe for wiring of circuit wiring / sub main / main as required as per technical specification including connections, testing and commissioning & as per explanatory note. 1x4.0 sq.mm | — | — | — | 14,36,400 | |
| — | 4320.00 | — | — | ||
| Supply of following sizes FRLSH PVC insulated multi stranded annealed copper conductor single core cable conforming to IS 694 (or Latest Version), and drawing in Laid (recessed /surface) PVC conduit pipe for wiring of circuit wiring / sub main / main as required as per technical specification including connections, testing and commissioning & as per explanatory note. 1x6.0 sq.mm | — | — | — | 4,10,400 | |
| — | 432.00 | — | — | ||
| Supply of Batten/Angle Holder conforming to IS : 1258-2005 (or latest version) & installation on the junction box of laid conduit including connections, testing & commissioning as per site requirement and conforming to CPWD General Specifications for Electrical Works Part-I Internal - 2023 and CPWD DSR (E&M) 2025 & as per explanatory note. | — | — | — | 55,728 | |
| — | 936.00 | — | — | ||
| Supply of ceiling rose, 3 pin conforming to IS : 371-1999 (or latest) & installation on the junction box of laid conduit including connections, testing & commissioning as per site requirement and conforming to CPWD General Specifications for Electrical Works Part-I Internal - 2023 and CPWD DSR (E&M) 2025 & as per explanatory note. | — | — | — | 70,200 | |
| — | 216.00 | — | — | ||
| Supplying & fixing suitable size GI box with modular plate and cover in front on surface or in recess including providing and fixing 25A modular socket outlet and 25A modular SP MCB " C " curve including connections, painting etc. as required and conforming to CPWD General Specifications for Electrical Works Part-I Internal - 2023 and CPWD DSR (E&M) 2025 & as per explanatory note. | — | — | — | 1,53,576 | |
| — | 72.00 | — | — | ||
| Supplying and fixing following modular switch /socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required and conforming to CPWD General Specifications for Electrical Works Part-I Internal - 2023 and CPWD DSR (E&M) 2025 & as per explanatory note. Bell push | — | — | — | 9,000 | |
| — | 648.00 | — | — | ||
| Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required and conforming to CPWD General Specifications for Electrical Works Part-I Internal - 2023 and CPWD DSR (E&M) 2025 & as per explanatory note. | — | — | — | 3,07,800 | |
| — | 648.00 | — | — | ||
| Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc.as required conforming to CPWD General Specifications for Electrical Works Part-I Internal - 2023 and CPWD DSR (E&M) 2025 & as per explanatory note. | — | — | — | 3,69,360 | |
| — | 150.00 | — | — | ||
| Supply, Installation, Testing and Commissioning of 1400 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal blades (almunium alloy), 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CM/M/W) minimum 6.00, Air delivery minimum 245 Cum/Min , 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, suitable for electronic regulator for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required. It shall also include the scope of supply and installation of safety cord of SS as per IS:302 Part 2 Sec-80. Dia & length of such cord shall be as per recommendation of OEM of fan and same shall be approved by railway conforming to CPWD General Specifications for Electrical Works Part-I Internal - 2023 and CPWD DSR (E&M) 2025 & as per explanatory note. | — | — | — | 4,43,850 | |
| — | 216.00 | — | — | ||
| Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required as per IS 11037 (reviewed 2025) and conforming to CPWD General Specifications for Electrical Works Part-I Internal - 2023 and CPWD DSR (E&M) 2025 & as per explanatory note. | — | — | — | 76,896 | |
| — | 250.00 | — | — | ||
| Supply, fixing, testing and commissioning of LED light luminaire, having system wattage 1x18-20 watt. LED tube and inbuilt LED driver, CRCA body powder coated, complete with all mounting arrangement, accessories. CRI >= 80, SDCM (standard deviation color matching) <3. The LED based 4 ft. tube light (lamp) shall be conforming to CEE/NR's spec. No. CEE/NR/121- Elect/PS/2018 (Rev- '3') or latest at Tech Spec-I attached & PCEE/NR's spec. No. PCEE/NR/121- Elect/PS/2019 (Rev- '4') at Tech Spec-II attached or latest & as per explanatory note. | — | — | — | 1,71,750 | |
| — | 50.00 | — | — | ||
| Supply, fixing, testing and commissioning of 45-50 watt LED based street light luminary with CRI >= 70, SDCM (standard deviation color matching) <5, single housing, side entry, high pressure aluminum die cast/extruded aluminum, IP 66 or better having system complete conforming to CEE/NR's spec. No. CEE/NR/121-Elect/PS/2018 (Rev-'3') or latest at Tech Spec-I attached & PCEE/NR's spec. No. PCEE/NR/121-Elect/PS/2019 (Rev- '4') at Tech Spec-II attached or latest & as per explanatory note. | — | — | — | 1,58,700 | |
| — | 72.00 | — | — | ||
| Supply, fixing, testing and commissioning of LT distribution board surface mounting/recessed double door out door type made up of CRCA sheet steel with anti corrosion treatment and suitable, IP 54 phosphatised powder painted complete with neutral link, earth point, Din rail and confirming to IEC 60947,Make- ABB, Siemens, LK, Schneider, Legrand or equivalent with following items of matching make to be fixed in distribution board, confirming to IEC 61439 Part-3, IE rules and site requirement & as per explanatory note. 40A 2P RCBO 30/100 mA= 01 No. (Incoming). 6-32A MCB SP "C" Series = 09 Nos. (Outgoing). It should be rodent entry proof. It should also include well dressing and coding of circuit IP2X terminal , reversible door with 180 degree opening, cement spill protection, detachable gland at top and bottom and short link for MCBs. It should also include proper tagging on electrical wires/cables which clearly indicate the incoming point or source and outgoing point of wires/cables. | — | — | — | 7,81,704 | |
| — | 30.00 | — | — | ||
| Shifting of existing meter box with Supply & fixing of thermoplastic PS polystrene weatherproof, dustproof, environment friendly, halogen & silicon free hinged transparent meter box size 168x253x115 mm complete as per site requirement & as per explanatory note. | — | — | — | 79,140 | |
| — | 38.00 | — | — | ||
| Design, supply, erection, testing and commissioning of LT Block distribution board cum Meter Box with provision for surface mounting Suitable for fixing 04 Nos. of energy meter, made up of CRCA sheet with anti-corrosion treatment, IP 54, out door type, phosphatised powder painted, (MCCB - Incoming & MCB - Outgoing) comprising with the following MCCB's fixed in it and Al bus-bar arrangement conforming to IS/IEC 61439 and IEC 60947, IE rules and site requirement. It should have digital voltmeter and ammeter. It should be dust and vermin proof and powder coating as per IS 13871-2021 (or latest version) IE rules and site requirement. It should be rodent entry proof and also provide polyamide cable gland with IP 68 protection & should suit the number, type and size of power cables & as per explanatory note. 63 A MCCB 4P 36 kA with adjustable thermal & fixed magnetic release = 01 No. (Incoming). 40A MCB DP "C" Series =04 Nos. (Outgoing). Note: It should have provision of meter sealing arrangements as well pad locking arrangements. It shall be marked as under " Railway property" and danger logo. It should have provision of transparent toughened glass/ fiber sheet so that meter screen should be visible from outside when door of DB box is closed. | — | — | — | 11,74,428 | |
| — | 720.00 | — | — | ||
| Dismantling of existing electrical wires, fittings, switches, socket, ceiling fans etc. from the site and transport to all these materials to the store. All released materials shall be property of railway. Contractor will submit all materials to general store at SSB or as decided by the railway administration & as per explanatory note. Note : Conventional light fittings shall be dismantled and replaced only after completion of codal life. Unit= Each Point | — | — | — | 10,080 | |
| — | 72.00 | — | — | ||
| Dismantling of existing old distribution board consisting of MCCBs/MCBs, Busbar, electrical cables etc. complete with outer metal box and associated supply cable from the site and transport to all these materials to the store. All released materials shall be property of railway. Contractor will submit all materials to general store at SSB or as decided by the railway administration & as per explanatory note. | — | — | — | 23,184 | |
| — | 60.00 | — | — | ||
| Supply, fixing, testing &commissioning of 6-32A MCB SP "C" series as per IS/IEC 60972 or latest in existing MCB distribution board as per site requirement & as per explanatory note. | — | — | — | 11,700 | |
| — | 40.00 | — | — | ||
| Supply, fixing, testing & commissioning of 6-32A MCB DP "C" series as per IS/IEC 60972 or latest in existing MCB distribution board as per site requirement & as per explanatory note. | — | — | — | 24,480 | |
| — | 40.00 | — | — | ||
| Supply, installation, testing & commissioning of 40-63 A DP MCB "C" series as per IS/IEC 60972 or latest in existing MCB distribution board as per site requirement & as per explanatory note | — | — | — | 44,120 | |
| — | 600.00 | — | — | ||
| Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground as per IS 1255 (reviewed 2016) or latest, IS 732:2019 or latest including excavation, sand cushioning, protective covering and refilling the trench [size width- not less than 35 cm and depth- 75 to 100 cm ] etc. as required as per detail drawing approved by competent authority. In case of any demolition of PCC, RCC, road, wall surface etc. the contractor should ensure repairing of the same on own expenses as per site requirement and satisfaction of railway representative and conforming to CPWD General Specifications for Electrical Works Part-II External 2023 and CPWD DSR (E&M) 2025 & as per explanatory note.Upto 35 sq. mm | — | — | — | 2,28,600 | |
| — | 300.00 | — | — | ||
| Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground as per IS 1255 (reviewed 2016) or latest, IS 732:2019 or latest including excavation, sand cushioning, protective covering and refilling the trench [size width- not less than 35 cm and depth- 75 to 100 cm ] etc. as required as per detail drawing approved by competent authority. In case of any demolition of PCC, RCC, road, wall surface etc. the contractor should ensure repairing of the same on own expenses as per site requirement and satisfaction of railway representative and conforming to CPWD General Specifications for Electrical Works Part-II External 2023 and CPWD DSR (E&M) 2025 & as per explanatory note.Above 35 sq. mm and upto 95 sq. mm | — | — | — | 1,33,500 | |
| — | 200.00 | — | — | ||
| Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground as per IS 1255 (reviewed 2016) or latest, IS 732:2019 or latest in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench [size width- not less than 55 cm and depth- (75-100) cm] etc. as required as per detail drawing approved by competent authority. In case of any demolition of PCC, RCC, road, wall surface etc. the contractor should ensure repairing of the same on own expenses as per site requirement and satisfaction of railway representative and conforming to CPWD General Specifications for Electrical Works Part-II External -2023 and CPWD DSR (E&M) 2025 & as per explanatory note.Upto 35 sq. mm | — | — | — | 59,200 | |
| — | 100.00 | — | — | ||
| Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground as per IS 1255 (reviewed 2016) or latest, IS 732:2019 or latest in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench [size width- not less than 55 cm and depth- (75-100) cm] etc. as required as per detail drawing approved by competent authority. In case of any demolition of PCC, RCC, road, wall surface etc. the contractor should ensure repairing of the same on own expenses as per site requirement and satisfaction of railway representative and conforming to CPWD General Specifications for Electrical Works Part-II External -2023 and CPWD DSR (E&M) 2025 & as per explanatory note.Above 35 sq. mm and upto 95 sq. mm | — | — | — | 31,400 | |
| — | 200.00 | — | — | ||
| Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required as per IS 1255 (reviewed 2016) or latest, IS 732:2019 or latest. In case of any demolition of PCC, RCC, road, wall surface etc. the contractor should ensure repairing of the same on own expenses as per site requirement and satisfaction of railway representative and conforming to CPWD General Specifications for Electrical Works Part-II External -2023 and CPWD DSR (E&M) 2025 & as per explanatory note.Upto 35 sq. mm (clamped with 1mm thick saddle) | — | — | — | 12,000 | |
| — | 100.00 | — | — | ||
| Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required as per IS 1255 (reviewed 2016) or latest, IS 732:2019 or latest. In case of any demolition of PCC, RCC, road, wall surface etc. the contractor should ensure repairing of the same on own expenses as per site requirement and satisfaction of railway representative and conforming to CPWD General Specifications for Electrical Works Part-II External -2023 and CPWD DSR (E&M) 2025 & as per explanatory note.Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp) | — | — | — | 14,300 | |
| — | 1500.00 | — | — | ||
| Laying, dressing, terminating, and testing of 1-core, 16 sq.mm to 120 sq.mm, 1.1 kV grade, PVC/ XLPE insulated, armoured/unarmoured Aluminium/ copper conductor cable for TN-S earthing system, laid in the same trench/HDPE pipe/Cable Tray along with power cables (laying mentioned in S. No. 24, 25, 26, 27, 28, 29) as per IS 732:2019 or latest, providing and fixing of cable identification tags, supply and fixing of suitable size brass/compression glands, crimping type Aluminium/copper lugs, jointing (if required), insulating tapes, ferrules, and making proper end terminations and connections to equipment and earth bus/bar, complete as required & as per explanatory note. | — | — | — | 1,27,500 | |
| — | 36.00 | — | — | ||
| Earthing with 40 mm dia. GI pipe class 'B' 4.5 meter long earth electrode as per IS:3043 (latest version) including construction of masonry enclosures with hinged cover plate of cast iron with locking arrangement (approx. size 400 mm x 400 mm) on top, and water pipe etc. with charcoal/coke and salt as required and provision of earth plate, connections from earth electrode to switch gear/pole as per drawing & as per explanatory note. | — | — | — | 2,13,984 | |
| — | 370.00 | — | — | ||
| Supplying and laying 25 mm X 5 mm G.I strip confirming to relevant IS as per IS:3043 (Latest version), fixing on surface or as per site condition, clamping or fixing with suitable arrangement as per site requirement, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required & as per explanatory note. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50 mm) | — | — | — | 56,980 | |
| — | 500.00 | — | — | ||
| Supply of XLPE LT AL cable complete of size 1Cx16 sq.mm. size as per IS 7098 (part1):2025 or latest, IS 732:2019 or latest relevant IS/IE rules (For TN-S Earthing system) & as per explanatory note. | — | — | — | 62,500 | |
| — | 1000.00 | — | — | ||
| Supply of XLPE LT AL cable complete of size 1Cx35 sq.mm. size as per IS 7098 (part1):2025 or latest, IS 732:2019 or latest relevant IS/IE rules (For TN-S Earthing system) & as per explanatory note. | — | — | — | 2,08,000 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
16CPWDGeneralSpecforElectWorkPart- Chapter16 of CPWDGenaralSpecPartIin
ATTACHMENT
TenderDocument.pdf
ATTACHMENT
SpecialConditionsofcontract.pdf
ATTACHMENT
ExplanatoryNote.pdf
ATTACHMENT
GCC-2022-ACS10_merged.pdf
ATTACHMENT
GCCAdvanceCorrectionSlipNo.11.pdf
ATTACHMENT
TECHSPEC-I.pdf
ATTACHMENT
TECHSPEC-II.pdf
ATTACHMENT
TECHSPEC-IIIforwiring-rewiring.pdf
ATTACHMENT
Chapter-16CPWDGeneralSpecforElectWorkPart-IInternal2023.pdf
ATTACHMENT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .