Rectification and replacement including Reinsulation of defective Stator coils Top and Bottom in all three phases with VPI system of insulated coils including Supervision Testing and Commissioning of 100 MW unit of Kadamparai PH
2023_EB_294174_1
HE-2456
Open Tender
Electrical Works
Item Rate
60 days
Kadamparai PH
Please refer Tender documents.
4 documents required · 4 mandatory
₹0
₹2.7 L
Yes
13 Jun 2023
10 Mar 2023
23 Mar 2023
10 Mar 2023
23 Mar 2023
10 Mar 2023
Amount
Charges towards de-soldering both the pole jumpers, removing the ‘V‘block and damper coils series link.
Charges towards removing the 8 Nos. static key and 8 Nos. sliding key per pole with special jigs and hydraulic jacks
Charges towards lifting of 4 Nos. rotor poles after ensuring all connections and disconnected and by using suitable lifting device.
Charges towards removing the top coils by de-wedging and removing the overhang bandings with special jigs and fixtures.
Charges towards removing the old failed insulation and re-insulating on both sides overhang portion on released slot insulation healthy top coils and testing by VPI system of insulation. The following tests are to be carried out : i.IR value at 5 KV before HVAC test ii.HVAC test at 18 KV iii.IR value at 5 KV after HVAC test
Charges towards removing the bottom coils by de-wedging and removing the overhang bandings with special jigs and fixtures.
Charges towards removing the old failed insulation and re-insulating on both sides overhang portion on released slot insulation healthy bottom coils and testing by VPI system of insulation The following tests are to be carried out : IR value at 5 KV before HVAC test HVAC test at 18 KV IR value at 5 KV after HVAC test
Charges towards cleaning the burnt out copper debris and carbon deposits completely with suitable method before HVAC test(dry ice cleaning)
Charges towards making of continuity of other coils in the circuit, testing the whole Generator to ascertain the healthiness of other coils. i) IR value at 5 KV megger before and after HV AC test. ii) HV AC as per instruction of field engineers. iii) PI value at 5 KV megger.
Charges towards installing the spare/re-insulated tested bottom coils (Spare coils shall be supplied by TANGEDCO) with using fresh liners, end banding the overhang portion with fiber tapes and cards using the binding cement of epoxy resin.
Charges for installing the spare/re-insulated tested top coils (Spare coils shall be supplied by TANGEDCO) with using fresh liners, wedges, end banding the overhang portion with fiber tapes and cards using the binding cement of epoxy resin,, soldering the non-connection and connection side end ferrules and jumpers and insulating the jumper joints & providing end caps.
Charges for supply of Class F new top stator coils(VPI type) Note :if sufficient spare healthy top coils are not supplied by TANGEDCO then this supply portion is required.
Charges for supply of Class F new Bottom stator coils (VPI type) Note :if sufficient spare healthy top coils are not supplied by TANGEDCO then this supply portion is required.
Charges towards removing the old failed insulations on slot portion and both overhang portions and re-insulating slot portion and both sides overhang portion including testing by using VPI System of Insulation. The following tests are to be carried out : i) IR value at 5 KV before HVAC test ii) HVAC test at 23 KV iii)IR value at 5 KV after HVAC test iv)Tan Delta and Capacitance Measurement (This is applicable for those top and bottoms coils where the slot insulation failed during HV test.)
Charges for dismantling, removing the bends, refurbishing and installation of 1 No. bus bar and insulation
Charges for re-insulation and installation of bus bar
Charges for re-insulation of jumper
Charges for re-insulation of rotor pole jumpers and take-off leads
Charges for re-positioning the pole in the rotor spider, locking the keys, fixing the ’V’ blocks with suitable insulation
Charges for making end connection, locking the jumpers and connection links with suitable insulated locks, soldering the end connection.
Charges for cleaning of stator and rotor windings and drying out
Charges for conducting the following test on stator and rotor. Stator:i) IR value at 5 KV megger before and after HV AC test. ii) HV AC as per instruction of field engineers.iii) PI value at 5 KV megger.iv) PI value v) Winding resistancevi) Tan Delta at 11 KV in the steps of 0.2VL, 0.4VL, 0.6VL, 0.8VL and 1.0 VL Rotor:i) IR value at 500V ii)Winding resistance iii)Surge test at 1 KV iv)AC Drop test
Charges for Dynamic in-site balancing test and vibration test of whole rotor assembly
Charges for assembling the stator top and bottom air guides, checker plates and commissioning the Generator.
CGST in % (For Bidders inside TamilNadu)
SGST in % (For Bidders inside TamilNadu)
IGST in % (For Bidders outside TamilNadu)
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .