| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.3 CrAccepted-AOC SWAGAT CO OP HSG SOCIETY LTD 22 303 CHAITANYA SHIVAJI RAJE COMPLEX MHADA COMPLEX OPP EKA NAGAR KANDIVALI W MUMBAI 400 067 | MUMBAI | MUMBAI SUBURBAN | MAHARASHTRA | 400067 | ₹1.3 Cr | L1 | Accepted-AOC L1 |
| 2 | L2₹1.4 Cr+₹5.4 L (4.04%)Rejected-Finance 1202 SAI PROVISO DHNISHT PLOT NO 72 73 SECTOR 20 KOPARKHAIRANE NAVI MUMBAI | THANE | MAHARASHTRA | 400601 | ₹1.4 Cr+₹5.4 L (4.04%) | L2 | Rejected-Finance Being other than lowest |
| 3 | L3₹2.0 Cr+₹67.8 L (50.3%)Rejected-Finance 104 A SYNTHOFINE ESTATE OFF AAREY ROAD GOREGAON EAST MUMBAI MAHARASHTRA 400063 | MUMBAI SUBURBAN | MAHARASHTRA | 400063 | ₹2.0 Cr+₹67.8 L (50.3%) | L3 | Rejected-Finance Being other than lowest |
Tender Value
Refer Docs
EMD Value
₹2.0 L
Closing Date
17 Dec 2022, 6:00 pmClosed
CWE (NW) Mumbai
Commander Works Engineer NW Dr Homi Bhabha Road Navy Nagar Colaba Mumbai 05
PROVISION OF AFDS SYSTEM FOR BLDG NO 227 216 O2 PLANT170 187 190 200 128 168 178 H16 H8 AT NAVAL DOCKYARD AND PROVISION OF EMERGENCY ESCAPE LIGHTING ALONG FIRE FIGHTER AND ESCAPE LADDERS OF A14 BUILDING UNDER GE NW KUNJALI COLABA MUMBAI 3rd CALL
2022_MES_541941_3
8494/CWE (NW) Mumbai/ E8
Open Tender
Civil Works
Item Rate
180 days
GE (NW) KUNJALI
Class B
7 documents required · 7 mandatory
₹1,000
Yes
GE (NW) Kunjali
₹2.0 L
Yes
27 Jan 2023
19 Nov 2022
19 Dec 2022
19 Nov 2022
17 Dec 2022
3 Dec 2022
19 Nov 2022 - 1 Dec 2022
Amount
Supplying installation, Testing & Commissioning of Microprocessor based 2 loop capacity , Networkable analogue addressable type fire alarm control panel with min.600 character LCD display, The panel should be equipped with sufficient numbers of 1 loop with up to 10 to 15% spare capacity with each loop shall have a capacity of minimum 99 detectors and 99 analog addressable devices in one loop. Four access levels, capable of taking Flash Scan devices, flash EPROM sufficient numbers of programmable relay controls for controlling AHUs, pressurization fans, ventilation fans at fire pump room, monitoring of fire sprinkler and fire hydrant pump, 240 volts AC power supply, automatic battery charger, 24 volts sealed lead acid batteries sufficient for 24 hours normal working and then be capable of operating the system for 2 hours during an emergency conditions as required. and panels shall have provision of intigraton with BMS System.(UL/EN Approved) as per tender specificaiton.Panel shall be integrated with respective to the zoning of PA System so that incase of fire so PA System shall automatically come in announcement mode as per tender specificaiton complete all as specified and directed by Engineer-in-Charge. Make : Honeywell/ schneider/Bosch
LANDLINE FIRE ALARM AUTO DIALER WITH sms and Memory Available To Store 10 Phone Numbers dialling facility to reach the fire brigade to get the intimation about the location of the area Builtin Emergency Speech Dialer with 8 Numbers & 1/ 2 Messages,NO/NC contacts for both fire and fault, Automatic changeover arrangement to standby supply with battery charger with low battery indication,Fault/ failure indication such as MAINS FAIL, short, open, Battery FAIL etc,Micro-Controller Based System,Both Dialling Modes Can Be Used (Pulse/Tone),Recorded Message Playback Speaker Provision Available complete all as specified and directed by Engineer-in-Charge. Make : Agni/Ravel/Atss
Supplying installation, Testing & Commissioning of Microprocessor based Repeater Networkable analogue addressable type fire alarm control panel with min.600 character LCD display,Four access levels, capable of taking Flash Scan devices, flash EPROM sufficient numbers of programmable relay controls for controlling AHUs, pressurization fans, ventilation fans at fire pump room, monitoring of fire sprinkler and fire hydrant pump, 240 volts AC power supply, automatic battery charger, 24 volts sealed lead acid batteries sufficient for 24 hours normal working and then be capable of operating the system for 2 hours during an emergency conditions as required. and panels shall have provision of intigraton with BMS System.(UL/EN Approved) as per tender specificaiton.Panel shall be integrated with respective to the zoning of PA System so that incase of fire so PA System shall automatically come in announcement mode complete all as specified and complete all as specified and directed by Engineer-in-Charge.
Supply, Installation, testing and commissioning addressable Manual call point(Pull down/Break Glass Type). The device shall have an LED which shall blink in normal state and get steady on activation to monitor the health status of the device and shall be underwritters laboratories listed, semi flush type complete all as specified and directed by Engineer-in-Charge. Make : Honeywell/Schneider/ Bosch
Supplying installation, Testing & Commissioning of Addressable monitor modules for Sprinkler Flow Switch and Door Holders complete all as specified and directed by Engineer-in-Charge. Make : Honeywell/Schneider/ Bosch
Supply fix and commissioning and test of addressable electronic hooter with built in amplifier unit with two tone generator of 100 meter range complete all as specified and directed by Engineer-in-Charge. Make : Honeywell/Schneider/ Bosch
Supplying installation, Testing & Commissioning of Analog addressable Multi Criteria (Optical +thermal) detector with mounting based LED for AFC(Above Celling & below celling .) as per tender specificaiton complete all as specified and directed by Engineer-in-Charge.. Make : Honeywell/Schneider/ Bosch
Supplying installation, Testing & Commissioning of Conventional Beam detector complete as required for hall & indoor open area. As per tender specificaiton complete all as specified and directed by Engineer-in-Charge. Make : Honeywell/Schneider/ Bosch
Supplying installation, Testing & Commissioning of Addressable control modules for AHU, Access control Integration & stairs Pressurization Fan Hooters / Sounders / Strobes etc.as per tender specificaiton complete all as specified and directed by Engineer-in-Charge. Make : Honeywell/Schneider/ Bosch
Supply and fix fault isolator module with automatic resetting arrangement complete all as specified and directed by Engineer-in-Charge. Make : Honeywell/Schneider/ Bosch
Supply & laying PVC FRLS armoured cable 1.5sq mm solid copper conductor 6 core, XLPE Insulated, Extruded PVC sheathed, galvanized steel strip, electric power cables (heavy duty) 1100 Volts grade, laid in duct / along pole/wall etc including making connection complete and making good the distrubed surface matching with existing surface complete all as specified and directed by Engineer-in-Charge. Note : 1. The cost of Al thimbles/lugs and cable gland etc is incl in quoted rate and no extra payment will be made for it.
Supplying installation, Testing & Commissioning of Response indicator for Above ceiling detectors & Cabin Detectors complete all as specified and directed by Engineer-in-Charge. Make : Honeywell/Schneider/ Bosch
Supplying installation, Testing & Commissioning of The GUI based main network software must be capable of graphically representing each facility being monitored with floor plans and icons depicting the actual locations of the various systems; and / or sensors’locations. The GUI software shall be located in control room in one of the blocks and shall monitor all the blocks panel connected with each other along with workstation complete all as specified and directed by Engineer-in-Charge.
Supply and fixing of battery powered exit signage , 220-240v, 50Hz having 2w LED, operation hours of 3 hours, operating environmental temp ranging from -5 to 45 degree centigrade. complete all as specified and directed by Engineer-in-Charge. Note: Exit signage can be replaced with other directional signs as per site requirement.
Supply and fixing of battery powered surface mounted downlighter , 220-240v, 50Hz having 12x1.5w LED, operation hours of 3 hours, operating environmental temp ranging from -5 to 45 degree centigrade complete all as specified and directed by Engineer-in-Charge.
Material and labour for point wiring with FRLS PVC insulated unsheathed multi stranded copper conductor cable of 1.5 sqmm size 1100 volts grade drawn through and including non metalic rigid PVC casing and caping not less than 25mm width with all accessories fixed on wall including FRLS PVC insulated, unsheathed multistranded copper onductor cable of size 1.5 sqmm as earth continuty conductor connecting to common earth dolly and PVC moulded box ISI marked for having the switches, switch sockets regulator etc complete all as specified and directed by Engineer-in-Charge. :-
One light point controlled by one switch complete all as specified and directed by Engineer-in-Charge.
Supply and fix switch piano, modular type 1 way 6 Amps 1 module 240 volts flush type complete all as specified and directed by Engineer-in-Charge.
ASHOK ENTERPRISES
Ascent Networks Pvt. ltd.
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .