Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹48.0 LAccepted-AOC D 2 ABHILASHA APARTMENT 11 A PURULIA ROAD RANCHI 834001 JHARKHAND | RANCHI | JHARKHAND | 834001 | L1 | Accepted-AOC Lowest quoted | |
| 2 | L2₹60.0 L+₹12.0 L (25.1%)Rejected-Finance 119 LANE NO 4 DAYA NAND NAGAR LAWRENCE ROAD AMRITSAR PUNJAB 143001 | AMRITSAR | PUNJAB | 143001 | L2 | Rejected-Finance Other than lowest quoted |
Tender Value
₹43.7 L
EMD Value
₹88,000
Closing Date
2 Dec 2024, 6:00 pmClosed
Shri Sahil Ratusaria, IDSE
Garrison Engineer Ranchi, 7th Club Road Ranchi, PIN-834001
ADDN/ ALTN TO LT OH LINE TO UG CABLE ALONGWITH CONTROL PANELS WITH LATEST CONTROL BREAKERS AT KHOJATOLI OFFRS MD ACCN AND HUSSAINIWALA LINE MD ACCN AT KHOJATOLI POCKET RANCHI MIL STN UNDER GE RANCHI
2024_MES_672121_2
8400/1248/E8
Open Tender
Civil Works
Item Rate
180 days
Garrison Engineer Ranchi, 7th Club Road Ranchi, PI
Class D Cat b (i)
6 documents required · 6 mandatory
₹500
GE Ranchi
₹88,000
Yes
30 Jan 2025
5 Nov 2024
4 Dec 2024
5 Nov 2024
2 Dec 2024
12 Nov 2024
Amount
Dismantling & taking down old unserviceable ACSR/AAC conductor of any size from LT over head line and removing from site complete all as specified Note - Old ACSR conductor shall be take in safe costody for weighing as sch of credit.
Dismantling & taking down old unserviceable shackle/pin insulators of any size and type complete and removal from site complete all as specified Note - Old shackle/pin insulator shall be take in safe costody for sch of credit.
Dismantling & taking down old unserviceable cross arm, channel, angles, flat iron various size/shape incl nut, bolt and washers etc complete and removal from site complete all as specified and as directed.Note - Old Rusted iron shall be take in safe costody for sch of credit.
Dismantling & taking down old unserviceable GI guard wire of any size from LT over head line and removing from site complete all as specified and directed Note - Old GI wire shall be take in safe costody for Sch of credit.
M&L for XLPE insulated heavy duty electric cable with aluminium multi stranded conductor 1100 volts grade served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall sheather laying in trenches/cable ducts, fixed to wall/pole and including taking down old unserviceable cable complete all as specified and directed of following sizes Make of cable - Polycab/KEI/Havells/ Finolex Note:- (i) Excavation & earth work, new sand, new bricks for cable protection shall be measured & paid seperatly in respective items here- in- before.
XLPE LT cable of size 240 Sqmm 3 ½ core
XLPE LT cable of size 150 Sqmm 3 ½ core
XLPE LT cable of size 120 Sqmm 3 ½ core
XLPE LT cable of size 95 Sqmm 3 ½ core
XLPE LT cable of size 50 Sqmm 3 ½ core
XLPE LT cable of size 35 Sqmm 3 ½ core
XLPE LT cable of size 25 Sqmm 3 ½ core
XLPE LT cable of size 16 Sqmm 4 core
XLPE LT cable of size 10 Sqmm 4 core
XLPE LT cable of size 6 Sqmm 4 core
Excavating in trenches not exceeding 1.5m wide and not exceeding 1.5m in depth for laying of cable, foundation etc, and getting out in soft /loose soil all as directed.Note - Excavation/earth work shall be done by manually manner with the safety of Data/OFC/telephone cable. If any cable damaged during the excavation to be repair same time and cost to be included in qouted rates.
Returning filling in including spreading, leveling Watering and well ramming in layers not exceeding 25cm all as directed.
Removing excavated surplus soil to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point all as directed.
M& L for Spreading ribbed soil in trenches as in cable cushioning all as per IS 1255-1983 and as directed. Note :- Excavated approved soil shall be ribbed by using sieve to separate composite particles etc as per IS and refiiling in trenches before laying of cable 8 CM and 15 CM after laying of cable. This is than gently punned down to a depth of 10 cm above the top of upper most cable (ii) For the purpose of measurement only punned thickness only will be considered for payment.
M&L for laying bricks 'B' class over a cable (Width wise) old laid dried complete all as specified and directed.
Material and labour for cutting of metallic road/ hard standing/hard rock/wall up to a size not exceeding 20cm width and not exceeding 60cm in depth for laying of protection pipe for cable including making good the disturbed road/hard standing by providing PCC (1:2:4) type B1, 40 mm grade crushed stone aggregate upto existing surface level or removing the any type of tiles carefully and refixing properly as per existing surface including suitable size of GI pipe (if necessary) complete all as specified and as directed by Engineer-in-charge.Note: 1. If damaged/broken the any type of tiles while removing, the contractor shall replace the broken tiles with new one.2. The Quoted rate is included for all materials/T&P/Machinery used in this item, no material can paid/measured separately.3. All the removable tiles/re fixable material shall kept carefully at a safe place for refixing with in this quoted rate.4. GI Pipe shall measured and paid separately under relevant item.
material and labour for Boring of holes under road, pavement, hard standing by adopting horizontal boring including supply and inserting of HDPE pipe of 100 mm dia not less than 6kg/cm working pressure confirming to IS all as specified and directed. Note: Depth will not be less than 1.00 M below the road pavement and hard standing boring shall be carried out without damaging the road and hard standing.
Earthing complete with galvanised steel earth plate electrode of size 600 x 600 x 6 mm thick burried directly in ground vertically to a depth not less than 2.25 mtr below ground level with top edge of plate not less than 1.5 m below ground level connected to and including galvanised earth strip of size 25x4 mm (up or 7.5 mtr length) and GI pipe 40 mm light grade for protection of GI earth strip by means of bolts, nuts, checknuts and washers made out of galvanised iron and connected to earth test point as shown in electrical plate No. 3 of SSR Part-1-2009 and as specified or indicated and testing on completion including excavation and earth work any in type of strata available at site, PCC (1:3:6) type C-1 for earth chamber, precast RCC slab 50 mm thick in cement concrete (1:2:4) type B-1 reinforced with welded steel wire fabric (xpm) weight not less the (4kg/sqm) funnel with GI watering pipe of 20mm bore medium grade, wire nuts and lugs complete all as speified and directed.
Description all as per item No.15 here-in-before but Main incoming MCCB 160 Amps and bus bar of rating 300A complete all specified and directed
Description all as per item No.15 here-in-before but Main incoming MCCB 125 Amps and bus bar of rating 200A complete all specified and directed
Description all as per item No.15 here-in-before but Main incoming MCCB 100 Amps and bus bar of rating 200A complete all specified and directed
S& F of terminal panel box of size 155 mm x 210 mm x 92mm of outdoor pole mounted front operated cubical type Box as per IEC 60439-1 (IS:8623) & IEC 60439 -2 dead back, free standing, dust and vermin proof, switchboard with IP 66 protection with suitable for use 440 volts, 3 phase 4 wire 50 Hz system. The Board/Panel shall be made out of moduler POLYCARBONATE THERMOPLASTIC ENCLOSURES. The gasket material shall be Polyurethane; while the gasket shall be internally embedded. The manufacturer of board/panel shall submit a copy of test report in accordance with IEC 60529. The Panel Should be assembled at manufactures factory (Make for terminal panel Box - Hensel/hager/Schniender of Equivalent to other manufacturer of POLYCARBONATE THERMOPLASTIC ENCLOSURES.and Panel box having 1x 6 Amp MCB (Make -Indo Asian(optipro /Havells/Legrand), 16 Sq.mm Terminal Block (04 Nos) , 6 Sq.mm Disconnected Terminal (01 No) ,4 Sq.mm Earth Terminal (01 No) including MS clamp flat 20 mm x3 mm in suitable fixed to pole with nut boltsand PVC gland in suitable for 6 to 16 Sq mm cable complete all specified and directed
M& L for Rigid non-metallic PVC conduit exclusive of boxes (junction/terminal) but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc. to be fixed on pole with all fittings including mouth pieces for passing of sub main wiring three core of copper wire upto size 2.5 sqmm to provide within the conduit and connection to LED light and terminal control box complete all as directed.Note - Sub main wiring to be paid separataly in respective items here in after.
M&L in repairs Cable PVC insulated PVC unsheathed un-armoured copper conductor (multi stranded) of cross sectional area 1.5 sq mm 3 core drawing in PVC conduit/Steel tubular pole all as required for connections to light fittings complete all as directed.
M& L for GI tubing light grade of size 50 mm dia fixed on walls / laid in trenches as protection pipe for under ground cable including provisioning of specials and clamps etc including taking down of old unseviceable pipe any type and any size complete all as speified and directed.Note - Excavation to be paid separately in respective items.
M& L for GI tubing medium grade of size 40 mm dia fixed on walls / laid in trenches as protection pipe for under ground cable including provisioning of specials and clamps etc including taking down of old unseviceable pipe any type and any size complete all as speified and directed.Note - Excavation/PCC cutting to be paid separately in respective items.
india trading company (BID ID -3175356)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .