Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹1.5 LAccepted-Finance | 1 | Accepted-Finance L1 Lowest | |
| 2 | 2₹1.7 L+₹17,666 (11.8%)Accepted-Finance 365 B 10 HENRY COMPLEX MATHIYAS NAGAR KP ROAD NAGERCOIL KANNIYAKUMARI DISTRICT 629001 | KANNIYAKUMARI | TAMIL NADU | 629001 | 2 | Accepted-Finance L2 |
Tender Value
₹1.7 L
Closing Date
1 Jan 2021, 12:30 pmClosed
Executive Engineer
Office of the Executive Engineer, Construction Division, APWD, Campbell Bay
Providing IEI and EEI for installation to Electric Car Charger unit at parking shed in APWD, Division Office, Campbell Bay.
2020_APWD_1785_1
NIT No. 18/EE/CD/CB/2020-21
Open Tender
Electrical Works
Item Rate
30 days
EE, CD, APWD, Campbell Bay
Please refer Tender documents.
5 documents required · 5 mandatory
₹0
Exempted
4 Jan 2021
24 Dec 2020
4 Jan 2021
24 Dec 2020
1 Jan 2021
24 Dec 2020
24 Dec 2020 - 31 Dec 2020
Amount
Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) a) 4 way (4 + 12), Double door
Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. a) 63 A
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required.
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. a) Above 35 sq. mm and upto 95 sq. mm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required. a) Above 35 sq. mm and upto 95 sq. mm
Supplying of one number XLPE insulated PVC outer sheathed with galvanised round steel wire or steel stip armoured aluminium conductor power cable of 1.1 KV grade of size 4 x 50 sq.mm conforming to IS 1554 (Part-I) 1988 amended upto date.
Supplying and laying of one number FR PVC round sheathed copper conductor cable of size 4 core 16 sq.mm Make:Havels, code: WHMFDSKB4016 along with one number single core 16 Sq.mm HR FRPVC Copper conductor cable Make:Havels, code:WHFFDN..G1016. In open masonary duct or DWC pipe as required.
Supplying of Double Walled Corrugated high density polythelene pipe having corrugation on the outer wall and plain surface inner wall conforming to IS 14930 Part-I and II of the following sizes.
50 mm outer dia 38 mm inner dia nominal size
77 mm outer dia 63 mm inner dia nominal size
Laying of one number Double wall corrugated HDPE Pipe of following size on wall surface including fixing of snap-fit couplers as required. a) 50 mm outer dia (clamped with 1 mm thick GI clamps).
Laying of one number Double wall corrugated HDPE pipe of following size in the existing masonry open duct including fixing of snap fit couplers at joints as requried. a) 50 mm outer dia.
Laying of one number Double wall corrugated HDPE pipe directly in ground at a depth of 50 cm including excavation and refilling etc. as required but excluding sand cushioning and protective covering. a) Upto 90 mm outer dia.
Supplying and fixing following rating, four pole, (three phase and neutal), 415 V, miniature circuit breaker (MCB), 'C' type in the existing MCB DB complete with connection, testing and commissioning etc. as reuired. Similar in make: ANCHOR (Panasonic) Code: BBD4323CHH (32A)/BBD4633CHH (63A).
Fabrication, installation, testing and commissioning of L.T outdoor type self supported cubical LT Panel board of size not less then 800 x 500 x 300mm, dust and vermin proof made out of 1mm thick CRCA sheet with front and rear opening, double leaf hinged door with locking arrangement embedded in pcc 1:2:4 with 04 Nos. copper busbar strips of size 25 x 6x 300 mm fixed with insulators and makeing necessary arrangement for fixing energy meter. fixing of porceline cutouts 200 Amps 04 No's and 01 No. 4 pole 160 Amps load disconnector switch and making necessary interconnections with 16 Sq.mm copper cable & lugs sizes etc. as required. Busbar shall be provided with colour coded rubberized sleeves bands for phases and neutral identification and duly painted with two coats of metal primer and two coats of synthetic enamel and conforming to section 4 of CPWD specification for Electrical works part IV substation 2007 etc. complete as required.
POWER ENGINEERING CO
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .