Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹44.5 LAccepted-AOC NO 68 ANJANEYA TEMPLE CROSS OPP M S RAMAIAH HOSPITAL NEW BEL ROAD BANGALORE 560 094 | BENGALURU URBAN | KARNATAKA | 560094 | L1 | Accepted-AOC LOWEST BIDDER | |
| 2 | L2₹44.6 L+₹8,544 (0.19%)Rejected-AOC | L2 | Rejected-AOC NOT BEING LOWEST | |
| 3 | L3₹45.4 L+₹91,908 (2.06%)Rejected-AOC 1 A BASEMENT 30 31 RAJA HOUSE NEHRU PALACE NEW DELHI 110 019 | SOUTH EAST | DELHI | 110019 | L3 | Rejected-AOC NOT BEING LOWEST | |
| 4 | L4₹47.3 L+₹2.8 L (6.28%)Rejected-AOC SAI VARENYA PARK VIEW FLAT NO 110 GROUND FLOOR 9TH MAIN 6TH CROSS TURAHALLI BANGALORE 560 061 | BANGALORE | BANGALORE | KARNATAKA | 560061 | L4 | Rejected-AOC NOT BEING LOWEST | |
| 5 | L₹70.0 LRejected-AOC | L | Rejected-AOC NOT BEING LOWEST |
Tender Value
Refer Docs
EMD Value
₹92,000
Closing Date
13 May 2024, 6:00 pmClosed
COL MANOJ NEGI
CWE AF North Bangalore Bellary Road JC Nagar Post Bangalore 560006
SPECIAL REPAIR/REPLACEMENT OF 125KVA DG SET AGAINST BER TECH AREA OF ASTE, 43.5 KVA DG SET WITH CONNECTING ACCESSORIES AGAINST BER AT IAM, IAF AND BER DG SETS AT VV CAMP OF ASTE UNDER GE (AF) MARATHAHALLI
2024_MES_643080_1
87532CWEAFNMAR
Open Tender
Civil Works
Item Rate
150 days
GE (AF) MARATHAHALLI
AS PER NIT
6 documents required · 6 mandatory
₹500
GE (AF) MARATHAHALLI
₹92,000
Yes
21 Jun 2024
19 Feb 2024
20 May 2024
19 Feb 2024
13 May 2024
27 Apr 2024
20 Feb 2024 - 29 Feb 2024
Amount
Supply , install and commissioning of Factory assembled Silent DG set with AMF panel of capacity 125 KVA , 100 KW , 1500 RPM , Turbo Charged, water cooled comprising of suitable Engine with microprocessor based Genset controller with silencer and canopy for soundles mode (sound level not exc level specified by central pollution control board) and alternator both mounted on a common base frame conforming to ISO-3046/BS-5514 and IS-10002 rated for 415 volts 50 cycles , 0.8 Power factor (PF) complete with residential silencer, AVM pads, battery with its leads, first fill of lub oil and all engine accessories such as self starter, alternator/dynomo with suitable coupling and base frame on foundation as recommended by the manufacture and consisting of other electrical component and maintenance free battey including suitable size of copper cable lead with teminal, all mounting accessories complete all as specified comprising with the following. (Make : Engine : Cummins/ Kirloskar/ Ashok leyland/ Alternator : Stamford/ Kirloskar/ Crompton Greaves A. Engine (a) Vertical inline multicylinder, cold starting in accordance with BS-5514/IS-10002 at 1500 RPM including the following accessories :-
(i) Fuel tank(Suitable for capacity for minimum 12 Hrs run). (ii) Fuel filter(Ore & Micro). (iii) Fuel feed pump(Inline monoblock/PT type) with governor. (iv) Lub oil filter. (v) Lub oil cooler. (vi) Dry type/ Oil bath type air cleaner. (vii) Exhaust Silencer(Industrial type). (viii) Radiator, Radiator fan & mounting. (ix) Fly wheel with starting ring. (x) Expansion bellows. (xi) Exhaust gas turbocharger. (xii) 12 Volt electric starter with 01 No maintenance free battery of suitable capacity. (xiii) Battery charging alternator (xiv) Engine control panel consisting with ON/OFF Start Key,Lub oil pressure guage, Battery charging ammeter,Coolant temp gauge, RPM Meter etc. (xv) Suitable flexible coupling
B. ALTERNATOR (i) Alternator, 3 phase, 415 Volts, 50 Hzs 0.8 PF 1500 RPM self excited, self regulated screen profected, drip proof alternator of capacity 125 KVA conforming to BSS 5000 (part 99) with insulation class "H", single bearing and automatic voltage regulator accessories C. ACOUSTIC ENCLOSURE (i) Acoustic enclosure as per latest CPCB norms . (ii) Air inlet louvers specially designed to operate at rated load even at 50 deg C air inlet temp. (iii) Powder coated for long lasting service life and superior finish. (iv) Insulation material meets exacting IS 8183. D. ACCESSORIES (i) Baseframe fabricated from CRCA sheet of suitable thickness as per manufacturer's design. (ii) Storage battery of suitable capacity as per manufacturer's instruction mounted on angle iron frame of suitable size as directed.
E. CONTROL PANEL (a) The Genset controller as per manufacturers/ OEM design complete with internal wiring, bus bar etc and fitted with the following accessories :- (i) MCCB of suitable capacity as per OEM – 01 No (ii) Digital Ammeter – 01 No (iii) Digital Voltmeter 3 Ph 415 volts – 01 No (iv) Indicating lamps (LED type) (R-Y-B) – 01 set F. AMF PANEL (a) The AMF panel shall be separate panel outside of Acoustic enclosure and made of CRCA sheet duly fabricated and powder coated and complete with internal wiring, bus bar etc and fitted with the following accessories :- (i) MCCB of suitable capacity as per OEM - 02 Nos (ii) Contactor of suitable capacity as per OEM - 02 Nos (iii) Digital Ammeter with suitable CT of size as per OEM (iv) Digital Voltmeter 3 Ph 415 volts as per OEM (v) Indicating lamps (LED type) (R-Y-B) – 01 set (vi) Relay, timmer and other acessories as per manufacturer.
Supply, install and commissioning of Factory assembled Silent DG set with AMF panel of capacity 50 KVA , 40 KW , 1500 RPM , Turbo Charged, water cooled comprising of suitable Engine with microprocessor based Genset controller with silencer and canopy for soundless mode (sound level not exc level specified by central pollution control board) and alternator both mounted on a common base frame conforming to ISO-3046/BS-5514 and IS-10002 rated for 415 volts 50 cycles , 0.8 Power factor (PF) complete with residential silencer, AVM pads , battery with its leads, first fill of lub oil and all engine accessories such as self starter, alternator/dynamo with suitable coupling and base frame on foundation as recommended by the manufacturer's and consisting of other electrical component and maintenance free battey including suitable size of copper cable lead with terminal, all mounting accessory complete all as specified comprising with the following. (Make : Engine : Cummins/ Kirloskar/ Ashok leyland/ Alternator : Stamford / Kirloskar/Crompton Greaves A. Engine (a) " Vertical inline multicylinder, cold starting in accordance with BS-5514/IS-10002 at 1500 RPM including the following accessories.
(i) Fuel tank(Suitable for capacity for minimum 12 Hrs run). (ii) Fuel filter(Ore & Micro). (iii) Fuel feed pump(Inline monoblock/PT type) with governor. (iv) Lub oil filter. (v) Lub oil cooler. (vi) Dry type/oil bathtype air cleaner. (vii) Exhaust Silencer(Industrial type). (viii) Radiator, Radiator fan & mounting. (ix) Fly wheel with starting ring. (x) Expansion bellows. (xi) Exhaust gas turbocharger. (xii) 12 Volt electric starter with 01 No maintenance free battery of suitable capacity. (xiii) Battery charging alternator (xiv) Engine control panel consisting with ON/OFF Start Key,Lub oil pressure guage, Battery charging ammeter,Coolant temp gauge, RPM Meter etc. (xv) Suitable flexible coupling
B. ALTERNATOR (i) Alternator, 3 phase, 415 Volts, 50 Hzs 0.8 PF 1500 RPM self excited, self regulated screen profected, drip proof alternator of capacity 50 KVA conforming to BSS 5000 (part 99) with insulation class "H", single bearing and automatic voltage regulator accessories C. ACOUSTIC ENCLOSURE (i) Acoustic enclosure as per latest CPCB norms. (ii) Air inlet louvers specially designed to operate at rated load even at 50 deg C air inlet temp. (iii) Powder coated for long lasting service life and superior finish. (iv) Insulation material meets exacting IS 8183. D. ACCESSORIES (i) Baseframe fabricated from CRCA sheet of suitable thickness as per manufacturer's design. (ii) Storage battery of suitable capacity as per manufacturer's instruction mounted on angle iron frame of suitable size as directed.
E. CONTROL PANEL (a) The Genset controller as per manufacturers/ OEM design complete with internal wiring, bus bar etc and fitted with the following accessories :- (i) MCCB of suitable capacity as per OEM – 01 No (ii) Digital Ammeter – 01 No (iii) Digital Voltmeter 3 Ph 415 volts – 01 No (iv) Indicating lamps (LED type) (R-Y-B) – 01 set F. AMF PANEL (a) The AMF panel shall be separate panel outside of Acoustic enclosure and made of CRCA sheet duly fabricated, bus bar etc and fitted with the following accessories :- (i) MCCB of suitable capacity as per OEM - 02 Nos (ii) Contactor of suitable capacity as per OEM - 02 No (iii) Digital Ammeter with suitable CT of size as per OEM (iv) Digital Voltmeter 3 Ph 415 volts as per OEM (v) Indicating lamps (LED type) (R-Y-B) – 01 set (vi) Relay, timmer and other acessories as per manufacturer.
Taking down old BER DG Set and keep in safe custody and supply, install and commissioning of Factory assembled Silent DG set with AMF panel of capacity 82.5 KVA , 66 KW , 1500 RPM , Turbo Charged, water cooled comprising of suitable Engine with microprocessor based Genset controller with silencer and canopy for soundless mode (sound level not exc level specified by central pollution control board) and alternator both mounted on a common base frame conforming to ISO-3046/BS-5514 and IS-10002 rated for 415 volts 50 cycles , 0.8 Power factor (PF) complete with residential silencer, AVM pads , battery with its leads, first fill of lub oil and all engine accessories such as self starter, alternator/dynomo with suitable coupling and base frame on foundation as recommended by the manufacturer and consisting of other electrical component and maintenance free battey including suitable size of copper cable lead with terminal, all mounting accessory complete all as specified comprising with the following. (Make : Engine : Cummins/ Kirloskar/ Ashok leyland/ Alternator : Stamford/ Kirloskar/ Crompton Greaves A. Engine (a) " Veritcal inline multicylinder, cold starting in accordance with BS-5514/ IS-10002 at 1500 RPM including the following accessories"
(i) Fuel tank(Suitable for capacity for minimum 12 Hrs run). (ii) Fuel filter(Ore & Micro). (iii) Fuel feed pump(Inline monoblock/PT type) with governor. (iv) Lub oil filter. (v) Lub oil cooler. (vi) Dry type/oil bath type air cleaner. (vii) Exhaust Silencer(Industrial type). (viii) Radiator, Radiator fan & mounting. (ix) Fly wheel with starting ring. (x) Expansion bellows. (xi) Exhaust gas turbocharger. (xii) 12 Volt electric starter with 01 No maintenance free battery of suitable capacity. (xiii) Battery charging alternator (xiv) Engine control panel consisting with ON/OFF Start Key,Lub oil pressure guage, Battery charging ammeter,Coolant temp gauge, RPM Meter etc. (xv) Suitable flexible coupling
B. ALTERNATOR (i) Alternator, 3 phase, 415 Volts, 50 Hzs 0.8 PF 1500 RPM self excited, self regulated screen profected, drip proof alternator of capacity 82.5 KVA conforming to BSS 5000 (part 99) with insulation class "H", single bearing and automatic voltage regulator accessories C. ACOUSTIC ENCLOSURE (i) Acoustic enclosure as per latest CPCB norms. (ii) Air inlet louvers specially designed to operate at rated load even at 50 deg C air inlet temp. (iii) Powder coated for long lasting service life and superior finish. (iv) Insulation material meets exacting IS 8183. D. ACCESSORIES (i) Baseframe fabricated from CRCA sheet of suitable thickness as per manufacturer's design. (ii) Storage battery of suitable capacity as per manufacturer's instruction mounted on angle iron frame of suitable size as directed.
E. CONTROL PANEL (a) The Genset controller as per manufacturers/ OEM design complete with internal wiring, bus bar etc and fitted with the following accessories :- (i) MCCB of suitable capacity as per OEM – 01 No (ii) Digital Ammeter – 01 No (iii) Digital Voltmeter 3 Ph 415 volts – 01 No (iv) Indicating lamps (LED type) (R-Y-B) – 01 set F. AMF PANEL (a) The AMF panel shall be separate panel outside of Acoustic enclosure and made of CRCA sheet duly fabricated and powder coated and complete with internal wiring, bus bar etc and fitted with the following accessories :- (i) MCCB of suitable capacity as per OEM - 02 Nos (ii) Contactor of suitable capacity as per OEM - 02 Nos (iii) Digital Ammeter with suitable CT of size as per OEM - 02 Nos (iv) Digital Voltmeter 3 Ph 415 volts as per OEM (v) Indicating lamps (LED type) (R-Y-B) – 01 set (vi) Relay, timmer and other acessories as per manufacturer.
Taking down old BER DG Set and keeping in safe custody and supply, install and commissioning of Factory assembled Silent DG set with AMF panel of capacity 15 KVA , 12 KW , 1500 RPM , Turbo Charged, water cooled comprising of suitable Engine with microprocessor based Genset controller with silencer and canopy for soundless mode (sound level not exc level specified by central pollution control board) and alternator both mounted on a common base frame conforming to ISO-3046/BS-5514 and IS-10002 rated for 415 volts 50 cycles , 0.8 Power factor (PF) complete with residential silencer, AVM pads , battery with its leads, first fill of lub oil and all engine accessories such as self starter, alternator/dynomo with suitable coupling and base frame on foundation as recommended by the manufacturer and consisting of other electrical component and maintenance free battery including suitable size of copper cable lead with terminal, all mounting accessory complete all as specified comprising with the following. (Make : Engine : Cummins/ Kirloskar/Ashok Leyland, Alternator : Stamford/ Kirloskar/ Crompton Greaves
A. Engine (a) Vertical inline multicylinder, cold starting in accordance with BS-5514/IS-10002 at 1500 RPM including the following accessories (i) Fuel tank(Suitable for capacity for minimum 12 Hrs run). (ii) Fuel filter(Ore & Micro). (iii) Fuel feed pump(Inline monoblock/PT type) with governor. (iv) Lub oil filter. (v) Lub oil cooler. (vi) Dry type/oil bath type air cleaner. (vii) Exhaust Silencer(Industrial type). (viii) Radiator, Radiator fan & mounting. (ix) Fly wheel with starting ring. (x) Expansion bellows. (xi) Exhaust gas turbocharger. (xii) 12 Volt electric starter with 01 No maintenance free battery of suitable capacity. (xiii) Battery charging alternator (xiv) Engine control panel consisting with ON/OFF Start Key,Lub oil pressure guage, Battery charging ammeter,Coolant temp gauge, RPM Meter etc. (xv) Suitable flexible coupling
B. ALTERNATOR (i) Alternator, 3 phase, 415 Volts, 50 Hzs 0.8 PF 1500 RPM self excited, self regulated screen profected, drip proof alternator of capacity 15 KVA conforming to BSS 5000 (part 99) with insulation class "H", single bearing and automatic voltage regulator accessories C. ACOUSTIC ENCLOSURE (i) Acoustic enclosure as per latest CPCB norms. (ii) Air inlet louvers specially designed to operate at rated load even at 50 deg C air inlet temp. (iii) Powder coated for long lasting service life and superior finish. (iv) Insulation material meets exacting IS 8183. D. ACCESSORIES (i) Baseframe fabricated from CRCA sheet of suitable thickness as per manufacturers design. (ii) Storage battery of suitable capacity as per manufacturer's instruction mounted on angle iron frame of suitable size as directed
E. CONTROL PANEL (a) The Genset controller as per manufacturers/ OEM design complete with internal wiring, bus bar etc and fitted with the following accessories :- (i) MCCB of suitable capacity as per OEM – 01 No (ii) Digital Ammeter – 01 No (iii) Digital Voltmeter 3 Ph 415 volts – 01 No (iv) Indicating lamps (LED type) (R-Y-B) – 01 set F. AMF PANEL (a) The AMF panel shall be separate panel outside of Acoustic enclosure and made of CRCA sheet duly fabricated, bus bar etc and fitted with the following accessories :- (i) MCCB of suitable capacity as per OEM - 02 Nos (ii) Contactor of suitable capacity as per OEM - 02 Nos (ii) Digital Ammeter with suitable CT of size as per OEM (iii) Digital Voltmeter 3 Ph 415 volts as per OEM (iv) Indicating lamps (LED type) (R-Y-B) – 01 set (v) Relay, timmer and other acessories as per manufacturer.
NOTE :- (for item No. 01 to 04) (i) PCC Foundation and platform as per manufacturer's design/recommendation to be followed during installation of DG Set will be measured and paid under relevant item of this BoQ. (ii) Silencer pipe of engine is to be extended out of the building with suitable dia of GI medium grade pipe duly heat insulated with suitable aluminium cladding which deemed included in the unit rate of Gen set. (iii) Lubricating oil shall be provided by the contractor cost of which deemed to be included in the unit rate of DG Set. (iv) Four Nos free servicing with complete material such as Lubricating oil, coolent, Lub oil filter, diesel filters, Air filter and fan belts etc as per manufacturer recommendation will be deemed included in the unit rate of DG set.
M & L for Earthing complete with galvanized steel plate electrode 600 mm x 600 mm x 6.0 mm buried directly in ground vertically in pit of depth not less than 2.25 metre below normal ground level with top edge of the earth plate at a depth not less than 1.5 metre below normal ground level surrounded from all sides with mixture of charcoal and common salt in alternate layers and electrode connected to galvanized iron strip 25 x 3 mm as earthing lead by means of GI bolts, nuts, check nuts and washers, earth wire protected by galvanized steel pipe 40 mm bore (light grade) connected to machinery/ equipment all as shown in electrical plate No. 3 of SSR-2009 Part I and including necessary excavation and earth work in any type of soil, 20 mm bore light grade GI pipe for watering funnel wire mesh, PCC (1:3:6), type C-1 chamber, RCC (1:2:4), type B-1, reinforced with 6 mm dia MS round bars @ 15 cm c/c both way for cover and MS frame etc., complete all as specified. NOTE: (i) The unit rate includes earth wire and protection pipe up to (maximum 7.5 metre from earth plate) earth point/test point. (ii) Earth pit shall be constructed at least 0.5 metre away from each earth chamber and earthwork is deemed included in the item.
M & L in repair for Earth continuity conductor or main earthing lead of 25 x 3 mm galvanized iron strip, buried in ground or fixed to wall complete.
Supply, laying & testing XLPE insulated, armoured, heavy duty electric cable with stranded aluminium conductor, 1100 volts grade, laid in trenches, sleeving through pipes or fixed on poles & walls or laid under floors including jointing with suitable size aluminium lugs complete of size 120 Sqmm nominal cross section x 3.5 core complete all as specifed and directed.
Supply and fixing of GI tubing, light grade, 40 mm bore with all fitting laid in trenches / pole / wall for protection of cables in repairs complete. Make - TATA / ZINDAL / Bansal .
Excavation in trenches in soft/loose soil not exceeding 1.5 metre wide and exceeding 1.5 metre but not exceeding 3.0 metres in depth for route of cable and getting out complete all as specified and as directed by the Engineer-in-Charge.
Returning, filling in soft/loose soil including spreading, leveling, watering and well ramming, in layers not exc 25 cm complete all as specified and directed by the Engineer-in-Charge.
Removing of surplus soil to a distance not exc. 50 metres and depositing where directed at a level not exc.1.5 metres above the starting point complete all as specified and as directed by the Engineer-in-Charge.
Supply, laying riddled earth soil for cushioning to cables with a layer of riddle earth soil 15cm deep before laying the cable and 8 cm depth after laying of cable, complete all as specified.
M & L for old size sub class ‘B’ bricks, laid in trenches as cable covers / protection complete all as specified and directed .
M&L for cement concrete 1:3:6 type C-2 using 40 mm graded stone aggregate in foundations filling and mass complete all as specified and as directed.
Supply, laying & testing XLPE insulated, armoured, heavy duty electric cable with stranded aluminium conductor, 1100 volts grade, laid in trenches, sleeving through pipes or fixed on poles & walls or laid under floors including jointing with suitable size aluminium lugs complete of size 50 Sqmm nominal cross section x 3.5 core complete all as specifed and directed.
Supply, laying & testing XLPE insulated, armoured, heavy duty electric cable with stranded aluminium conductor, 1100 volts grade, laid in trenches, sleeving through pipes or fixed on poles & walls or laid under floors including jointing with suitable size aluminium lugs complete of size 70 Sqmm nominal cross section x 3.5 core complete all as specifed and directed.
Supply, laying & testing XLPE insulated, armoured, heavy duty electric cable with stranded aluminium conductor, 1100 volts grade, laid in trenches, sleeving through pipes or fixed on poles & walls or laid under floors including jointing with suitable size aluminium lugs complete of size 16 Sqmm nominal cross section x 4.0 core complete all as specifed and as directed.
Material and labour for boring of holes under road, pavement hard standing by trenchless technology using ultra sound technique and necessary machine including HDPE pipe 100 to 150 mm dia suitable for 0.4 mpa working pressure.
Taking up underground unserviceable cable of any size from existing trench including bricks, etc and removing of materials from work site all as directed by Engr-in-Charge.
Taking down/ disconnecting DG Set of any capacity and deposited to MES store yard complete all as specified and directed.
Mohan Engineering Installation and Services
MONA GENERATOR SEVICES PVT. LTD.
PRANATHI DEVELOPERS
B5BUILDING SOLUTIONS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .