Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹22.2 LAccepted-AOC | ₹22.2 L Quoted ₹23.9 L | L1 | Accepted-AOC Being Lowest Bidder |
| 2 | L2₹38.8 LRejected-Finance 15 CP COLONY MORAR GWALIOR MP 474 006 | GWALIOR | GWALIOR | MADHYA PRADESH | 474006 | ₹38.8 L | L2 | Rejected-Finance Being Other than Lowest |
| Sl No | Description | Qty | Unit | m/s anil traders L1 | M/s Anupam Construction Co. L2 |
|---|---|---|---|---|---|
| 1.00 | Disconnecting and removing existing unserviceable/damaged mild steel sheet enclosure of any description and in any position complete all as specified and directed. | 15 | Each | 50 ₹750 | 1,000 ₹15,000 |
| 2.00 | Supply ,install, testing & commissioning of Indoor type, Wall mounted (with anchor bolts & nuts and PCC work as required) compartmentalized type Meter Cabinet of overall dimension 1800mm (L) x 800mm (W) x 200mm (D) made out of 2.0 mm thick CRCA Sheet with front door having inspection window duly covered with transparent polycarbonate / glass panel for viewing KWh meter . All doors should have gasket and locking arrangement to meet ingress protection level IP-43. The cabinet shall be painted both internally and externally with powder coated paint (RAL 7032 : SIEMENS GREY) two coats after necessary over a coat of red oxide . The cabinet shall be comprising of following accessories :-
a) Four pole MCCB, 125 Amps with breaking capacity 25 KA ICU = ICS having fixed thermal and fixed magnetic release and spreader link at both incoming and outgoing side.- 01 No.
b) Copper Bus Bar of size 25mm x 3mm duly mounted on FRP insulators and necessary drilling for 1 incoming & minimum 8 outgoing connections and duly covered with heat shrinkable PVC sleeves of standard colour code - 4 Nos.
c) MCB SPN 40 Amps, 10 KA - 8 Nos ( To be connected with 8 Nos Meters)
d) MCB SP 10 Amps, 10 KA -2 No ( For common lighting & spare)
e) LED indicating Lamps -03 Nos.
f) Internal wiring with 1100V grade FRLS PVC insulated multi flexible copper wire of sizes duly crimped with copper lugs of suitable size & type all as mentioned below :-
i) MCCB to Bus Bar - 10.0 Sqmm copper
ii) Bus Bar to Cable Connector via KWh meter - 6.0 Sqmm
Note:- 1. The panel shall be suitable to accomodate 08 smart energy meter with all accessories.
2. Meter dismantling and refixing will be paid in respective item of Sch/BOQ. 3. Individual qtr sub main wiring will be disconnected from old panel and reconnected to new
panel.
4. The quoted rate shall be deemed to be included of above. | 7 | Each | 50,000 ₹3.5 L | 1,10,000 ₹7.7 L |
| 3.00 | Supply ,install, testing & commissioning of Indoor type, Wall mounted (with anchor bolts & nuts and PCC work as required) compartmentalized type Meter Cabinet of overall dimension 1500mm (L) x 800mm (W) x 200mm (D) made out of 2.0 mm thick CRCA Sheet with front door having inspection window duly covered with transparent polycarbonate / glass panel for viewing KWh meter . All doors should have gasket and locking arrangement to meet ingress protection level IP-43. The cabinet shall be painted both internally and externally with powder coated paint (RAL 7032 : SIEMENS GREY) two coats after necessary over a coat of red oxide . The cabinet shall be comprising of following accessories :-
a) Four pole MCCB, 100 Amps with breaking capacity 25 KA having fixed thermal and fixed magnetic release and spreader link at both incoming and outgoing side.- 01 No.
b) Copper Bus Bar of size 25mm x 3mm duly mounted on FRP insulators and necessary drilling for 1 incoming & minimum 6 outgoing connections and duly covered with heat shrinkable PVC sleeves of standard colour code - 4 Nos.
c) MCB SPN 40 Amps, 10 KA - 6 Nos ( To be connected with 6 Nos Meters)
d) MCB SP 10 Amps, 10 KA -2 No ( For common lighting & spare)
e) LED indicating Lamps -03 Nos.
f) Internal wiring with 1100V grade FRLS PVC insulated multi flexible copper wire of sizes duly crimped with copper lugs of suitable size & type all as mentioned below :-
i) MCCB to Bus Bar - 10.0 Sqmm copper
ii) Bus Bar to Cable Connector via KWh meter - 6.0 Sqmm
Note:- 1. The panel shall be suitable to accomodate 06 smart energy meter with all accessories.
2. Meter dismantling and refixing will be paid in respective item of Sch/BOQ.
3. Individual qtr sub main wiring will be disconnected from old panel and reconnected to new
panel.
4. The quoted rate shall be deemed to be included of above. | 8 | Each | 40,000 ₹3.2 L | 95,000 ₹7.6 L |
| 4.00 | Taking down Electric Meter any make and any size and deposit in safe custody with MES store yard and re-fixing after completion of work complete all as specified and directed. | 104 | Each | 20 ₹2,080 | 100 ₹10,400 |
| 5.00 | M&L for disconnecting and removing existing unserviceable /damaged mild steel sheet enclosure of any description and in any position complete and Supply ,install, testing & commissioning of Indoor type, Wall mounted (with anchor bolts & nuts and PCC work as required) compartmentalized type Meter Cabinet of overall dimension 1800mm (L) x 800mm (W) x 200mm (D) made out of 2.0 mm thick CRCA Sheet with front door having cut out duly covered with transparent polycarbonate / glass panel for viewing KWh meter and other door shall be opaque. All doors should have gasket and locking arrangement to meet ingress protection level IP-43. The cabinet shall be painted both internally and externally with powder coated paint (RAL 7032 : SIEMENS GREY) after necessary surface treatment. The cabinet shall be fabricated as per the drawing and comprising of following accessories :-
(A)
a) Copper Bus Bar of size 25mm x 3mm duly mounted on FRP insulators and necessary drilling for 1 incoming & minimum 8 outgoing connections and duly covered with heat shrinkable PVC sleeves of standard colour code - 4 Nos.
b) LED indicating Lamps.
c)Internal wiring with 1100V grade FRLS PVC insulated multi flexible copper wire of sizes duly crimped with copper lugs of suitable size & type all as mentioned below :-
i) MCCB to Bus Bar - 10.0 Sqmm copper
ii) Bus Bar to Cable Connector via KWh meter and MCB - 6.0 Sqmm
iii) Bus Bar to LED Lamp via MCB - 1.5 Sqmm
(B)
The Panel shall have suitable provision and space for fixing of following :-
(a) MCCB 125 Amps 4 pole - 01 No
(b) MCB SPN 40 Amps - 08 Nos ( To be connected with 08 Nos meter)
(c) MCB SP 10 Amps - 02 No ( for common lighting & spare)
(d) Smart Energy Meter - 08 Nos
Note:- The serviceable items retrived from dismantling panel shall be refixed in above panel and quoted rate deemed to be inclusive of above cost of fixing. | 5 | Each | 50,000 ₹2.5 L | 1,10,000 ₹5.5 L |
| 6.00 | M&L for disconnecting and removing existing unserviceable /damaged mild steel sheet enclosure of any description and in any position complete and Supply ,install, testing & commissioning of Indoor type, Wall mounted (with anchor bolts & nuts and PCC work as required) compartmentalized type Meter Cabinet of overall dimension 1500mm (L) x 800mm (W) x 200mm (D) made out of 2.0 mm thick CRCA Sheet with front door having cut out duly covered with transparent polycarbonate / glass panel for viewing KWh meter and other door shall be opaque. All doors should have gasket and locking arrangement to meet ingress protection level IP-43. The cabinet shall be painted both internally and externally with powder coated paint (RAL 7032 : SIEMENS GREY) after necessary surface treatment. The cabinet shall be fabricated as per the drawing and comprising of following accessories :-
(A)
a) Copper Bus Bar of size 25mm x 3mm duly mounted on FRP insulators and necessary drilling for 1 incoming & minimum 8 outgoing connections and duly covered with heat shrinkable PVC sleeves of standard colour code - 4 Nos.
b) LED indicating Lamps.
c)Internal wiring with 1100V grade FRLS PVC insulated multi flexible copper wire of sizes duly crimped with copper lugs of suitable size & type all as mentioned below :-
i) MCCB to Bus Bar - 10.0 Sqmm copper
ii) Bus Bar to Cable Connector via KWh meter and MCB - 6.0 Sqmm
iii) Bus Bar to LED Lamp via MCB - 1.5 Sqmm
(B)
The Panel shall have suitable provision and space for fixing of following :-
(a) MCCB 100 Amps 4 pole - 01 No
(b) MCB SPN 40 Amps - 06 Nos ( To be connected with 06 Nos meter)
(c) MCB SP 10 Amps - 02 No ( for common lighting & spare)
(d) Smart Energy meter - 06 Nos
Note:- The serviceable items retrived from dismantling panel shall be refixed in new panel and quoted rate deemed to be inclusive of above cost of fixing. | 5 | Each | 40,000 ₹2 L | 95,000 ₹4.8 L |
| 7.00 | S&F MCB single pole 6 to 30 Amps, "B" Curve 10KA ,240 Volts complete all as specified and directed. | 3 | Each | 90 ₹270 | 140 ₹420 |
| 8.00 | S&F MCB Single pole and neutral 40 Amps, 240 Volts complete all as specified and directed. | 10 | Each | 250 ₹2,500 | 500 ₹5,000 |
| 9.00 | Supply and fixing in repair MCB DB SPN 12 way double door 230 volt, IP-43, supply complete fixed properly and to connect their incoming/outgoing electric connections by means of suitable size of lugs/thimbles and to provide required sizes of flexible conduit at any open surfaces near DB's of cables/wires complete all as specified and directed. | 25 | Each | 1,200 ₹30,000 | 1,300 ₹32,500 |
| 10.00 | Supply and fixing in repair MCB DB SPN 16 way double door 230 volt, IP-43, supply complete fixed properly and to connect their incoming/outgoing electric connections by means of suitable size of lugs/thimbles and to provide required sizes of flexible conduit at any open surfaces near DB's of cables/wires complete all as specified and directed. | 10 | Each | 1,500 ₹15,000 | 1,600 ₹16,000 |
Updated dates
Tender Value
₹40.0 L
EMD Value
₹80,000
Closing Date
19 Nov 2025, 6:00 pmClosed
GE(AF) ADM AREA
GE (AF) ADM AREA GWALIOR - 474020
REPAIR/REPLACEMENT OF BLDG MAIN/DISTRIBUTION PANEL, METER BOX INCLUDING REPLACEMENT OF CONNECTED SERVICE CABLE, EARTHING AND OTHER MISC E/M MAINTENANCE WORKS UNDER GE (AF) ADM AREA GWALIOR
2025_MES_736141_1
8523/E8
Open Tender
Civil Works
330 days
GE (AF) ADM AREA GWALIOR
As per tender documents
8 documents required · 8 mandatory
₹500
GE (AF) ADM AREA
₹80,000
Yes
26 Dec 2025
18 Oct 2025
25 Nov 2025
18 Oct 2025
19 Nov 2025
1 Nov 2025
Amount
Disconnecting and removing existing unserviceable/damaged mild steel sheet enclosure of any description and in any position complete all as specified and directed.
Taking down Electric Meter any make and any size and deposit in safe custody with MES store yard and re-fixing after completion of work complete all as specified and directed.
S&F MCB single pole 6 to 30 Amps, "B" Curve 10KA ,240 Volts complete all as specified and directed.
S&F MCB Single pole and neutral 40 Amps, 240 Volts complete all as specified and directed.
Supply and fixing in repair MCB DB SPN 12 way double door 230 volt, IP-43, supply complete fixed properly and to connect their incoming/outgoing electric connections by means of suitable size of lugs/thimbles and to provide required sizes of flexible conduit at any open surfaces near DB's of cables/wires complete all as specified and directed.
Supply and fixing in repair MCB DB SPN 16 way double door 230 volt, IP-43, supply complete fixed properly and to connect their incoming/outgoing electric connections by means of suitable size of lugs/thimbles and to provide required sizes of flexible conduit at any open surfaces near DB's of cables/wires complete all as specified and directed.
Supply and fixing in repair MCB DB SPN 8 way double door 230 volt, IP-43, supply complete fixed properly and to connect their incoming/outgoing electric connections by means of suitable size of lugs/thimbles and to provide required sizes of flexible conduit at any open surfaces near DB's of cables/wires complete all as specified and directed.
Supply and fixing in repair MCB DB SPN 4 way double door 230 volt, IP-43, supply complete fixed properly and to connect their incoming/outgoing electric connections by means of suitable size of lugs/thimbles and to provide required sizes of flexible conduit at any open surfaces near DB's of cables/wires complete all as specified and directed.
Supply and fixing factory made epoxy powder coated distribution board TP & N 4 ways (VTPN MCCB DB) with metal door (IP-43 protection) fabricated from minimum 1.6mm thick CRCA sheet and fixed flush to wall and suitable for universal mounting and including 200 Amps copper bus bar, neutral bar, strandard DIN rail, earth bar and cable ties for cable management, top and bottom removable gland plates with Knockouts and suitable for one TPN-MCCB 100 /125 Amps as incomer and 12 SP MCBs (or any combination of SP/TP MCBs )outgoings incl taking out VTPN MCB DB complete all as specified & directed.
S&F in repair MCB single pole 6 to 30 Amps, "B" Curve 10KA ,240 Volts complete all as specified and directed.
S&F in repair MCB Single pole and neutral 40 Amps, 240 Volts complete all as specified and directed.
Supply and fixing in repair MCB TPN 100 Amps, 10 KA, 240 Volts complete all as specified and directed.
Supplying & fixing MCCB, 3 pole, 125 Amps, 50Hz, 415 Volts with rupturing capacity 16 KA with thermal magnetic release and adjustable overload setting to be fixed in distribution board complete all as specified and directed.
Taking down old unserveceable submain wiring and M&L for concealed sub main wiring with two single core FRLSH PVC insulated and unsheathed copper stranded conductor of size 6 Sqmm 1100 Volts and one run of copper stranded conductor of size 6 Sqmm for continuous earthing drawn in and incl rigid non metallic PVC conduit pipe ISI marked of size not less than 20 mm dia including connecting their incoming/outgoing electric connections by using required sizes of lugs/thimbles complete all as specified and directed. Note :- 1. Two single core cable and one run of earth copper conductor will be measured and paid as one unit length. 2. Flexible conduict of suitable sizes shall be used for open conductor wire.
M&L for earthing with galvanized steel earth plate electrode of size 600x600x6mm buried directly in ground (earth pit not less 2.25 mtr deep below ground level) with top edge of plate should not less than 1.50 mtr below normal ground level and connected to galvanized iron earth lead wire of size 4mm dia by means of bolts, nuts, washers of galvanized iron or steel etc. with earth protected by 15mm bore light grade GI protected pipe and including necessary excavation earth work concrete pit of PCC 1:3:6 type B-1 using 20mm graded aggregate , CI cover of suitable size watering arrangement with funnel wire mesh 20 mm dia GI light grade watering pipe, filling with common salt and charcoal etc complete all as shown in electrical plate No 3 of MES Schedule Part-I including testing complete all as specified and directed.
Excavation in trenches in soft/loose soil not exceeding 1.5 m deep and not exceeding 1.5 mtr wide and getting out including forming bottom surface to required levels/gradients/slopes for foundations/laying of cable etc. all as specified and directed including taking out existing cable protection brick cover etc.
Returning, filling in, including spreading leveling, watering and well ramming the excavated soil in layers not exceeding 25 cm thick complete all as specified and directed.
Removal of surplus excavated soil to a distance not exceeding 50 Mtr distance and depositing as directed at a level not exceeding 1.5 mtr above starting point complete all as specified and directed.
M & L for sand filling with clean dry fine sand unwashed including gently punning around cables in trenches for cable protection complete all as specified and directed. Note:- Punned thickness shall be measured & paid.
M&L bricks for cover underground cable with one layer of bricks using sub class 'B' bricks (Old size) laid flat across the cable complete all as specified and directed. (Excavation and earth work will be measured separately).
Supply , laying , connecting and testing LT 1100 volt grade electric cable XLPE insulated, screened, PVC bedded, galvanised steel strip armoured (heavy duty) ISI marked with aluminium stranded conductor gross sectional area 50 Sqmm , 3.5 core laid in trenches / duct / pipe etc complete all as specified and directed including taking down old unserveceable cable . Note:- 1. Earthwork & excavation shall be measured & paid separetely under respective items. 2. Cutting PCC, Hard standing, tiles shall be measured and paid seperately under respective items.
Supply , laying , connecting and testing LT 1100 volt grade electric cable XLPE insulated, screened, PVC bedded, galvanised steel strip armoured (heavy duty) ISI marked with aluminium stranded conductor gross sectional area 35 Sqmm , 3.5 core laid in trenches / duct / pipe etc all as specified and directed including taking down old unserveceable cable . Note:- 1. Earthwork & excavation shall be measured & paid separetely under respective items. 2. Cutting PCC, Hard standing, tiles shall be measured and paid seperately under respective items.
Supply & Fix in repair 50 mm bore light grade galvanized iron tubing ISI marked including all fittings etc laid in trenches or fixed on wall protection pipe complete all as specified and directed.
M&L for cutting of existing bituminous road/path/hard standing/PCC/Chequered tiles/Interlocking tiles suitable for laying cable protection pipe 50 mm dia under the road/path/hard satnding at a depth not less than 60 CM below the normal ground level, Returning filling soil and making good the disturbed surface of road/path/hardstanding by using cement concrete 1:2:4 type B1, using 20 mm graded stone aggregate 0.45 mtr wide and 0.30 mtr thick complete all as specified and directed.
Supply and Installation of Smart RF AC Single Phase Meter , Two Wire, Tamper Proof of Class 1.0, 240 V, 50 Hz, 10 A-60 A conforming to IS-16444 and relevant IEC standards with inbuilt 865-867 MHz Radio Frequency communication facility with self healing Mesh network with default and on demand display, billing data generation facility, anti-tamper features, Microprocessor and LED/LCD based circuitry including taking down old unsv meter complete all as specified and directed.
Supply and Installation of Smart RF AC Threee Phase Meter , Four Wire, Tamper Proof of Class 1.0, 415 V, 50 Hz, 10 A-60 A conforming to IS-16444 and relevant IEC standards with inbuilt 865-867 MHz Radio Frequency communication facility with self healing Mesh network with default and on demand display, billing data generation facility, anti-tamper features, Microprocessor and LED/LCD based circuitry including taking down old unsv meter complete all as specified and directed. Note for item No 29 & 30 • Meter Should support the following data : 15/30 min instantaneous data for voltage, current, power factor, power, cumulative energy and frequency, 30 load survey data for energy, monthly billing survey for Cumulative Energy and Max Demand to software. • Meter should have connect / disconnect functionality operable from prepaid billing software • The meter should support open communication protocol DLMS with the software
Material and labour for point wiring for one light point of extended length exceeding 15 meter but not exceeding 20 meter controlled by one switch with using 1.5 Sqmm (nominal area) single core 1100 Volts grade FRLSH PVC insulated unsheathed multistranded copper conductor with and including PVC concealed conduit of medium grade of suitable size not less then 20 mm dia all as directed with using new sunken type pressed steel box/terminal boxes of suitable size, 2mm thick duly painted with one coat of red oxide primer and two coats of black bituminous paint for mounting fittings wiring accessories with and including all accessories and using 1.5 Sqmm (nominal area) single core 1100 Volts grade FRLSH PVC insulated unsheathed multistranded copper conductor as in earth wire connected to common earth dolly complete including taking down old U/S wiring with conduit complete all as specified and directed.
Supply and fixing in repairs Street light fittings LED 45W 230 volt AC with lumen efficiency 120 Lm/W , on site warranty with high pressure die cast aluminium housing and heat resistance complete with driver ,lamp bracket, high power LED as light source with acrylic cover, out door luminaire with IP-66 protection and in including suitable bracket (32/40 mm GI pipe light grade), clamp, nut-bolt and washers complete all as specified and directed. Cat Part No - OSL-GRY-LSRT015045XC of Jaquar or Cat part No ENDURASUNDOWNSL45WLED765PASYBOPC of Havells or BRP031 LED45 CW MR PSU GR DX of Philips.
Supply and fixing aluminium landscape luminaire with high power LEDs as light source new generation,RUBY LED POST TOP IP 65 LED 40 Watt post-top family, energy saving, environmental friendly, long life aesthetically designed with symmetrical light distribution, spun aluminium landscape luminaire with high power LEDs as light source complete including taking down unserviceable landscape luminaire of any type and any size complete all as specified and directed.
M/s Anupam Construction Co. (BID ID -3469086)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.42 MB
Tender8523.pdf
Tender Documents • 0.79 MB
BOQ_824293.xls
BOQ • 0.32 MB
Download all tender documents and submit your bid