Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.2 LAccepted-Finance | ₹1.2 L | L1 | Accepted-Finance L1 |
| 2 | L2₹1.4 LRejected-Finance | ₹1.4 L | L2 | Rejected-Finance L2 |
| 3 | L3₹4.8 LRejected-Finance 176 SARWAL COLONY JAMMU | ₹4.8 L | L3 | Rejected-Finance L3 |
| 4 | L4₹26.4 LRejected-Finance | ₹26.4 L | L4 | Rejected-Finance L4 |
| Sl No | Description | Qty | Unit | GLOBAL ENGINEERS L4 | M/S A A ENTERPRISES L2 | KAPIL GUPTA L1 | VEE GEE ENGINEERS L3 |
|---|---|---|---|---|---|---|---|
| 1.00Supply, Installation, Testing & Commissioning of 11KV CT/PT unit with Trivector Meter | |||||||
| 1.01 | 11kV Pilfer resistant metering cubicle for 3phase 4 wire metering system made of MS Sheet steel thickness not less than 2mm duly power coat painted suitable for indoor as well as outdoor as per the site requirement. The cubicle shall be painted through 7-tank process. The External dimensions should be adequate. Panel having two compartments upper Meter compartment and lower CT/PT compartment. Provided with synthetic or semi synthetic gasket firmly glued to the sufrace, Dust, weather and Vermin proof and shall comply degree of protection IP 65 both the chambers having one sided hinged door arrangments. The metering panel shall be provided with two No MS channels of size 100 x 50 mm on the front and rear sides duly welded and 4 No of lifting hooks. It should be possible to take meter reading manually, through CMRI and computer without opening the LV chamber door. | 1 | Nos | 1,45,000 ₹1.4 L | 10,000 ₹10,000 | 13,000 ₹13,000 | 99,999 ₹99,999 |
| 1.02 | Single Phase, Single core, single ratio, Epoxy resin Cast Current Transformers suitable for 11kV, copper wound primary type with rated burden 5VA and accuracy class 0.5 or better and conforming to IS2705 (part-I & II) amended upto date. ISF shall be upto 5
The CT ratio shall be as under:
i. 2.5 /5 for 25kVA DT
ii. 5/5 for 63kVA DT
iii. 7.5/5 for 100kVA DT
iv. 15/5 for 200kVA DT
v. 20/5 for 250kVA DT
vi. 25/5 for 400kVA DT
vii. 50/5 for 630kVA DT
viii. 75/5 for 1MVA DT | 3 | Nos | 1,45,000 ₹4.3 L | 15,000 ₹45,000 | 7,000 ₹21,000 | 27,000 ₹81,000 |
| 1.03 | 11kV/ 110 V, Three phase epoxy resin cast PT with rated burden 15VA per phase and accuracy class 0.5 or better and conforming to IS:3156 (part-I&II) amended upto date with proper colour coded identification. PTs shall be of uniform insulating and withstand separate source 23kV pf for one minute. | 1 | Kms | 15,00,000 ₹15 L | 15,000 ₹15,000 | 17,000 ₹17,000 | 27,000 ₹27,000 |
| 1.04 | Bus Bar details:
CTs bus bar:- 40x6 mm copper strip or adequate size
PTs bus bar: Copper wire 8 SWG or 30x0.6mm copper flat strip to connect PT terminal or adequate size
duly insulated by the monoplast tape | 1 | Set | 50,000 ₹50,000 | 1,000 ₹1,000 | 1,500 ₹1,500 | 9,999 ₹9,999 |
| 1.05 | PVC Copper wire flexible multi-strand of required size for secondary connections for CT wiring the minimum wire size shall be 4 mm2 (RYB) and for PT wiring minimum wire size shall be 2.5 mm2 (RYB). | 1 | Nos | 45,000 ₹45,000 | 1,000 ₹1,000 | 1,100 ₹1,100 | 4,500 ₹4,500 |
| 1.06 | Copper Lugs preferably ring type duly crimped for termination of wires and tapes | 1 | Kg | 2,500 ₹2,500 | 1,000 ₹1,000 | 600 ₹600 | 999 ₹999 |
| 1.07 | Grounding bus of minimum 40mm copper, 25cm long fixed to the unit in HV chamber. The CTs, PT meter and 11kV Cable sheath shall be grounded to the bus through grounding wire (green) of min size 10mm2 | 1 | no | 50,000 ₹50,000 | 10,000 ₹10,000 | 800 ₹800 | 4,500 ₹4,500 |
| 1.08 | 3Ph3 Wire HT CT/PT operated Fully static Smart Tri-Vector Energymeters DLMS Compliant Category 'C' with RS232 port for modem compatibility. 11kV/110V, Ph-Ph (3P,3W) meters for measurement of different electrical parameters including Active Energy (kWh/ MWh), Reactive Energy (kVArh/MVArh), Apparent Energy (kVAh/ MVAh) etc. (make L&T, Secure, ABB) | 1 | Nos | 2,50,000 ₹2.5 L | 15,000 ₹15,000 | 13,000 ₹13,000 | 54,000 ₹54,000 |
| 1.09 | Independent flexible PVC pipes for CT wiring and PT wiring of appropriate size from HT compartment to meter compartment | 1 | Nos | 5,000 ₹5,000 | 15,000 ₹15,000 | 500 ₹500 | 999 ₹999 |
Tender Value
Refer Docs
EMD Value
₹3,000
Closing Date
28 Jul 2025, 2:00 pmClosed
Executive Engineer JPDCL ED-I Parade Jammu
Office of Executive Engineer JPDCL ED-I Parade Jammu
Rate contract for Supply, Erection, Testing and Commissioning of 11KV CT/PT Combined Metering unit alongwith Trivector Meter and 3 Phase 4 Wire Prodigy meter at various distribution Transformers under Electric Division-I Parade Jammu
2025_PDD_280564_1
ED-I/e-NIT/37 of 2025-26 Dated 04.07.2025
Open Tender
Electrical Works
10 days
Parade Jammu
Please refer tender documents
11 documents required · 11 mandatory
₹500
Executive Engineer JPDCL ED-I Parade Jammu
₹3,000
6 Jan 2026
4 Jul 2025
29 Jul 2025
4 Jul 2025
28 Jul 2025
5 Jul 2025
Amount
Supply, Installation, Testing & Commissioning of 11KV CT/PT unit with Trivector Meter
11kV Pilfer resistant metering cubicle for 3phase 4 wire metering system made of MS Sheet steel thickness not less than 2mm duly power coat painted suitable for indoor as well as outdoor as per the site requirement. The cubicle shall be painted through 7-tank process. The External dimensions should be adequate. Panel having two compartments upper Meter compartment and lower CT/PT compartment. Provided with synthetic or semi synthetic gasket firmly glued to the sufrace, Dust, weather and Vermin proof and shall comply degree of protection IP 65 both the chambers having one sided hinged door arrangments. The metering panel shall be provided with two No MS channels of size 100 x 50 mm on the front and rear sides duly welded and 4 No of lifting hooks. It should be possible to take meter reading manually, through CMRI and computer without opening the LV chamber door.
Single Phase, Single core, single ratio, Epoxy resin Cast Current Transformers suitable for 11kV, copper wound primary type with rated burden 5VA and accuracy class 0.5 or better and conforming to IS2705 (part-I & II) amended upto date. ISF shall be upto 5 The CT ratio shall be as under: i. 2.5 /5 for 25kVA DT ii. 5/5 for 63kVA DT iii. 7.5/5 for 100kVA DT iv. 15/5 for 200kVA DT v. 20/5 for 250kVA DT vi. 25/5 for 400kVA DT vii. 50/5 for 630kVA DT viii. 75/5 for 1MVA DT
11kV/ 110 V, Three phase epoxy resin cast PT with rated burden 15VA per phase and accuracy class 0.5 or better and conforming to IS:3156 (part-I&II) amended upto date with proper colour coded identification. PTs shall be of uniform insulating and withstand separate source 23kV pf for one minute.
Bus Bar details: CTs bus bar:- 40x6 mm copper strip or adequate size PTs bus bar: Copper wire 8 SWG or 30x0.6mm copper flat strip to connect PT terminal or adequate size duly insulated by the monoplast tape
PVC Copper wire flexible multi-strand of required size for secondary connections for CT wiring the minimum wire size shall be 4 mm2 (RYB) and for PT wiring minimum wire size shall be 2.5 mm2 (RYB).
Copper Lugs preferably ring type duly crimped for termination of wires and tapes
Grounding bus of minimum 40mm copper, 25cm long fixed to the unit in HV chamber. The CTs, PT meter and 11kV Cable sheath shall be grounded to the bus through grounding wire (green) of min size 10mm2
3Ph3 Wire HT CT/PT operated Fully static Smart Tri-Vector Energymeters DLMS Compliant Category 'C' with RS232 port for modem compatibility. 11kV/110V, Ph-Ph (3P,3W) meters for measurement of different electrical parameters including Active Energy (kWh/ MWh), Reactive Energy (kVArh/MVArh), Apparent Energy (kVAh/ MVAh) etc. (make L&T, Secure, ABB)
Independent flexible PVC pipes for CT wiring and PT wiring of appropriate size from HT compartment to meter compartment
Pedestal made out of MS Channel of size 75 x 40 mm or angle iron of size 65 x 65 x 5 mm, duly painted as per site requirement for mounting of metering panel including concrete foundation wherever required including cost of nuts and bolts
3 Core 11 kV Aluminium cable XLPE armoured 35 mm2 including cost of clamp for its fixing where ever required.
Cable termination kits suitable for 3 x 35 mm2 XLPE Cable (indoor/outdoor)
Earthing 40 mm GI Pipe or 20 mm GI rod, 2.5 mtr for metering unit. Earthing of metering cubicle through two No 25 x 5 mm flat iron.
Supply, Installation, Testing & Commissioning of 3 Phase 4 Wire Prodigy meter
Supply, Installation, Testing & Commissioning ( Including Transporation) of 3 Phase 4 Wire Prodigy meter with all necessary cables of required capacity for making connections including Thimbles & Lugs duly crimped for termination of wires with tapes for meter connections
M/S A A ENTERPRISES (BID ID -2408379)
VEE GEE ENGINEERS (BID ID -2421987)
GLOBAL ENGINEERS (BID ID -2422832)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid