Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹25.8 LAccepted-AOC | L1 | Accepted-AOC LOWEST | |
| 2 | L2₹28.8 L+₹1.9 L (7.06%)Rejected-Finance H NO 861 SECTOR 1 4 HOUSING BOARD COLONY NEAR POLY CLINIC HISAR HARYANA | HISAR | HARYANA | 125001 | L2 | Rejected-Finance HIGHER | |
| 3 | L3₹36.5 L+₹9.6 L (35.7%)Rejected-Finance 2ND FLOOR PLOT NO 338 UDHYOG VIHAR PHASE IV GURUGRAM 122015 HARYANA | GURUGRAM | HARYANA | 122015 | L3 | Rejected-Finance HIGHER | |
| 4 | L4₹37.9 L+₹11.1 L (41.2%)Rejected-Finance | L4 | Rejected-Finance HIGHER |
Tender Value
₹27.7 L
EMD Value
₹56,000
Closing Date
26 Aug 2021, 5:00 pmClosed
Abhishek Jatain, EE
Executive Engineer, Constn.Divn.Hr.PWD B and r,Br., Chandigarh
Replacement of 2 Nos. old D.G. Sets (200 KVA and 45 KVA) with 1 Nos. 250 KVA DG set at the residence of Honble Chief Minister Haryana Sector-3,Chandigarh.
2021_HRY_182735_1
PWD/CHD/CD-CHD/1160
Open Tender
Construction Works
Works
120 days
Chandigarh
Please refer Tender documents.
3 documents required · 3 mandatory
₹5,000
₹56,000
Yes
Chandigarh
9 Jun 2022
9 Aug 2021
31 Aug 2021
9 Aug 2021
26 Aug 2021
9 Aug 2021
12 Aug 2021
Amount
Part-I ( c ) Moulded case Circuit breakers. Supply and erection of moulded case circuit breakers on wall or on existing pedestal including bonding to earth and necessary connections. 250 Amp. To 300 Amp. 415 V 35 KA 3 Phase HSR 31.12.c (iii)
(Q) Earthing Earthing with GI earth plate 600 mm x 600 mm x 6 mm thick including accessories and providing masonry enclosures with cover plate having locking arrangement and watering pipe etc. (but without charcoal or coke and salt) complete as required. HSR 31.22(iii)
Extra for charcoal or coke and salt for G.I. Plate or copper plate earth electrode. HSR 31.22(v)
Pdg. and fixing 25 mm x 5 mm G.I. Strip on surface or in recess for connections etc. as required with all labour and material. HSR 31.22(xv)
Pdg. and fixing 4.00 mm dia G.I.wire on surface or in recess for loop earthing as required . HSR 31.22(xvi)
Supply and erection of under ground cable ,loose in existing pipe or trenches complete with necessary connections . 150 Sq. mm 3.5 Core Armoured Cable. HSR 31.26 (xxxi)
Supply and erection of suitable compression type brass cable glands for underground Cable. 120 Sqmm to 185 Sqmm Cable 3 to 3.5 Core HSR 31.28 (v)
(X) Miscellaneous . Supply and erection of aluminium lugs heavy duty including crimping etc. upto the entire satisfaction of the Engineer-in-charge of the work. 150 sqmm . HSR 31.35 (ix) (k)
S/E of mark double walled corrugated (DWC) HDPE pipe laid 1 Mtr. Below ground level including digging and refilling of earth including cost of suitable size socket / cuppler for HDPE pipe including cost of labour and material required to complete the job in all respect upto the entire satisfaction of Engineer in charge of work. HDPE 90/75 mm outer dia / inner dia HSR 31.67 ( ii )
Part-II S/I/T/C of 250 KVA Cummins CP CB-II, Liquid Cooled Silent DG Set comprising of Cummins make Engine Model 6L 8.9, TAA-G4, 6 cylinders, developing 335 BHP at 1500 RPM & 250 KVA Stamford make Alternator rated at 3 Phase, 415 Volts, Frequency 50 Hz, 0.8 P.F, Speed 1500 RPM, Voltage Regulation +/- 1% all load between no load to full load and factor 0.8 to unity, overload capacity 10% for one hour in any 12 hours of operation without exceeding temperature rise limits specified in BS:2613 or BS:5000 when corrected to ambient temperature at site and aligned on a comman MS base frame complete with M30S Fuel Tank, Resident exhaust silencer, Enclosure type Drip proof and screen procted IP-23, AVM pads fitted on base frame, 2 No. 24 Volts DC Battery (Exide / Tata) with battery leads, 1st fill of Lube Oil, all housed in Sound Proof Acoustic Enclosure with all labour and petty material required to complete the job in all respect upto the entire satisfation of Engineer in Charge of work. NS
Part-III Earth work in excavation in foundations, trenches, etc. in all kinds of soils, not exceeding 2 meters depth including dressing of bottom and sides of trenches, stacking the excavated soil, clear from the edge of excavation and subsequent filling around masonry, in 15 cm layers with compaction, including disposal of all surplus soil, as directed within a lead of 30 meters. HSR 6.6
Cement concrete 1:6:12 with stone aggregate with 40 mm nominal size in foundation and plinth. HSR 10.32
First class brick work laid in cement sand mortar 1:4 in foundation and plinth. HSR 11.4
12mm thick cement plaster in cement mortar 1:4 HSR 15.5
Base course of floors consisting of 100mm thick cc 1:8:16 & 100mm sand filling HSR 14.1
Fe 500 EQR TMT steel bars for R.C.C.works where not included in the complete rate of R.C.C. including bending binding and placing in position complete. HSR 18.22
Cement concrete 1: 1 ½:3 with stone aggregate 20mm nominal size in foundation and plinth HSR 10.42
Pvdg. & laying sand under floor from all lead & lift i/c loading/unloading and carriage to site of work from nearest approved quarry, ramming, watering etc. complete in all respect as per entire satisfaction of Engineer-in-charge. NS-1
Pvdg. & fixing 80mm thick pre-polished interlocking paver tiles with sand filling complete in all respect as per entire satisfaction of Engineer-in-charge. NS-2
Constg. Shed with iron channel and MS pipe with roofing of Tata sheet complete in all respect as per entire satisfaction of Engineer-in-charge. NS-3
Pvdg. & fixing the cock mesh with 1 ¼” angle frame i/c cost of painting complete in all respect as per entire satisfaction of Engineer-in-charge. NS-4
Less old Buyback of 200 KVA (Ruston & Hornsby make) DG Set @ Rs. 75000/- Each. Less old Buyback of 45 KVA (Kirloskar Make) DG Set @ Rs. 30000/- Each.
M/S NATWADIA ELECTRICAL COMPANY
Netromics Engineering Solutions Private Limited
ADVANCE ELECTRICAL
stage.html
html • 0.05 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .