Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹35.1 LAccepted-AOC NO 7 3RD MAIN ROAD MUNI REDDY LAYOUT HORAMAVU MAIN ROAD BANASAWADI BANGALORE 560043 | BENGALURU URBAN | KARNATAKA | 560043 | L1 | Accepted-AOC L1 | |
| 2 | L2₹37.5 L+₹1.7 L (4.78%)Rejected-AOC NO 6 NJ BUILDING GANGAMMA TEMPLE ROAD JALAHALLI POST BANGALORE 560 013 | BANGALORE | BANGALORE | KARNATAKA | 560013 | L2 | Rejected-AOC L2 | |
| 3 | L3₹39.5 L+₹3.7 L (10.3%)Rejected-AOC | L3 | Rejected-AOC L3 | |
| 4 | L4₹41.0 L+₹5.2 L (14.5%)Rejected-AOC | L4 | Rejected-AOC L4 | |
| 5 | L5₹41.3 L+₹5.5 L (15.3%)Rejected-AOC | L5 | Rejected-AOC L5 |
Tender Value
₹44.9 L
EMD Value
₹89,880
Closing Date
11 Jun 2024, 6:00 pmClosed
GE (AF) Yelahanka
GE (AF) Yelahanka Bangalore-63
REPAIR/REPLACEMENT OF PUMP SETS, MOTOR, PANEL FOOT VALVES, FIRE HYDRANTS AND ALLIED WORKS AT AFS YELAHANKA
2024_MES_653027_1
8263/E8
Open Tender
Civil Works
Item Rate
330 days
Yelahanka
As per NIT
9 documents required · 9 mandatory
₹500
GE (AF) Yelahanka
₹89,880
Yes
13 Jul 2024
14 May 2024
18 Jun 2024
14 May 2024
11 Jun 2024
28 May 2024
Amount
Repairs and servicing of Split case centrifugal two stage, pump set 50 HP Pump Set DSM 100/36, Kirloskar make, with and including replacing the following worn out parts and re-erecting, testing and commissioning all as specified and as directed (a) Coupling bolts (b) Coupling rubber bushes (c) Split casing gaskets (d) Gland bolt and gland packing (e) Shaft sleeves (f) Replacing the air cock greasing nipples etc. , (g) replacing impeller and fixing of rubber mounting vibration pad mounting frame, foot valve leather with nuts and bolts etc., installed inside the pump house all as directed by Engineer-in-Charge.
All as per Item No-1, herein before but pump set of capacity 30 HP TYPE DSM-3
All as per Item No-1, herein before but pump set of capacity 40 HP TYPE DSM-3
Repairs and servicing to Squirrel cage induction motor SPDP type, 3 Phase 415 volts, AC, 50 HZ, 50 HP, Kirloskar make, driving the pump set DSM 100/36, cleaning the inside of stator, rotor, varnishing and drying, re-erecting, aligning with the pump, testing and commissioning, with and including replacement of DE and NDE bearings, grease nipples, any other minor parts required for proper functioning, over hauling, terminals etc and the motor after preparing the surface all as specified and directed.
All as per Item No-4, herein before but for 40 HP TYPE DSM-3
All as per Item No-4, herein before but for 30 HP TYPE DSM-3
Repairs and servicing of Centrifugal Monoblock pump set Make : KIRLOSKAR, KDS type, driven by Squirrel cage induction motor, TEFC, 3 Phase 415 volts, AC, 50 HZ, 15 HP, cleaning the inside of stator, rotor, varnishing and drying, re-erecting, testing and commissioning, with and including replacement of DE and NDE bearings, shaft seal, any other minor parts required for proper functioning, and applying two coat of synthetic enamel paint after preparing the surface all as specified and directed
Repairs and servicing of Centrifugal Monoblock pump set, KDS type, driven by Squirrel cage induction motor, TEFC, 3 Phase 415 volts, AC, 50 HZ, 12.5 HP, stripping out the burnt winding and rewinding with super enameled copper winding wire of the same gauge varnishing and drying, re-erecting, testing and commissioning, with and including replacement of DE and NDE bearings, shaft seal, any other minor parts required for proper functioning, and applying two coat of synthetic enamel paint after preparing the surface all as specified and directed
All as per Item No-8, herein before but of capacity 3 HP
All as per Item No-8, herein before but of capacity 5 HP
All as per Item No-8, herein before but of capacity 10 HP
S&F gland packing of required size of gland of superior quality to centrifugal / monoblock pumps of following capacities all as specified and directed
For 30 to 50 HP pump set
For 3 to 15 HP pump sets
Repair/servicing of star delta starter 10 HP to 20 HP remove carbon with carbon remover and clean contactor parts smoothly with brush and replaced the burned wiring and thimbles all as specified and as directed.
Repair/servicing of star delta starter 30 HP to 50 HP remove carbon with carbon remover and clean contactor parts smoothly with brush and replaced the burned wiring and thimbles all as specified and as directed.
S&F in repairs fully automatic star delta starter complete suitable for centrifugal pump set 30 HP complete all as specified and directed.
S&F in repairs fully automatic star delta starter complete suitable for centrifugal pump set 40 HP complete all as specified and directed.
S&F in repairs fully automatic star delta starter complete suitable for centrifugal pump set 50 HP complete all as specified and directed.
S&F in repairs fully automatic star delta starter complete suitable for centrifugal pump set 15 HP complete all as specified and directed.
S&F in repairs direct on line starter suitable for 5HP to 7.5HP all as specified and as directed.
S&F in repairs Cast Iron foot valve of 150 mm bore conforming to IS 4038 including provision of nuts bolts and washers etc., complete all as specified and directed.
S&F in repairs Cast Iron foot valve of 100 mm bore conforming to IS 4038 including provision of nuts bolts and washers etc., complete all as specified and directed.
S&F in repairs Cast Iron foot valve of 80 mm bore conforming to IS 4038 including provision of nuts bolts and washers etc., complete all as specified and directed.
Taking out unserviceable existing foot valve, Supply and Fixing Cast Iron foot valve of 50 mm bore including nuts bolts and wahsers etc., Complete all as specified and as directed.
Dismantling the delivery pipe line of submersible pump set from water mains, lifting/taking out of GI column pipes of 50mm dia, submersible cable, defective submersible pump sets any capacity from borewells up to 100 mtr depth for repairs and lowering of repaired pump sets with GI column pipe 50mm dia, cable etc complete in the borewell at various sites under GE (AF) Yel. The job is inclusive of M&L for jointing of submersible cable, reconnecting the delivery pipe line to water mains, testing for satisfactory running and continous flow of water complete all as directed. Note: Reparing/ Servicing of submersible pump set shall be mesured and paid separately.
Repairs and servicing of defective submersible pump of capacity of 5 HP, 7.5 HP and 10 HP by dismantling the pump and removing unserviceable parts, assemble the pump properly after replacement of unserviceable parts. Note : (a) The rates are inclusive of transportating the pump set to workshop and back to site. (b) The rates are inclusive of turning/finishing work for fixing of parts properly. (c) Unserviceable parts if any replaced shall be measured and paid separately as supply only under Item No-26. (d) The rates are inclusive of testing, installation and satisfactory functioning of the pump set.
Supply only of following parts of submersible pump sets of capacity upto 10 HP :-
(a) CI Stage casing
(b) GM Bush
(c) SS Sleeve
(d) suitable size impeller
(e) MS Key for Shaft
(f) SS studs with nuts of suitable size for pump
(g) SS coupling bush common for pump and motor with key
(h) High Tensile steel shaft
Repairs and servicing of defective submersible motors of capacity 5 HP, 7.5 HP and 10 HP by dismantling the motor and removing unserviceable parts, assemble the motor properly after replacement of serviceable parts. Note : (a) The rates are inclusive of transportating the motor set to workshop and back to site. (b) The rates are inclusive of turning/finishing work for fixing of parts properly and testing, installation etc. (c) Unserviceable parts if any replaced shall be measured and paid separately as supply only under Item No-28. (d) Rewinding of motor and servicing of rotor, if required will be measured and paid separately..
Supply only of following parts of submersible motor of capacity upto 10 HP
(a) Bearing Bush gun metal
(b) Bearing Bush ss with rubber
(c) Oil seal
(d) Sand guard
(e) SS studs with nuts of suitable size for motor
Rewinding of mono block pump set single phase of capacity 1 to 2 HP by taking out burnt copper winding from stator, cleaning the casing and slots with wire brush and washing with pressure water and dried it, re-winding the motor with required gauge of insulated copper wire and making the winding leak proof and connection lead suitable size of cable upto 2 mtr long all as specified and directed.
Rewinding of submersible motor 3 phase of capacity 3 HP by taking out burnt copper winding from stator, cleaning the casing and slots with wire brush and washing with pressure water and dried it , re-winding the motor required gauge of insulated copper wire and making the winding leak proof and connection lead suitable size of submersible cable upto 2 mtr long all as specified and directed.
All as per item No 30 herein above but of capacity 5 HP
All as per item No 30 herein above but of capacity 7.5 HP
All as per item No 30 herein above but of capacity 10 HP/12.5 Hp
Repairs to GI column pipe of 50mm bore, by cutting the worn out portion of threads and rethreading at each end of pipe all as specified and directed.
Supply and replacement of unserviceable GI socket heavy duty 50mm dia suitable for GI column pipe all as specified and directed.
S&F in repairs Gun metal gate valve with iron wheel head ISI marked screwed both ends complete for 50 mm dia iron pipes Complete all as specified and as directed by Engr-in-Charge.
S&F in repairs Gun metal gate valve with iron wheel head ISI marked screwed both ends complete for 40 mm dia iron pipes Complete all as specified and as directed by Engr-in-Charge.
S&F in repairs Gun metal gate valve with iron wheel head ISI marked screwed both ends complete for 25 mm dia iron pipes Complete all as specified and as directed by Engr-in-Charge.
Taken out and replacement of unserviceable GI column pipe & fittings threaded both side heavy duty 50mm dia from bore well all as specified and directed
S&F in repairs flat cable PVC insulated and sheathed multi-stranded copper conducor water proof suitable for submersible pump set of size 6 Sqmm 3 core complete all as specified and directed.
S&F in repairs flat cable PVC insulated and sheathed multi-stranded copper conducor water proof suitable for submersible pump set of size 4 Sqmm 3 core complete all as specified and directed.
S&F in repairs flat cable PVC insulated and sheathed multi-stranded copper conducor water proof suitable for submersible pump set of size 10 Sqmm 3 corecomplete all as specified and directed.
Dismantling the electric connection from the induction motor and taking down the motor 50 HP after removing the necessary nuts/ bolts and coupling etc and transporting to local workshop and Dismantling and opening the AC motor by unscrewing the bolts / nuts end cover etc and taking out the burnt starter and rotor windings, cutting and removing the burnt out copper windings complete from the startor slots including necessary cleaning thoroughly with a wire brush and dried it . Material and labour for rewinding with super enameled copper wire as per the existing gauge including placing the fibre glass sleeves and insulating paper glass F (numen) and applying appropriate varnish dirying replacement of bearings 2 Nos and properly assembling including testing and transporting back to the Pump House , assembling the motor carefully to its original position including necessary electric and other connections and testing to the satisfaction of Engineer-in-Charge.
All as per herein above item No- 43 but Capacity 40HP
All as per herein above item No -43 but Capacity 30HP
Dismantling the electric connection from the motor and taking down the motor 15 HP after removing the necessary nuts/ bolts and coupling etc and transporting to local workshop and Dismantling and opening the AC motor by unscrewing the bolts / nuts end cover etc and taking out the burnt starter and rotor windings, cutting and removing the burnt out copper windings complete from the startor slots including necessary cleaning thoroughly with a wire brush and drying and applying a coat of varnish etc all as specified and including material and labour for rewinding with super enameled copper wire as per the existing gauge including placing the fibre glass sleeves and insulating paper glass F (numen) and applying appropriate varnish dirying replacement and properly assembling including testing and transporting back to the Pump House , assembling the motor carefully to its original position including necessary electric and other connections and testing to the satisfaction of Engineer-in-Charge all as specified and directed.
All as per herein above item No 46 but Capacity 10 to 12.5 HP
All as per herein above item No 46 but Capacity 7.5 HP
All as per herein above item No 46 but Capacity 5 HP
All as per herein above item No 46 but Capacity 3 HP
Cutting and cleaning the grass wild vegetation, from roots, shapings shrubs, bush, undergrowth,roots, removing vegetation over the fencing and removing rootas, removing, vegetation over the fencing and removing unwanted materials to a distance exceeding 400 mtrs away from the pump house at NPH, 1&2 Pump houses/water supply installations and arround UG sumps as well as OH rservoirs alongwith surrounding areas complete all as directed.
M & L for preparation of old surfaces and applying two coats of synthetic enamel paintings with approved colours to pumpsets capacity of various sizes of centrifugal and monoblock pumpsets for the following:-
1 HP to 15 HP
30 HP to 50 HP
Dismantling and Taking down old Unservice GI pipe of dia 20 mm bore from Wall/trench /floor complete all as directed. Note : Excavation and refilling and removing surplus soil shall be measured and paid seperately.
All as per item No.53 herein above but 25mm dia GI Steel tubing
All as per item No.53 herein above but 40mm dia GI Steel tubing
All as per item No.53 herein above but 50mm dia GI Steel tubing
S&F of GI tubing medium grade 15mm dia with all fittings complete fixed to walls/ceilings or laid in floor all as specified and directed.
All as per item No. 57 herein above but 20mm dia GI Steel tubing
All as per item No. 57 herein above but 25 mm dia GI Steel tubing
All as per item No. 57 herein above but 40 mm dia GI Steel tubing
All as per item No. 57 herein above but 50 mm dia GI Steel tubing
Taking out unserviceable existing sluice valve any type, S&F 150mm dia bore Sluice Valves both side flanged and ISI marked (IS-780) of sluive valve cast iron body with stainless spindle and fly nuts, class PN-1.6 and Cast Iron hand wheel and joining with nut, bolt, washeres and rubber insertion packing 6mm thick etc, complete all as specified and as directed
Taking out unserviceable existing sluice valve any type, S&F 100mm dia bore Sluice Valves both side flanged and ISI marked (IS-780) of sluive valve cast iron body with stainless spindle and fly nuts, class PN-1.6 and Cast Iron hand wheel and joining with nut, bolt, washeres and rubber insertion packing 6mm thick etc, complete all as specified and as directed
Taking out unserviceable existing sluice valve any type, S&F 80mm dia bore Sluice Valves both side flanged and ISI marked (IS-780) of sluive valve cast iron body with stainless spindle and fly nuts, class PN-1.6 and Cast Iron hand wheel and joining with nut, bolt, washeres and rubber insertion packing 6mm thick etc, complete all as specified and as directed
Supply Only Calcium based granular high strength Chlorine chemical suitable for drinking water treatment Complete as per Manufacturers Specifications and as directed.
Supply Only Chlorine test kit with coloured sample Complete with all testing fitments and OT - solution in Rexene finished box Complete all as specified and as directed.
Chemical and Bacteriogical analysis of water as per IS 10500 parmeter,sample collected from bore well /shallow wells /BWSSB water /user point all as directed by Engr-in-charge Note : water to be tested once in 06 months from approved NABL Lab.
Taking out the unserviceable /corrored GI pipe (Suction pipe ) 150 mm dia from UG sump/shallow well supply and fixing GI Pipe medium grade 150mm dia 3.5 mtr to 4 mtr length including bends and provn to fixing foot valve complete all as specified and directed.
Taking out the unserviceable /corrored GI pipe (Suction pipe ) 100 mm dia from UG sump/shallow well supply and fixing GI Pipe medium grade 100mm dia 3.5 mtr to 4 mtr length including bends and provn to fixing foot valve complete all as specified and directed.
Taking out the unserviceable /corrored GI pipe (Suction pipe ) 80 mm dia from UG sump/shallow well supply and fixing GI Pipe medium grade 80mm dia 3.5 mtr to 4 mtr length including bends and provn to fixing foot valve complete all as specified and directed.
Excavation in trenches in Soft / Loose soil not exceeding 1.5 metre wide and not exceeding 1.5 metre deep for laying of pipe etc, getting out and forming bottom surface to required gradient Complete all as specified and as directed.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm in any type of Soils complete all as specified and directed.
Removing excavated surplus soil to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point all as directed.
Returning and filling of trenches in two parts (i) using riddled soil obtained from excavated soil upto depth of 30cm (8cm below cable and remaining above cable) for cushioning of cable and (ii) refilling the trench of remaining depth with normal excavated soil all as specified and directed. Note : (i) Excavated soil shall be riddled by using sieve to separate composite particles etc as per IS 1255-1983 and refilling in trenches as in cable cushioning.
S&F sub class 'B' laid flat adjecent to each other for Protection on cable all as specified and as directed
Taking out old unserviceable UG cable and Supply and laying 120 Sqmm, 3.5 Core LT UG cable grade PVC XLPE insulated, PVC sheathed armoured, heavy duty, in trenches / walls / poles / passing through pipes with multistranded aluminium conductor including lugs / thimbles / ferrules connection, testing and commissioning Complete all as specified and as directed.
Taking out old unserviceable UG cable and Supply and laying 70 Sqmm, 3.5 Core LT UG cable grade PVC XLPE insulated, PVC sheathed armoured, heavy duty, in trenches / walls / poles / passing through pipes with multistranded aluminium conductor including lugs / thimbles / ferrules connection, testing and commissioning Complete all as specified and as directed.
Taking out old unserviceable UG cable and Supply and laying 35 Sqmm, 4 Core LT UG cable grade PVC XLPE insulated, PVC sheathed armoured, heavy duty, in trenches / walls / poles / passing through pipes with multistranded aluminium conductor including lugs / thimbles / ferrules connection, testing and commissioning Complete all as specified and as directed.
Taking out old unserviceable UG cable and Supply and laying 25 Sqmm, 4 Core LT UG cable grade PVC XLPE insulated, PVC sheathed armoured, heavy duty, in trenches / walls / poles / passing through pipes with multistranded aluminium conductor including lugs / thimbles / ferrules connection, testing and commissioning Complete all as specified and as directed.
Material and Labour for G.I. tubing light grade of size 50mm bore for protection of cables to be laid under roads, crossings / culverts Complete all as specified and as directed.
Material and labour for repairs to LT panel by disconnecting all connected cable, consisting 400 amp 4 pole change over switch - 01 No, 400A MCCB 4 pole 01 No , 63 Amp 3pole MCCB 03 Nos and 63 Amp and 40 Amp 3 pole MCB . Cleaning /servicing by blower with and including replacing the indication lamps , analog voltmeter , ammeter (0 to 600 Amp) square type 4 inch with CTs . Replacing the unsrviceable door hinges ,Lock , rubber beeding and reinsulated the bus bar with colour code heat shrinkable sleave, complete painting , rewiring with copper wire and reconnecting the cables with new lugs if required all as specified and directed at site .
Dismantling and taking out old unserviceable copper cable 16 sqmm from starter to Pump , Supply and laying 16 Sqmm, single Core insulated, PVC unsheathed multistranded copper cable in walls / floors passing through flexible conduit including lugs / thimbles / ferrules connection, testing and commissioning Complete all as specified and as directed.
Dismantling and taking out old unserviceable copper cable 10 sqmm from starter to Pump , Supply and laying 10 Sqmm, single Core insulated, PVC sheathed multistranded copper cable in walls / floors passing through flexible conduit including lugs / thimbles / ferrules connection, testing and commissioning Complete all as specified and as directed.
Dismantling the cable and taking out the wall mounted LT Panel, Supply, installation, testing and commissioning of in door type cubicle wall mounted panel board suitable for 3 phase 4 wire 415 V, 50 Hz , fabricated 2mm thick CRCA sheet with front openable, double door system lockable/ open able. The bottom side contains a detachable plate having size with glands. Provision of threaded earthing stud at side , duly compartmentalized for each control gear, TPN alluminum bus bar of rating not less than the 1.5 times the rated capacity of the incomer MCCB. The TPN bus bar shall be insulated with colour coded heat shrinkable sleave. All control wires shall be with 2.5 sqmm multi strand copper conductor and shall be propely bunched, tied, ferruled for proper identification and crimped with adequate size of lugs, mounted on wall with angle iron 45 x45x 6 mm with and including following accessories complete all as specified and directed by Engr in charge. INCOMING (a) MCCB 4 pole 63 A 16 KA 415 Volts - 1 No (b) Intelligent AC digital display three phase LCD ammeter 0 to 100A and voltmeter 0 to 500V with CT (c) Indication lamp RYB -set of 03 -01 No OUTGOING (a) MCCB 3 pole 32 Amps 10 KA 415 Volt -3 Nos (b) Star delta starter suitable for 12.5 HP - 2 Nos
Dismantling the cable and taking out the wall mounted LT Panel , Supply, installation, testing and commissioning of in door type cubicle wall mounted panel board suitable for 3 phase 4 wire 415 V, 50 Hz , fabricated 2mm thick CRCA sheet with front openable, double door system lockable/ open able. The bottom side contains a detachable plate having size with glands. Provision of threaded earthing stud at side , duly compartmentalized for each control gear, TPN alluminum bus bar of rating not less than the 1.5 times the rated capacity of the incomer MCCB. The TPN bus bar shall be insulated with colour coded heat shrinkable sleave. All control wires shall be with 2.5 sqmm multi strand copper conductor and shall be propely bunched, tied, ferruled for proper identification and crimped with adequate size of lugs, mounted on wall with angle iron 25 x 25 x5mm with and including following accessories complete all as specified and directed by Engr in charge. INCOMING (a) MCCB 4 pole 40 A 10 KA 415 Volts - 1 No (b) Intelligent AC digital display three phase LCD ammeter 0 to 60 A and voltmeter 0 to 500V with CT (c) Indication lamp RYB -set of 03 -01 No OUTGOING (a) MCCB 3 pole 32 Amps 10 KA 415 Volt -2 No (b) DOL starter 5 HP - 1 No (c) MCB SPN 20 Amp - 2 Nos
Dismantling the cable and taking out the wall mounted LT Panel , Supply, installation, testing and commissioning of in door type cubicle wall mounted panel board suitable for 3 phase 4 wire 415 V, 50 Hz , fabricated 2mm thick CRCA sheet with front openable, double door system lockable/ open able. The bottom side contains a detachable plate having size with glands. Provision of threaded earthing stud at side , duly compartmentalized for each control gear, TPN alluminum bus bar of rating not less than the 1.5 times the rated capacity of the incomer MCCB. The TPN bus bar shall be insulated with colour coded heat shrinkable sleave. All control wires shall be with 2.5 sqmm multi strand copper conductor and shall be propely bunched, tied, ferruled for proper identification and crimped with adequate size of lugs, mounted on wall with angle iron 45 x45x 6 mm with and including following accessories complete all as specified and directed by Engr in charge. INCOMING (a) MCCB 4 pole 200 A 25 KA 415 Volts - 1 No (b) Intelligent AC digital display three phase LCD ammeter 0 to 300A and voltmeter 0 to 500V with CT (c) Indication lamp RYB -set of 03 -01 No OUTGOING (a) MCCB 4 pole 160 Amps 25 KA 415 Volt -1 No (b) MCCB 4 pole 100 Amps 25 KA 415 Volt -1 No (c) MCCB 4 pole 63 Amps 16 KA 415 Volt -1 No
Dismantling the cable and taking out the LT Panel , Supply, installation, testing and commissioning of indoor type cubicle panel board suitable for 3 phase 4 wire 415 V, 50 Hz and tested at CPRI for 415 volts factory fabricated in an approved factory having modern fabrication process powder coating with suitable gasket to make it dust/vermin proof and general construction comprising the outer shell shall be made out of 2 mm thick CRCA sheet and MS angle section 40x40x6 mm base frame factory fabricated with front openable, double door system lockable/ open able. The bottom of the outer shell contains a detachable plate having size with glands. The outer shell shall be mounted on stand having zine coating not less than 80 microns. Provision of threaded earthing stud at bottom . Inner shell shall be made out of 2.0 mm thick CRCA sheet duly compartmentalized for each control gear, TPN alluminum bus bar of rating not less than the 1.5 times the rated capacity of the incomer MCCB. The TPN bus bar shall be insulated with colour coded heat shrinkable sleave. All control wires shall be with 2.5 sqmm multi strand copper conductor and shall be propely bunched, tied, ferruled for proper identification and crimped with adequate size of lugs including PCC work with and including following accessories complete all as specified and directed by Engr in charge. INCOMING (a) MCCB 4 pole 100 A 16 KA 415 Volts - 1 No (b) Intelligent AC digital display three phase LCD ammeter 0 to 160A and voltmeter 0 to 500V with CT (c) Indication lamp RYB -set of 03 -01 No OUTGOING (a) MCCB 3 pole 40 Amps 10 KA 415 Volt -3 No (b) Star Delta starter suitable for 15 HP - 2 Nos
Material and labour for earthing complete with galvanised steel plate electrodes of size 600x600x6mm thick burried directly in ground with earth pit not less than 2.25 meter deep below normal ground level with top edge of plate not less than 1.5 meter below normal ground level connected to galvanised 32x 6 mm earth lead by means of nuts bolts check nuts GI washers earth strip protected by galvanised iron pipe 40 mm bore (light grade) for poles/lightening arrestors/GO Switch/transformer/ panel including connection as directed including concrete pit in PCC (1:3:6) type CI, precast RCC cover slab of size 30x30x10 cm with one handle for lifting made out of 8 mm diameter MS bar finnel wire mesh 20 mm bore galvanised iron pipe (medium grade) for watering charcoal or coke and salt in alternate layers necessary earth work in any type of soil complete all as shown in electrical plate No 3 of SSR Part I including testing on completion all as specified and directed.
Supply and replacement of 63mm dia 15 meter long RRL type A hose complete with male and female coupling as all as speficied directed
Supply and replacement of 63mm dia 30 meter long RRL type A hose complete with male and female coupling as all as speficied directed
Repair and replacement of MS hose reel drum of swining type with 19mm dia rubber braided hose of 36 Mtr length (up streem) and shut of nozzle ,tapping to 100mm dia wet raised with 25 mm dia MS pipe complete all as directed
Repair and replacement of pressure gauge 4 inch dia 0-21 Kgs rating for pump sets and complete all as specified and directed all asdirected by Engr-in- charge
Repair and replacement of CI butterfly valve 100mm dia conforming to IS complete all as specified and directed by Engr- in- charge
Repair and replacement of CI butterfly valve 150mm dia conforming to IS complete all as specified and directed by Engr- in- charge
Supply and laying in repair 150mm dia MS heavy duty 'C' class as per IS 1239 Part -I laid in trenches /fixed on walls / floor complete all as specified and directed Note : Excavation refiliing and removing surplus soil shall be measured and paid separately
Supply and laying in repair 100mm dia MS heavy duty 'C' class as per IS 1239 Part -I laid in trenches /fixed on walls / floor complete all as specified and directed Note : Excavation refiliing and removing surplus soil shall be measured and paid separately
Supply and laying in repair 80mm dia MS heavy duty 'C' class as per IS 1239 Part -I laid in trenches /fixed on walls / floor complete all as specified and directed Note : Excavation refiliing and removing surplus soil shall be measured and paid separately
S&F of Hose box made of 18 gauge MS Sheet 800mm X 600mm X 250mm with double door with 4 mm thick glasses and door frame made of 16 gauge MS sheet painted fire red out side and brilliant white inside yard including taking out the existing box complete all as specified and directed.
S&F of Fire hydrant Post 80mm Dia GI / MS both flanged type 1.5m Height complete all as specified and directed.
S&F of fire hydrant landing valve type A (single head outlet) of 63 mm dia conforming to IS 5290 complete all as specified and directed.
Disconnecting the Jacky pump and motor 10 HP to 15 HP from its existing foundation servicing the motor with replacing the bearing with new one , applying grease with grease gun ,, Dismantling the pump and cleaning the impeller, Replace the burned T nuts and bolts, replacing the gland packing, rubber coupling. assembling the Pump and motor, refixing on foundation channel with new bolts and nuts, coupling the pump and motor with correct alignment, connecting electrical connections, testing and commissionning all as specified and directed by the Engineer-in-charge.
Repairs and servicing of horizontal Split type single delivery centrifugal pump set 100 HP PumpSet Kirloskar make, duly replacing the following worn out parts and re-erecting, testing and commissioning all as specified and as directed (a) Coupling bolts (b) Coupling rubber bushes (c) Split casing gaskets (d) Gland bolt and gland packing (e) Shaft sleeves (f) Replacing the air cock greasing nipples etc. ,(g) Replacing of fan blade and fixing of rubber mounting vibration pad mounting frame, suction pipe up to the sump, delivery pipe, valves, meter, specials etc., installed inside the pump house all as directed by Engineer-in-Charge.
Repairs and servicing to Squirrel cage induction motor , 3 Phase 415 volts, AC, 50 HZ, 100 HP, make CG, cleaning the inside of stator, rotor, varnishing and drying, re-erecting, aligning with the pump, testing and commissioning, including replacement of DE and NDE bearings, grease nipples, any other minor parts required for proper functioning, over hauling including replacing worn out minor parts, terminals etc and the motor after preparing the surface all as specified and directed by Engineer-in-Charge.
Dismantling the electric connection from the induction motor and taking down the motor 100 HP after removing the necessary nuts/ bolts and coupling etc and transporting to local workshop and Dismantling and opening the AC motor by unscrewing the bolts / nuts end cover etc and taking out the burnt starter and rotor windings, cutting and removing the burnt out copper windings complete from the startor slots including necessary cleaning thoroughly with a wire brush and drying and applying a coat of varnish etc all as specified and including material and labour for rewinding with super enameled copper wire as per the existing gauge including placing the fibre glass sleeves and insulating paper glass F (numen) and applying appropriate varnish dirying replacement of bearings 2 Nos and properly assembling including testing and transporting back to the Pump House , assembling the motor carefully to its original position including necessary electric and other connections and testing to the satisfaction of Engineer-in-Charge.
M&L for replacing unserviceable CI impeller suitable for 50 HP pump make Kirlosker all as specified and directed.
M&L for replacing unserviceable CI impeller suitable for 40 HP pump make Kirlosker all as specified and directed.
M&L for replacing unserviceable fan blade suitable up to 50 HP Pump all as specified and directed.
M&L for replacing unserviceable fan blade suitable up to 40 HP Pump all as specified and directed.
Supply only orthodine solution 500ml bottle all as directed.
S&F in repairs Voltmeter Analog size 4 inch x 4 inch , 0-500 Volts Complete all as specified and as directed.
S&F in repairs Cast Iron Non return valve 100mm bore conforming to IS including nuts bolts and washers packing etc., Complete all as specified and as directed.
S&F in repairs Cast Iron Non return valve 80mm bore, conforming to IS including nuts bolts and washers packing etc., Complete all as specified and as directed.
M&L for Plain Cement Concrete (1:2:4), type B1 (using 20mm graded stone aggregate) as in Coping, bands benching etc including finishing the concrete surfaces even and smooth without using extra cement including necessary form work Complete all as specified and directed by Engr-in-Charge.
S&F in repairs MCCB 3 Pole, 415 volts 50 HZ AC suitable for current carrying capacity 160 Amps rating, fixed and thermal magnetic release with rupturing capacity 25 KA all as specified and directed.
S&F in repairs MCCB 3 Pole, 415 volts 50 HZ AC suitable for current carrying capacity 25 Amp to 100 Amp rating, fixed and thermal magnetic release with rupturing capacity 16 KA all as specified and directed.
S&F in repairs MCCB 4 Pole, 415 volts 50 HZ AC suitable for current carrying capacity 200 Amps rating, fixed and thermal magnetic release with rupturing capacity 35 KA all as specified and directed.
S&F in repairs MCCB 4 Pole, 415 volts 50 HZ AC suitable for current carrying capacity 250 Amps rating, fixed and thermal magnetic release with rupturing capacity 35 KA all as specified and directed.
S&F in repair MCCB 4 Pole, 415 V, with Microprocessor release 160 Amps with breaking capacity 36 KA all as specified and directed by Engr-in- charge
Supply and Fixing in repairs Ammeter digital type 0-200 Amps Complete all as specified and as directed.
S&F synthetic Rubber insulated mats 2 mm thick for voltage upto 3.3 kv as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of sizes 2m x 1m.
S&F in repair On load change over switch 400 Amp 4 Pole 415 volts ,50 Hz suitable for existing panel board all as specified and directed by Engr-in- charge
S&F in repairs Gun metal gate valve with iron wheel head ISI marked screwed both ends complete for 20 mm dia iron pipes Complete all as specified and as directed by Engr-in-Charge.
ANAND REFRIGERATION
JITHU CONSTRUCTION COMPANY
JyothsnaNursery
SRI AYYAPPA ENTERPRISES
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .