Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹31.7 LAccepted-AOC 0 HISAR HISAR HARYANA 125004 UDYAM HR 06 0052049 | HISAR | HARYANA | 125004 | L1 | Accepted-AOC Being a lowest bidder and reasonable | |
| 2 | L2₹33.4 L+₹1.2 L (3.82%)Rejected-Finance | L2 | Rejected-Finance Other than lowest | |
| 3 | L3₹33.7 L+₹1.6 L (4.94%)Rejected-Finance 53 TOLLYGUNGE CIRCULAR ROAD KOLKATA 700 053 | KOLKATA | WEST BENGAL | 700053 | L3 | Rejected-Finance Other than lowest | |
| 4 | L4₹34.1 L+₹2.0 L (6.16%)Rejected-Finance 1 1 MEREDITH STREET KOLKATA 700072 INDIA | KOLKATA | WEST BENGAL | 700072 | L4 | Rejected-Finance Other than lowest | |
| 5 | L5₹35.7 L+₹3.5 L (10.9%)Rejected-Finance 244 22 ONKAR NAGAR B TRI NAGAR TRI NAGAR NEW DELHI 110035 NORTH WEST DELHI DELHI 110035 INDIA | NORTH WEST DELHI | DELHI | 110035 | L5 | Rejected-Finance Other than lowest |
Tender Value
₹31.5 L
EMD Value
₹63,000
Closing Date
29 Jan 2024, 6:00 pmClosed
GE (FW) Kolkata
D9 Commissariat Road Hastings Kolkata 700022
REPAIR/REPLACMENT AND MAINTENANCE OF FIRE FIGHTING SYSTEM, FIRE ALARM PANEL, DETECTORS AND CONNECTED ALLIED WORK AT NEW COMD BLDG, P-1 BLDG, OD-2 AND OTHER BLDG INSIDE FORT WILLIAM UNDER GE (FW) KOLKATA
2024_MES_636385_1
8207/E8
Open Tender
Electrical and Maintenance Works
Item Rate
330 days
GE(FW) Kolkata
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
GE (FW) Kolkata
₹63,000
31 Mar 2024
8 Jan 2024
30 Jan 2024
8 Jan 2024
29 Jan 2024
22 Jan 2024
Amount
Dismantling of Centrifugal Pump set of capacity 60 to 100 HP (Make: Kirloskar), electric driven AC 3 phase, 415 Volts, transporting to workshop, dismantling, removing the burnt out windings, cleaning the starter slots and rewinding with super enamelled copper wire of suitable gauge, insulating, proper heat varnishing, re-assembling and re-installing the pump set complete in existing position complete all as specified and directed by the Engineer-in-Charge.
All as item serial No 1 but suitable upto 20HP
All as item serial No 1 but suitable upto 15HP
S&F Ball bearing for AC 3 phase 415 Volts induction motor / monoblock/ Centrifugal pump set of the following capacities, in replacement as directed by the Engineer-in-Charge :-
Motor / Pump set of capacity 60 HP. Make-SKF/NBC /KSA
Motor / Pump set of capacity 20HP Make-SKF/NBC/KSA
Motor / Pump set of capacity 15HP Make-SKF/NBC /KSA
Dismantling and taking out of the following capacity pump sets of any type (monoblock/centrifugal) complete of any make from any installation , transporting to workshop and re-installation in same position after replacement of worn out spare parts and painting with one coat of synthetic enamell paint to pump only including commissioning and testing on completion all as directed by the Engr-in-Charge. Note : Spares parts will be measured and paid separately under relevent item
Motor / Pump set of capacity 60 HP.
Motor / Pump set of capacity 20HP
Motor / Pump set of capacity 15HP
Disconnecting of all electric connection, taking out 3 phase, 415 Volts induction electric motor from any installation of any make (other than, as catered under Item No. 1 & 2 here-in-before), transporting to workshop, dismantling, overhauling with proper heat varnishing, (for proper insulation), re-metalling, machine polishing of rotor shaft, terminal box and applying one coat synthetic enanel paint, transporting back to work-site for reinstallation of the same including testing complete for the following capacities :-
Motor of capacity 60 HP
Motor of capacity 20 HP
Motor of capacity 15 HP
Supply only cast iron impeller, suitable for 60 HP capacity monoblock pump as directed by the Engineer-in-Charge.Make - Kirloskar/CG/
All as item serial No 17.00 but suitable for 20 HP
All as item serial No 17.00 but suitable for 15 HP
S&F in repair gun metal double male / female suction hose coupling, 63 mm dia, ISI marked, complete all as specified and as directed .
S&F in repair 63 mm dia gun metal branch pipe, instantenous inlet, male threaded outlet, 15 mm bore nozzle long suitable for fire hydrant, complete all as specified and as directed.
S&F in repair 18 SWG thick mild steel hose box of size 800 mm x 600 mm x 250 mm, double door with 4 mm thick glass and door frame made of 16 guage MS sheet painted fire red outside and brilliant white inside yard suitable for 2 numbers 63 mm dia hose and 01 number branch pipe, including writing the BOX Sl no with synthetic enamel paint as per sample complete all as specified and as directed .
S&F in repair Sprinkler Glass Bulb type (Standard Response) as per IS:15105/TAC guidelines 68 degree temperature rating pendent type as per sample suitable for FF Sprinkler system, complete all as specified and as directed .
Supply, fixing, testing and commissioning in replacement of 200mm dia heavy duty class 'C' MS pipe, 6mm thick ISI marked as per IS:1239 with all necessary fittings & fabrication like tees, elbow, flanges, reducer, gaskets, nut and bolts etc welding or screwed joint as required including fixing of pipe with necessary standard standard clamps structural steel supprt as required/directed at site including painting of two coats of synthetic enamel paint of post office red color over two coats of red oxide primer complete all as specified and as directed .
All as per item No. 26 above but size of pipe 150mm.
All as per item No. 26 above but size of pipe 100mm.
S&F in repair 150 mm bore CI sluice valve of Class PN-1.6, long body type, heavy duty, ISI marked (IS-780 & 5312) flanged end with iron wheel and SS spindle including rubber gasket joints, nuts, bolts etc including testing complete all as specified and as directed.
M&L for complete removal of old painted surfaces of fire fighting MS pipes and applying two coats of synthetic enamel paint over a coat of red oxide zinc chrome primer (using spray gun) including preparation of surfaces for any description/type with arrow mark of pipes (with other color as directed by engr-in-charge) complete all as specified and as directed for the following size of pipes :-
80 to 100 mm bore pipes
150 to 200 mm bore pipes
S&F in repair 63 mm bore, 15 metre long fire hose, RRL (Reinforced Rubberised Lined), type "I" marked (Conforming to IS-636) with male & female coupling as per IS: 903 binded with SS wire for SS couplings, complete all as specified and as directed..
Supply and fix in repairs MS pump set base frame suitable for 15 to 20 HP pump set incl necessary dismantling of old PCC and provision of new PCC 1:2:6 foundation, MS foundation bolt, nut & washers complete all as directed.
Supply and fix in repairs MS pump set base frame suitable for 60 to 100 HP pump set incl necessary dismantling of old PCC and provision of new PCC 1:2:6 foundation, MS foundation bolt, nut & washers complete all as directed.
Re-filling of CO-2 gas to existing cylinders any size and capacity (ranging from 2 Kg to 45 Kgs) including necessary hydro testing Complete with certificate of the company complete all as specified and as directed .
S&F in repairs SS hydrant valve for fire fighting equipment 63 mm bore complete all as specified and as directed by the Engineer-in-Charge.
S&F in repair gun metal female adaptor outlet 63mm dia, suitable for fire hydrant, complete all as specified and as directed by the Engineer-in-Charge.
S & F Pressure gauge dial type with range 0 to 14 kg/sqcm including necessary MS pipe & stop cock suitable size as in repair complete all as specified and directed .
S&F in repair gun metal male adaptor outlet 63mm dia, suitable for fire hydrant, complete all as specified and as directed ..
S&F 200 mm bore CI Butterfly valve, lever operated type heavy duty, ISI marked (BS-5155), including rubber gasket joints, nuts, bolts etc including testing as in repair complete all as specified and as directed.
M&L for complete removal of old painted surfaces of mild steel hose box of size 800 mm x 600 mm x 250 mm, double door (any description) and applying two coats of synthetic enamel paint over a coat of red oxide zinc chrome primer (fire red outside and brilliant white inside yard) including preparation of surfaces for any description/type complete all as specified and as directed by the Engineer-in-Charge.
M&L for testing of Wet riser/Down comer system including pipe lines of high rise bldgs Signal Regt/Old Cmd bldg (P-1)] complete with all connected panel and valves on Yearly basis incl minor repair of Panel, gauge and other equipment all major items mentioned in above schedule will be measured and paid seperately all as specified and directed by Engr-in-Charge. (Note: Testing of fire fire fighting system shall be carried out through reputed agency having minimum 05 Yrs experience in fire fighting works. Necessay supporting documents shall be submitted by bidder for approval of Accepting Officer before commencement of work. All major items mentioned in above schedule will be meaured and paid separetely).
M&L for Complete Checking and testing of Wet Riser System, Sprinkler pipe line System of high rise bldgs (NEW OTM CMD BLDG) with all connected fire fighting Pump, electric motor Panels, MCCB, Pressure Switch, Air Vessel, Timer and all valves of any type around the Bldg and Pump house as well as in Bldgs on yearly basis incl minor repair of the equipment, all major items mentioned in above schedule will be measured and paid seperately all as specified and directed by Engr-in-Charge. (Note: Testing of fire fire fighting system shall be carried out through reputed agency having minimum 05 Yrs experience in fire fighting works. Necessay supporting documents shall be submitted by bidder for approval of Accepting officer before commencement of work. All major items mentioned in above schedule will be meaured and paid separetely).
Supply and fix in repair hose reel of Drum, swinging type (wall mounted type ) as per IS: 884, with 20mmX30mtr, long Thermoplastic Hoseas per IS: 12585, ISI marked with PVC 3/4 Shut off Nozzle (Hydraulically Crimped. complete all as specified and as directed by the Engineer-in-Charge.
Supply and fix in repair hose reel, with 20mmX30mtr, long Thermoplastic Hoseas per IS: 12585, ISI marked with PVC 3/4 Shut off Nozzle (Hydraulically Crimped. complete all as specified and as directed by the Engineer-in-Charge.
S&F in repair Zone card for conventional fire alarm control panel upto 24 zones, complete all as specified and as directed by the Engr-in-Charge.( P1 BLdg & OD-II)
S&F in repair Power Supply Card for Conventional fire alarm control panel upto 24 zones, complete all as specified and as directed by the Engineer-in-Charge. ( P1 BLdg & OD-II)
S&F in repair Alarm ACK/Reset Card for Conventional fire alarm control panel upto 24 zones, complete all as specified and as directed by the Engineer-in-Charge. ( P1 BLdg & OD-II)
S&F in repairs Addressable Intelligent Control Module for hooter complete all as specified and as directed by the Engineer-in-Charge.
S&F in repairs PVC Conduit of 25mm dia (medium grade) for fire fighting wiring complete all as specified and as directed by the Engineer-in-Charge.
S&F in repair Conventional type Smoke Detector including base as specified and as directed by the Engineer-in-Charge.
S&F in repair Conventional type Heat Detector including base complete all as specified and as directed by the Engineer-in-Charge.
S&F in repair Conventional type Manual Call Point complete all as specified and as directed by the Engineer-in-Charge.
S&F in repair addressable intelligent Manual call point, housed in 16 SWG sheet housing, resettable type complete all as specified and as directed by the Engineer-in-Charge.
S&F in repair fire alarm sounders/sirens /hooter housed in 16 SWG sheet enclosure, electronic type horizontal single stage continous normal operation for atleast 50 minutes with sound level 65 DB to 120 DB measured at 1.5 Mtr with sound output variation of + 5 DB 500 mtr range suitable for fire alarm control panel complete all as specified and as directed by the Engineer-in-Charge.
S&F in repair PVC insulated armoured copper conductor cable size 1.5 sqmm 2 core FRLS, 1100 volts fixed on wall/celling with fixing accessories complete all as specified and as directed by the Engineer-in-Charge.
S&F in repair Battery 12 Volts, 7 AH, dry type complete all as specified and as directed by the Engineer-in-Charge.
Comprehensive monthly maintenance of auto fire alarm system (of SIEMENS make) installed in New Command Bldg (OTM). Detailed scope of work consists of the following:- (i) Daily inspecting, checking and cleaning, repairing if required all the equipments of fire detection system. (ii) Operational test of all the equipment of fire detection system in presence of rep of users and Engr-in-charge. (iii) The contractor will submit test report regarding functioning of all the equipments duly signed by contractor, user's rep and Engr-in-Charge. (iv) Details of fire equipments required to be maintained are as under:- (a) UL Listed auto fire alarm control panel having micro processor based 3 Nos loop cards (252 device/loop card) - 02 No. (b) UL Listed intelligent addressable multi-criteria detector with base- 587Nos. (c) Manual call point - 88 Nos. (d) Control module for hooter - 61 Nos. (e) Fault isolator - 04 Nos. (f) Wall mounted hooter - 10 Nos. (g) Response indicator - 196 Nos.
NOTES TO ITEM NO. 48:- (i) Maintenance shall be carried out through the OEM or his authorised technician. Supporting documents in this regard shall be submitted for approval of Accepting Officer prior to commencement of work. (ii) The OEM rep or the authorised technician shall attend the site daily and remain at site during office hours. Failue to do so shall invite penalty as stipulated in particular specfications. Proper attendance register shall be maintained duly signed by the contractor and Engr-in-Charge. (iii) Emergency visit will be carried out when called for, in addition to the normal monthly maintenance in case of any failure in the system due to any cause whatsoever without any additional cost. (iv) Material required for replacement will be measured and paid separately under respective items of this schedule.
S&F in repairs Power Transmission Board for FADP complete all as specified and as directed by the Engineer-in-Charge.
S&F in repair Detectors, intelligent addressable type multi Sensor with Heat and Smoke detector Photoelectric with optical base complete all as specified and as directed by the Engineer-in-Charge.
S&F in repair Response indicator as per sample suitable for the Fire alarm system complete all as specified and as directed by the Engineer-in-Charge.
S&F in repairs XDLC for fire alarm panel at New Comd bldg complete all as specified adn as directed by the Engineer-in-Charge.
Repair /Maint of fire fighting conventional FIRE ALARM SYSTEM including rectification, fault identification of complete fire detection system installed at P-1 Bldg & OD-II including minor repair, Yearly testing one time and cleaning of all detector after each testing and replacing the defective parts involved for smooth operation/function of F/Fighting system including cleaning, adjustment, minor repairs of smoke detector, heat detector, Manual call Point and also Checking of fire fighting wiring & FDA Panel etc complete all as specified and directed by Engr-in-Charge. The details of Fire equipments required repairs/maintenance are as under :- (a) Conventional Fire Alarm Panel with 20 zone (total 20 zones )- 01 nos (b) Conventional Smoke detector and Heat detector with base - 960 nos (iii) Conventional Manual Call Point - 30 nos, (iv) UL listed intelligent Hooter-30 Nos (v) Zone Module - 20 Nos
NOTES TO ITEM NO. 53 :- (i) Checking & Repairing if required all the equipments of fire detection system (ii) Operational test of all the equipment of Fire detection system of rep of users and Engr-incharge, (iii) The Contractor will submit test report regarding functioning of all the equipments duly signed by contractor, user's rep and Engr-in-charge (iv) Emergency visit will be carried out when called for in addition to the breakdown call in case of any failure in the system, without any extra cost. (v) Materials required for replacement will be measured and paid seperately under respective items of this schedule
S&F Three pole power contactor of type ML-6, suitable for 415 Volts, including necessary incoming and outgoing elect connections, copper lugs, etc., as in repair complete all as specified and as directed.
S&F Three pole power contactor of type ML-3, suitable for 415 Volts, including necessary incoming and outgoing elect connections, copper lugs, etc., as in repair complete all as specified and as directed.
S&F Three pole power contactor of type ML-2, suitable for 415 Volts, including necessary incoming and outgoing elect connections, copper lugs, etc., as in repair complete all as specified and as directed.
S&F ML bi-metal overload relays, ranging from 10 Amp to 16 Amp, including necessary incoming and outgoing elect connections, copper lugs, etc., as in repair complete all as specified and as directed.
S&F AC electronicl timer ST 100 3 phase electronic timer ranging from 3 - 30 sec including necessary incoming and outgoing elect connections, copper lugs, etc., as in repair complete all as specified and as directed.
M&L Stripping off existing starter panel and replace of single phase preventor matching with motor of type VSP-3 and re-assembling of the panel including rectification of fault and safety device, adjustment of time etc complete as directed .
S&F MCCB 3 pole 25 KA breaking capacity 63 A with thermal magnetic release as in repair complete all as directed by the Engr-in-Charge.
S&F MCCB 3 pole 25 KA breaking capacity 100 A with thermal magnetic release as in repair complete all as directed by the Engr-in-Charge..
S&F MCCB 3 pole 25 KA breaking capacity 200 A with thermal magnetic release as in repair complete all as directed by the Engr-in-Charge.
S&F Three pole power contactor MNX-12 suitable for 415V, 50Hz as in repair all as directed.
S&F Three pole power contactor MNX-25 suitable for 415V, 50Hz as in repair complete all specified and as directed.
S&F Three pole power contactor MNX-32 suitable for 415V, 50Hz as in repair complete all specified and as directed.
S&F Three pole power contactor MNX-50 suitable for 415V, 50Hz as in repair complete all specified and as directed.
S&F Three pole power contactor MNX-95 suitable for 415V, 50Hz as in repair complete all specified and as directed.
DILIP CONSTRUCTION
S.S.ENTERPRISE
PODDAR SALES CORPORATION
NIRMAL SALES CORPORATION
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .