Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance 1 SHAKTI NAGAR JAMMU JAMMU KASHMIR 180001 | JAMMU | JAMMU AND KASHMIR | 180001 | Admitted-Finance |
Tender Value
₹33.4 L
EMD Value
₹66,880
Closing Date
15 Jul 2024, 1:00 pmClosed
Executive Engineer
Executive Engineer, JDA Division No.1,Rail Head Complex, Jammu
Design, SITC of fire fighting system including allied works on turnkey basis at JDA Office Building ( OB 8) , Fruit Complex, Narwal, Jammu including (CAMC) for two years after completion of warranty / DLP of one year. ( 3rd Time)
2024_HAUDD_251151_1
JDA-I/2024-25/e-NIT/07 Dated 25.06.2024
Open Tender
Machineries/ Mechanical Engg Items
Item Rate
180 days
Jammu
As Per SBD
3 documents required · 3 mandatory
₹2,000
Yes
Vice Chairman, JDA
₹66,880
Yes
31 Oct 2024
25 Jun 2024
15 Jul 2024
25 Jun 2024
15 Jul 2024
25 Jun 2024
Amount
Providing and laying of underground M S Pipe (Class-B) ISI marked, capable of withstanding 150 per cent of the working pressure including water hammer effects and test pressure up to 12.0 kg/cm². including cutting/ screwing, welding etc and providing and fitting of all fittings including flanges, bends, tees, elbows, reducers, clamps, hinges etc along with all the earth works. These underground pipes shall be wrapped and coated by providing twin coatings of bitumen, wrapping with first coating then wrapping with bituminous Hessian cloth, of following sizes: If the pipes are laid above the ground as per necessity of ground condition ,they should be properly embedded/ covered in concrete blocks (Payment to be made as per actual measurements.)
a) 150 mm dia
b) 100 mm dia
c) 80 mm dia
Same as above but for over ground M.S Pipes (B class) including cutting holes & chases in bricks or RCC wall/slab & Making good the same. Painting with one coat of primer and two coats of synthetic enamel of approved shade of following sizes: ( mtr ) (Payment to be made as per actual measurements.)
a) 150 mm dia
b) 100 mm dia
c) 80 mm dia
c) 25 mm dia
SITC of single headed oblique pattern hydrant SS Landing valve with 80mm dia flanged inlet and 63mm dia Instantaneous type female outlet complete with cap and all Accessories ISI marked.
Supply of non – percolated flexible hose RRL 63 mm dia x 15 mtr long complete with instantaneous type 63 mm dia male and female ISI market coupling and riveted to hose pipe with rivets and copper wire and ISI marked.
Supply and Installation of gunmetal 63 mm dia short branch Pipe with 20 mm dia nozzle.
SITC of first aid hose reel wall mounting swinging type complete with drum and brackets, 25 mm dia ball valve and 20 mm dia 30 mtr long hose pressure pad hose with shut off nozzle complete as required.
SITC of cast iron double flanged ISI marked butterfly valve complete with rubber insertion, nuts, bolts, washers and tested to to minimum of 20 kg / sq cm pressure, of the following sizes:
a) 150 mm dia
b) 100 mm dia
c) 80 mm dia
SITC of following accessories:
a) 25mm dia spring loaded air release valve
b) Pressure Guage
c) 25 mm dia ball valve
d) Pressure Switch
SITC of cast iron double flanged ISI marked NRV complete with rubber insertion, nuts, bolts, washers etc. of following sizes:
a) 150 mm dia
b) 80 / 100 mm dia
SITC of gunmetal Fire Brigade connection with collecting head 63mm,4 way instantaneous type male couplings with flanged outlet complete with blank caps nuts, bolts & rubber insertions, conforming IS:904-1983
Supply and laying of 3½ core armoured 10 sq. mm aluminum cable from motor to electric panel for automation of the jockey pump.
Supplying & lying of 3.5 core armoured 35 sq mm Aluminum cable frommotor to electrical panel for automation of the system.
DIESEL Fire Pump: SITC of Diesel Driven main fire Pump suitable for automatic operation and consisting of following ,complete in all respect as required Horizontal type multistage centrifugal pump of cast iron body and bronze impeller with stainless steel shaft , mechanical seal confirming to IS 1520 capacity min 1620 LPM with 70 mtr head with Diesel driven Engine 60 HP 1500 RPM water cooled conforming to IS Standard complete with auto starting mechanism ,12/24 volt electric starting equipment ,diesel tank exhaust pipe extended up to 10 meter outside pump room house duly insulated with 50 mm thick glass wool with 1.0 mm thick aluminium sheet cladding ,residential silencer ,instruments and protection as per standard specification .stop solenoid for auto stop in the event of fault with auto indications ,painted with post office red colour etc as required along with 125 mm suction and 100 mm delivery P/F of M.S Fabricated base plate , coupling set ,coupling guard ,foundation bolts etc as per requirement .Suitable Cement concrete foundation duly plastered and with anti vibration pads. Job also includes laying of necessary foundations Dampers, laying of suction and delivery line with installation of suitable rating Sluice and NRV in suction and delivery line and interconnection with sump tank and main common delivery line ,
Main Electric Fire Pump: SITC of Electric Driven Fire Pump suitable for automatic operation and consisting of following ,complete in all respect as required. Horizontal type multistage centrifugal pump of cast iron body and bronze impeller with stainless steel shaft , mechanical seal confirming to IS 1520 capacity min 1620 LPM with 70 mtr head Suitable (40-50) HP Squirrel cage,Induction motor TEFC Synchronous speed 1500 rpm/2900 rpm suitable for operation on 415 volt ,3 phase 50 Hz AC supply with IP protection for enclosure ,Horizontal Foot Mounted Type With F class Insulation Conforming to IS -325. P/F of M.S Fabricated base plate, coupling set ,coupling guard ,foundation bolts etc as per requirement .Suitable Cement concrete foundation duly plastered and with anti vibration pads. Job also includes laying of necessary foundations Dampers, laying of suction and delivery line with installation of suitable rating Sluice and NRV in suction and delivery line and interconnection with sump tank and main common delivery line , , Jockey pump : SITC of Electric Driven Jockey Pump suitable for automatic operation and consisting of following ,complete in all respect as required. Horizontal type multistage centrifugal pump of cast iron body and bronze impeller with stainless steel shaft , mechanical seal confirming to IS 1520 capacity 180 LPM with 70 mtr head Suitable (10-15) HP Squirrel cage,Induction motor TEFC Synchronous speed 1500 rpm/2900 rpm suitable for operation on 415 volt ,3 phase 50 Hz AC supply with IP protection for enclosure ,Horizontal Foot Mounted Type With F class Insulation Conforming to IS -325. P/F of M.S Fabricated base plate, coupling set ,coupling guard ,foundation bolts etc as per requirement .Suitable Cement concrete foundation duly plastered and with anti vibration pads. Job also includes laying of necessary foundations Dampers, laying of suction and delivery line with installation of suitable rating Sluice and NRV in suction and delivery line and interconnection with sump tank and main common delivery line ,
Jockey pump : SITC of Electric Driven Jockey Pump suitable for automatic operation and consisting of following ,complete in all respect as required. Horizontal type multistage centrifugal pump of cast iron body and bronze impeller with stainless steel shaft , mechanical seal confirming to IS 1520 capacity 180 LPM with 70 mtr head Suitable (10-15) HP Squirrel cage,Induction motor TEFC Synchronous speed 1500 rpm/2900 rpm suitable for operation on 415 volt ,3 phase 50 Hz AC supply with IP protection for enclosure ,Horizontal Foot Mounted Type With F class Insulation Conforming to IS -325. P/F of M.S Fabricated base plate, coupling set ,coupling guard ,foundation bolts etc as per requirement .Suitable Cement concrete foundation duly plastered and with anti vibration pads. Job also includes laying of necessary foundations Dampers, laying of suction and delivery line with installation of suitable rating Sluice and NRV in suction and delivery line and interconnection with sump tank and main common delivery line ,
SITC of Air vessel 250mm dia and 1.5 mtr high with dished top, made of 6mm thick MS pipe complete with provision for 25 mm dia air release valve, 25mm dia stop valve, 25 mm dia drain valve , pressure gauge& all accessories as req and painted.
Earthwork excavation in trenches including back filling and leveling the top after laying of MS pipe. ( rmt)
Supply & installation of weather proof hose cabinets fabricated from 18 swg MS sheet/section with full front glass door and suitable to accommodate 2 nos 15 mtr long hoses and 1 no branch pipes as req.
Supply, Installation, Testing and Commissioning of UL listed Intelligent Addressable Smoke detector, optical type with blinking LED and standard base, being capable of addressed electronically. Manual Addressing (Dip/ Rotary Switches) not acceptable.
Supply, Installation, Testing and Commissioning of UL Listed Intelligent Addressable Double action manual pull station, capable of being addressed electronically. Manual Addressing (Dip/ Rotary Switches) not acceptable.
Supply, Installation, Testing and Commissioning of UL Listed Addressable Fault Isolator module complete as required for determining the short in a circuit and separating the segment having the short capable of being addressed electronically. Manual Addressing (Dip/ Rotary Switches) not acceptable.
Supply, Installation, Testing and Commissioning of UL listed micro processor based 2 wire fault tolerant loop, of following loop capacity (each loop accessing minimum 125 detectors and 125 modules ) fire alarm/detection and voice evacuation control panel with 960 Character LCD Display. The panel shall be able to give location of all fire/fault conditions of addressable units via the address codes. Further, the panel must be able to automatically switch ON /OFF respective control module when ever any alarm is triggered. The panel shall have rectifier, Loop cards, L C D unit to indicate Fire/Fault Signal with address and analog output, external/inbuilt printer to log all fire or fault events complete in all respects. The panel shall have a built in power supply and battery charger along with maintenance free 24 AH, 2 x 12 volt SMF Lead acid batteries capable of running for a minimum of 8 hours with battery charger complete as required. A) 1 Loop panel
S/l of 2 x 1.5 sqmm dia PVC insulated copper conductor armoured cable directly on the surface complete as req.
S/l of 4 x 1.5 sqmm dia PVC insulated copper conductor armoured cable directly on the surface complete as req.
Providing & fixing ABC type fire extinguishers 4 Kg cap. Complete with discharge arrangement, high-pressure hose pipe complete as req.
Providing & fixing CO2 type fire extinguishers 4.5 Kg cap. Complete with wheel valve arrangement, high-pressure wire Braided hose pipe as req.
Supplying & fixing a set of GI fire bucket with round bottom each set comprising of 4 Nos of buckets each of 9 ltr cap. Including fixing suitable brackets in the hook for holding buckets Painted with red paint & filled of sand in 2 buckets of each set.
S/f of 5 kg ABC type modular type ceiling mounted Fire Extinguisher as required
Providing and fixing Lift/Floor and fire signage’s printed on photo luminescent U1000 aluminium sheet of 1.0 mm (+10%) containing Lumigen III as base chemical covered under UV stabilize coating and of appropriate size (Glosign or eq. Make) including fixing on wall, door, ceiling etc. with proper clamps, hangers, cleats, anchor fasteners etc. complete in all as directed. ( sqinch )
Comprehensive Annual maintenance contract of the fire fighting system for 2 years after completion of DLP of one year
1st Year
2nd Year
AQUACHEM ENGINEERS (BID ID -2054495)
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .