Shri Jitender Singh, IDSE,EE
GE (N) Bathinda
REPAIR / MAINTENANCE AND IMPROVEMENT OF BUILDING PANEL BOARDS, MCCB, DB AND MCB AND SUB MAIN WIRING AT ZONE A UNDER GE (N) BATHINDA AT BATHINDA MIL STN
2025_MES_691941_1
8939/NIT-60/24/28/E8
Open Tender
Civil Works
Item Rate
120 days
Bathinda
Class D Category b (i)
8 documents required · 8 mandatory
₹500
Yes
GE (N) Bathinda
₹70,000
Yes
10 Mar 2025
4 Jan 2025
26 Feb 2025
4 Jan 2025
24 Feb 2025
17 Feb 2025
4 Jan 2025 - 16 Jan 2025
Amount
Removing of existing Serviceable/ Unserviceable MCCBs, MCBs, Bus bars and connected wiring acessories from existing panel board for cleaning and spray painting the same wall mounted indoor LT panel board including repair of hinges complete prewired, with locking arrangements and hanging bracket suitable for fixing on wall including necessary internal wiring for MCBs and other connected acessories , electric meter and suitable opening for cable entry with gland comprising all as specified and directed by Engr-in- charge. Note :- After the spray painting and cleaning and refixing of bus bars re-connecting energy meters its original position and necessary replacement of bus bars and its connected items included in the quoted rate.
Supply and fixing MCCB 4 Pole, 415 V, Adjustable type, 160 Amps with breaking capacity 36 KA. all as specified and directed.
Supply and fixing MCCB 4 pole 100 Amps 415V with breaking capacity 16 KA. all as specified and directed.
Supply and fixing MCCB 4 pole 63 Amps 415V with breaking capacity 16 KA. all as specified and directed.
Dismantling & Taking down carefully existing unserviceable DBs any type and size including MCCB, MCB, RCCB etc all as specified and as directed.
Supply and fixing sheet metal enclousers made out of CRCA mild steel sheet not less than 1.2 mm thick, double door, powder coated DB VTPN 4 way 415 Volt,(concealed in wall or as directed) protection class IP-54, dust and vermin proof suitable for incorporation of MCCB's upto 125Amp and isolators etc including making good disturbed surfaces of walls as necessaty complete all as specified and directed by Engineer-in-charge.
Supply and fixing (concealed in wall or as directed) factory made DB (made out of CRCA sheet not less than 1.2 mm thick) TPN, 4 Way 433 V (8+12 modules), double door, earth bar, copper bus bar 200 Amp and neutral link, protection class IP-54 suitable for mounting MCB/Isolator, conforming to IS-8623, BS-5484, dust and vermin proof,including making good disturbed surfaces of walls as necessaty complete all as specified and directed by Engineer-in-charge.
Supply and fixing sheet metal enclousers made out of CRCA mild steel sheet not less than 1.2 mm thick, IP-54 protection, flush mounted with metal door, powder coated DB SPN 12 way, 230 V AC with 200 Amp rated bus bar, double door,12 modules, dust and vermin proof suitable for incorporation of MCB's and isolators etc complete all as specified.
Supply and fixing (concealed in wall or as directed) factory made DB (made out of CRCA sheet not less than 1.2 mm thick) SPN, 8 Way 240V, double door, earth bar, copper bus bar 200 Amp and neutral link, protection class IP-54 suitable for mounting MCB/Isolator, conforming to IS-8623, BS-5484, dust and vermin proof, and including making good disturbed surfaces of walls as necessaty complete all as specified and directed by Engineer-in-charge.
Supply and fixing (Concealed with wall) single pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole MCB of capacity 25 Amps, 240 volts for ACs/ Geysers supply complete all as specified and directed by Engineer-in-Charge.
Supply and fixing MCCB four pole, 125 A 415V with breaking capacity 16KA all as specified and directed.
Supply and fixing MCB TPN, 40 to 100 Amps, 415 Volt AC, C curve, 4 module capacity not less than 10 KA complete all as specified and directed by Engineer-in-Charge.
Supply and fixing MCB SP suitable for 230 volts AC supply 6 to 32 Amps, SP rupturing capacity not less than 10KA, C Curve complete all as specified directed.
Supply and fixing MCB SPN 40 to 63 Amps, 10 KA, 'C' curve 230 V AC, 50 Hz including necessary attachment complete all as specified and directed by Engineer-in-Charge.
Supply and fixing RCCB of capacity 63 Amps, 4 pole 100mA for earth leakage protection all as specified and directed.
Supply and fixing RCCB of capacity 63 Amps, 2 pole 100mA, for earth leakage protection all as specified and directed.
Supply and fixing sub main wiring complete with two single core 4 sqmm,1100 volts grade, PVC insulated, multi stranded copper conductor cable FRLSH with continuous copper earth conductor of 4 sqmm of same specifications in existing PVC concealed conduit incl taking down old unserviceable submain wiring complete all as specified. Note :- 3 runs of cable shall be measured as one RM.
Supply and fixing sub main wiring complete with two single core 4 sqmm,1100 volts grade, PVC insulated, multi stranded copper conductor cable FRLSH with continuous copper earth conductor of 4 sqmm of same specifications in & including PVC conduit size 20mm incl taking down old unserviceable submain wiring complete all as specified. Note :- 1. 3 runs of cable and 1 run of PVC conduit shall be measured as one RM. 2. Unit rate shall include the cost of cutting chases and making good the disturbed surfaces to match with existing surfaces.
Supply and fixing sub main wiring complete with two single core 6 sqmm,1100 volts grade, PVC insulated, multi -stranded copper conductor cable FRLSH with continuous copper earth conductor of 6 sqmm of same specifications in existing PVC concealed conduit incl taking down old unserviceable submain wiring complete all as specified. Note :- 3 runs of cable shall be measured as one RM.
Supply and fixing submain wiring complete with two single core 6 sqmm 1100 volts grade, PVC insulated multi stranded copper conductor cable FRLSH with continuous copper earth conductor of 6 Sqmm of same specifications in & including PVC conduit size 20 mm incl taking down old unserviceable submain wiring complete all as specified. Note :- 1. 3 runs of cable and 1 run of PVC conduit shall be measured as one RM. 2. Unit rate shall include the cost of cutting chases and making good the disturbed surfaces to match with existing surfaces.
Supply and fixing for Sub main wiring complete with two single core 10 sqmm,1100 volts grade, PVC insulated, multi -stranded copper conductor cable FRLSH with continuous copper earth conductor of 10 sqmm of same specifications in existing PVC concealed conduit incl taking down old unserviceable submain wiring complete all as specified. Note :- 3 runs of cable shall be measured as one RM.
Supply and fixing for submain wiring complete with two single core 10 sqmm 1100 volts grade, PVC insulated multi stranded copper conductor cable FRLSH with continuous copper earth conductor of 10 Sqmm of same specifications in & including PVC conduit size 20 mm incl taking down old unserviceable submain wiring complete all as specified. Note :- 1. 3 runs of cable and 1 run of PVC conduit shall be measured as one RM. 2. Unit rate shall include the cost of cutting chases and making good the disturbed surfaces to match with existing surfaces.
Material and labour for Earthing complete with galvanised iron earth plate electrode of size 60cm x 60cm x 6mm buried directly in ground (earth pit not less than 2.25 mtr deep below ground level ) with top edge of the plate not less than 1.5 metre below normal ground level, connected to and including earth continuity GI wire 4 mm (upto test point from earth plate i.e. 7.5m min) by means of GI bolts/nuts/washers and including protected by 15mm dia GI light grade protection pipe from earth plate to test point, including making of test point. Earth plate shall be surrounded by packed layer of char coal/coke & salt all around bottom and top with alternative layer. 20mm GI light grade pipe for watering (should be 10cm above GL) and including socket, plug, funnel, wire mesh, RCC cover and (including steel for cover) PCC (1:2:4) type B1 (using 20 mm graded stone aggregate) as in earthing pit including necessary form work, excavation & earth work, all as specified & shown in electrical plate No. 3 of SSR (Part – I) including taking out/dismantling old unserviceable earthing system complete all as directed by Engineer-in-charge. Note:- (i) PCC chamber shall be constructed at least 1.5 metre away from the earth electrode and pipe for watering shall be provided in slanting manner.
M/S Aggarwal construction co. (BID ID -3247151)
AJ. Owners (BID ID -3248144)
M/S Gagan Khosla (BID ID -3246953)
M/s BHUPINDRA ENGINEERING WORKS (BID ID -3248384)
m/s s.n. builders (BID ID -3245118)
M/s VISHAL ELECTRIC STORE (BID ID -3248353)
M/s NIRMAN BUILDERS (BID ID -3248308)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .