Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Fee/PreQual/Technical 2 3 AMIT VIJAY APT CHSL KASTURBA CROSS ROAD NEAR BHANU PARK KANDIVALI WEST MUMBAI 400 067 | MUMBAI | MUMBAI | MAHARASHTRA | 400067 | Admitted-Fee/PreQual/Technical |
| 2 | Admitted-Fee/PreQual/Technical 3 NEW TRIMURTY CO OP HOUSING SOCIETY INGOLE NAGAR WARDHA ROAD NAGPUR 440005 MAHARASTRA | NAGPUR | NAGPUR | MAHARASHTRA | 440005 | Admitted-Fee/PreQual/Technical |
| 3 | Admitted-Fee/PreQual/Technical GROUND FLOOR 72 BUSINESS PARK CROSS ROAD C MAROL INDUSTRIAL AREA MIDC ANDHERI EAST MUMBAI MUMBAI MAHARASHTRA 400093 | MUMBAI SUBURBAN | MAHARASHTRA | 400093 | Admitted-Fee/PreQual/Technical |
| 4 | Admitted-Fee/PreQual/Technical 203 ELECON CHAMBER ANDHERI KURLA ROAD VILLAGE TOWN NEAR SAKINAKA TELEPHONE EXCHA CITY ANDHERI EAST MUMBAI MAHARASHTRA 400072 INDIA | MUMBAI SUBURBAN | MAHARASHTRA | 400072 | Admitted-Fee/PreQual/Technical |
| 5 | Admitted-Fee/PreQual/Technical B 248 BASEMENT BLOCK B CHITTARANJAN PARK NEW DELHI 110019 11 SOUTH DELHI DELHI 110019 | SOUTH EAST DELHI | DELHI | 110019 | Admitted-Fee/PreQual/Technical |
Tender Value
₹36.6 L
EMD Value
₹73,120
Closing Date
13 Aug 2026, 2:00 pmClosed
Chief Engineer and DCE (CED, PD and EP)
Chief Engineer and DCE (CED, PD and EP)
Non Destructive Testing of various plant buildings at Zirconium Complex, Pazhayakayal, Tuticorin 628152.
2026_NFC_918076_1
C/1445/2026
Open Tender
Civil Works
Item Rate
180 days
NFC, Pazhayakayal
Please refer Tender documents.
8 documents required · 8 mandatory
₹0
₹73,120
14 Aug 2026
20 Jul 2026
14 Aug 2026
20 Jul 2026
13 Aug 2026
23 Jul 2026
20 Jul 2026 - 22 Jul 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 0General Notes: 1) All quoted rates for all items shall be inclusive of scaffolding upto heights of 3.5 meters. 2) All quoted rates shall be inclusive of all the tools/equipment/machinery/instrument and labour required for the work. 2) Profometer/cover meter shall be used before extraction of cores in RC members for identifying the location of reinforcement. No extra payment will be made for the same. 3) The tests shall be consucted as per latest editions/amendments of relevant IS codes or equivalent international codes. 4) The detailed test reports along with visual inspection reports as per the department requirement for base level data or for structural condition assessment shall be submitted, furnishing test results /findings and recommendations etc. to arrive at the present condition of the structure and identifying the structural elements that needs to be rehabilitated. The suitable methodology for rehabilitation along with specification of material to be used shall also be submitted along with the report. 5) Survey should be conducted by an experienced graduate civil and electrical engineers under the supervision of NDT level 2 certified Engineer. 6) Tests should be conducted at NABL accredited testing agency. 7) The reports of visual inspection and test results of NDT/other tests and suitable methodology for rehabilitation shall be certified by NDT level 2 certified engineer. | |||||
| 1 | Detailed inspection and physical observation of the Buildings/Structures, submission of detailed documentation/reports, identification and analysis of damage/distress in the RCC/Steel structures like cracks, corrosion, buckling, spallings, visual deformation, distress arising from design deficiencies, environmental exposure, construction errors or operational overloading etc through visual examination, drawings and photographs, distress mapping, dimensional checks of members/connections wherever required, classification of members based on results /findings into Fairly damaged, Moderately damaged, Severely damaged members, identifying minimum of 3 (Three) members from each of the above classification for in-situ testing to arrive at the present condition of the structure, recommendations for rehabilitation / restoration of RCC/Steel members if required, the specification of materials and methodology for the rehabilitation /restoration of the structure or providing baseline data for the structure as envisaged and directed by Engineer- in- charge.
NOTE;
1) Due to security reasons, Department at will arrange photography free of cost. | 37 | Per Structure | - | - |
| 2 | Carrying out Ultrasonic Pulse Velocity test on RC members (per member 4 reading spaced at 300mm center to center) selected at random to assess the quality of concrete as per IS 516 Part 5/Sec-1:2018, (Amendment November 2019) including submission of evaluation report of test results carried out on footings, columns, beams, slabs or any other RCC member etc., as directed by Engineer-in-Charge. | 500 | Per member | - | - |
| 3 | Carrying out Rebound hammer test on RC members (per location (150x150mm grid) considering 9 readings/impacts will be recorded) selected at random to assess the in-situ strength of the concrete near to surface as per IS 516 Part 5/Sec-4:2020 including submission of evaluation report of test results carried out on footings, columns, beams, slabs or any other RCC member etc., as directed by Engineer-in-Charge. | 500 | Per location | - | - |
| 4Carrying out tests for Electro chemical parameter for Half cell potential survey, corrosion rate and resistivity on RC members at random locations and affected areas as per IS 516 (Part-5/sec-2)2021 or equivalent international codes including submission of evaluation report of test results carried out on footings, columns, beams, slabs or any other RCC member etc., as directed by Engineer-in-Charge. | |||||
| 4.01 | Half Cell Potential survey for reinforcement | 60 | Per location | - | - |
| 4.02 | Corrosion rate for concrete | 60 | Per location | - | - |
| 5Extraction of concrete core samples using suitable instrument from RC members on locations identified on the basis of rebound hammer tests and ultrasonic pulse velocity tests and carrying out tests on extracted cores to assess the following parameters of the concrete as per latest edition of IS 516 (Part 4/5), IS 14959, IS 4032, IS 456 etc. including submission of evaluation report on compressive strength, density of concrete, water absorption, UPV of core, Carbonation depth, Ph value, chloride content, sulphate content percentage by weight of cement. Note: The cores hole in RC member shall be filled with cementitious non shrink grout of Fosroc GP2 or approved equivalent including suitable aggregates as per manufacturer's specifications and as directed by EIC. | |||||
| 5.01 | Compressive Strength | 70 | Per sample | - | - |
| 5.02 | Density | 70 | Per sample | - | - |
stage.html
html • 0.04 MB
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.75 MB
FinancialBidDocument.pdf
Tender Documents • 0.69 MB
BOQ_964811.xls
BOQ • 0.42 MB
Bidderdeclaration.pdf
Tender Documents • 0.40 MB
GCCSCC.pdf
Tender Documents • 1.20 MB
Biddocument7_AERBControlofWorks.pdf
Tender Documents • 0.27 MB
Biddocument5TECHFORMSATOH.xls
Tender Documents • 0.08 MB
Corrigendum_1.pdf
PDF • 0.79 MB
PreBidQueryReply.pdf
PDF • 0.38 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .