Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹28.0 LAdmitted-Finance HOUSE NO 142 GALI NO 07 PREM VIHAR NANGLI SAKRAWATI NAJAFGARH NEW DELHI 110043 | NEW DELHI | NAJAFGARH | DELHI | 110043 | ₹28.0 L | L1 | Admitted-Finance |
| 2 | L2₹29.9 L+₹1.9 L (6.95%)Admitted-Finance 1 225 5 6 SADAR BAZAR DELHI CANTT 110010 | NEW DELHI | DELHI | 110010 | ₹29.9 L+₹1.9 L (6.95%) | L2 | Admitted-Finance |
| 3 | L3₹31.0 L+₹3.0 L (10.6%)Admitted-Finance | ₹31.0 L+₹3.0 L (10.6%) | L3 | Admitted-Finance |
| 4 | L4₹31.6 L+₹3.7 L (13.0%)Admitted-Finance NO 9 BYRAVESHWARA INDUSTRIAL ESTATE ANDRAHALLI MAIN ROAD NEAR PEENYA 2ND STAGE BENGALURU 560 091 | BENGALURU URBAN | KARNATAKA | 560091 | ₹31.6 L+₹3.7 L (13.0%) | L4 | Admitted-Finance |
| 5 | L5₹33.8 L+₹5.8 L (20.7%)Admitted-Finance 10 WARD NO 18 PLOT NO 34 KAMDENU FURNTIURE SIKAR RAJASTHAN 332025 | SIKAR | RAJASTHAN | 332025 | ₹33.8 L+₹5.8 L (20.7%) | L5 | Admitted-Finance |
| Sl No | Description | Qty | Unit | DS CONSTRUCTION L9 | mayur enterprises L6 | Vijay Electricals L4 | M/s JAIMAA ASSOCIATES L3 | KISHORE ENTERPRISES L7 | M P TYAGI ENGINEERS AND CONTRACTORS L2 | Ruchi enterprises L5 | S K ENGINEERS AND CONTRACTOR L1 | SB ENTERPRISES L8 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1.00 | M&L for servicing /testing of breaker/control panel including CT/ PT and relays in control panel of VCB of capacity 630-800 Amps and rating 11 KV complete as details mentioned as under :- (a) Details of servicing of breaker :-
(i) Adjustment of mechanism if required.
(ii) Clean the circuit breaker to remove dust and dirt. The envelope of the vacuum interrupter and insulating materials shall be wiped with a clean cloth.
(iii) Apply a small amount of oil to rotary sections, sliding surfaces, pins, coupling section, etc.use grease for the operating shaft and bearings, and machine oil for other parts.
(iv) Check for rust and wear.
(v) Check Spring Tension and pitting of the Cluster Contacts.
(vi) Visual check for rust and deformation. (vii) Check for loosened bolts and nuts, broken spring washers and snap pins etc.
(viii) Check for loosened connections, rust, damaged lead wires.
(ix) Check whether the contacts are damaged by arcing.
(x) Checking of control circuit & tighten the connections if any.
(xi) Check close & trip coil.
(xii) Checking of Jaw Contacts Conditions and repair/adjust.
(xiii) Replace the jaw contacts,If required.
(xiv) Improvement of resistance of epoxy insulator and epoxy body by applying post heated varnish.
(xv) Replacement of Dashpot/shock absorbers .
(xvi) Replacement of carbon brush of spring charging motor
(xvii) Checking, cleaning, tightening , testing the busbars incl bus chambers,support insulator, Spouts, CT/PT etc.
(b) The following test shall be carried out:-
(i) Primary Injection Test of CT / PT
(ii) Closing & Opening Timing Test for all three poles.
(iii) IR Test with megger in open and closed condition. | 26 | Each Job | 3,000 ₹78,000 Lowest | 3,500 ₹91,000 | 3,500 ₹91,000 | 5,000 ₹1,30,000 | 5,000 ₹1,30,000 | 19,999 ₹5,19,974 | 3,999 ₹1,03,974 | 4,599 ₹1,19,574 | 3,999 ₹1,03,974 |
| 1.01(c) Testing of following relays of control panel with Secondary Injection Kit ,checking and programming of relay : -(i) Over current and earth fault relay (d) Testing of followig Aux relay (i) DC Supply supervision relay. (ii) Master trip relay | ||||||||||||
| 2.00 | Supplying, installation, commissioning and testing in replacement of 11 KV Current Transformer (CT`s), indoor type, resin cast epoxy type, of 13.1 KA/Sec having ratio 200/100/5-5 Amps having Core1: Class 5P10, 10VA for protection , Core2: Class 0.5, 10VA for metering including associated wiring complete all as specified and directed by Engr-In-Charge. | 1 | Set of 3 | 25,000 ₹25,000 | 11,000 ₹11,000 | 9,000 ₹9,000 | 9,000 ₹9,000 | 25,000 ₹25,000 | 4,999 ₹4,999 Lowest | 15,000 ₹15,000 | 5,000 ₹5,000 | 6,199 ₹6,199 |
| 3.00 | All as per item No 2 here-in-before but having ratio 150/75/5-5 Amp complete all as specified and directed by Engr-In-Charge. | 3 | Set of 3 | 25,000 ₹75,000 | 11,100 ₹33,300 | 9,000 ₹27,000 | 9,000 ₹27,000 | 24,000 ₹72,000 | 4,999 ₹14,997 Lowest | 9,000 ₹27,000 | 5,000 ₹15,000 | 6,099 ₹18,297 |
| 4.00 | All as per item No 2 here-in-before but having ratio 100/50/5-5 Amp complete all as specified and directed by Engr-In-Charge. | 3 | Set of 3 | 25,000 ₹75,000 | 11,000 ₹33,000 | 9,000 ₹27,000 | 9,000 ₹27,000 | 22,000 ₹66,000 | 4,999 ₹14,997 Lowest | 9,999 ₹29,997 | 5,000 ₹15,000 | 6,099 ₹18,297 |
| 5.00 | Supplying, installation, commissioning and testing in replacement of PT unit three phase, three limbs, upto 11 KV draw-out type, resin cast dry type, single ratio having primary voltage 11 KV & secondary voltage 110 volts, 50 VA class-1 including necessary bus bar connections & wiring for metering complete all as specified and directed by Engr In Charge. | 4 | Set of 03 | 65,000 ₹2,60,000 | 13,000 ₹52,000 | 12,000 ₹48,000 | 16,000 ₹64,000 | 22,000 ₹88,000 | 4,999 ₹19,996 Lowest | 50,000 ₹2,00,000 | 5,000 ₹20,000 | 9,999 ₹39,996 |
| 6.00 | S&F in replacement of LED indication lamp 24/110 Volts for breaker ON/OFF/TRIP/Breaker Spring Charged/R-Y-B etc for 11 KV control panel including associated wiring, if reqd, complete all as specified and directed by Engr In Charge. | 15 | Set of 03 | 150 ₹2,250 | 55 ₹825 | 50 ₹750 Lowest | 200 ₹3,000 | 200 ₹3,000 | 99 ₹1,485 | 200 ₹3,000 | 250 ₹3,750 | 199 ₹2,985 |
| 7.00 | Supply and installation in replacement Anti-condensation space-heater withThermostatic control in cable and circuit breaker compartments of HT switchgears complete all as specified and directed by Engr-In-Charge. | 10 | Each | 500 ₹5,000 | 1,000 ₹10,000 | 200 ₹2,000 Lowest | 600 ₹6,000 | 200 ₹2,000 Lowest | 499 ₹4,990 | 300 ₹3,000 | 500 ₹5,000 | 259 ₹2,590 |
| 8.00 | S&F in replacement of isolating contact assembly suitable for 630/800 amps, 11 KV HT VCB complete all as specified and directed by Engr-In-Charge. | 5 | Each | 500 ₹2,500 | 2,000 ₹10,000 | 200 ₹1,000 Lowest | 1,600 ₹8,000 | 1,200 ₹6,000 | 499 ₹2,495 | 990 ₹4,950 | 500 ₹2,500 | 229 ₹1,145 |
| 9.00 | S&F in replacement of fixed contact block complete suitable for 630/800 amps, 11 KV HT VCB complete all as specified and directed by Engr In Charge. | 5 | Each | 500 ₹2,500 | 2,000 ₹10,000 | 200 ₹1,000 Lowest | 1,600 ₹8,000 | 1,200 ₹6,000 | 499 ₹2,495 | 200 ₹1,000 Lowest | 500 ₹2,500 | 229 ₹1,145 |
Tender Value
₹49 L
EMD Value
₹98,000
Closing Date
19 Aug 2026, 6:00 pmClosed
GE Utility Electric Supply
GE Utility Electric Supply Delhi Cantt-10
REPAIR AND MAINTENANCE OF 11 KV SWITCHGEARS 11 KV CABLE DISTRIBUTION SYSTEM WITH PROTECTION SYSTEM WITH ALLIED WORKS AT KABUL LINE BAIRD PLACE KOTWALI LINE CEDZ OFFICE CDA ARMY AND ASSOCIATED AREA OF AGE
2026_MES_780183_1
GE ELECT/TOKEN-09/2026-2027
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
GE Utility Electric Supply
As Per Tender Documents
7 documents required · 7 mandatory
₹500
GE Utility Electric Supply
₹98,000
25 Aug 2026
22 Jul 2026
21 Aug 2026
22 Jul 2026
19 Aug 2026
5 Aug 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | M&L for servicing /testing of breaker/control panel including CT/ PT and relays in control panel of VCB of capacity 630-800 Amps and rating 11 KV complete as details mentioned as under :- (a) Details of servicing of breaker :-
(i) Adjustment of mechanism if required.
(ii) Clean the circuit breaker to remove dust and dirt. The envelope of the vacuum interrupter and insulating materials shall be wiped with a clean cloth.
(iii) Apply a small amount of oil to rotary sections, sliding surfaces, pins, coupling section, etc.use grease for the operating shaft and bearings, and machine oil for other parts.
(iv) Check for rust and wear.
(v) Check Spring Tension and pitting of the Cluster Contacts.
(vi) Visual check for rust and deformation. (vii) Check for loosened bolts and nuts, broken spring washers and snap pins etc.
(viii) Check for loosened connections, rust, damaged lead wires.
(ix) Check whether the contacts are damaged by arcing.
(x) Checking of control circuit & tighten the connections if any.
(xi) Check close & trip coil.
(xii) Checking of Jaw Contacts Conditions and repair/adjust.
(xiii) Replace the jaw contacts,If required.
(xiv) Improvement of resistance of epoxy insulator and epoxy body by applying post heated varnish.
(xv) Replacement of Dashpot/shock absorbers .
(xvi) Replacement of carbon brush of spring charging motor
(xvii) Checking, cleaning, tightening , testing the busbars incl bus chambers,support insulator, Spouts, CT/PT etc.
(b) The following test shall be carried out:-
(i) Primary Injection Test of CT / PT
(ii) Closing & Opening Timing Test for all three poles.
(iii) IR Test with megger in open and closed condition. | 26 | Each Job | - | - |
| 1.01 | (c) Testing of following relays of control panel with Secondary Injection Kit ,checking and programming of relay : -(i) Over current and earth fault relay
(d) Testing of followig Aux relay
(i) DC Supply supervision relay.
(ii) Master trip relay | - | - | - | - |
| 2 | Supplying, installation, commissioning and testing in replacement of 11 KV Current Transformer (CT`s), indoor type, resin cast epoxy type, of 13.1 KA/Sec having ratio 200/100/5-5 Amps having Core1: Class 5P10, 10VA for protection , Core2: Class 0.5, 10VA for metering including associated wiring complete all as specified and directed by Engr-In-Charge. | 1 | Set of 3 | - | - |
| - | All as per item No 2 here-in-before but having ratio 150/75/5-5 Amp complete all as specified and directed by Engr-In-Charge. | 3 | Set of 3 | - | - |
| - | All as per item No 2 here-in-before but having ratio 100/50/5-5 Amp complete all as specified and directed by Engr-In-Charge. | 3 | Set of 3 | - | - |
| - | Supplying, installation, commissioning and testing in replacement of PT unit three phase, three limbs, upto 11 KV draw-out type, resin cast dry type, single ratio having primary voltage 11 KV & secondary voltage 110 volts, 50 VA class-1 including necessary bus bar connections & wiring for metering complete all as specified and directed by Engr In Charge. | 4 | Set of 03 | - | - |
| - | S&F in replacement of LED indication lamp 24/110 Volts for breaker ON/OFF/TRIP/Breaker Spring Charged/R-Y-B etc for 11 KV control panel including associated wiring, if reqd, complete all as specified and directed by Engr In Charge. | 15 | Set of 03 | - | - |
| - | Supply and installation in replacement Anti-condensation space-heater withThermostatic control in cable and circuit breaker compartments of HT switchgears complete all as specified and directed by Engr-In-Charge. | 10 | Each | - | - |
| - | S&F in replacement of isolating contact assembly suitable for 630/800 amps, 11 KV HT VCB complete all as specified and directed by Engr-In-Charge. | 5 | Each | - | - |
| - | S&F in replacement of fixed contact block complete suitable for 630/800 amps, 11 KV HT VCB complete all as specified and directed by Engr In Charge. | 5 | Each | - | - |
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.42 MB
TD9.pdf
Tender Documents • 1.28 MB
BOQ_873908.xls
BOQ • 5.87 MB
AmendNO1.pdf
PDF • 0.85 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .