Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹39.0 LAccepted-AOC 8 51 PLOT NO 6 LIC COLONY SUJATA NAGAR PENDURTHY MANDAL VISAKHAPATNAM 530042 AP | 530042 | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹39.9 L+₹22,610 (0.57%)Rejected-AOC FLAT NO 101 2ND FLOOR RAGHAVENDRA RESIDENCY PLOT NO 1 2 3 SURVEY NO 27 PICKET SECUNDERABAD 500026 | HYDERABAD | TELANGANA | 500026 | L2 | Rejected-AOC Not being L1 | |
| 3 | L3₹40.5 L+₹83,620 (2.11%)Rejected-AOC | L3 | Rejected-AOC Not being L1 | |
| 4 | L4₹42.2 L+₹2.6 L (6.56%)Rejected-AOC | L4 | Rejected-AOC Not being L1 | |
| 5 | L5₹43.6 L+₹3.9 L (9.94%)Rejected-AOC 1 6 620 CHAITANYAPURI INDRA NAGAR DILSUKHNAGAR HYDERABAD TELANGANA 500060 UDYAM TS 09 0007870 37AAEPO0535A1Z8 B 36AAEPO0535A1ZA R MSME STATUS AS VERIFIED | RANGA REDDY | TELANGANA | 500060 | L5 | Rejected-AOC Not being L1 |
Tender Value
₹45 L
EMD Value
₹90,000
Closing Date
24 Mar 2022, 6:00 pmClosed
GARRISON ENGINEER UTILITY SECUNDERABAD
GE UTILITY SECUNDERABAD MUDFORT SECUNDERABAD-500003
REPAIR/RENEWAL OF LT PANEL BOARD, SEGREGATION OF LOAD AND CONNECTED CABLING WORK AT MCEME, LALBAZAR JCOS ACCN, ROBERT EAST AND WEST AND ADJOINING AREA UNDER GE (U) SECUNDERABAD
2022_MES_511472_1
GE(U)/SEC/TOKEN/73 OF 2021-2022
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
SECUNDERABAD
AS PER NIT
8 documents required · 8 mandatory
₹500
GARRISON ENGINEER UTILITY SECUNDERABAD
₹90,000
Yes
30 Aug 2022
2 Mar 2022
31 Mar 2022
2 Mar 2022
24 Mar 2022
12 Mar 2022
Amount
Taking down/out unserviceable UG Cables of any Cross Sectional Area and Connections including Pipes, Bricks, etc. of any descriptions, laying in Trenches and/or fixing with Walls/Poles including Segregating of Serviceable Materials viz Bricks, Pipes, etc. and keep in Safe custody for re-use, complete all as specified and as directed.
Supply, laying , testing and commissioning of XLPE insulated, armoured heavy duty UG electric cable with aluminium conductor, 1100 volts grade, cross-sectional area laid in trenches / duct or fixed to wall / passing through pipe on pole with suitable size cable glands, crimping type cable lugs for stranded aluminum conductor of following sizes complete all as specified and directed :-
4 core X 10 Sqmm
4 Core X 16 Sqmm
4 Core X 25 Sqmm
3.5 Core X 35 Sqmm
3.5 Core X 50 Sqmm
3.5 Core X 70 Sqmm
3.5 Core X 95 Sqmm
3.5 Core X 120 Sqmm
3.5 Core 150 Sqmm
3.5 Core 185 Sqmm
3.5 Core 240 Sqmm
Note for item Nos 2.01 to 2.11 : Excavation, earth work, sand cushioning and cable protection items etc shall be measured and paid under respective items of BOQ. Make : Universal/Havells/kei/gloster/POLYCAB
Taking down and Relaying of LT cable of size 10 sqmm to 120 Sqmm 2/3.5 core after carrying out necessary Repair such as joining with Epoxy joint and laid with sand Cushioning and brick protection and making connection By using Lugs all as specified and directed by ingr in charge. Note: (a) Earth work , sand Cushioning, brick protection, Lt Joints shall be measured and paid separately under Relevent Item. (b) Retrived serviceable bricks/ PCC cover shall be reused under relevent item) (c) Excavation, Retuning, Sand and extra brick shall be measured and paid separately.
Excavation in trenches, n exc 1.5 m wide and n exc 1.5 m in depth, for foundation of PCC/Steel pole, laying of cable in trenches etc and getting out in hard / dense/soft/loose soil complete all as specified and directed.
All as per item No 4 here in before but depth above 1.5 m & below 3 m
Returning, filling in, including spreading, leveling, watering and well ramming in layers not exc 25 cm in soils complete all as specified and directed.
Removing excavated material (soils) n exc. 50m and depositing where directed at a level n exc. 1.5 m above the starting point complete all as specified and directed.
Spreading riddled earth (after preparation of excavated earth) in Cable duct for cushioning of cable laid in trenches complete all as directed by Engineer-in-Charge Note:- (a) Punned thickness 18 CM (6.25 Cm below cale and 11.75 cm above cale) will be measured for payment purpose. The earth removed during excavation to be used as rddled earth after crushing and sieving. (b) Quoted rate deemed to be inclusive of all arrangement as mentioned.
Supply and Lay reinforced precast concrete cable cover LV, Type I,flat, size 250x150x40 mm complete all as specified and directed.
M&L for PCC 1:3:6 type C1 using 20mm graded aggregate set in cement mortar 1:4 as in coping/pedestals of poles including necessary form work complete and applying two coats of white wash to exposed surface of coping/platform complete all as specified and directed.
M&L for PCC 1:3:6 type C2 using 40mm graded aggregate as in foundation, filling and mass concrete for pole / stay / post etc complete all as specified and directed.
M&L brick protection with common burnt brick sub class ‘B’ of size 230x115x75mm for cable protection complete all as directed by Engr-in-charge.
M&L for stay assembly with all accessories as shown in Electrical Plate No 1 of SSR Part I (2009) with 16 mm dia stay rod and including 7/2.24 mm size stay strand and stay clamps including dismantling old unserviceable stay assembly complete all as specified and directed. Note : Loop type insulator, excavation, earth work and concrete shall be measured and paid separately under relevant items of this schedule.
Supplying, errecting and fixing steel tubular swaged poles with cast iron base plate of size 300mm x 300mm x 6mm, finial taper plug, bolts, nuts & screws for type 410 SP-31 (9.0 metres long) including painting with two coats of aluminum paint over one coat of redoxide primer on all exposed surfaces and tarring with black bituminous paints to embedded portion in PCC and providing 3 Nos of 30cm wide circular bands with black & yellow paint starting from plinth level at a gap of 30 cm in between 2 bands and numbering of poles, in yellow paint over black painted back ground at a height of 2m from bottom of pole with 5 cm large bold letters 2" (inch) wide complete all as specified and directed. Note: Excavation, earth work, PCC in foundation and coping shall be measured and paid separately under relevant item of this schedule. Make :- Bansal/National tubing company/Bombay steels/jindal steel product
M&L Pipe bracket for street light fitting made out of 40mm dia GI pipe, medium grade, tubing bend to shape, 1.5m long fixed to pole wall including provn of two sets of clamps made out of flat iron of size 40x6 mm including of provn of bolts, nuts and washers complete all as specified and directed.
Supply & lay heavy duty PVC insulated multi stranded Aluminum conductor 3 core of size 2.5 Sqmm, 230 volts, 50 HZ complete all as specified and directed.
Supply & lay Galvanised Iron tubing 50mm bore, light grade in protection of cable at road crossing/hard standing/pole protection fixed with MS clamps of size 40 X 4 mm, nut bolts and washer as per site requirement including taking down old unserviceable pipes complete all as specified and directed.
All as per item No 17 above but GI tubing 80 mm bore.
M&L cutting of road/hard standing upto a size not exceeding 20 cm in width and not exceeding 60 cm in depth for laying of LT UG cable/protection pipe line making good the disturbed portion so as to match existing finishing with PCC 1:2:4 type B1/cement mortar in CM (1:2) complete all as specified and directed
Supply, fixing, connecting and testing energy saving, environmental friendly long life Varsatile pressure die cast aluminium alloy for housing (heat sink) with IP66 protection road way light fitting with high power LED as light source of capacity 90 watts with warranty option of 2 years with suitable driver and cable gland for maintaining ingress protection with Epoxy powder coated siemens grey finish after phosphochromate treatment, Tempered protective toughened glass,thermal shock and impact resistant fixed to the housing with SS screws , High efficiency long life LED chip in modules with lumen efficacy of >140 lm/W with PC lens and system lumen 6000. Powered by Built-in electronic LED driver with APFC (SMPS based constant current supply), lower THD, Open Circuit protection, Phase to Phase protection, Over Voltage protection, Surge Voltage protection. CCT 5700, CRI>70, THD<10%, PF>.95, IP66, IK07.Life class of 50,000 hrs @ L70, Operating Temperature:-10 TO +50 DEG.C; Input Supply Voltage Range:140-270 V, Frequency : 50-60 HZ, Driver safety requirement standards :IS 15885-2-13,
Test report to be submitted for Driver performance requirements as per IS 16104, for Photo bilogical safety norms as per : IS 16108, Certification as per LM 79 for Luminaire, LM 80 for LED Source, with all standard accessories etc, including connection by using 3 core 1.5 sqmm HV Round Cable complete all as specified and as directed. Make Philips Model number BRP409 LED 115 CW SLC FG PSU GR V2 or Havells Cat No. ENDURAPEARLPLUSSL90WLED757PASYTOPCASTHO, SURYA CAT NO: SLEUL90W IP66 PLX XL or Wipro cat No. LR02-102-XXX-57-G2 as approved by GE.
All as per item No. 20 here-in-before but Flood light of high power LED as light source of capacity 120 watts. Make: Havells Model Number JETAIRISFLS 120WLED757APWBLT G, SURYA CAT NO SLEFL120 W IP66 LUMOS MAX or Wipro cat No. LF20-132-060-57-G2 OR CG MODEL NO LFLN-120-CDL/60-M as approved by GE.
All as per item No. 20 here-in-before but Flood light of high power LED as light source of capacity 150 watts. Make: Bajaj Cat No.BARFEG 150W LED or Havells Cat No. JETAIRISFLS150WLED757PSYMLTG, SURYA CAT NO SLEFL150 W IP66 LUMOS MAX or Wipro cat No. LF20-192-060-57-G2 OR CG MODEL NO LFLN-150-CDL/60-M as approved by GE.
Supply, fixing, connecting and testing post top light fitting in spherical shape polycarbonate PMMA clear diffuser and IP65 protection, new generation energy saving and environmental friendly long life aesthetically desinged aluminium decorative luminaires with high power LED as light source of capacity 1X35/36/ 40 watts, fixed on the top of gate piller complete all as specified and directed. Make:- PHILIPS Cat Part No BGP300 LED28 757PSU PC IN S1 or CG MODEL NO LPTO 40 CDL/ Surya Model NO : SLEPT 36 W - ETPP / Havells Cat No. RUBYPT35WLED757PSYMTOPC or Wipro cat No.LP07-431-XXX-57-CL as approved by GE.
Supply and fix cable junction box thermoplastic body IP 66 , size 225mmx295mmx122mm suitable for helogen free and weather proof for out door installation with metric knockout for cable entry suitable for cable size 16-35 sqmm including clamp, lugs,cable terminal & 6-10 amps MCB complete all as specified and directed. Make:- HENSEL/ Neptune or equivalent make as approved by GE.
Supply, Installation, test and Commissioning CPRI APPROVED factory fabricated, out door type, LT FEEDER PILLAR BOX made out of 3.00 mm thick CRCA Sheet of size 0.75 MX.70mX.35 M with projected Globe roof for rain water protection Dust and Vermin Proof, Double door with both side opening including Neoprene Rubber Gasket,, suitable for 440 Volt 3 Phase 4 Wire System ,including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate comp-lete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers, etc. and embeded with 50X50X6mm Mild Steel Angle Iron Frame and 600 mm above the Normal Ground Level comp -lete with internal connection with suitable size of cable ,cable lugs,and cable glands PCC Foundation in Cement Concrete 1:3:6 (20mm Graded Stone Aggregate) and Test-ing after Installation complete all as specified and comprising of the following :– (a) Aluminium bus bar 200amps - 04 Nos, supported with suitable size of heavy duty porcelin stand lock with suitable size of brass nut, bolts and washer with heat shrinkable PVC sleeving. The bar shall be colour coded (red, yellow and blue) for three phases and black for neutral. (b) MCCB 100 amps ,415 volt ,16 KA Breaking capacity 4 pole Electromagnetic release duly connected to Bus Bar As IN COMING - 01 Nos. Make Legrand model no: 420015 or equivalent from Schinder/L&T/Hagar/C&S as approved by GE
Supply, Installation, test and Commissioning CPRI APPROVED factory fabricated, out door type, LT FEEDER PILLAR BOX made out of 3.00 mm thick CRCA Sheet of size 0.75 MX.70mX.35 M with projected Globe roof for rain water protection Dust and Vermin Proof, Double door with both side opening including Neoprene Rubber Gasket,, suitable for 440 Volt 3 Phase 4 Wire System ,including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate comp-lete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers, etc. and embeded with 50X50X6mm Mild Steel Angle Iron Frame and 600 mm above the Normal Ground Level comp -lete with internal connection with suitable size of cable ,cable lugs,and cable glands PCC Foundation in Cement Concrete 1:3:6 (20mm Graded Stone Aggregate) and Test-ing after Installation complete all as specified and comprising of the following :– (a) Aluminium bus bar 200amps - 04 Nos, supported with suitable size of heavy duty porcelin stand lock with suitable size of brass nut, bolts and washer with heat shrinkable PVC sleeving. The bar shall be colour coded (red, yellow and blue) for three phases and black for neutral. (b) MCCB 160 amps ,415 volt ,16 KA Breaking capacity 4 pole Electromagnetic release duly connected to Bus Bar As IN COMING - 01 Nos. Make Legrand model no: 420015 or equivalent from Schinder/L&T/Hagar/C&S as approved by GE
Supply, installing, testing and commissioning, factory made and tested, CPRI approved LT panel board indoor type, weather, vermin proof, cubical type, platform mounted, suitable for 415 volts, 3 phase 4 wire 50 Hz AC supply system all as specified and directed, with necessary bus bar arrangement with insulated bus bar 400 Amps rating , 4 strips, the panel should be dust proof, IP 54 class protection and made out of 3.15mm thick CRCA mild steel sheet with 50x50x6mm angle iron frame with necessary earth work excavation, hinged doors, front and rear opening and locking arrangement and duly powder coated on the out side and inside, cable glands and lugs for incomming and out going cable etc, independent chamber to accommodate complete all as specified and directed including following accessories :-
Supply, installing, testing and commissioning, factory made and tested, CPRI approved LT panel board outdoor type, weather, vermin proof, cubical type, platform mounted, suitable for 415 volts, 3 phase 4 wire 50 Hz AC supply system all as specified and directed, with necessary bus bar arrangement with insulated bus bar 400 Amps rating , 4 strips, the panel should be dust proof, IP 54 class protection and made out of 3.15mm thick CRCA mild steel sheet with 50x50x6mm angle iron frame with necessary earth work excavation, hinged doors, front and rear opening and locking arrangement and duly powder coated on the out side and inside, cable glands and lugs for incomming and out going cable etc, independent chamber to accommodate complete all as specified and directed including following accessories :-
Supply, installing, testing and commissioning, factory made and tested, CPRI approved LT changeover panel board outdoor type, weather, vermin proof, cubical type, platform mounted, suitable for 415 volts, 3 phase 4 wire 50 Hz AC supply system all as specified and directed, with necessary bus bar arrangement with insulated bus bar 500 Amps rating, 4 strips, the panel should be dust proof, IP 54 class protection and made out of 3.15mm thick CRCA mild steel sheet with 50x50x6mm angle iron frame with necessary earth work excavation, hinged doors, front and rear opening and locking arrangement and duly powder coated on the out side and inside, cable glands and lugs for incomming and out going cable etc, independent chamber to accommodate complete all as specified and directed including following accessories :-
Notes for LT panel board / FP BOX : (a) All incoming and out going cables are to be connected to the above panels with proper lugs, double compression copper stain less steel armoured cable gland, nuts, bolts etc the cost of the items deemed to be included in the quoted rates. (b) Make of MCCB's and MCB's to be used in the panels are : L&T/LEGRAND /Siemens/C&S. (c) The panel shall be Fabricated from a reputed firm(CPRI Approved) . (d) All Internal connection between ACB, MCCB ( ABOVE 63 AMPS ) and Changeover and Bus bar shall be done by aluminium strip of suitable size and capacity. (e) All MCCB to be connected with both side Spreader Link and all Incomer and outgoing MCCB of Panels should be thermal magnetic release with adjustable settings ( Min 70 % to 100 %) and Ics = 100% Icu
(f) Sufficient space to be provided for cable connection between MCCB and Bottom of the panel board.( Minimum space for MCCB up to 200 amps = 35 CM , Minimum space for MCCB 250 to 400 amps = 45 CM , Minimum space for MCCB above 400 amps = 55 CM ) (g) Base of the panel should not be less than 500 mm above the ground level. Necessar PCC for base /foundation required deemed to be included in the quoted rate. (h) Cable alley / chamber to along with connector of suitable size to be provided for connection of Out going cable. (j) Necessary approval of drawing to be taken from GE before placing order to the manufacturer. (k) All existing incoming and out going cables also to be connected to the above panel as per site requirement with proper lugs, glands nuts, bolts etc. (l) Door hinge of industrial type heavy duty to be provoded minimum 3 nos for each door. (m) The rate shall deemed to be include in the item rate for al the points mentioned above.
Supply, Install, testing and commissioning of APFC Power Panel of 70 KVAR 6 stage, outdoor type, factory made, CPRI approved, cubical feeder pillar box panel board IP 54 free standing suitable for working on 440 volts, 3 phase 50 Hz A C supply, floor mounted made out of 3.15mm thick CRCA sheet, duly powder coated, compartmental design with locking arrangements, weather and vermin proof with proper ventilation slots incl taking down old unsv one complete of suitable size comprising of following items:-
(f) MCCB 3 pole rupturing capacity 10 KA of appropriate rating for protection of individual capacitor bank confirming to IS 8828, IEC 898. Make: L&T/Legrand/ABB/Havells/C&S. (g) Venttilation fans of required size to dissipiate the heat liberated by capacitor units complete with automatic switching ON and OFF of fans depending upon the temperature of the panel. (h) Bus bar of appropiate rating for incoming and out going connection suitable to withstand short circuit current of 50 KA and current rating not less than 1.5 time of load current made of copper mounted on SMC silicon free, Chlorine freepost insulators and arranged in such a way that the joints are minimum. (j) Emergency stop push button to disconnect the unit in case of emergency. (k) Indicator LED type for phase indication and capacitor banks ON and OFF Indication. Make:- L&T/ Legrand/C&S (k) Auto / Manual Control for each capacitor bank (l) Current transformer 01 No of appropriate rating, to be fixed in incoming existing LT panel for operation of APFC relay complete with control wiring. Make: L&T/C&S or equivalent as approved by GE. (m) Internal wiriing with suitable size of PVC insulated stranded copper conductor cable duly crimped with copper lugs & ferruled. Note: All accessories prewired with suitable size copper conductor cable insulated with fibre glass insulation to with stand high temperature placed in cubical panel box.
Supply, Install, Testing and Commissioning of Advance Maintenance Free G.I. SAFE EARTHING Electrode with PIPE of not less than 50 mm outer dia) and two meter length, The electrode should be of galvinised (80 -100 micron) along with earth lead as Galvanised steel strip of size 32 X6 mm 7.5 m. The GI Electrode shall be pre-filled with Cristaline Conductive Material (CCM). The GI electrode shall be surrounded with 25 kg BackFill compound to provide maximum contact between the electrode and Back Fill Compound. The earting pit cover should be factorty built (size TOP- 10 Inch, Bottom -13 Inch, Height 10.25 Inch ) made of heavy duty Polypropylene complete all as specified and directed. Make: ASHLOK/INDELEC/JMV/TERCEL/TRUE POWER
S& F in replacement of old unserviceable lugs after cutting the worn out /faulty cable end from LT pillar/panel box including necessary earth work for taking out the cable from loop line, returning, filling in and making cable lead by providing aluminum lugs including crimping with crimping tools in the existing LT cable 3.5 core upto 25 Sqmm including necessary connection complete all as specified and directed.
All as per item No 34 here in before but aluminium lugs of size 35 Sq mm.
All as per item No 34 here in before but aluminium lugs of size 50 Sq mm.
All as per item No 34 here-in-before but aluminium lugs of size 70 Sq mm.
All as per item No 34 here-in-before but aluminium lugs of size 95 Sq mm.
All as per item No 34 here-in-before but aluminium lugs of size 120 Sq mm.
M & L for digital ammeter of range 0 to 500 volts and size 96 mm square dial including taking down old defective ammeter complete all as specified and directed.
S&F cable route indicator for LT UG cable of 1100 volts bolted with 25x5 mm flate iron member of height 0.80 mtrs and 80 mm CI plate embeded in PCC 1:3:6 type C2 of size 15x15x20 cm block complete all as specified
M&L for road crossing/drain crossing by adopting trench less tunneling work through specified pipe jacking method by erecting the equipment to true to the allignment and gradient by haidrolic pipe jacking technique complete including tunneling, excavation in any type of soils including hard rock, HDPE pipe medium duty duty of size 100 mm dia in any length including jointing materials to carry LT UG cables of size upto 240 Sqmm and necessary conveyance charges of machinery and other required materials in co-ordination with the concerned authorites complete all as specified and as directed.
M&L for replacement of broken earth pit made out of PCC 1:2:4 type B1 using 20 mm graded crushed stone aggregate, 20 mm thick and earth pit cover made out of RCC 1:2:4 type B1, cover reinforced with 8 mm dia MS deformed bars @ 100 mm centre to centre both ways with hook made out of 8 mm dia bar, watering arrangement with funnel and wire mesh and including reconnecting of earth lead of any type with new nuts, bolts and washers etc as required at site complete all as specified and directed.
S&F On-Load changeover switch (In sheet steel enclosure), AC 21 (Side Handle), 4 pole of capacity 400 Amps, 415 Volts, 50 Hz, Conforms to HSN Code : 8536 complete all as specified and directed. Make : Standard or techno commercial equivalent mdolel in Havells/Benlo/L&T as approved by GE.
S&F On-Load changeover switch (In sheet steel enclosure), AC 21 (Side Handle), 4 pole of capacity 200 Amps, 415 Volts, 50 Hz, Conforms to HSN Code : 8536 complete all as specified and directed. Make : Standard or techno commercial equivalent Mdolel in Havells/Benlo/L&T as approved by GE.
S&F MCCB box made of sheet of suitable size Powder coated Suitable for fixing at Pole / wall including two set of clamps comprisinf with the following (i) MCCB 63 Amps 16 KA TP WITH BOTH SIDE SPREADER LINK.
Dismantling of damage/broken coping of PCC/steel pole of any size and and removing the debries from site and M&L for coping by using PCC(1:3:6 type B2 ) of size 50 Cm x50 CMx30 cm complete all as specified and directed
Supply and fixing lantren of dia 60 CM for fixing of flood light, cap type to be fixed on the top of 9 m SP-31 Steel pole , made of MS pip medium grade dia greater than the top dia of the pole of length 0.35 M supported by MS flat iron of size 50X6 mm 8 nos including two coat of aliminium painting over a coat of redoxide primer complete all as directed
Dismantling LT steel tubuler pole of any height by taking out from PCC foundation complete and shifting to other location as directed including fixing the pole in true vertical position including excavation and earth work, PCC 1:4:8 type D2 (using 40mm graded stone aggregate) as base concrete and PCC 1:3:6 type C2 (using 20mm graded stone aggregate) in both foundation and coping of poles all as specified in SSR Part I-2009 and applying two coats of aluminium paint to pole surface complete all as directed by Engineer-in-Charge.
Supply, lay, commissioning and testing of cable jointing Kit Heat shrinkable type for 1100 V grade cable for straight through joint with jointing material and accessories suitable for LT UG cable of size 16 to 50 Sqmm, 3.5 Core complete all as specified and directed.
All as per item No 50 here in before but suitable for aluminium conductor cable of size from 70 sqmm, 3.5 Core to 95 Sqmm, 3.5 Core
All as per item No 50 here in before but suitable for aluminium conductor cable of size from 120 sqmm, 3.5 Core to 185 Sqmm, 3.5 Core
All as per item No 50 here in before but suitable for aluminium conductor cable of size from 240 sqmm, 3.5 Core to 240 Sqmm, 3.5 Core
Supply, lay, commissioning and testing of cable jointing Kit for 1100 V grade cable for outdoor End termination heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 16 to 50 Sqmm, complete all as specified and directed.
All as per item No 54 here in before but suitable for aluminium conductor cable of size from 70 sqmm, 3.5 Core to 95 Sqmm, 3.5 Core
All as per item No 54 here in before but suitable for aluminium conductor cable of size from 120 sqmm, 3.5 Core to 150 Sqmm, 3.5 Core
All as per item No 54 here in before but suitable for aluminium conductor cable of size from 185 sqmm, 3.5 Core to 240 Sqmm, 3.5 Core
M/L for cross arms, bracing, supports clamps and back plates fabricated from structural steel section incl nuts, bolts washers, welding, bending cold or hot drilling holes for bolts in any shapes or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint including disconnecting/taking out old existing unsv cross arms complete all as specified and directed.
M&L preparing Steel and Iron Surfaces of any description, over 100mm width or girth and applying One Coats of Synthetic Enamel Paint (First quality) over a Coat of Red Oxide Zinc Chrome Primer, complete all as specified and as directed.
M&L for twin core 1100 volt grade aluminium service wire cross sectional area 4.0 Sqmm for connection of light complete all as specified and directed
M&L for twin core 1100 volt grade aluminium service wire cross sectional area 6.0 Sqmm for connection of light complete all as specified and directed
S&F MCCB box made of sheet of 2mm thick size 40X30X20 CM Powder coated Suitable for fixing at Pole including two set of clamps/wall byusing anchor bolt comprising MCCB 125 Amps 16 KA FP WITH BOTH SIDE SPREADER LINK complete all as specified and directed.
S&F on wall with necessary arrangements busbar chamber 100 amps 4 way 4 pole wall mounted IP-31 , made out of 1.6 mm thick CRCA sheet epoxy powdwer coated single layer operational voltage 440 Volt, Short circuit current capacity 25 KA for 1 Second including necessary cable connections complete all as specified and directed. Note: Quoted rates inclusive of necessary fixing arrangement and cable connections , cable glands as required for proper fixing / functioning of Bus Bar Chamber. Make : Havells/ HPL/Standerd.
S&F on wall with necessary arrangements busbar chamber 200 amps 4 way 4 pole wall mounted IP -31 , made out of 1.6 mm thick CRCA sheet epoxy powdwer coated single layer operational voltage 440 Volt , Short circuit current capacity 25 KA for 1 Second including necessary cable connections complete all as specified and directed. Note: Quoted rates inclusive of necessary fixing arrangement and cable connections , cable glands as required for proper fixing / functioning of Bus Bar Chamber. Make : Havells/ HPL/Standerd,
Supply and lay PVC Insulated, PVC sheathed industrial HV round multicore flexible cable with copper conductor three core 2.5 sqmm including PVC conduit 20 mm dia medium grade and necessary bends, fittings and fixtures as required for connection of light fittings. (Used for garden light connection, excavation, returning filling etc will be measured and paid separately).
Material and Labour for drawing two runs of PVC insulated unsheathed single core multi stranded copper conductor FRLS cable of size 2.50 sq mm with one run of PVC insulated unsheathed single core multi stranded copper conductor FRLS cable of size 2.50 sq mm including 20mm dia PVC conduit of dia 20 mm medium gradeexclusive of boxes but inclusive of all tees, bends, elbow, reducers etc and fixing accessories such as couples, lock nuts, saddles, pipe hooks, clamps etc complete all as specified
Supply, lay, test and commissioning of galvanized iron tubing 50 mm bore light grade with all fitting for fixing of garden light incl necessary clamp, bolt/nut if any and making hole on wall complete all as specified and as directed.
Supply, installation, testing and commissioning of Surge protection device (Type 1+2, Metal oxide varistor) suitable for installation at main incoming panel board of any Building/installation and capability to discharge high current surge without any destruction of the installation with the following specifications :- (i) Maximum continuous operating voltage 440 Volt (ii) I imp in kA ( 10/350us wave) 12.5 (iii) I max in kA ( 8/20us wave) 80 (iv) Three phase / 4 pole Note : Quoted rates deemed to be inclusive of enclosure as required for proper installation and connection by using copper wire of suitable size of appx length 3 mtr, copper lugs etc.
M&L for repairing of automatic operation of highmast lantren including all arrangements required including crane and replacement of all unserviceable spares of highmast lighting system of height 12 m to 16 meter . Quoted rates deemed to be inclusive of the following:- (i) crane as required for taking down of high mast pole including light without any damage to the mast, lantern and lights etc and refixing the same after repairing of the all problem on the same position (ii) Necessary disconnection and reconnection of electrical connection. (iii) Replacement of all unserviceable spare like High mast head, high mast ring , stainless steel wire, clamp, winch, transition plate, service door , Hook ring, nose plate, cabinet, gear, reel, transmission belt etc including servicing of gear box , filling of gear oil, greasing etc complete (quoted rates deemed to be inclusive of all spares required for proper functioning of lantern system except stainless steel wire, High mast head, high mast ring etc.
All as per item No 69 here in before but for highmast system above 16.5 meter and upto 25 meter
Supply only steel wire rope 6mm dia (7/19 construction) suitable for highmast system including u bolt complete all as directed
Taking down, transport to workshop , Re-winding of electric motor 3 phase installed at highmast pole of capacity 2.2/3 HP and refixing of the same including necessary arrangement complete all as directed
S&F MCB DB SPN 4 way double door including MCB TPN 6 to 32 Amps 10 KA C Curve complete all as specified and directed
S&F 5 core 2.5 sqmm 1100 volt grade copper flexible cable suitable for connection of highmast light complete all as specified and directed
Supply and drawn sub main wiring with two runs of 6 Sq mm single core PVC insulated unsheathed cable upto and including 1100 volts grade with multistranded copper conductor drawn through and including non metalic PVC rigid conduit accessories surface type on walls, floors etc including one run of 6.0 Sqmm PVC insulated copper conductor for earth continuity wire all as specified (Note : Two runs of copper conductor and one run of copper earth wire including PVC conductor will be measured and paid as one unit only)
Supply and drawn sub main wiring with four runs of 10 Sq mm single core PVC insulated unsheathed cable upto and including 1100 volts grade with multistranded copper conductor drawn through and including non metalic PVC rigid conduit accessories surface type on walls, floors etc including two runs of 10.0 Sqmm PVC insulated copper conductor for earth continuity wire all as specified (Note : Four runs of copper conductor and one run of copper earth wire including PVC conductor will be measured and paid as one unit only)
M&L for Making hole 2 nos ( one hole near JB another hole near bottom portion of bracket) on existing steel tubuler pole ( SP -31 ) of suitable size for passing of Street light connection HV Round cable 3 core 1.5 / 2.5 Sqmm from Junction Box to street light complete all as directed
Pertially Demolition of coping of pole as required for placing of cable protection pipe and making good the same by using PCC and rendering complete al as speccified and directed. Note: Quoted rates deemed to be inclusive of PCC and rendering.
Disconnection existing LT UG cable of any size from pole/OH line and connect the same to federpiller box by using cable lugs etc as required complete all as directed
L and S ENTERPRISES
Srinivash Engineers
SUN LIGHT HOUSE
DPS sales and services india
sree venkateswara enterprises
SANJEEV CONSTRUCTIONS
Srinivasa Consructions
STANDARD AGENCIES
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .