Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.1 CrAdmitted-Finance | ₹1.1 Cr | L1 | Admitted-Finance |
| 2 | L2₹1.3 Cr+₹12.9 L (11.3%)Admitted-Finance 10TH FLOOR UNIT 2 TECHNIPLEX 2 VEER SAVARKAR FLYOVER S V ROAD GOREGOAN WEST MUMBAI 400 062 | MUMBAI | MUMBAI SUBURBAN | MAHARASHTRA | 400062 | ₹1.3 Cr+₹12.9 L (11.3%) | L2 | Admitted-Finance |
| 3 | L3₹1.3 Cr+₹13.0 L (11.4%)Admitted-Finance | ₹1.3 Cr+₹13.0 L (11.4%) | L3 | Admitted-Finance |
| 4 | L4₹1.3 Cr+₹14.5 L (12.8%)Admitted-Finance | ₹1.3 Cr+₹14.5 L (12.8%) | L4 | Admitted-Finance |
| 5 | L5₹1.4 Cr+₹22.3 L (19.7%)Admitted-Finance | ₹1.4 Cr+₹22.3 L (19.7%) | L5 | Admitted-Finance |
| Sl No | Description | Qty | Unit | Maxcool Solutions Pvt.Ltd L1 | VAV Airconditioning L2 | Neptune Engineering L3 | Divine Air L4 | GEMINI COOLING SYSTEMS PROJECTS PRIVATE LIMITED L5 | Blue Star Limited L6 | Superior Aircon Pvt. Ltd. L7 |
|---|---|---|---|---|---|---|---|---|---|---|
| 1.00 | VRV OUTDOOR UNIT
Supply, Installation, Testing and Commissioning of Air-cooled Variable Refrigerant Volume(VRV) Outdoor Unit having top discharge comprising of multiple Scroll Compressor all inverter driven, full charge of refrigerant gas (R-410A), lubricating oil and all accessories as per specifications. The condensing unit shall be suitable for Cooling with multi-row condenser coil made of aluminium fins and copper tubes.Multi-kit for multiple outdoor unit connection should be included in price. It also includes lifting and shifting of the outdoor units upto the desired location. The condensing unit shall be suitable for operation on 415 ± 10% volts, 50Hz, 3Phase AC power supply and condensing unit shall be of following capacities:-
(a) 40 HP Nominal Higher Capacity | 6 | Each | - | - | - | - | - | - | - |
| 2.00VERTICAL FLOOR MOUNTED AHU Supply, Installation, Testing and Commissioning of AHU with 6RD DX Cooling coil Floor Mounted , double skin having panel thickness 43mm thick polyurethene foam (thermal break profile) 38 kg/m3 Puf having backward curved centrifugal flow fan with motor type TEFC Sq. Cage Induction Motor DoP-IP55 and Motor Efficiency rating IE2. Prefilter type Pre-filter 500FPM EU4/ 10micron. Coil made with copper tubing and fins with aluminium. Unit should be equiped with vibration isolators between fan and coil section and also vibration isolators should be provided between floor and base. Total static pressure of 40mmwg. It also includes lifting and shifting of the outdoor units upto the desired location. Fan outlet velocity of 1500 FPM. The AHU unit shall be as per following:- | ||||||||||
| 2.01 | Supply, Installation, Testing and Commissioning of 13000± 2% CFM AHU | 6 | Each | - | - | - | - | - | - | - |
| 2.02 | Supply , Installation, Testing and Commissioningof AHU Expansion Valve and Control Box(To connect ODU to AHU) | 12 | Each | - | - | - | - | - | - | - |
| 3.00 | Supply , Installation, Testing and Commissioningof Centralised Remote Controller ( CRC) with individual as well as zonal control of minimum 64 indoor units. The wiring length of CRC should be a minimum of 1000 metre. It should be connectable with unified ON/Off controller, schedule timer and BMS system.Airflow volume and direction should be controllable in stepped manner for individual units/groups. (Make Daikin DCS302CA61 or Equivalent) | 1 | Each | - | - | - | - | - | - | - |
| 4.00Supply, Installation, Testing & Commissioning of high pressure copper refrigerant piping suitable for R 410a refrigerant of suitable size as required and duly insulated with 19mm/13mmthick closed cell elastomeric insulation in tubing form inclusive of nitrile rubber and UV treatment. External Refrigerant piping shall be laid on GI covered cable trays. Piping inside occupied spaces shall be supported by ladder type GI Slot channel. Entire refrigerant piping work be carried out in accordance with the specifications. Piping shall be of following sizes: | ||||||||||
| 4.01 | 36 to 45 mm Dia Copper pipe with 19mm thick insulation | 600 | Mtr. | - | - | - | - | - | - | - |
| 4.02 | 21 to 35 mm Dia Copper pipe with 19mm thick insulation | 120 | Mtr. | - | - | - | - | - | - | - |
| 4.03 | 11 to 20 mm Dia Copper pipe with 19mm thick insulation | 720 | Mtr. | - | - | - | - | - | - | - |
| 5.00 | Supply, Installation, Testing and Commisioning of all communication/control cables between indoor and outdoor unit and also between Outdoor unit and central remote controller as per OEM specifications as required. | 1,250 | Mtr. | - | - | - | - | - | - | - |
Tender Value
₹1.4 Cr
EMD Value
₹2.8 L
Closing Date
9 Mar 2020, 6:00 pmClosed
Jt. Gen. Manager (Engg-E)
Jt. Gen. Manager (Engg-E), AAI, Goa Airport, Goa
Improvement of Air conditioning system at Domestic and International departure at NITB Goa Airport SH Improvement of Air conditioning at Domestic Security Hold Area
2020_AAI_43881_1
AAI/Goa/Engg/JGM(E)/Imp. AC/ENIT-15
Open Tender
Electrical Works
Works
120 days
Goa Airport
As per NIT
15 documents required · 15 mandatory
₹1,120
Airports Authority of India
₹2.8 L
23 Mar 2020
25 Feb 2020
13 Mar 2020
26 Feb 2020
9 Mar 2020
26 Feb 2020
26 Feb 2020 - 3 Mar 2020
Amount
VRV OUTDOOR UNIT Supply, Installation, Testing and Commissioning of Air-cooled Variable Refrigerant Volume(VRV) Outdoor Unit having top discharge comprising of multiple Scroll Compressor all inverter driven, full charge of refrigerant gas (R-410A), lubricating oil and all accessories as per specifications. The condensing unit shall be suitable for Cooling with multi-row condenser coil made of aluminium fins and copper tubes.Multi-kit for multiple outdoor unit connection should be included in price. It also includes lifting and shifting of the outdoor units upto the desired location. The condensing unit shall be suitable for operation on 415 ± 10% volts, 50Hz, 3Phase AC power supply and condensing unit shall be of following capacities:- (a) 40 HP Nominal Higher Capacity
VERTICAL FLOOR MOUNTED AHU Supply, Installation, Testing and Commissioning of AHU with 6RD DX Cooling coil Floor Mounted , double skin having panel thickness 43mm thick polyurethene foam (thermal break profile) 38 kg/m3 Puf having backward curved centrifugal flow fan with motor type TEFC Sq. Cage Induction Motor DoP-IP55 and Motor Efficiency rating IE2. Prefilter type Pre-filter 500FPM EU4/ 10micron. Coil made with copper tubing and fins with aluminium. Unit should be equiped with vibration isolators between fan and coil section and also vibration isolators should be provided between floor and base. Total static pressure of 40mmwg. It also includes lifting and shifting of the outdoor units upto the desired location. Fan outlet velocity of 1500 FPM. The AHU unit shall be as per following:-
Supply, Installation, Testing and Commissioning of 13000± 2% CFM AHU
Supply , Installation, Testing and Commissioningof AHU Expansion Valve and Control Box(To connect ODU to AHU)
Supply , Installation, Testing and Commissioningof Centralised Remote Controller ( CRC) with individual as well as zonal control of minimum 64 indoor units. The wiring length of CRC should be a minimum of 1000 metre. It should be connectable with unified ON/Off controller, schedule timer and BMS system.Airflow volume and direction should be controllable in stepped manner for individual units/groups. (Make Daikin DCS302CA61 or Equivalent)
Supply, Installation, Testing & Commissioning of high pressure copper refrigerant piping suitable for R 410a refrigerant of suitable size as required and duly insulated with 19mm/13mmthick closed cell elastomeric insulation in tubing form inclusive of nitrile rubber and UV treatment. External Refrigerant piping shall be laid on GI covered cable trays. Piping inside occupied spaces shall be supported by ladder type GI Slot channel. Entire refrigerant piping work be carried out in accordance with the specifications. Piping shall be of following sizes:
36 to 45 mm Dia Copper pipe with 19mm thick insulation
21 to 35 mm Dia Copper pipe with 19mm thick insulation
11 to 20 mm Dia Copper pipe with 19mm thick insulation
Supply, Installation, Testing and Commisioning of all communication/control cables between indoor and outdoor unit and also between Outdoor unit and central remote controller as per OEM specifications as required.
Supply & installation, testing and commissioning of Rigid heavy class 50mm CPVC piping for drain, complete with fittings, supports as per specifications and duly insulated with 6 mm thick closed cell crosslinked polyethylene (XLPE) tubular insulation.
Supply, Installation, Testing of fabricated ductwork complete with fire retardant gaskets, slip on flanges, GI Angle supports etc. in accordance with the specifications.
SITC of 20Gauge, GI Ducting
SITC of Angle Support for Duct Network (25mmx25mmx3mm)
Supply, Installation and Testing of 125mm deep Antivibration Canvass Joints made out of imported fire retardant fabric with extruded aluminium frame/ flange on both sides of approved make.
Supply, Installation, Testing & Balancing of Round supply air Jet diffusers as per the approved shop drawings and specifications with fixed air distribution grid, removable key-operated volume control damper. a. 312 mm Dia. Round Jet diffusers with volume control dampers having neck size as mentioned in the "Approved for Construction" shop drawings.
Supply, Installation, Testing & Balancing of 200mm Linear Grills for return air as per the approved shop drawings & specifications.
Supply and Application of internal acoustic insulation for ducts using open cell elastomeric insulation with adhesive, longitudinal & transverse joints sealed with adhesive armasound/ k-Fonic in a neat & clean manner. (a) 13 mm/15mm thick as per OEM Specification
Supply and installation of aluminium foil faced closed cell elastomeric nitrile rubber thermal insulation exhibiting class"O" properties on supply and return air ducts with sealing of longitugnal and transverse joints with SR-505 adhesive as per the approved specifications. Quoted price shall be inclusive of adhesive, tapes and other accessories as per specification. (a) not less than 13 mm thick
Supply and Application of internal acoustic insulation for AHU using open cell elastomeric insulation with adhesive, longitudinal & transverse joints sealed with adhesive armasound/ k-Fonic in a neat & clean manner. (a) not less than 25 mm thick
Supply and Application of internal acoustic insulation for AHU BOX using open cell elastomeric insulation with adhesive, longitudinal & transverse joints sealed with adhesive armasound/ k-Fonic in a neat & clean manner. (a) not less than 25 mm thick
Fabrication and fixing of Aluminium composite panel cladding on outside with 3mm /0.25 mm thick ACP sheets, aluminium tubes 50 x 25 x 1.2 mm thick frame work, 50*50*2.3mm mild steel frame work, 6mm thick commercial plywood fixed inside, silicon sealants etc complete.
Air-Balancing ,Testing and Commissioning of whole system
SITC of M.S Outdoor Unit Stand of minimum 150mm height for mounting outdoor units with anti vibration rubber pads.
Gas Charging of the System
Civil Works including 12 core cuts of around 150mm diameter and other minor civil works as and where required for the work to be completed as per instructions from Engineer-in-charge.
SH-2: Electrical Works VRF Feeder Panel- Supply, Installation, Testing & Commissioning, Indoor type cubicle panel, body made out of 2mm thick CRCA sheet, totally enclosed, IP 42, floor/wall mounted with channel base frame, dust and vermin proof, indoor, compartmentalised, suitable for operation on 3 phase and neutral, 415 V, 50Hz AC system, including control wiring with 2.5 sq mm size wires/cable, interconnection, duly powder coated painting etc. including supply & installation of following switchgears, metering instruments and accessories as per following specifications:- INCOMER : 2 Nos. 250A four pole Module case Circuit Breaker (Ics = Icu = 50 KA) with built in thermal based release unit with adjustable setting. BUSCOUPLER : 1 Nos. 250A four pole Module case Circuit Breaker (Ics = Icu = 50 KA) with built in thermal based release unit with adjustable setting. OUTGOING : (i) 8 Nos. 63A four pole Module case Circuit Breaker (Ics = Icu = 30 KA) with built in thermal based release unit with adjustable setting. (ii) 8 Nos. 63A four pole Residual Current Circuit Breaker, 300mA Sensitivity for each outgoing. INSTRUMENTS: 2 Nos. digital multifunction meter (Ammeter + Voltmeter) including suitable rating CTs for 3 phase, 4 wire operation as per specification. INDICATIONS : RYB (LED Type) phase indicating lamps controlled by 2 amp MCB for all incomer & ON /OFF indication for all Incomers and Outgoings. BUSBAR : 400 Amp TPN Aluminium busbar. All Incomers and Bus Coupler shall be mechanically and electrically interlocked with suitable accessories.
Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 volts, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 amps tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB’s (but without MCB’s and incomer ) as required. 12 Way Double Door(8+36)
Supplying and fixing 100 amps rating, 415 volts, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of Triple pole and Neutral in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Supplying and fixing 100A rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Supplying and fixing 32 amps rating, 415 volts, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of Triple Pole in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Supply of following 1.1KV grade aluminium/copper conductor XLPE/PVC insulated PVC sheathed armoured cable as per IS 7098 (Part I) 1988 as required.
3.5 Core 185 Sq. mm Aluminium
3.5 Core 70 Sq. mm Aluminium
3.5 Core 35 Sq. mm Aluminium
4 Core 2.5 Sq. mm Copper
Laying and fixing of following sizes of one number PVC insulated and PVC sheathed/XLPE Power cable of 1.1kv grade on existing cable tray with cable clamp/saddles etc. as required. Above 95 sq mm and up to 185 Sq.mm
Laying and fixing of following sizes of one number PVC insulated and PVC sheathed/XLPE Power cable of 1.1kv grade on existing cable tray with cable clamp/saddles etc. as required. Above 35 sq mm and up to 95 Sq.mm
Laying and fixing of following sizes of one number PVC insulated and PVC sheathed/XLPE Power cable of 1.1kv grade on existing cable tray with cable clamp/saddles etc. as required. Upto 35 sq mm
Laying and fixing of following sizes of one number PVC insulated and PVC sheathed/XLPE Power cable of 1.1kv grade on wall surface as required. Upto 35 sq. mm
Supply and making end termination with brass compression gland and aluminium/copper lugs as per cable for following size XLPE insulated PVC sheathed aluminium/copper conductor cable of 1.1 KV grade complete as required. 3.5C x 185 Sq.mm Aluminium
Supply and making end termination with brass compression gland and aluminium/copper lugs as per cable for following size XLPE insulated PVC sheathed aluminium/copper conductor cable of 1.1 KV grade complete as required. 3.5C x 70 Sq.mm Aluminium
Supply and making end termination with brass compression gland and aluminium/copper lugs as per cable for following size XLPE insulated PVC sheathed aluminium/copper conductor cable of 1.1 KV grade complete as required. 3.5C x 35 Sq.mm Aluminium
Fabricating and installing following size of perforated GI cable trays including horizontal and vertical bends, reducers, tees, cross members and other accessories as required, and duly suspended from the ceiling with suspenders/supported on wall including painting of all welded area etc. as required. 300 mm width x 50mm depth x 2 mm thickness.
Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required.
VAV Airconditioning
Neptune Engineering
Divine Air
GEMINI COOLING SYSTEMS PROJECTS PRIVATE LIMITED
Blue Star Limited
Superior Aircon Pvt. Ltd.
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.70 MB
E-tenderVRFDSHA.pdf
Tender Documents • 7.53 MB
BOQ_47524.xls
BOQ • 0.27 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .