Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹32.0 LAccepted-AOC | L1 | Accepted-AOC Being lowest tender | |
| 2 | L2₹33.3 L+₹34,457.50 (1.04%)Rejected-Finance | L2 | Rejected-Finance Not being lowest tender | |
| 3 | L3₹33.9 L+₹90,709 (2.75%)Rejected-Finance C 187 NIRMAN VIHAR DELHI 92 | L3 | Rejected-Finance Not being lowest tender |
Tender Value
₹34.0 L
EMD Value
₹67,980
Closing Date
29 Mar 2025, 6:00 pmClosed
GE (AF) ADM AREA
GE (AF) ADM AREA GWALIOR-474020
RENEWAL/REPLACEMNENT OF OH LINES INTO UG CABLES, PROVN OF EXTERNAL ELECTRIC SUPPLY, LED LIGHTS AND CONNECTED WORKS AT VARIOUS LOCATION AT AF STN GWALIOR
2025_MES_691611_2
8483/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE (AF) ADM AREA GWALIOR
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE (AF) ADM AREA
₹67,980
Yes
19 May 2025
8 Mar 2025
2 Apr 2025
8 Mar 2025
29 Mar 2025
15 Mar 2025
Amount
Dismantling and taking down old unserviceable aluminium conductor, steel reinforced (ACSR) of any type/size & in any position from existing LT Poles / Lines including jumpers and guard wire, line separators complete all as specified & directed.
Dismantling and taking down old wornout cross arms bracings, nut and bolts complete all as specified & directed
Supply, laying, connecting and testing LT 1100 volt grade electric cable XLPE insulated, screened, PVC bedded, galvanised steel strip armoured (heavy duty) ISI marked with aluminium stranded conductor cross sectional area 185 Sqmm , 3.5 core in trenches/on surface of wall/ in GI pipe including dressing and clamping the cable with MS Zinc Passivated clamps and fixing suitable thimbles/lugs including cable glands of suitable size etc and complete all as specified in PS and directed . Note:- Earthwork & excavation shall be measured & paid separetely under respective items
Supply , laying , connecting and testing LT 1100 volt grade electric cable XLPE insulated, screened, PVC bedded, galvanised steel strip armoured (heavy duty) ISI marked with aluminium stranded conductor cross sectional area 150 Sqmm , 3.5 core in trenches/on surface of wall/ floor/in GI pipe including dressing and clamping the cable with MS Zinc Passivated clamps and fixing suitable thimbles/lugs including cable glands of suitable size etc and including cable path indicators at distance of every 25 m duly marked with "MES LT cable" complete all as specified in PS and directed . Note:- Earthwork & excavation shall be measured & paid separetely under respective items
Supply , laying , connecting and testing LT 1100 volt grade electric cable XLPE insulated, screened, PVC bedded, galvanised steel strip armoured (heavy duty) ISI marked with aluminium stranded conductor cross sectional area 120 Sqmm , 3.5 core in trenches/on surface of wall/ in GI pipe including dressing and clamping the cable with MS Zinc Passivated clamps and fixing suitable thimbles/lugs including cable glands of suitable size etc and including cable path indicators at distance of every 25 m duly marked with "MES LT cable" complete all as specified in PS and directed . Note:- Earthwork & excavation shall be measured & paid separetely under respective items
Supply , laying , connecting and testing LT 1100 volt grade electric cable XLPE insulated, screened, PVC bedded, galvanised steel strip armoured (heavy duty) ISI marked with aluminium stranded conductor cross sectional area 95 Sqmm , 3.5 core in trenches/on surface of wall/ in GI pipe including dressing and clamping the cable with MS Zinc Passivated clamps and fixing suitable thimbles/lugs including cable glands of suitable size etc and including cable path indicators at distance of every 25 m duly marked with "MES LT cable" complete all as specified in PS and directed . Note:- Earthwork & excavation shall be measured & paid separetely under respective items
Supply , laying , connecting and testing LT 1100 volt grade electric cable XLPE insulated, screened, PVC bedded, galvanised steel strip armoured (heavy duty) ISI marked with aluminium stranded conductor cross sectional area 70 Sqmm , 3.5 core in trenches/on surface of wall/ in GI pipe including dressing and clamping the cable with MS Zinc Passivated clamps and fixing suitable thimbles/lugs including cable glands of suitable size etc and including cable path indicators at distance of every 25 m duly marked with "MES LT cable" complete all as specified in PS and directed . Note:- Earthwork & excavation shall be measured & paid separetely under respective items.
Supply , laying , connecting and testing LT 1100 volt grade electric cable XLPE insulated, screened, PVC bedded, galvanised steel strip armoured (heavy duty) ISI marked with aluminium stranded conductor cross sectional area 50 Sqmm , 3.5 core in trenches/on surface of wall/ in GI pipe including dressing and clamping the cable with MS Zinc Passivated clamps and fixing suitable thimbles/lugs including cable glands of suitable size etc and including cable path indicators at distance of every 25 m duly marked with "MES LT cable" complete all as specified in PS and directed . Note:- Earthwork & excavation shall be measured & paid separetely under respective items
Supply , laying , connecting and testing LT 1100 volt grade electric cable XLPE insulated, screened, PVC bedded, galvanised steel strip armoured (heavy duty) ISI marked with aluminium stranded conductor cross sectional area 35 Sqmm , 3.5 core in trenches/on surface of wall/ in GI pipe including dressing and clamping the cable with MS Zinc Passivated clamps and fixing suitable thimbles/lugs including cable glands of suitable size etc and including cable path indicators at distance of every 25 m duly marked with "MES LT cable" complete all as specified in PS and directed . Note:- Earthwork & excavation shall be measured & paid separetely under respective items
Supply , laying , connecting and testing LT 1100 volt grade electric cable XLPE insulated, screened, PVC bedded, galvanised steel strip armoured (heavy duty) ISI marked with aluminium stranded conductor cross sectional area 16 Sqmm , 4 core in trenches/on surface of wall/ in GI pipe including dressing and clamping the cable with MS Zinc Passivated clamps and fixing suitable thimbles/lugs including cable glands of suitable size etc and including cable path indicators at distance of every 25 m duly marked with "MES LT cable" complete all as specified in PS and directed. Note:- Earthwork & excavation shall be measured & paid separetely under respective items
Supply , laying , connecting and testing LT 1100 volt grade electric cable XLPE insulated, screened, PVC bedded, galvanised steel strip armoured (heavy duty) ISI marked with aluminium stranded conductor cross sectional area 10 Sqmm , 2 core in trenches/on surface of wall/ in GI pipe including dressing and clamping the cable with MS Zinc Passivated clamps and fixing suitable thimbles/lugs including cable glands of suitable size etc and including cable path indicators at distance of every 25 m duly marked with "MES LT cable" complete all as specified in PS and directed. Note:- Earthwork & excavation shall be measured & paid separetely under respective items.
Supply, laying, connecting and testing LT 1100 volt grade electric cable XLPE insulated, Cores laid up, Thermoplastic Tape Inner sheathed, Unamoured ISI marked with aluminium stranded conductor gross sectional area 4 Sqmm , 2 core in GI pipe including dressing and clamping the cable with MS Zinc Passivated clamps and fixing suitable thimbles/lugs including cable glands of suitable size etc complete all as specified in PS and directed. Note:- Earthwork & excavation shall be measured & paid separetely under respective items
Supply & Fixing 100 mm bore light grade galvanized iron tubing ISI marked including all fittings etc laid in trenches or fixed on wall for protection pipe complete all as specified and directed.
Supply & Fixing 80 mm bore light grade galvanized iron tubing ISI marked including all fittings etc laid in trenches or fixed on wall for protection pipe complete all as specified and directed.
Supply & Fixing 50 mm bore light grade galvanized iron tubing ISI marked including all fittings etc laid in trenches or fixed on wall for protection pipe complete all as specified and directed.
Supply & Fixing 40 mm bore light grade galvanized iron tubing ISI marked including all fittings etc laid in trenches or fixed on wall for protection pipe complete all as specified and directed.
Supply & Fixing 15 mm bore light grade galvanized iron tubing ISI marked including all fittings etc fixed on pole including suitable size clamps, nut and bolts protection pipe for street light cable from junction box to street light complete all as specified and directed
Supply, install, testing and commission of LT Panel outdoor type IP-54 protection as per IS-2147 CPRI Approved suitable for AC supply 3 phase 4 wire, 415 V, 50 Hz having dust and vermin proof MS sheet with suitable appropriate size complete painting , PCC etc comprising of controlling MCCB/ACB supported on F class DMC/FRP insulator with short circuit withstand capacity 21 MVA for 1 second, the fixing of the doors shall be such that the doors should automatically come to closed including canopy on top and gland provision in bottom made out of 3 mm thick shall be powder coated externally & internally after carrying out pre coating seven tank process comprises of degreasing, rising, derusting, rinsing, phosphating, rinsing & passivation thickness of powder coating shall be 80 micron, colour shade of powder coating shall be Siements Gray (RAL-7032) complete including locking arrangement and the fixing of the doors shall be such that the doors should automatically come to closed portion if not kept open with effort and using suitable angle iron frame and supports not less than 40 x 40 x 6 mm deep and base channel shall be grouted in CM 1:3 complete including taking down old panel of any size and discription all as specified in PS and direceted and the following accessories
Ser Item No 18 contd../- A :- Incoming (a) 1000 Amps, 50 KA, 4 pole, 50 Hz, 415 V MOD type ACB with SR 18G or equivalent complete - 01No (b) Phase indicating lamps LED type RYB including holder with MCB control of suitable size (set of three) - 01 set (c) Volt meter digital type 0-500 volts -01 No (d) Ammeter digital type 0 -1000 Amp - 01 No B: Aluminium bus bar suitable for 1600 Amp load 415 volts distribution system- 1 set C: Outgoing (a) MCCB 250 Amps 4 pole, 50 Hz, 415 V with rupturing capacity 35 KA, ICs=ICu with thermal setting 80 to 100 % - 03 No (b) MCCB 315 Amps 4 pole, 50 Hz, 415 V with rupturing capacity 35 KA, ICs=ICu with thermal setting 80 to 100 % -01 No (c) MCCB 150 Amps 4 pole, 50 Hz, 415 V with rupturing capacity 25 KA, ICs=ICu with thermal setting 80 to 100 % -01 No (d) MCCB 125 Amps 4 pole, 50 Hz, 415 V with rupturing capacity 25 KA, ICs=ICu with thermal setting 80 to 100 % - 01 No (e) MCCB 63 Amps 4 pole, 50 Hz, 415 V with rupturing capacity 16 KA, ICs=ICu with thermal setting 80 to 100 % -01 No (f) Supply and fixing inside of panel time switches astro type (Having logitude and latitude of Indian cities in memory including air break power contactor) 415 V single phase of 32 Amp rating with contactor fitted inside steel enclosure. (g) Spare slots for MCCB Maximum capacity of Out going -01 Nos
Ser Item No 18 contd../- NOTE : (a) Panel shall be fitted with chromium plated brass name plate engraved with current rating of the panel and indicating whether it is transformer control panel or otherwise as applicable. (b) Door shall be hinged along with locking arrangement and fixing shall be such that the doors should automatically come to closed position if not kept open with efforts. (c) Danger Notice board size 150 x 100 mm, 2 mm thick fixed on panel at both front and back side (d) Panel shall be fixed on plinth (platform) to be constructed as specified in PS and rate for the same shall be included under quoted rate by the contractor.
S&F MCCB 100 Amps 4 Pole, 36 KA, ICs=ICu, 415 V, 50 Hz with thermal setting between 80% to 100% adjustable type and connecting up in the existing panel location including taking out existing unserviceable MCCB complete all as specified and as directed by Engineer-in-Charge.
S&F MCCB 125 Amps 4 Pole, 36 KA, ICs=ICu, 415 V, 50 Hz with thermal setting between 80% to 100% adjustable type and connecting up in the existing panel location including taking out existing unserviceable MCCB complete all as specified and as directed by Engineer-in-Charge.
Supply and installation & Testing factory made CPRI approved LT feeder pillar box for 3 phase, 4 wire, 415 Volt, AC, 50Hz, outdoor, cubical type, weather, dust and vermin proof, pedestal mounting type front operated applications with and including S&F aluminium bus bar rating capacity 200 Amps and neutral 300 Amps rating capacity mounting of insulators, RYB indicator incoming controlled with fixed type MCCB 4 Pole of capacity 125 Amps and breaking capacity Icu= 36KA, ICs=ICu and outgoing MCCB 63 Amp 3 pole, 25 KA, ICs=ICu - 03 Nos including canopy on top and gland provision in bottom made out of 3 mm thick shall be powder coated externally & internally after carrying out pre coating seven tank process comprises of degreasing, rinsing, derusting, rinsing, phosphating, rinsing & passivation thickness of powder coating shall be 80 micron, colour shade of powder coating shall be Siements Gray (RAL-7032) complete including locking arrangement and the fixing of the doors shall be such that the doors should automatically come to closed portion if not kept open with effort and using suitable angle iron frame and supports not less than 40 x 40 x 6 mm deep and base channel shall be grouted in CM 1:3 with including necessary excavation and grouting work complete all as specified in PS and directed.
Ser Item No 21 contd../- NOTE : (a) Panel shall be fitted with chromium plated brass name plate engraved with current rating of the panel and indicating whether it is transformer control panel or otherwise as applicable. (b) Door shall be hinged along with locking arrangement and fixing shall be such that the doors should automatically come to closed position if not kept open with efforts. (c) Danger Notice board size 150 x 100 mm, 2 mm thick fixed on panel at both front and back side (d) Panel shall be fixed on plinth (platform) to be constructed as specified in PS and rate for the same shall be included under quoted rate by the contractor.
Supply and installation, testing and commissioning factory made CPRI approved LT feeder pillar box for 3 phase, 4 wire, 415 Volt, AC, 50Hz, outdoor, cubical type, weather, dust and vermin proof, pedestal mounting type front operated applications with and including S&F aluminium bus bar rating capacity 400 Amps and neutral 300 Amps rating capacity mounting of insulators, RYB indicator and incoming controlled with and including fixed type MCCB 3 Pole of capacity 250 Amps and breaking capacity Icu= 36KA, ICs=ICu and outgoing MCCB 100 Amp 3 pole, 25 KA, ICs=ICu - 04 Nos including canopy on top and gland provision in bottom made out of 3 mm thick MS sheet and shall be powder coated externally & internally after carrying out pre coating seven tank process comprises of degreasing, rising, derusting, rinsing, phosphating, rinsing & passivation thickness of powder coating shall be 80 micron, colour shade of powder coating shall be Siements Gray (RAL-7032) complete including locking arrangement and the fixing of the doors such that the doors should automatically come to closed portion if not kept open with effort and with including necessary excavation and foundation/PCC platform as specified in PS complete all as specified and directed.
Ser Item No 22 contd../- NOTE : (a) Panel shall be fitted with chromium plated brass name plate engraved with current rating of the panel and indicating whether it is transformer control panel or otherwise as applicable. (b) Door shall be hinged along with locking arrangement and fixing shall be such that the doors should automatically come to closed position if not kept open with efforts. (c) Danger Notice board size 150 x 100 mm, 2 mm thick fixed on panel at both front and back side (d) Panel shall be fixed on plinth (platform) to be constructed as specified in PS and rate for the same shall be included under quoted rate by the contractor.
Supply and installation, testing and commissioning factory made CPRI approved LT feeder pillar box for 3 phase, 4 wire, 415 Volt, AC, 50Hz, outdoor, cubical type, weather, dust and vermin proof, pedestal mounting type front operated applications with and including S&F aluminium bus bar rating capacity 400 Amps and neutral 300 Amps rating capacity mounting of insulators, RYB indicator and incoming controlled with and including fixed type MCCB 3 Pole of capacity 315 Amps and breaking capacity Icu= 36KA, ICs=ICu and outgoing MCCB 100 Amp 3 pole, 25 KA, ICs=ICu - 04 Nos including canopy on top and gland provision in bottom made out of 3 mm thick MS sheet and shall be powder coated externally & internally after carrying out pre coating seven tank process comprises of degreasing, rising, derusting, rinsing, phosphating, rinsing & passivation thickness of powder coating shall be 80 micron, colour shade of powder coating shall be Siements Gray (RAL-7032) complete including locking arrangement and the fixing of the doors such that the doors should automatically come to closed portion if not kept open with effort and with including necessary excavation and foundation/PCC platform as specified in PS complete all as specified and directed.
Ser Item No 23 contd../- NOTE : (a) Panel shall be fitted with chromium plated brass name plate engraved with current rating of the panel and indicating whether it is transformer control panel or otherwise as applicable. (b) Door shall be hinged along with locking arrangement and fixing shall be such that the doors should automatically come to closed position if not kept open with efforts. (c) Danger Notice board size 150 x 100 mm, 2 mm thick fixed on panel at both front and back side (d) Panel shall be fixed on plinth (platform) to be constructed as specified in PS and rate for the same shall be included under quoted rate by the contractor.
Material and labour for earthing complete with galvanized steel earth plate electrode 600mm x 600mm x 6mm buried directly in ground vertically to a depth not less than 2.25 metre below normal ground level (with top edge of earth plate not less than 1.5 metre below ground level) connected to galvanized iron earth strip 32 x 6 mm (main earthing lead) by means of galvanized bolts, nuts and washers all as shown in electrical plate No 3 of MES Schedule Part-I (2009) connected to earth test point & to main switch board with & including adequate quantity of charcoal dust and common salt alround earth plate & 40 mm dia GI pipe medium grade for earth lead protection pipe for suitable length and GI pipe 20 mm dia medium grade for watering pipe with funnel & wire mesh including necessary earth work and PCC (1: 3 : 6) type C-1 for earth pit , internal surface of concrete shall be plastered with 10mm thick plaster in CM 1:4 and 40 mm thick precast RCC cover 1 : 2 : 4 ,type B-1( using 20 mm graded crushed stone aggregare ) reinforced with 8 mm dia TMT bars @ 75 mm c/c both ways with 12mm dia round bar as in handle including taking down of existing earthing complete all as specified & directed. Note: (i) Test result of earthing to be submitted by the contractor for all earthing . (ii) Earth filling shall be done by vegetable soil. (iii) Soil should be free from stone, boulders,aggragates,gravel etc. (iv) The rate quoted by the bidders shall be also be deemed to include Supply of charcoal and common salt.
M&L for PCC (1:4:8) Type D-2 using 40mm graded stone aggregate as in foundation/repairs to damaged road/footpath/plinth for panels etc. including necessary formwork complete all as specified and direcetd.
M&L for PCC (1:2:4) Type B-1 using 20mm graded stone aggregate as in repair to footpath/hard standing/plinth for panels etc. including necessary formwork complete all as specified.
Supplying and fixing Sintex PVC boxes of suitable size with and including 10 cm long aluminium bus bar of size 20x3 mm size 4 Nos mounted on porcelain insulators including one No. MCB SPN, ‘C’ series, 5/6 Amps and connecting the bus bars to cables with using suitable aluminum lugs etc fixed on pole using 30x5 mm flat iron GI clamps, nuts, bolts & washers etc complete all as specified and directed.
Demolition for cement concrete/road in ground floor and paving n. exc 15 cm thickness below or above ground level including removal of rubbish to a distance not exc 50 mtr etc complete all as specified
M&L for boring of holes under road, pavement, hard standing by mannual boring and including supply and laying, insertion of HDPE pipe of 150 mm dia of suitable working pressure all as specified and directed.
Excavation in trenches in soft/loose soil not exceeding 1.5 m deep and not exceeding 1.5 mtr wide and getting out including forming bottom surface to required levels/gradients/slopes for foundations/laying of cable etc. all as specified and directed.
Returning, filling in, including spreading leveling, watering and well ramming the excavated soil in layers not exceeding 25 cm thick complete all as specified and directed
Removal of surplus excavated soil to a distance not exceeding 50 Mtr distance and depositing as directed at a level not exceeding 1.5 mtr above starting point complete all as specified and directed
M & L for sand filling with clean dry fine sand unwashed including gently punning around cables in trenches for cable protection complete all as specified and directed. Note: Punned thickness of sand shall be measured for payment
M&L bricks for cover underground cable with one layer of bricks using sub class 'B' bricks (Old size) laid flat across the cable complete all as specified.
Supply, installation, testing and commissioning of LT Panel outdoor type IP-54 protection as per IS-2147 CPRI approved (Design approved assembly) suitable for AC supply 3 phase 4 wire, 415 V, 50 Hz having dust and vermin proof MS sheet 3.15 mm thick with suitable appropriate size complete powder coated externally and internally after carrying out pre coating seven tank process, thickness of powder coating shall be not less than 80 micron. Colour shade of powder coating shall be Siemens Gray (RAL 7032) fixed on plastered brick masonry plinth constructed in C shape of required size as specified and PS comprising of controlling MCCB/ACB supported on F class DMC/FRP insulator with short circuit withstand capacity 21 MVA for 1 second, the fixing of the doors shall be such that the doors should automatically come to closed and comprising the following accessories :-
Supply and installation, testing and commissioning factory made LT feeder pillar box of size not less than 60cmX45cmX30cm for 3 phase, 4 wire, 415Volt, AC, 50Hz, outdoor, cubical type, weather, dust and vermin proof, pedestal mounting type suitable for front operated applications having aluminium bus bar rating capacity 400Amps and neutral 300Amps rating capacity mounting of insulators, incoming controlled with and including fixed type MCCB 3 Pole of capacity 250 Amps and ICs=ICu with breaking capacity Icu= 36KA including canopy on top and gland provision in bottom made out of 3 mm thick MS sheet and shall be powder coated externally & internally after carrying out pre coating seven tank process comprises of degreasing, rising, derusting, rinsing, phosphating, rinsing & passivation thickness of powder coating shall be 80 micron, colour shade of powder coating shall be Siements Gray (RAL-7032) complete including locking arrangement and the fixing of the doors such that the doors should automatically come to closed portion if not kept open with effort and with including necessary excavation and foundation/PCC platform as specified in PS complete all as specified and directed.
Ser Item No 36 contd../- NOTE : (a) Panel shall be fitted with chromium plated brass name plate engraved with current rating of the panel and indicating whether it is transformer control panel or otherwise as applicable. (b) Door shall be hinged along with locking arrangement and fixing shall be such that the doors should automatically come to closed position if not kept open with efforts. (c) Danger Notice board size 150 x 100 mm, 2 mm thick fixed on panel at both front and back side (d) Panel shall be fixed on plinth (platform) to be constructed as specified in PS and rate for the same shall be included under quoted rate by the contractor.
Supply, fixing, testing and commissioning MCCB, 630 Amps, 3 pole, 415 Volts, AC supply, having breaking capacity four standard ratios of ICS = thermal adjustable setting 75% and 100% and ICs=ICu, Icu=35/36 KA complete all as specified and directed.
Supplying & fixing PVC insulated, served with inner sheathed PVC tape weatherproof stranded Alumunium conductor cable twin core Size of cable with aluminium conductor 2.5 sq. mm for connected to flood light fittings with connector laying with walls and including clamps for proper layout of cables etc complete all as specified and directed by Engineer-in-Charge.
Supply and fixing of Energy saving, environmental friendly, long life , Exlusive innovative die -cast aluminium IP65 flood light luminair with high power LED as light source 100 W LED 6000K made out of pressure die cast aluminum housing with toughened glass and high power LEDs all as specified and directed by Engineer-in-Charge.
BABA DEVELOPERS (BID ID -3268797)
M/S KAPIL CONSTRUCTION CO (BID ID -3268708)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .