Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
Tender Value
₹41.7 L
EMD Value
₹42,000
Closing Date
9 Feb 2022, 5:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
SE ETC MEERUT
130 D PAARESHAN BHAWAN VICTORIA PARK MEERUT
WORK TENDER
2022_UPTCL_675213_1
T-96/21-22/ETC/MT
Open Tender
Electrical Works
Item Rate
90 days
MEERUT
Please refer Tender documents.
2 documents required · 2 mandatory
₹3,540
SE ETC MEERUT
₹42,000
24 Feb 2022
28 Jan 2022
10 Feb 2022
28 Jan 2022
9 Feb 2022
28 Jan 2022
90 days
Amount
PART-A (Work)
SHIFTING OF DAMAGED 63 MVA T/F IMP MAKE TO ANOTHER PLACE AND ERECTION OF 132 KV BUS COUPLER ALONG WITH SUPPLY OF MATERIAL AT 132 KV SUB-STATION KANKERKHERA SHALL BE CARRIED OUT AS DETAILED HERE UNDER.
Shifting of Damaged 63 MVA 132/33 KV T/F IMP MAKE from existing place to plinth up to 20 Mtr. Distance including turning to tank if required, including all T & P and work required to complete the job satisfactorily.
Additional shifting 20 Mtr. @ 5mtr Per job
Erection of 145 KV Circuit Breaker for 132 KV Bus coupler Bay
Erection of 145 KV Bus Isolator without earth switch (Motorized)
Erection of Auxiliary Sub-Station Structure for 132 KV Transfer BUS Coupler Bay
Proper stacking and shifting of main & auxiliary structure in open switchyard at erecting place as per shop bill norms.
Erection of 132 KV Auxiliary structure lattice type ALP & BBL consisting of PI, Isolator . Erection of structure as per drawing with the help of GI nuts & Bolts flat spring washer matching the hole, cutting and matching the member if required include cost of all men and T & P excluding GI structure nut and bolts to complete the work erection of auxiliary structure lattice type ALP, BBL upon foundation and its proper tightening.
Making hole in part of GI auxiliary structure / cutting of GI angle drilling of hole existing/ defective structure /plate/Angle and grinding machine with all cost of men, T & P etc.
Laying of following size control cables in the cable trenches from various equipments in switchyard to control & relay panel in control room including proper dressing and cleaning as per technical specification.
2 Core x 2.5 Sq.mm.
4 Core x 2.5 Sq.mm.
6 Core x 2.5 Sq.mm.
10 Core x 2.5 Sq.mm.
Termination of Control cable
Earthing of structure, various equipments, junction box, Control and relay panel and with the help of following M.S. Flat including Painting of M.S. Flat with one coat of red oxide and two coat of green enameled paint, Berger / Asian /Shalimar paint of first quality after cleaning of rust, dust including cost of all material and labour and T&P. (as per technical specification) MS Flat shall be provided by the contractor.
ERECTION OF 132 KV SECTION ISOLATOR AT 132 KV SUB-STATION KANKER KHERA SHALL BE CARRIED OUT AS DETAILED HERE UNDER.
Opening cutting of R, Y & B phase of 132 KV Main Bus Bar made of Moose between bus sections below gantry step by step
Dismantling of following existing jumpers from main bus bar by opening of all associated clamp step by step during bus bar.
ACSR Moose conductor of
Dismantling of 132 KV old main bus bar-I section (R, Y & B) Moose conductor and lowering down of conductor from sub-station gantry to complete dismantling works including dismantling of all associated tension clamps, fittings & disc insulators etc.
Erection of Main & Auxiliary structure lattice type BTM ,AXM, BBL, BTIetc. consisting of column, beam, and auxiliary structure the job consist of shifting of all material from store to site of erection, erection of structure as per drawing with the help of GI nut & bolt, flat & spring washer, matching the hole, cutting & matching of member if required including cost of all men and T & P excluding GI structure Nut & bolt to complete the work. Erection of Main & Auxiliary structure lattice type BCT, ALP etc. upon foundation and its proper tightening.
Sorting and stacking of main & auxiliary structure.
Stringing of 132 KV Twin moose main bus. The work includes cutting & bending of conductor, fixing of bolted type tension fitting Hoisting of disc insulator and shifting of material from store site to erection site and all other associated work to complete the work satisfactorily as per drawing and technical specification.
Jumpering of 132 KV Equipment, jumper from main bus to 132 KV switchgear, Moose/Zebra conductor.
Earthing of equipment’s by cutting straightening, bending, laying 700 mm below ground and above ground of following size of MS flat for earthing of main and auxiliary structure, equipment’s structure Transformer body and its neutral point including welding with main earthmat and with object to be earthed. Excavation of trenches, its back filling and all other associated work as required completing the work. ( MS Flat size- 50x6mm) Flat shall be provided by the contractor.
Erection of 145 KV Bus Isolator without earth switch
ERECTION OF NEW 40 MVA T/F ALONG AT 132 KV SUB-STATION KANKERKHERA SHALL BE CARRIED OUT AS DETAILED HERE UNDER.
Erection of Main & Auxiliary Sub-Station Structure for 40 MVA Transformer Bay
Proper stacking and shifting of Main & auxiliary structure in open switchyard at erecting place as per shop bill norms.
Erection of Main & Auxiliary structure lattice type ATM, ABL, BCT, ALP, BPL etc. consisting of column, beam, peak, mast etc. and auxiliary structure for installation of isolator, CTs, PTs, LA etc. erection of structure as per drawing with the help of GI nuts & Bolts flat spring washer matching the hole, cutting and matching the member if required include cost of all men and T & P excluding GI structure nut and bolts to complete the work erection of main & auxiliary structure lattice type ATM, BTM, AXM, ABL, CCM,CGM, EKR, BBR, BCT, ALP, BPL, BTI etc. upon foundation and its proper tightening.
Making hole in part of GI Main/auxiliary structure / cutting of GI angle drilling of hole existing/ defective structure /plate/Angle and grinding machine with all cost of men, T & P etc.
Erection of following equipment as per instruction manual of various equipment’s and technical specification including shifting of material / equipment from store to erection site including all other associated works to complete the job satisfactorily.
Erection of 36 KV Vacuum Circuit Breaker
Erection of 145 KV Current Transformer
Erection of 36 KV Current Transformer
Erection and mounting of 145/36 KV CT/PT junction box.
Erection of 145 KV Tandem Isolator without earth switch (Motorized)
Erection of 36 KV Bus Isolator.
Erection of 120 KV Lighting Arrestors
Erection of 30 KV Lighting Arrestors
Erection of following control and relay Panels as per instruction manual and technical specification including shifting of panel from store to erection site including all other associated works to complete the job satisfactorily.
Erection of 132 KV control relay panel for 40 MVA Transformer.
Erection of LT out door cubical for LT supply
Erection of 40 MVA RTCC Panel.
Stringing of various main, Transfer bus bar and jack buses of 132 KV and 33 KV with different type conductor and different length of span as mentioned below .the work includes cutting &bending of conductor fixing of single /double bolted type tension fitting /suspension hoisting of disc Insulator and shifting of material from store .site to erection site and all other associated work to complete work satisfactorily as per drawing and technical specification.
132 KV Jack Bus for 40 MVA Transformer
Bay wise interconnection of equipment with specified conductor of various 132 KV & 33 KV Equipment with Main /Transfer / jack Bus bar of ACSR Zebra /Panther conductor. The work Includes cutting of conductor. Bending in proper shape .clamping with the help of clamp and all other associated work to complete job.
40 MVA Transformer Bay 132 KV side Jack Bus
40 MVA Transformer Bay 132 KV side Bus
33 KV side Transformer bay Twin Zebra
Laying and Termination of following size control cable in trench/cable trays from different control room equipment to 132/33 KV Isolator, circuit breakers CT/PT & their junction boxes. Transformer marshaling box. Isolator box & other outdoor equipment’s installed in 132/33 KV switch yard as per cable schedule. Including carriage of cable drum from store and all other associated work.
Control cable of size 2 core x 2.5 mm2
Control cable of size 4 core x 2.5 mm2
Control cable of size 6 core x 2.5 mm2
Control cable of size 10 core x 2.5 mm2
Termination of control cable
Installation work of 40 MVA Transformer.
Shifting of main tank of 40 MVA Transformer from unloading point to the plinth up to 30 Mtr. distance including turning of tank if required including all T & P and labour required to complete the job satisfactorily.
Complete erection of 40 MVA 132/33 KV Transformer by erection of radiator, conservator t and all bushing oil pipe lines, cooling fans etc. to complete the job satisfactorily.
Circulation of complete Transformer oil in Transformer tank through centrifuging machine, centrifuging machine shall be provided by the contractor, oil capacity (Approx. 20 KL)
Laying & Termination of following size PVC power cable from ACDB /DCDB installed on control room / 33/.04 KV station Transformer marshaling box etc. in 132/33 KV switchyard in side 500mm below ground level including excavation of trench & laying on its edge along with cable of both side filling the same with Ganga sand and then putting the bricks on 115mm side cover the trench & then filling with earth. Proper termination at both side by providing crimping type aluminum lugs as per requirement including cost of bricks sand cable route marker as per cable schedule including carriage of cable drum from store and all other associated works.
Power cable 31/2 core x 300 mm2 /150 mm2
300 mm2 Power cable termination.
Fabrication of 3 meter long electrode with 40 mm dia. M S round bar having 150 mm long conical shape by digging cutting, straightening etc. and then placing it vertical. inside the ground with Top 700mm below the ground level including shifting of MS round bar from storage place at the Sub-Station to switchyard.
Delta earthig of 120/33 KV LA's of 132 KV Lines and 40 MVA Transformers neutral by consisting of 3/6 Nos. 3.0 Mtr long electrode of 40mm dia. having 150mm long conical shape, its placing inside the ground in rectangular/triangular shape and connection all 3/6 Nos. electrodes with 75x10/50x6mm MS flite laid on its edge and then this rectangle/triangle shape be connected to main earth mat at two place in opposite direction strictly as per drawing.
120 KV Lighting Arrestors (Rectangle shape 6 electrode )
30 KV Lighting Arrestors (Rectangle shape 6 electrode )
132/33 KV 40 MVA Transformer (Triangular shape 3 electrode)
Earthing of equipment’s by cutting straightening, bending, laying 700mm below ground and above ground of following size of MS flat for earthing of main and auxiliary structure, equipment’s structure. Transformer body and its neutral point including welding with main earthmat and with object to be earthed excavation of trenches its back filling. All other associated work as required to complete the work. MS Flat shall be provided by the contractor.
Laying of MS Flat of size 75x10 mm
Laying of MS Flat of size 50x6 mm
Laying of MS Flat of size 25x6 mm
Painting of MS flat of different size after cleaning of rusted surface 1st coat of Red Oxide and 2 coat of Bus Green Paint to complete the work.
MS Flat of size 75x10 mm
MS Flat of size 50x6 mm
MS Flat of size 25x6 mm
Periphery and switchyard lighting
Providing and fixing of half round GI pipe OD-50mm for mounting the 120 Watt LED light upon gantry mounting of 2 No GI bracket up on gantry and fixing GI pipe complete with nut bolt and washer as per technical specification.
Providing and fixing of junction box on gantry structure with 1 No MS flat 40x5 mm of size 200x200x150 mm made of MS sheet of 16 gauge dully powder coated inside mounting 1 No 6 Amp MCB 1 No TB of 4 terminal & 1 No Kit Kat 16 Amp fixed upon mica sheet and back side mounting a flat 40x5 mm with 1 No 16mm dia. hole and mounting PVC pipe from ground level to box as per technical specification.
Providing & fixing of new generation energy saving and environment friendly long life versatile pressure die cost aluminum out door high been flood light with high power 120 Watt LED as light source and exclusively designed polycarbonate cover along with electronic driver complete fitting suitable for 220 V input supply for ISI make CGL/Hevels/ Surya/ Philips/Bajaj of equivalent etc. including electrical connection also to be done by the contractor.
DISMANTLING OF 10 MVAR CAPICATOR BANK AND RE -ERECTION OF CAPICATOR BANK IN OTHER PLACE SHALL BE CARRIED OUT AS DETAILED HERE UNDER.
Dismantling of 10MVAR, 33KV capacitor Bank along with Column, Beam, Bus bar Isolator, CT , NCT, Breaker, Lightening arrestor, Reactor, CTs, NCT, Isolator, Capacitor unit Reactor and unit structure, Jumper and electrical connection and other associated work.
Erection of 10MVAR 33KV capacitor Bank along with Column, Beam, Bus bar Isolator, CT , NCT, Breaker, Lightening arrestor, Reactor, CTs, NCT, Isolator, Capacitor unit Reactor and unit structure, Jumper and electrical connection and other associated work.
Erection of Auxiliary Sub-Station Structure for 10 MVAR Capacitor Bank
Proper stacking and shifting of auxiliary structure in open switchyard at erecting place as per shop bill norms.
Erection of auxiliary structure lattice type ABL, ALP, BPL etc. consisting of auxiliary structure for installation of isolator, CTs, PTs, LA etc. erection of structure as per drawing with the help of GI nuts & Bolts flat spring washer matching the hole, cutting and matching the member if required include cost of all men and T & P excluding GI structure nut and bolts to complete the work erection of main & auxiliary structure lattice type ATM, BTM, AXM, ABL, CCM,CGM, EKR, BBR, BCT, ALP, BPL, BTI etc. upon foundation and its proper tightening.
Making hole in part of GI auxiliary structure / cutting of GI angle drilling of hole existing/ defective structure /plate/Angle and grinding machine with all cost of men, T & P etc.
Bay wise interconnection of equipment with specified conductor of various 33 KV Equipment with Main /Transfer / jack Bus bar of ACSR Zebra /Panther conductor. The work Includes cutting of conductor. Bending in proper shape .clamping with the help of clamp and all other associated work to complete job.
33KV side Capacitor Bank
STRENTHENING OF 33 KV MAIN BUS BAR FROM SINGLE TARANTULLA TO TWIN TARANTULLA SHALL BE CARRIED OUT AS DETAILED HERE UNDER.
Dismantling of 33 KV Old/ Damaged Main bus bar Sections (R, Y, & B) of Single Tarantulla conductor and lowering down of conductor from sub-station gantry to complete dismantling work including dismantling of all associated Tension clamps, fittings & Disc insulators etc.
Dismantling of Jumpering of 33 KV Equipment, jumper from main bus to 33 KV switchgear, Moose/Panther conductor.
Dismantling of Jumpering of 33 KV Equipment, jumper from Section Isolator 33 KV switchgear, Moose/Zebra conductor.
Stringing and proper sagging of new 33 KV Main bus bar Sections (R, Y & B) by Twin Tarantulla conductor the work includes fitting of tension clamps, Hoisting of 70 KN Disc, tension fittings, Spacers PG Clamps etc. and cutting of conductor as required.
Jumpering of 33 KV Equipment, jumper from main bus/Line Isolator to 33 KV switchgear, Twin Panther conductor.
Jumpering of 33 KV Equipment, jumper from Section Isolator for Twin Tarantulla Conductor.
PART-B (Supply)
Supply of following material for requirement of Bus Coupler Bay.
132 KV isolator clamp made of LM -6 Aluminum alloy, one side suitable for isolator rod and another side for Zebra conductor.
PG Clamp Zebra to Zebra
PG Clamp Zebra to Panther
PG Clamp Panther to Panther
Bolted type single Tension fitting for Twin Moose conductor suitable for 1 x10 No Disc insulators with turn buckle and hardware set as per technical specification.
Bolted type single Tension fitting for Twin Moose conductor suitable for 1 x10 No Disc insulators without turn buckle and hardware set as per technical specification.
4 Bolted Type PG clamp suitable for moose-to-moose conductor Complete with HDG nut bolt & washer as per technical specification.
132 KV section Isolator clamp for Twin moose conductor with height rising type completes with hot dip galvanize nut, bolts and washer as per technical specification.
Spacer for 250mm spacing for Twin Moose Conductor 02 bolted complete with hot dip galvanized nut, bolts & washer as per technical specification.
Spacer for 100mm spacing for Twin Moose Conductor 02 bolted complete with hot dip galvanized nut, bolts & washer as per technical specification.
Bimetallic 33 KV Bus Isolator clamp for Twin Zebra/Moose conductor complete with hot dip galvanized nut, bolts and washer as per technical specification.
Bimetallic 33 KV Bus Isolator clamp for Panther conductor complete with hot dip galvanized nut, bolts and washer as per technical specification.
33 KV Circuit Breaker clamp suitable for Twin Zebra/Moose conductor complete with hot dip galvanized nut, bolts and washer as per technical specification.
33 KV Circuit Breaker clamp suitable for Panther conductor complete with hot dip galvanized nut, bolts and washer as per technical specification.
33 KV CT clamp suitable for Twin Zebra/Moose conductor complete with hot dip galvanized nut, bolts and washer as per technical specification.
33 KV NCT clamp suitable for Panther conductor complete with hot dip galvanized nut, bolts and washer as per technical specification.
33 KV LA clamp suitable for Twin Zebra/Moose conductor complete with hot dip galvanized nut, bolts and washer as per technical specification.
33 KV Bus Post clamp suitable for Panther conductor complete with hot dip galvanized nut bolts & washer as per technical specification.
Bolted type single Tension fitting for Zebra/ Moose Conductor suitable for 1x10 No Disc insulators complete with hardware set as per technical specification.
Bolted type single Tension fitting for Panther Conductor suitable for 1x4 No Disc insulators complete with hardware set as per technical specification.
Bolted type single Suspension fitting for single Zebra/ Moose conductor suitable for 1x10 No Disc insulator with hardware set as per technical specification.
3 Bolted Type PG clamp suitable for Panther to Panther conductor Complete with HDG nut bolt & washer as per technical specification.
4 Bolted Type PG Clamp suitable for Zebra to Zebra conductor complete with HDG nut bolt & washer as per technical specification.
4 Bolted Type PG Clamp suitable for Zebra to Panther conductor complete with HDG nut bolt & washer as per technical specification.
132 KV Bus Post clamp suitable for Zebra conductor complete with hot dip galvanized nut bolts & washer as per technical specification.
Bimetallic terminal connector for 40MVA T/F HV side bushing rod 30 mm dia. made of aluminum alloy LM-6 suitable for ACSR Zebra /Moose conductor of matching with bushing rod complete with hot dip galvanized nut & bolts as per technical specification.
Bimetallic terminal connector for 40 MVA T/F LV side bushing rod 30 mm dia. made of aluminum alloy LM-6 suitable for Twin Zebra /Moose conductor matching with bushing rod complete with hot dip galvanized nut & bolts as per technical specification.
Bimetallic 132 KV CT clamp made of aluminum alloy LM-6 for Zebra/Moose conductor with HDG nut & bolts and washer as per Technical specification.
132 KV Bus Isolator clamp suitable for Zebra /Moose conductor complete with hot dip galvanized nut, bolts and washer as per technical specification.
132 KV Tandom Isolator clamp suitable for Zebra /Moose conductor complete with hot dip galvanized nut, bolts and washer as per technical specification.
132 KV Circuit Breaker clamp suitable for Zebra /Moose conductor complete with hot dip galvanized nut, bolts and washer as per technical specification.
132 KV LA clamp suitable for Zebra/ Moose conductor complete with hot dip galvanized nut, bolts and washer as per technical specification.
Supply of 33 KV bolted type tension fitting for Twin Tarantulla conductor 1x4 No disc insulator with turn buckle complete with hardware fitting d-shackle, d-socket, Ball hook, yoke plate, d-clip it tension clamp etc. as per technical specification.
Supply of 33 KV bolted type tension fitting for Twin Tarantulla conductor 1x4 No disc insulator without turn buckle complete with hardware fitting d-shackle, d-sockete, Ball hook, yoke plate, d-clip it tension clamp etc. as per technical specification.
4 bolted type PG clamp made of aluminum alloy LM -6 with GI Nut , bolts and washer suitable for Tarantulla to Panther conductor as per technical specification.
03 bolted type PG clamp made of aluminum alloy LM -6 with 01 Nut, bolts and washer suitable for Panther to Panther conductor as per technical specification.
4 bolted type PG clamp made of aluminum alloy LM -6 with GI Nut, bolts and washer suitable for Tarantulla to Zebra anther conductor as per technical specification.
4 bolted type PG clamp made of aluminum alloy LM -6 with GI Nut , bolts and washer suitable for Tarantulla to Moose anther conductor as per technical specification.
33 KV LA Clamp for ACSR Panther Conductor Complete with HDG nuts & bolts and washer as per technical specification.
33 KV PT Clamp for ACSR Panther Conductor Complete with HDG nuts & bolts and washer as per technical specification.
33 KV Line Isolator clamp suitable for Twin Panther conductor one side connecting the Panther conductor and another side a plate with 04 Nos. 12mm dia. hole as per technical specification.
33 KV Section Isolator clamp suitable for Twin Tarantulla conductor one side connecting the Tarantulla conductor and another side a plate with 04 Nos. 12mm dia. hole as per technical specification.
Spacer for 250mm spacing suitable for Twin Tarantulla conductor 02 bolted made of aluminum alloy LM-06 complete with hot dip galvanized nut bolt and washer as per technical specification.
Spacer for 60mm spacing suitable for Twin Panther conductor 01 bolted made of aluminum alloy LM-06 complete with hot dip galvanized nut bolt and washer as per technical specification.
Gupta Elect and Engg Works
Meena Elect & Engg. Works
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .