EE(E)/ELD-10/DDA
EE(E)/ELD-10/DDA, B2B, Janakpuri, ND-58.
RMO of Lifts, DG set, Wet riser and Sprinkler system, FA and PA system along with duplex type Talk back system, Common lighting, CCTV system and electrical installations in MS buildings at plot no 1,2,5 and 7A District Centre Janakpuri.
2026_DDA_893958_1
36/EE (E)/ELD-10/DDA/2025-26
Open Tender
Electrical Works
365 days
EE(E)/ELD-10/DDA
Please refer Tender documents.
16 documents required · 16 mandatory
₹0
₹1.6 L
Yes
SE(E)/DWK.
5 Feb 2026
14 Jan 2026
24 Jan 2026
14 Jan 2026
23 Jan 2026
14 Jan 2026
19 Jan 2026
Providing lift operators for rescue & coordination of KONE make lifts as per inventory and terms & conditions attached. (i) Lift rescue operator Gr-II- 3 Nos
Operation & maintenance of DG set, electrical & fire installations / equipment’s,FA& PA system along with duplex type Talk back system and CCTV system as per additional conditions, inventory at annexure A & preventive maintenance schedule at annexure B attached. (i) Wireman Gr-I 1 Nos ( In general shift ) (ii) Pump operator Gr-II - 9 Nos (3 No. In each shift round the clock.) (ii) Khallasi Gr-III -3 Nos (1 No. In each shift round the clock.)
Supplying & replacement of storage type lead acid battery of following rating with minimum 3 year warranty for different DG sets i/c P/F battery cable , thimbles, connections, testing etc. as reqd. a)12 V , 180 AH
Supplying, installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85% ,Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range -15 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, Flicker free, (flicker should be below 5 %), life time (LED,Driver & electrical circuitary), of minimum 50000 Burning Hours with , 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C). Powder coated CRCA sheet Body (Thickness ≥ 0.5 mm).
Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required. 250 Amp
Supplying & Replacement of 3 Pole Power Contactors of following rating in the existing panel board suitable for 415 volt, 50 Hz, 3 Phase AC supply i/c connection testing commissioning etc. complete as reqd. a) 125 Amp,AC-3, Type ML-6
a) 100 Amp, AC-3, Type ML-4
b)45 Amp, AC-3, Type ML-3
Providing and fixing following rating and breakingcapacity and pole MCCB with thermomagneticrelease and terminal spreaders in existing cubiclepanel board including drilling holes in cubicle panel,making connections, Ics=100% Icu and OperationalVoltage 690V etc. as required. a) 250 A,50KA,FPMCCB
b) 200 A,36KA,FPMCCB
c) 125 A,36KA,FPMCCB
Supply and drawing of following sizes of FRLS /HFFR/PVC insulated ,single core copper conductor cable in the existing surcace / recessed steel / PVC conduit as required. a)2x1.5 sq. mm
b)2x4 sq. mm
Dismantling and repairing i/c S/R of following worn out parts of existing 12.5HP clear water pump of kirloskar make suitable for operation on 415 volts , 3 phase ,50 hz ,AC supply i/c re-assembling/re-installation the same, connection with suction and delivery line, valves, testing etc. completed as reqd:- (i) S/R of Pump shaft (SS)- 1 No.
(ii) S/R of Bal bearing - 2 Nos.
(iii) S/R of Gland plate- 2 Set
(iv) S/R of Gland bush- 2 Nos .
(v) S/R of impeller- 1 Nos .
Dismantling and rewinding i/c S/R of following worn out parts of existing 12.5HP kirloskar make Induction motor(for clear water) i/c re-assembling/re-installation the same, connection with suction and delivery line, valves, testing etc. i/c rotor turning,coupling,connection plate etc.completed as reqd:- (i) Rewinding of 12.5 HP motor - 1No.
Supply Installation,Testing and commissioning of 1200 mm sweep,BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85,Air delivery minimum 215 CMM,350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm,suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required.
Servicing of 100/125 KVA DG set (Cummins make engine) i/c supply and replacement of following items testing etc complete as required. i) Oil Filter - 2 Nos ii)Diesel Filter -2Nos. iii) Air cleaner element- 1 set iv) Coolant- 5 ltr v)Battery terminal- 4 Nos. vi)Engine oil-35 ltr
Servicing of 25/40 KVA DG Set (Kirloskar make engine) i/c supply and replacement of following items testing etc complete as required i) Oil Filter -1 No. ii) Diesel Filter -1 set. iii) Air cleaner element-1 set iv) Coolant-3 ltr v) Battery terminal-2 No vi) Engine oil-10 ltr
Repairing of AMF panel of 125KVA//100KVA D.G set with supplying and replacement of following parts i/c connection testing& commissiong etc complete as required. a) panel comlpete wiring with materials-1No b)Battery charger 24 volt -1 No c)Relay 8 pin-2 nos. d)Relay 4 pin-2 Nos e)starter Relay-1 No f) push button -2 Nos. g)panel repairing and servicing charges.
Repairing of AMF panel of 40KVA D.G set with supplying and replacement of following parts i/c connection testing& commissiong etc complete as required. a) panel comlpete wiring with materials-1No b)Battery charger 12 volt -1 No c)Relay 8 pin-2 nos. d)Relay 4 pin-2 Nos e)starter Relay-1 No f) push button -2 Nos. g)panel repairing and servicing charges.
Supply and Replacement of Automatic star delta starter suitable upto 125 HP centrifugal pump sets suitable for 415 volt,50 Hz AC supply,i/c dismantling the Existing damaged/burnt out i/c connection,testing etc completed as required
LED Flood Light, powder coated pressure diecast aluminium (System lumen efficacy ≥105 <120lm/Watt).Supplying, Installation, Testing & Commissioningof Flood Light, powder coated pressure die castaluminium body with built in or separate driver asper the requirement with Driver efficiency>85%, Input voltage: Input voltage: 140-270 Volt AC,frequency 50/60 hz, Operating temp range -5 0C to52 DELHI SCHEDULE OF RATE (E&M) 2025 ,50 0C, internal surge protection of 5 KV L,N,E as perIEC 61000-4-5, Driver efficiency >85%,THD < 10%as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection,EMI-EMC as per CISPR -15, lenses for beamangle 30 deg-120deg as per the application and the project requirement., suitable tilt able fitting, life time(LED, Driver & electrical circuitry) of minimum 50000Burning Hours with 70% of initial Lumen maintained till life ends as per LM80extrapolation IES TM-21-11 report, CCT 3000°K /4000°K / 5700°K /6500°K (As per ANSI Bin) , SDCM(Standard Deviation Color Matching) <5,Maximum power consumption should not morethan the specified rating and Fixture shall be ofrelevant BIS standard complete in all respect i/cexternal connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductorsingle core cable and earthing etc. as required withMinimum 5 year OEM warranty. System lumenefficacy ≥105 <120 lm/Watt output .LM79 & LM80Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape sizeand CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management:heat sink of aluminium housing such that LEDjunction temperature shall not rise above 90°C) a) 150 watt.
Supplying of following size of XLPE aluminum conductor armoured power cable of 1.1 KV grade including providing & fixing thimbles connection,testing etc as required at site .a) 2CX10 sq.mm Size
Laying and fixing of one number PVC insulated and PVC sheathed/XLPE power cable of 1.1 kv grade of following size on wall surface as required.a) UP to 35 sq.mm ( clamped with 1mm thick saddle.)
Dismantling and reparing i/c S/R of worn out parts of existing 3HP Dewatering pump(sewage sub.type/weda type) i/c re-assembling/re-installation the same, connection with suction and delivery line, valves, testing etc. completed as reqd:-
Supplying and fixing 3 inch flexible hosepipe for dewatering pump in basement i/c connection,testing complete as required
Please Enable Macros to View BoQ information
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 2.13 MB
Tendernotice_2.pdf
PDF • 3.08 MB
BOQ_939634.xls
BOQ • 0.65 MB
Download all tender documents and submit your bid