Superitending Engineer, EDC GZB
A-37, Hydle Colony, Kavinagar, Ghaziabad
The following work is to be carried out for attending leakage of power T F HT LT side and badly damaged Radiator with welding providing connector etcof power T F No 1 and 2 at 33 11 kv Farid nagar sub station of EDSD III Modinagar under EDD Modina
2020_PVVNL_497908_1
E-Tender No-21/20-21, EDC GZB
Open Tender
Miscellaneous
Item Rate
Superitending Engineer, EDC GZB
Please refer Tender documents.
3 documents required · 3 mandatory
₹1,180
Superitending Engineer, EDC GZB
₹2,000
Yes
11 Aug 2020
30 Jul 2020
11 Aug 2020
30 Jul 2020
11 Aug 2020
30 Jul 2020
Amount
Opening of jumpers and cable lugs connected to the T/F & drain out of transformer oil from the T/F in to the oil Drums after opening the valve of the tank.
Opening of inspection plate & replacing the damaged packing sheet
Re-fixing of inspection plate with tightening of bolt &nut
Replacement packing sheet of HT side bushing after opening the bolt & nut of bushing re-fixing the packing sheets and Re tightening the same.
Replacement packing sheet of LT side bushing after opening the bolt & nut of bushing re-fixing the packing sheets and Retightening with help of nut and bolt.
Replacement the packing sheet of neutral bushing on the top of T/F after opening the bushing bolts & nut and earthing strip & re-fixing the neutral bushing on the top of the T/F and tightening of the bolt & nut and re -fixing the earthing strip .
Replacement of HT bushing rod made of solid copper /brass with nut bolt and washer.
Replacement of LT bushing rod made of solid copper /brass with nut bolt and washer.
Replacement of HT bushing made of good quality Porcelain Complete with etc packing
Replacement of LT bushing made of good quality Porcelain Complete with etc packing
Dismantling of old broken /damaged radiator with the help of crane re fixing the same after completion of work.
Cartage of damaged radiator up to fabricator shop for welding of damaged radiator and back up to S/S.
Replacement of damage /defective radiator packing .
Replacement of damage /defective radiator valve packing .
Providing and replacement of brass bolted type lugs/ connector for Power T/F.
Tightening of all nut & bolt properly & refilling the T/F oil in T/F up to the oil mark.
Reconnecting the cable lugs HT & LT side & its tightening reconnecting the jumpers & energisation of T/F.
Cleaning the above T/F after completing all works.
Agni Automation and Security
NAVEEN ELECTRICALS
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .