Directorate of Municipal Administration
vishwanath
Shifting of Electric Transformer and electric poles in 2nd cross road Raghavendra badawane at ward no 39 of Mysuru City Corporation limits
DMA/2024-25/EL/WORK_INDENT34959/CALL-2
DMA/2024-25/EL/WORK_INDENT34959/CALL-2
Reserved
Electrical
Electronic Documents, First(One Cover)
DMA City Corporation Mysuru
5 documents required · 5 mandatory
₹500
₹11,950
7 Mar 2025
7 Mar 2025
12 Mar 2025
Shifting of Electric Transformer and electric poles in 2nd cross road Raghavendra badawane at ward no 39 of Mysuru City Corporation limits
Pre-Stressed Tubular Spun Pole - 11 Mtr Long, 500 Kg WL
Erection of 11 Mtr long Concrete Spun Pole in a pit of 2.5 Mtr
depth (Mechanised Labour)
Digging of Pit 2.5 Mtr depth for erection of 11 Mtr long Tubular Spun Pole as per approved Drawing - Ordinary Soil
Three H Frame without Transformer Seating and Seating angle support cross arm for 11 Mtr Spun Pole for 63/100/250/500 kVA (UG Cable) - MS
Labour charges For Three H Frame without Transformer Seating and Seating angle support cross arm for 11 Mtr Spun Pole up to
and including 250 kVA (UG Cable) (excluding erection of Pole)
11 kV, Special 3 Pin Cross Arm - GI
Fixing of V-Shape/Horizontal cross arm including Single Top
Support Brace and Insulator fixing
HT ST Support 50x8 mm Flat - GI
Fixing of HT/LT Single Top Support
11 kV, 5 kN Composite/Polymeric Pin Insulator (24 mm dia FRP Rod)
11 kV, 45 kN Polymeric Insulator
11 kV, 200 Amps Single Break GOS
Fixing of GOS including wiring (11 kV Single Break 200
H - Frame Set for fixing 11 kV, 200 Amps Single Break GOS - (For DP structure for providing New GOS for sectionalisation) - MS
Labour charges for Erection of H-Frame
ACSR Conductor as per IS-398 (Part - 2/1996) - Rabbit ACSR (6/3.35 mm Al + 1/3.35 mm St), Std Wt: 214 Kg/KM
Labour charges for Stringing of Rabbit ACSR conductor, binding of conductor on each insulator and dead ending on strain or disc/strain insulator by means of clamps
Transparent Alkathine tube 19 mm dia, 2 mm thick in coils of 30 Mtr
11 kV, 3 Core, XPLE HT UG Cable with pressure extruded inner sheeth, ROUND WIRE ARMOURED as per IS-7098 (Part-2) Armouring wires dia and Resistivity as per IS-3975 -- 95 Sqmm, (54 GI Wires - 2.5 mm ...
Laying of cable in Existing Trench/GI pipe/Stone Ware/RCC Hume pipe using Wooden/Aluminum Rollers as directed by the departmental staff - HT Cable - 3x95 to 150 Sqmm
Heat Shrinkable Outdoor Type Cable Termination Kit for XLPE Cable - 3x95 Sqmm
Labour charges for Heat Shrinkable Outdoor Type HT Cable Termination Kit - 3x95 to 3x150 Sqmm
11 kV, 3 Core, XPLE HT UG Cable with pressure extruded inner sheeth, ROUND WIRE ARMOURED as per IS-7098 (Part-2) Armouring wires dia and Resistivity as per IS-3975 -- 240 Sqmm, (55 GI Wires - 3.15 ...
Laying of cable in Existing Trench/GI pipe/Stone Ware/RCC Hume pipe using Wooden/Aluminum Rollers as directed by the departmental staff - HT Cable - 3x185 to 240 Sqmm
Heat Shrinkable Straight Through Jointing Kit for XLPE Cable with Copper Lug & Al Ferrule - 3x240 Sqmm
Labour charges for Heat shrinkable Straight Through Jointing kit for HT UG cable - 3x185 to 3x240 Sqmm
Heat Shrinkable Outdoor Type Cable Termination Kit for XLPE Cable - 3x240 Sqmm
Labour charges for Heat Shrinkable Outdoor Type HT Cable Termination Kit - 3x185 to 3x240 Sqmm
Cable Covering Tile 125x250x40 mm
Labour charges for Covering cable with Tiles
Providing M-Sand : Supplying and filling in plinth, foundations / UG cable work with approved M-sand including watering, ramming, consolidating and dressing. The rate includes the cost of material, la...
Earth work excavation for Foundation by mechanical means for all works & depth upto 3 m, as per drawing and technical specifications, including setting out, shoring, strutting, barricading, caution li...
Providing, laying and jointing HDPE pipes of specified grade and
conforming to IS 4984-2016 with latest ammendments and conveying to work site including loading and unloading at both destinations and ...
Providing, Laying and Fixing of GI pipes conforming to IS 1239:1990 with latest amendments complete with GI fittings (excluding the cost of fittings) with cuts and threads wherever necessary, includin...
Route & Joint indicating slab with MS Anchor rod
Labour charges for Fixing of Route & Joint Indicating Slab
Guy Wire & GI Wire as per IS-2141 -- 8 SWG GI Wire (4.064 mm Dia), Std Wt: 131 Kg/KM
Supplying, fixing, wiring, earth electrode for grounding conduits, I.C. cutouts and other equipment's on the meter board using 40mm dia 2.90mm thick GI pipe 2.5 mtr long buried in a pit. The pit shoul...
1.1 kV Ceramic Pin Insulator (Shell only)
1.1 kV GI Pin for 1.1 kV Ceramic Shell Insulator
No. 8 Strain Insulator
1.1 kV, LT Aerial Bunched Cable, XLPE insulation confirming to IS-14255: 1995 -- 3x95 + 1x70 + 1x16 Sqmm Street light (Insulated Messenger cum Neutral)
Labour charges for Stringing of 1.1 kV grade Aerial Bunched 3 Core cable of XLPE insulation of size (3x95) (Phase Conductor) + (1x70) (Insulated Messenger Neutral) + (1x16) (Street Light Control)
Releasing & reerection of LT Distribution Box for 250 kVA DTC (Excluding wiring)
Releasing & refixing of LT Metering Box with clamping arrangement for mounting on the Transformer structure with necessary terminal strip and CT mounting arrangement for housing the ETV Meters and co...
Releasing & restringing of Rabbit ACSR conductor, binding of conductor on each insulator and dead ending on strain or disc/strain insulator by means of clamps
Releasing of RCC/PSCC Pole of 9 to 10 Mtr long in a pit of 1.8 Mtr depth
Digging of Pit 1.8 Mtr depth for errection of 9 to 10 Mtr Long Steel/RCC/PSCC supports as per approved Drawing. - Ordinary Soil
Erection of RCC/PSCC Pole of 9 to 10 Mtr long in a pit of 1.8 Mtr depth
RCC Pole - 9 Mtr Long, 145 Kg WL
Releasing & re-erection of 100 kVA Transformer
Suspension Clamp Assembly 16 to 70 Sqmm Bare Messenger (Exclusive of Pole Clamp and Eye Hook)
Labour charges for Erection of Suspension Clamp - 25 to 95 Sqmm bare/Insulated messenger
Pole Clamp for HT/LT AB cable
Labour charges for Pole Clamp for HT/LT AB cable
Eye Hook (Flat Type) for fixing Clamp
Dead End Clamp/Anchor Clamp Assembly 25 to 95 Sqmm Bare Messenger(Exclusive of Pole Clamp and Eye Hook)
Universal Hook and Bolt & Nut
Labour charges for fixing of Universal Hook
End Cap for 50/70 Sqmm
Labour charges for End Cap for 50/70 Sqmm
Releasing of 11 Mtr long Concrete Spun Pole in a pit of 2.5 Mtr
depth (Mechanised Labour)
Releasing of V-Shape/Horizontal cross arm including Single Top
Support Brace and Insulator fixing
Releasing of Single Pole Mounted Transformer Structure For 100 kVA
Releasing of Rabbit ACSR conductor, binding of conductor on each insulator and dead ending on strain or disc/strain insulator by means of clamps
Releasing of GOS including wiring (11 kV Single Break 200
Providing and laying in position Cement Concrete for levelling course for all works in foundation. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes...
Providing Size Stone masonry with hard stone in foundation & plinth with Cement mortar 1:6 (1 cement : 6 coarse sand)
Providing 20 mm cement plaster with cement mortar 1:3 (1 cement: 3 coarse sand) finished with a floating coat of neat cement to brick/stone masonry including rounding off corners wherever ...
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
Indent 34959 CALL-2.doc
Tender Document • 0.98 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .