Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹21.2 LAccepted-AOC BASUDEBPUR BELKHALI HOWRAH PIN 711 322 | HOWRAH | HOWRAH | WEST BENGAL | 711322 | L1 | Accepted-AOC BEING L1 | |
| 2 | L2₹36.2 L+₹1.1 L (3.24%)Rejected-Finance 7A BENTINCK STREET KOLKATA 700 001 | KOLKATA | KOLKATA | WEST BENGAL | 700001 | L2 | Rejected-Finance Being L2 is rejected | |
| 3 | L3₹36.8 L+₹1.7 L (4.83%)Rejected-Finance | L3 | Rejected-Finance Being L3 is rejected | |
| 4 | L4₹37.5 L+₹2.4 L (6.85%)Rejected-Finance 12 1 FERRIGHAT ROAD P O BHATPARA DIST NORTH 24 PGS WEST BENGAL PIN 743123 | BHATPARA | NORTH 24 PARGANAS | WEST BENGAL | 743123 | L4 | Rejected-Finance Being L4 is rejected |
Tender Value
Refer Docs
EMD Value
₹85,746
Closing Date
5 Jun 2025, 12:00 pmClosed
EE/DED
Opposite of PWD Inspection Bungalow Kachari Road, Siliguri 734001, District Darjeeling
Construction of Cancer Care Centers at North Bengal Medical College and Hospital, Siliguri under North Bengal Construction Division-- SITC of Intelligent addressable fire alarm System.
2025_WBPWD_847794_1
WBPWD/EE/DED/e-NIT- 05 of 2025-26
Open Tender
ELECTRICAL WORKS ORG
Item Rate
180 days
SILIGURI
Please refer Tender documents.
4 documents required · 4 mandatory
₹85,746
15 Oct 2025
17 May 2025
9 Jun 2025
17 May 2025
5 Jun 2025
17 May 2025
Amount
SITC of Microprocessor based Intelligent, addressable 10 Loops ( Expandable upio 12 loops ) fire alarm control panel ( VDS / UL / FM / ULC approved ) fully networkable with each loop capable of taking 12O devices, 1/4 VGA display character alpha-numeric liquid crystal display.The panel shall be soft addressable type.The panel shall be able to give pin point location of all frre/ fault conditions. Further, the panel must be able to automatically switch off respective control switches when ever any alarm is triggered.The Panel should be able to store sufficient numbers of log events in its Memory as per recommended standards. IS / NBC. Shiuld have the provision for incorporating with BMS
The panel shall have in built rectifier, provision for external & internal printer ( if required ), Loop cards, L C D unit to indicate Fire/Fault Signal with address and analog output, complete in all respects, in built Surge protection facility, integral SMF lead acid batteries with sealed cells of 24 V capable of running for 24 hours normal working and then be capable of operating the system for 30 minutes during Emargency condition, with integral battery charger complete as required.
The FACP shall be capable of being networked ( future expansion ) with other similar FACP located at different part of the premises through single RS 485 bus.The FACP shall have provision for interfacing with the public address system and BMS( RS 485 ). The panel should have modbus output & ready to communicate with remote computer. The system must be preloaded with licenced software. (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward /Secutron/ Securiton/ Apollo /Morley / System Sensor )
SITC of Analog Addressable Intelligent multisensor detector (VDS / UL / FM / ULC approved ) with inbuilt optical smoke sensors as well as additional heat detector sensor with decentralise intelligence, soft addressable Photothermal type with inbuilt fault isolator as per NFPA style 7 wiring complete with base having IP as per recommended standard.(Note : Detectors without built-in fault isolator is also acceptable but in such case the contractor shall provide one independent fault isolator module for every group of addressable devices ( Numbers of addressable devices in a group will be as per latest recommended IS / NBC ) without any additional cost). (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward /Secutron/ Securiton/ Apollo / Morley / System Sensor )
SITC of Addressable Heat Detector (Fixed temperature cum rate of rise) ( VDS / UL / FM / ULC approved ) with twist lockable removal base, built - in fault isolator, drift compensation feature etc including connections as per specifrcations complete as reqd and having IP as per recommended standard(Note : Detectors without built-in fault isolator is also acceptable but in such case the contractor shall provide one independent fault isolator module for every group of addressable devices ( Numbers of addressable devices in a group will be as per latest recommended standards ) without any additional cost). (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward /Secutron/ Securiton/ Apollo / Morley / System Sensor )
SITC of Addressable Manual Call Point ( VDS / UL / FM / ULC approved )soft addressable type with in built fault isolator as per NFPA style 7 wiring complete as required. (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward /Secutron/ Secrrrifnn / Anollo / Morlew / Swsfern Sensor)
SITC of Addressable Loop Powered Hooter ( sound output of minimum 90 db ) cum strobe (strength of light 10 cd)complete with inbuilt isolator & IP65 base and ( VDS / UL I FM / ULC approved) approved. (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward /Secutron/ Securiton/ Apollo / Morley / System Sensor )
SITC of Addressable transponder/ Monitor Modules ( VDS / UL / FM / ULC approved ) for monitoring flow switches/Fire exit doors / AHU / Lift etc complete as required. Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward /Secutron/ Securiton/ Apollo / Morley / System Sensor)
SITC of Addressable Relay Modules (VDS / UL & FM approved) for switching / integration of Lift / AHU etc complete as required. (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward /Secutron/ Securiton/ Apollo / Morlev / Svstem Sensor )
SITC of LED type Response Indicator ( VDS / UL / FM / ULC approved) having 2 Nos. red coloured LED lamps including connections etc. (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward /Secutron/ Securiton/ Apollo I Morley I System Sensor )
SITC of Repeater Panel ( VDS / UL / FM / VLC approved) which will act as an add-on device for remote display of FACP status information of the FDA operating front related to the detectors and decetors zones.Event messages are displayed via LED collective indicators and on the 2-Line LCD display with the associated detecors zone number and a programmable additional text. Each message is signalled via the built-in buzzer. the buzzer can be acknowledged by pressing a button. The requisite LCD indicator panel can be operated on as RS 485 bus. (Approved Make: Esser/Cerberus pro/ Bosch/ Johnson Controls/ Notifer / Edward /Secutron/ Securiton/ Apollo / Morley / System Sensor)
Supplying, Installing, Testing & Commissioning of conventional type been (infra-Red Light) detector (VDS / UL / FM / ULC approved) with long range projected Beam consist of separate transmeter & receiver, having input module for individual addressing of the detector, as required for high hight application. (Approved Make: Cerberus pro/Jhonson control/ Bosch/System Sensor)
SITC of Power supply 23OV AC to 24V DC with all other accessories. (Make: Reputed)
Supply & Laying of 2 Core 1.5 sq.mm FRLS shielded copper Cable (For Loop) (Make. Finolex/RR Kable/Polycab ) with 20 mm NB PVC rigid conduit pipe(Make: Precision /AKG / ATUL / VIP / Universal / BEC/Polycab) on the surface of the wall.
TERMS & CONDITIONS a.The Fire Alarm system shall comply with latest requirements of - 1. National Fire protection Association (NFPA) Standards. 2. IS 21.89 3. NFPA 70 National Electric Code 4. NFPA 72 National Fire Alarm Code 5. local Statutory Regulations 6. Manufacturer Recommendation.
b. TESTS:l.The system shall be tested and commissioned by a qualifred competent,trained engineer or technician authorized by the manufacturer of the fire alarm equipment to technically supervise and participate during all of the adjustments and tests for the system. 2. Before energizing the cables and wires, check for correct connections and test for short circuits. ground faults, continuity, and insulation and other tests as per above standards must be done.
c. Auto CAD Drawing of whole FDA system & submission of 5 et hard copy of drawing and soft copy (in Auto-CAD format) is to be submitted.
d. The Agency must procure the materials from the Manufacturer / OEM or from their authorised sales channel so that the standard warranty / support of the Manufacturer / OEM becomes applicable to the oroducts to be delivered and installed bv them.
e. Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution, of work/submission of bill.
f. If any refurbished material is supplied and installed, penal action will be taken as per existing rules
PERFECT IMAGE SOLUTIONS (BID ID -6449466)
MAM ENTERPRISE (BID ID -6458623)
Creative Projects (BID ID -6491818)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .