Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹22.7 LAccepted-AOC 25 A BR SAMY LANE KATTOOR COIMBATORE 641009 | COIMBATORE | COIMBATORE | TAMIL NADU | 641009 | L1 | Accepted-AOC Being L1 Bidder | |
| 2 | L2₹24.9 L+₹2.1 L (9.44%)Rejected-Finance CHEMBISSERY PUTHIYAKAVU TRIPUNITHURA P O KOCHI 682301 | ERNAKULAM | KERALA | 682301 | L2 | Rejected-Finance Being Not L1 Bidder | |
| 3 | L3₹30.5 L+₹7.8 L (34.2%)Rejected-Finance | L3 | Rejected-Finance Being Not L1 Bidder |
Tender Value
₹24 L
EMD Value
₹48,000
Closing Date
22 Jun 2022, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE DSSC
GE DSSC WELLINGTON BARRACKS-POST, WELLINGTON, THE NILGIRIS, TAMIL NADU,PIN-643231
PROVN OF HT 11 KV INTERCONNECTION BETWEEN (RING MAIN) BETWEEN GORKHA CAMP SUB STN AND SUB STN NO-18 INCL CONNECTED WORKS AT DSSC WELLINGTON
2022_MES_524582_1
8243/E8
Open Tender
Civil Works
Item Rate
120 days
WELLINGTON
PLEASE REFER TENDER DOCUMENTS AND NIT
8 documents required · 8 mandatory
₹500
GE DSSC WELLINGTON
₹48,000
Yes
29 Jun 2022
17 May 2022
24 Jun 2022
17 May 2022
22 Jun 2022
31 May 2022
60 days
Amount
Supply, install, commissioning testing of Outdoor Type with Motorized mechanism, right side extensible Ring Main Unit comprising of 2 I/C + 2 O/G with Vacuum Circuit Breakers of Nominal Voltage - HT 11 KV, 630 A, 50 Hz, 21 KA rms for 3 Sec, rated lightning withstand voltage - 75 KVp, rated power freq withstand voltage - 28 KV rms for 1 Min, rated peak current - 50 KA all as specified & as directed with & incl the following items/specifications : MAKE : SCHNEIDER/ABB/SIEMENS
(a) Each Module of HT Compartment function unit must comprise of a Vacuum Circuit Breaker in combination with a three-position-switch. The three-position-switch must fulfill the operations of disconnector function & earthing function. (b) Details of items/eqpts in each Module of HT Compartment function is as follows : (i) Vacuum Circuit Breaker, 11 KV, 630 A, 21 KA of make SCHNEIDER/ABB/SIEMENS. (ii) Integrated manually operated earth-switch. (iii) Self powered Electronic Numerical Protection Relay providing Over-Current & Earth-Fault Protection of Make C&S (CSPR or CSDPR Relay) or techno-commercially equivalent. (iv) 03 Nos of Ring Core type CTs of protection ration 50-25/1+1A, AC of Class : 10P10-5P10, Burden : 2.5VA (v) Capacitive Voltage Indication, fixed type : LED Display. (vi) ON, OFF, Earth Indication on the front mimic of the panel. (vii) Cable Box for termination of HT 11 KV (E) UG Cable upto 1 x 3C x 300 Sqmm. (viii) Standard cable cover. (ix) Shunt Trip Coil - 24V DC. (x) Set of 2 NO + NC Contacts. (xi) Emergency Trip Push Button. (xii) Set of 11 KV Boots.
NOTE: (i) Design/drawing/BOM of the RMU showing the dimensions is to be obtained from OEM / Auth Supplier & is to be got approved from the GE & Engr-In-Charge before placing final order to the manufacturer. (ii) Quoted rate is deemed to be inclusive of Factory Inspection/Testing of the RMU before dispatch by an E/M Officer nominated by the Accepting Officer (iii) Anything missed out in the technical specifications but technically required for efficient working is deemed to be included in the quoted rates. (iv) The complete installation, commissioning & testing of the RMU Panel is to be got done from the OEM or their auth Rep/Sister Concern/Channel Partners only. (v) Necessary PCC foundation/plinth shall be as per the recommendations of OEM & cost of the same is deemed to be included in the quoted rates.
M & L for earthing complete with Galvanised steel earth plate electrode 600mm x 600mm x 6 mm thick buried directly in ground (in vertical position) earth pit not less than 2.25 mtr below normal ground level with the top edge of the earth plate not less than 1.5 mtr (B.G.L.) and connected to GI earth strip 32 x 6 mm by means of bolts, nuts, check nuts, and washers of galvanized iron including PCC pit & cover with suitable handle, including necessary excavation and earth work in any type of soil, 20 mm dia medium grade galvanized steel tube for watering with one end fixed with suitable funnel and wire mesh, 40 mm bore medium grade galvanized steel tubing for drawing earth lead GI strip protection & common salt, charcoal in alternate layers etc. complete all as shown in EP No 3 of SSR Part 1 and testing on completion complete all as specified and as directed by the Engr-in-Charge/GE. Note:- On testing after completion, if the desired earth resistance is not obtained the earthing will be redone to the entire satisfaction of Engr-in-Charge at no extra cost.
M & L for laying earth continuity conductor or main earthing lead of 32 x 6 mm galvanised iron strip, fixed to wall on batten or recess or chasses or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc, as required complete all as specified and as directed.
Supply, laying, jointing & testing XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) with stranded aluminum conductor, 11000 volts grade (Earthed), of size 95 Sqmm, 3 core in trenches / through GI pipe / fixed along with pole structure etc complete all as specified & as directed. Make : HAVELLS/GLOSTER/FINOLEX. Note : Necessary earthwork etc. shall be measured & paid separately under relevant items of work.
Supply and fix cable jointing kit for 11 KV (Earthed) grade cable for OUTDOOR termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured Al conductor cable of size 95 Sq mm complete all as specified and as directed. Make : RAYCHEM/M-SEAL/BIRLA-3M.
M & L for GI pipe light grade with all running fittings (ISI Marked), laid in trenches, under road or fixing on wall/pole/crossing drain/nallah etc. of bore 80 mm complete all as specified and directed. Make : TATA/JINDAL/PRAKASH. Note : Wherever GI Protection pipes are to be placed/fitted above earths surface, cost of necessary clamping/fixing arrangements to the entire satisfaction of Engr-in-Charge is deemed to be included in the unit quoted rates.
M & L for cutting the existing hardstanding /PCC /WBM road at a depth of not less than 75 cm & 30 cm in width for passing of HT cables through GI pipes, returning filling in, complete incl finishing the surfaces by providing cement concrete type B1 (1:2:4) with 20 mm graded aggregate upto 20 cm, finishing to a uniform smooth surface complete all as specified and as directed.
Note for Item Nos 6, 7 & 8 : Any damages made to the existing services of MES/WCB/TNEB/Other Depts like HT/LT UG cables, Water Supply/Sewage Pipe lines, OFC/BSNL/ITRC/Signal communication cables etc. during the excavation/boring/road cuting etc. progress of the work shall be made good with proper jointing kits etc. as per original to the entire satisfaction of Engr-in-Charge & GE & the cost of the same is deemed to be included in the unit quoted rates. Decision of the AO shall be final & binding in this matter.
Excavation in trenches n.exc 1.5m wide and n.exc 1.5m in depth for laying of pipe and getting out in hard/dense soil complete all as specified and as directed.
Returning, filling in including spreading, levelling, watering and well ramming in layers n.exc 25cm thick with excavated soil complete all as specified and as directed.
Removing of excavated material (soil) to a distance n.exc 50m and depositing where directed at a level n.exc 1.5m above the starting point complete all as specified and as directed.
M & L for providing sand cushioning for protection of UG cable in trenches with Coarse River Sand/ Riddled Earth of approved quality as approved in writing by GE including filling, spreading and punning down to desired thickness complete all as specified and as directed.
Supply and laying un-reinforced precast concrete cable cover, class HV, Type 1, flat, size 300 x 180 x 40 mm in trenches for protection of UG Cable with width equal to length of PCC cover, laid dry & flat complete all as specified & as directed. Make : Mehtab/Supreme Tiles/Sukhi Enterprises.
S & F Pin type, porcelain, vitreous, brown insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 150 mm height, 150 mm dia suitable for 11000 volts grade complete all as specified and as directed. MAKE : BHEL/JAYSHREE/MEI
S & F lightening arrester non-linear metal oxide type, complete with all fittings, transmission/ distribution class, discharge capacity 65 Kilo amps suitable for 11 KV out door type including necessary connection and fittings all as per IS-3070 Part-III and IEC 1994 including dismantling of old unsv lightening arrestor including strap bolts, nuts and washers etc. complete all as specified and as directed. Make : ELPRO/OBLUM/BHEL/CG
M & L for swing out expulsion fuse single pole (Drop Out Fuse) with fuse carrier , fuse element mounted on insulator & fitted on steel frame etc for 11000 volts of capacity 25 amps complete all as specified and as directed. MAKE : JAIPURIA BROS/BHEL/PACTIL/MEI
M & L for switch air break, gang operated (GOD), out door type, triple pole, HT 11 KV, 400 Amps, vertical type with 9 insulators mounted with fixed contacts of phosphor bronze and moving contacts of copper, manually operated from ground level with operating mechanism including mild steel galvanised medium grade 25mm bore single length operating rod, pad locking arrangement incl making necessary jumper connections with & including PVC flexible connection pipes duly wrapped colour insulation tapes etc. complete all as specified and as directed. MAKE : JAIPURIA BROS/BHEL/PACTIL/MEI
M & L for cross arms bracings supports, clamps and back plates fabricated from structural steel sections incl nuts, bolts, washers welding, bending cold or hot, drilling holes for bolts in any shpae or size as indicated or directed and inclusive of one primer coat of red oxide zinc chrome primer and two coats of aluminium paint incl preparation of surfaces complete all as specified and as directed.
M/s.Rejoy Constructions
Saket Enterprises
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .