Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹46.5 LAdmitted-Finance | L1 | Admitted-Finance | |
| 2 | L2₹47.3 L+₹75,050.36 (1.61%)Admitted-Finance | L2 | Admitted-Finance | |
| 3 | L3₹52.1 L+₹5.5 L (11.9%)Admitted-Finance | L3 | Admitted-Finance | |
| 4 | L4₹54.3 L+₹7.7 L (16.6%)Admitted-Finance 145 1 0 NEAR OLD LIC SHIV NAGAR VILLAGE TOWN MODIPURAM CITY MEERUT MEERUT UTTAR PRADESH 250110 INDIA | MEERUT | UTTAR PRADESH | 250110 | L4 | Admitted-Finance | |
| 5 | L5₹63.8 L+₹17.3 L (37.1%)Admitted-Finance | L5 | Admitted-Finance |
| Sl No | Description | Qty | Unit | Nichi Manufacturing Private Limited L1 | M/S RAGHAV and BROTHERS L3 | Perennial Contractors Pvt. Ltd. L6 | Raj Engineers L2 | Shiva Electricals Company L5 | Hi-tech power transmission L4 |
|---|---|---|---|---|---|---|---|---|---|
| 1.00 | Renovation/Repairing of old T/F Plinth | 3 | Job | 97,500 ₹1,15,050 | 1,95,000 ₹2,30,100 | 1,35,000 ₹1,59,300 | 60,000 ₹70,800 | 45,000 ₹53,100 Lowest | 1,20,000 ₹1,41,600 |
| 2.00 | Temparary power T/F. Plinth for 10 MVA T/F. | 2 | Job | 40,000 ₹47,200 | 64,000 ₹75,520 | 3,00,000 ₹3,54,000 | 1,10,000 ₹1,29,800 | 30,000 ₹35,400 Lowest | 44,000 ₹51,920 |
| 3.00 | Safe carriage of Following Item from any store Centre (Under Juridiction fo PVVNL) to Site Store with loading & unloading at both ends respectively 11 KV V.C.B. (Outgoing) 200/100/5A, 350 MVA | 3 | No | 10,500 ₹12,390 Lowest | 10,500 ₹12,390 Lowest | 22,500 ₹26,550 | 21,000 ₹24,780 | 16,500 ₹19,470 | 15,000 ₹17,700 |
| 4.00 | 33 KV VCB 800/ 1250 Amp, 750 MVA with Steel Structure | 4 | No | 28,000 ₹33,040 | 18,000 ₹21,240 Lowest | 30,000 ₹35,400 | 40,000 ₹47,200 | 22,000 ₹25,960 | 20,000 ₹23,600 |
| 5.00 | 11 KV VCB 600/300/5A & 1200/600/5 Amp I/C 350 MVA | 3 | No | 10,500 ₹12,390 Lowest | 10,500 ₹12,390 Lowest | 22,500 ₹26,550 | 30,000 ₹35,400 | 16,500 ₹19,470 | 15,000 ₹17,700 |
| 6.00 | Control panel I/C for 33 KV Double T/F | 4 | No | 10,000 ₹11,800 Lowest | 20,000 ₹23,600 | 30,000 ₹35,400 | 40,000 ₹47,200 | 22,000 ₹25,960 | 20,000 ₹23,600 |
| 7.00 | 11 KV Bus Coupler | 1 | No | 3,000 ₹3,540 | 6,000 ₹7,080 | 7,500 ₹8,850 | 6,000 ₹7,080 | 5,500 ₹6,490 | 2,000 ₹2,360 Lowest |
| 8.00 | 33 KV C.T 400/200 1A, 200/100/1A | 24 | No | 31,200 ₹36,816 Lowest | 48,000 ₹56,640 | 72,000 ₹84,960 | 69,600 ₹82,128 | 1,32,000 ₹1,55,760 | 48,000 ₹56,640 |
| 9.00 | 11 KV 3×300 mm2 XLPE Cable | 220 | Mtr | 8,800 ₹10,384 | 6,600 ₹7,788 Lowest | 11,000 ₹12,980 | 15,400 ₹18,172 | 18,700 ₹22,066 | 22,000 ₹25,960 |
| 10.00 | 11 KV 3×185 mm2 XLPE Cable | 180 | Mtr | 7,200 ₹8,496 | 3,600 ₹4,248 Lowest | 9,000 ₹10,620 | 12,600 ₹14,868 | 15,300 ₹18,054 | 18,000 ₹21,240 |
Tender Value
₹86.5 L
EMD Value
₹88,000
Closing Date
15 Sept 2025, 3:00 pmClosed
Superintending Engineer
Electricity Construction and Works Circle-II, Room No. 125, Urja Bhawan, Old Building, P.V.V.N.L., Victoria Park, Meerut
Increasing Capacity of Substation Kankerkhera Town, Substation Sofipur, Substation Maliyana , Mohakampur in District Meerut under Business Plan 2025-26
2025_PVVNL_1069875_1
05/ECWC2/MRT/2025-26
Open Tender
Electrical Works
Lump-sum
90 days
Meerut
Please refer tender Notice and Tender documents
3 documents required · 3 mandatory
₹3,540
Payable to E.E.E.C.W.D., Meerut
₹88,000
10 Oct 2025
30 Aug 2025
17 Sept 2025
30 Aug 2025
15 Sept 2025
30 Aug 2025
Renovation/Repairing of old T/F Plinth
Temparary power T/F. Plinth for 10 MVA T/F.
Safe carriage of Following Item from any store Centre (Under Juridiction fo PVVNL) to Site Store with loading & unloading at both ends respectively 11 KV V.C.B. (Outgoing) 200/100/5A, 350 MVA
33 KV VCB 800/ 1250 Amp, 750 MVA with Steel Structure
11 KV VCB 600/300/5A & 1200/600/5 Amp I/C 350 MVA
Control panel I/C for 33 KV Double T/F
11 KV Bus Coupler
33 KV C.T 400/200 1A, 200/100/1A
11 KV 3×300 mm2 XLPE Cable
11 KV 3×185 mm2 XLPE Cable
ACSR Panther/Dog Conductor
PCC 11 mtr.
Heavy Stock Material
11 KV Cable jointing kit 3x300mm outdoor heat
11 KV Cable jointing kit 3x300mm indoor heat
11 KV Cable jointing kit 1x185 mm outdoor heat
11 KV Cable jointing kit 1x185 mm indoor heat
24 Volt Battery & Battery Charger
33 KV Fuse set
33 KV Bus Isolator
33 KV Disc Insulator Polymeric
33 KV Disc Fitting 70 KN
11 KV Disc Insulator Polymeric
11 KV Disc Fitting 45 KN
Earthing of pole by MS Earthing rod 20x2500 mm
Stay Set Complete
11 KV Polymeric pin Insulator
33 KV Line Isolator
11 KV XLPE cable 1x1000sqmm
11 KV Cable J/Kit O/D for 1x1000 sqmm
11 KV Cable J/Kit I/D for 1x1000 sqmm
1600/5A I/C VCB with bus bar 1600 Amp
Painting of Structures Painting of the following structure with one coat of ready mixed primer and two coats of ISI Mark Aluminium paint after rubbing with sand paper to the surface of the structure including labour and T&P complete in all respect. Terminal Gantry/Bus Bar Gantry/Line Isolator/Bus Isolator/Post Insulator/Fuse Set/C.T.s/P.T.s/L.A.'s structures etc.
Hiring of D/G Set including carriage, loading, unloading & operating charges (with fuel) at 33/11 KV Substation under construction in case L.T. supply is not available near S/S within prescribed accessible limit. 63 KVA, 3 Phase D/G Set for testing of equipment installed at Substation
Dismantling of Existing 5 MVA/10 MVA Transformer (Control cable, Earthing, 11 KV bus bar, power cable, cable stand, Nutral Stand, Rediators, Conervator & Draining oil from Rediators filig in the dreams and other to be done as neccesary.
Safely Shifting of 5MVA/ 10 MVA Transformer from Plinth and kept side in Switchyard at suitable place with all accessories
Installation of 33/11 KV, 5 MVA/ 10 MVA/ 20 MVA Transformer : Shifting of available 5MVA/10 MVA/20 MVA 33/11 KV, Transformer to transformer plinth in Switch Yard.
Erection of shifted Transformer at plinth by fixing all accessories like radiators, conservator tank, filling the transformer oil to desired level and ensuring that there is no leakage, complete job in all respect.
Boring and lowering of G.I. Pipe size 32 mm dia. into the ground up to water level with the lower end of solid copper cone Approx 225mm long and 750 gm in weight shall be provided and screwed in pipe as well as bringing out a continuous copper wire 6 SWG from the cone up to the ground surface where it will be bolted to the M.S. earth Strip for Transformer neutral connection, the earth strip will be welded to the G.I. pipe and neutral earthing support.
Fabrication and erection of neutral earthing L Type support made of size 100×50mm. Structure shall be 5.3 Mtr. long with 1 Mtr. Arms. Structure shall be grouted in ratio 1:3:6 in block size 300×300×700mm and painted with one coat of Ready Mixed primer and Two coat of enamel Aluminum paint work includes connecting neutral bushing rod of power Transformer and M.S. Earthing strip with the help of flexible copper bond, M.S. Bolt and washer. Including Providing of MS Channal (125x65x6, 100x50x6), MS Angle (65x65x6), Earthing Strip (50x6), Copper bond, MS Nuts bolts & Providing other accessories it required.
Fabrication and erection of cable support made of two pieces of M.S. Channel (100×50×6) mm, 3.75 meter long, joined to each other by means of 5 Nos. M.S. Flat (50×6)mm pieces of size 600 mm long each by welding at equal intervals and grouting in a block of size (300×300×700)mm in CC 1:3:6 complete with one coat of ready mixed primer and two coats of Al. paint. Work includes providing of three Nos. M.S. clamps made of (50×6)mm M.S. Flat for holding the cable including nuts and bolts. Including Providing of MS Channal (125x65x6, 100x50x6), MS Angle (65x65x6), Earthing Strip (50x6), Copper bond, MS Nuts bolts & Providing other accessories it required.
Fabrication and grouting of M.S. frames 4.60 mt. long for support of copper Bus Bar. Bus Bar will be provided in L.V. Side of Power transformer. The M.S. frame shall be made of M.S. channel (100×50)mm in 'T' shape. Providing 2 Nos. support of M.S. Angle iron (50×50×6)mm, 0.60 mt. long below the top channel, drilling of 3 Nos. hole on the top channel for fixing of 11 KV pin insulator/post Insulator. The work also includes the fixing of 3 Nos. 11 KV pin/post insulator with pin and binding the copper Bus Bar with the pin/post insulator by Aluminum binding wire in complete. Including Providing of MS Channal (125x65x6, 100x50x6), MS Angle (65x65x6), Earthing Strip (50x6), Copper bond, MS Nuts bolts & Providing other accessories it required.
Providing & Fixing of copper bus bar size (2500x75x6)mm for transformer & cable Connection with providing empire tape and HT Tape for proper insulation work (approx 2 Mtr each)
H.T. Power Cable Laying : Laying 11 KV, (3×300) mm2/(3×185)mm2 /1x1000 mm2 XLPE, Cable from power transformer to 11 KV Incoming switch gear in the cable trench 0.45 m wide, 0.90m depth. Providing 150 mm local sand for cushion beneath and 150 mm above the cable (quantity of local sand required 0.375 cubm/m in length). Making of Chulla for safely laying of cable at incoming switchgear end. The cable shall be duly protected by brick. On both side of cable by laying brick vertically and bricks would also be laid horizontally on top of vertically laid bricks along the cable (minimum 18 Nos. of bricks are to be laid top and outer side along the cable. The work includes digging of trenches, laying of cable in under ground trenches, joining of terminal's, back filling of earth and testing and commissioning of power cable etc. Spare cable shall be left over and laid in the trenches in shape of 6m ring at both ends.
Laying and dressing of 11 KV 3×300 mm2/3×185 mm2 /1x1000 mm2 power cable in air/Trench.
Preparation of 11 KV Power Cable ends : Making of 11 KV XLPE Heat shrinkable out door jointing kits after duly plumbing and taping of cable, providing, fixing and crimping of proper size good quality lugs.
Making of 11 KV XLPE heat shrinkable indoor jointing kits in switch gears after carefully removing the insulation of cable, providing and crimping of proper size of lugs, plumbing and taping of cable with good quality available insulation tape with J/Kit boxes. Fixing and insulating of lugs on cable with switch gear complete in all respect.
33 KV Bus Bar Jumpering : Jumpering, including clamping/binding with ACSR Dog/panther conductor
Providing & fixing of PG clamps duly casted made of aluminum alloy complete with G.I. Nut, bolts, washers and spring washers suitable for ACSR Dog/panther Conductor
wearing of 160 mm dia 3 mtr. long G.I. pipe in the feeder cable of size of (3×300)mm2/(3×185)mm2 XLPE power cable before making the outdoor cable boxes. The work includes the sealing of G.I. Pipe, top end and lower end of the pipe is to be buried in to the ground about ½ m and proper dressing of cable etc. The work includes lifting, mounting and clamping of 11 KV feeder cable boxes on the feeder with double pole structure and making connections including supply of cable mounting clampls etc.
Plinth for new 5 MVA/10 MVA T/F (as per Specification) with Providing & fixing Rail Piece 90 LBS 7 Mtr (2x3.5 Mtr)
Installation of 11 KV Switch Gears in Control Room : Carefully & safely shifting of 11 KV switch gears from outside to inside the switch gear room grouting foundation of bolts in C.C. ratio of 1:2:4 (including cutting of RCC floor and finishing of RCC floor) as per requirement placing, aligning and fixing of 11 KV anchor GI bolts and nuts of proper size for completion of work.
Control Cable Laying : Providing & Laying of different size of (2×2.5)mm2 Copper control cables i.e. from Buchholz realy to Marshalling box Marshalling box to switch gear room, 33 KV CT's to CT's Junction Box, CT 33 KV, 33 KV P.T, V.C.B. Control Panel Junction Box to 33 KV VCB control panel and control panel to 33 KV VCB outdoor operating mechanism panel from T/F etc. in the cable trench including making proper connection at Buchholz Relay, Marshalling box as per required for installed equipment.
Providing & Laying of different size of (4×2.5)mm2 Copper control cables i.e. from Buchholz realy to Marshalling box Marshalling box to switch gear room, 33 KV CT's to CT's Junction Box, CT 33 KV, 33 KV P.T, V.C.B. Control Panel Junction Box to 33 KV VCB control panel and control panel to 33 KV VCB outdoor operating mechanism panel from T/F etc. in the cable trench including making proper connection at Buchholz Relay, Marshalling box as per required for installed equipment.
Construction of 11 KV Double Poles : Excavation of foundation pit in mix soil/normal soil/soft & hard rock and its back filling and leveling etc. The size of the pit will be (900×600)mm and having depth of 1/6th of the full length of the support & Erection of support. The work includes carriage and handling of supports from site store to pit site. 11 Mtr. PCC pole
Erection and grouting of 2 Nos. 11 Mtr. PCC pole for making DP Structure including & fabrication fixing of M.S. Channel, M.S. Angle, TPMO, Fuse Set, disc. insulators, pin insulators, stone pad, number plate, danger board, barbed wire etc. The work includes supply and fixing of necessary clamps with nuts, bolts and washers. The work also includes grouting of Double pole support in C.C. 1:4:8 (cement, sand & brick ballast) in block of size (0.45m × 0.45 × 1/6 length of the pole) including earthing of Double pole with M.S. earthing rod complete in all respect. Including Providing TPMO, Fuse set, stone pad, Number plate, danger board, barbed wire & other accessories if required .
Grouting of stay rods (16×1800)mm including all work of excavation, cement concrete in size (0.60 × 0.60 × 0.30)m in ratio 1:4:8 cement, sand, 40mm brick ballast) as per drg. including back filling, proper ramming etc and fixing tightening & nozzling of stay wire with stay rod with the poles of required tension as per drawing Including providing & Fixing Stay Insulator Providing complete stay set, Stay wire 7/10 SWG, nuts bolt & all other accerssories if required.
Construction of plinth for the structure of 33 KV VCB as per details Plinth for 33 KV V.C.B. (Qty.- 01) Excavation of earth of size (2.4×1.5×1.0) m pits for construction of plinth.
Brick Ballast ratio (1:4:8) (cement, sand & brick ballast ) for foundation work (2.4×1.5×0.15)m plinth.
C.C. work in ratio 1:2:4 (cement, coarse sand &stone grit) of 20mm size for making plinth of size (2.4×1.5×1.00)m and grouting of foundation bolts 04 Nos. for 33 KV VCB.
12 mm thick plaster with cement mortar in ratio 1:4 (cement & fine sand) of plinth of 0.15 m above ground level size (2.4×1.5)m.
Assembling and installation of 33 KV VCB on the VCB out door structure on the plinth.Adjustment of operating mechanism in proper alignment for smooth operation of the same. The work also includes fabrication of addition arrangement for proper fixing, if required.
Construction of fire wall between Transformer (as per Specification)
Construction of Control Cable Trench of size 30cmx30cm with Trench wall thickness 23cm with trench covers as per Respo norms Including providing GI Strip 25x3 for control cable laying
Construction of SSO Approach Road (as per Specification)
Excavation of Earth, Erection of Structure 33 KV Bus Isolator, Grouting and Plinthing of completed Structure with fabrication work if required including installation of 33 KV Bus Isolator on Structure. Including Providing of MS Channal (125x65x6, 100x50x6), MS Angle (65x65x6), Earthing Strip (50x6), Copper bond, MS Nuts bolts & Providing other accessories it required.
Excavation of Earth, Erection of Structure 33 KV Fuse Set, Grouting and Plinthing of completed Structure with fabrication work if required including installation of 33 KV fuse set on Structure. Including Providing of MS Channal (125x65x6, 100x50x6), MS Angle (65x65x6), Earthing Strip (50x6), Copper bond, MS Nuts bolts & Providing other accessories it required.
Excavation of Earth, Erection of Structure 33 KV Lightening Arrestor, Grouting and Plinthing of completed Structure with fabrication work if required including installation of 33 KV LA on Structure. Including Providing of MS Channal (125x65x6, 100x50x6), MS Angle (65x65x6), Earthing Strip (50x6), Copper bond, MS Nuts bolts & Providing other accessories it required.
Excavation of Earth, Erection of Structure 33 KV Post Insulator, Grouting and Plinthing of completed Structure with fabrication work if required including installation of 33 KV Post Isolator on Structure. Including Providing of MS Channal (125x65x6, 100x50x6), MS Angle (65x65x6), Earthing Strip (50x6), Copper bond, MS Nuts bolts & Providing other accessories it required.
Excavation of Earth, Erection of Structure 33 KV CT, Grouting and Plinthing of completed Structure with fabrication work if required including installation of 33 KV CT on Structure Including providing and fixing of CT junction box. Including Providing of MS Channal (125x65x6, 100x50x6), MS Angle (65x65x6), Earthing Strip (50x6), Copper bond, MS Nuts bolts & Providing other accessories it required.
Erection of 24 Volt Battery and Battery charger with fixing of fitting
Outdoor switchyard Earthing with 32 mm.size MS round Earth mat with Delta Earthing on power Transformer Neutral & 33 KV LA as per respo specification Including Providing of MS Round 32mm dia
Safe Carriage of dismantled old 5 MVA Power Transformer from 33/11 KV Substation(allotted)/Store to 33/11 KV S/S Ratual outside of switchyard This includes the following works :– Draining of oil from conservator, radiators of the 5 MVA transformer already available site/store into the dry & clean drums and stocking at the safe place. Dismantling of conservator, radiators and other accessories from allotted 5 MVA Transformer. Shifting of 5 MVA transformer main body and others accessories from the Sub-Station switchyard to loading point outside the switchyard. Loading of main tank of transformer along with conservator, radiators, transformer oil and other accessories on the trailer/truck. Carriage of transformer conservator, radiators, transformer oil and other accessories
Unloading of main transformer body, conservator, radiators, transformers oil and other accessories at unloading point out side the switchyard of 33/11 KV Ratual Shifting of 5 MVA transformer main body and others accessories from the Sub-Station switchyard to plinth at the switchyard. Providing and fixing of 5 MVA Power T/F’s Radiator Sealing Package (16 Each) Cleaning & painting of 33/11 KV, 5 MVA Power Transformer complete with radiators, conservator tank etc. with good quality two coats of assian/narolack make paint after applying one coat of red oxide. Topping up of the transformer oil from drums into the conservator and radiators of the 5 MVA transformer and releasing the air etc. and Transit Insurance of 5 MVA Transformer
Dismantling of Damage 33 KV VCB, CT from Structure and kept aside outside of switch yard
Bus bar Gantry Structure Complete with providing RS joist & other Material Including Fabrication & Grouting work as per Specification
Existing pannal shifting in control room If required
Installation of 03 No 33 KV CT & Post Insulator on Structure & their connections with providing CT Junction box if required
Making for alignment/Febraction of new I/C VCB to existing O/D VCB & Fabrication of Bus bar
Shifting of exisiting 03 Nos. 33 KV Control pannel & 02 No Unused OLTC & 01 No. FTR
Carriage including loading unloding at both side of old material received from site of PVVNL store including empty cable drums
Testing & commissiong of Substaion
Dismantling & construction of boundary wall for installation of new T/F.
Providing & Fixing 33 KV post Insulator
Providing & fixing Earthing rod complete set with GI wire 6 SWG
Raj Engineers (BID ID -5535930)
M/S RAGHAV and BROTHERS (BID ID -5533189)
Hi-tech power transmission (BID ID -5517355)
Shiva Electricals Company (BID ID -5536196)
Perennial Contractors Pvt. Ltd. (BID ID -5534849)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .