| 1 | L1₹1.2 CrAccepted-AOC HOUSE NO 40 CHOTTI BARADARI PART I GARHA ROAD NEAR MEDICAL COLLEGE JALANDHAR PB 144022 | JALANDHAR | JALANDHAR | PUNJAB | 144022 | ₹1.2 Cr Quoted ₹1.3 Cr | L1 | Accepted-AOC BEING LOWEST REASONABLE BIDDER |
| 2 | L2₹1.3 Cr+₹1.4 L (1.10%)Rejected-Finance 13 29 304 IIIRD FLOOR EAST PATEL NAGAR OPP HOTEL SIDDARATHA NEW DELHI 110008 | WEST | DELHI | 110008 | ₹1.3 Cr+₹1.4 L (1.10%) | L2 | Rejected-Finance OTHER THAN LOWEST BIDDER |
| 3 | L3₹1.3 Cr+₹6.1 L (4.76%)Rejected-Finance DIWANBADA MANEGAON POST OFFICE KHAMARIA JABALPUR 482005 M P | JABALPUR | MADHYA PRADESH | 482005 | ₹1.3 Cr+₹6.1 L (4.76%) | L3 | Rejected-Finance OTHER THAN LOWEST BIDDER |
| 4 | L4₹1.3 Cr+₹6.3 L (4.90%)Rejected-Finance B 87 SHAM NAGAR KHAYALA ROAD NEW DELHI 110018 | NEW DELHI | NEW DELHI | DELHI | 110018 | ₹1.3 Cr+₹6.3 L (4.90%) | L4 | Rejected-Finance OTHER THAN LOWEST BIDDER |
| 5 | L5₹1.4 Cr+₹12.3 L (9.59%)Rejected-Finance 58 CHANDRALOK BLDG MAYO HOSPITAL ROAD NAGPUR 440018 | NAGPUR | NAGPUR | MAHARASHTRA | 440018 | ₹1.4 Cr+₹12.3 L (9.59%) | L5 | Rejected-Finance OTHER THAN LOWEST BIDDER |
| Sl No | Description | Qty | Unit | Paragon Electrotechnics L5 | Leo Network power systems L2 | Vijaypower Generators Limited L6 | UNITED ENGINEERING CORPORATION L1 | C L BHATIA L3 | New Era Engineers L4 |
|---|---|---|---|---|---|---|---|---|---|
| 1.00 | Taking down old Unserviceable LT panel / switch gear / APFC panel of any type and any size complete all as specified and directed. | 45 | Each Job | 500 ₹22,500 Lowest | 1,000 ₹45,000 | 2,100 ₹94,500 | 800 ₹36,000 | 1,000 ₹45,000 | 1,200 ₹54,000 |
| 2.00 | M&L for Earthing in replacement complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6 mm thick buried directly in ground ,(Earth pit not less than 2.25 metre deep below ground level) with top edge of plate not less than 1.5 metre below normal ground level ,connected to and including galvanised iron earth Strip 32 X 6 mm by means of nut, bolts, check nuts and washers of galvanised iron or steel and provision of charcoal dust and common salt packed all around the earth plate including necessary excavation and earth work in any type of soil and testing complete all as specified and directed and shown in electrical Plate No. 3 of MES SSR part-I(2009) (a) Excavation and earth work for drilling hole for electrode in any type of Soil.
(b) PCC pit in cement concrete 1:2:4 type B-1(using 20mm graded crushed stone aggregate), Pre-cast RCC cover with suitable handle 40 mm thick in PCC 1:2:4 type B-1(using 20mm graded crushed stone aggregate), reinforced with welded steel wire fabric weighing not less than 1.87 Kg/ Sq metre.
(c) Funnel with watering pipe of GI 20 mm nominal bore light grade and lugs etc complete all as specified and directed | 90 | Each Set | 7,500 ₹6,75,000 | 6,250 ₹5,62,500 | 6,500 ₹5,85,000 | 5,150 ₹4,63,500 | 4,800 ₹4,32,000 Lowest | 6,000 ₹5,40,000 |
| 2.10(d) 40 mm nominal bore medium grade GI protection pipe 5 meter long for protection of earthing lead complete all as specified and directed. (e) Requisite quantity of common salt and charcoal. (f) Testing of earthing. Note:- GI strip and protection pipe from earth electrode to test point max upto 7.50M shall be deemed to be included in the unit rate as quoted by the contractor. | |||||||||
| 3.00Supply, laying or fixing or passing through pipe commissioning and testing of XLPE insulated, armoured heavy duty, electric cable with aluminium conductor, 1100 volts grade of the following cross section area including suitable size lugs including taking out /dismantling of existing cable complete all as specified and directed. (Note:- Excavation & earth work, sand cushioning, brick protection & GI pipe where required shall be measured & paid for separately under relevant items of this BoQ.) | |||||||||
| 3.01 | 10 Sqmm 2 core | 50 | RM | 110 ₹5,500 | 123 ₹6,150 | 168 ₹8,400 | 110 ₹5,500 | 155 ₹7,750 | 105 ₹5,250 Lowest |
| 3.02 | 16 Sqmm 4 core | 100 | RM | 170 ₹17,000 | 192 ₹19,200 | 245 ₹24,500 | 160 ₹16,000 Lowest | 164 ₹16,400 | 160 ₹16,000 Lowest |
| 3.03 | 25 Sqmm 4 core | 300 | RM | 220 ₹66,000 | 235 ₹70,500 | 285 ₹85,500 | 220 ₹66,000 | 255 ₹76,500 | 210 ₹63,000 Lowest |
| 3.04 | 35 Sqmm 3.5 core | 500 | RM | 270 ₹1,35,000 | 259 ₹1,29,500 | 327 ₹1,63,500 | 245 ₹1,22,500 | 298 ₹1,49,000 | 240 ₹1,20,000 Lowest |
| 3.05 | 50 Sqmm 3.5 core | 500 | RM | 340 ₹1,70,000 | 349 ₹1,74,500 | 396 ₹1,98,000 | 340 ₹1,70,000 | 384 ₹1,92,000 | 328 ₹1,64,000 Lowest |
| 3.06 | 70 Sqmm 3.5 core | 300 | RM | 458 ₹1,37,400 | 444 ₹1,33,200 | 561 ₹1,68,300 | 460 ₹1,38,000 | 512 ₹1,53,600 | 440 ₹1,32,000 Lowest |
Tender Value
₹1.2 Cr
EMD Value
₹1.9 L
Closing Date
27 Jun 2025, 6:00 pmClosed
CWE JABALPUR
HQ CWE JABALPUR OPPOSITE SUPPLY DEPT SADAR 482001
SPECIAL REPAIR TO REPAIR AND REPLACEMENT OF OLD UNSERVICEABLE PANEL, LT CABLE, FEEDER PILLAR BOXES AND ALLIED WORKS UNDER GE (WEST) JABALPUR
2025_MES_709925_1
81110/E8
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
CWE JABALPUR
AS PER NIT
7 documents required · 7 mandatory
₹1,000
GE (WEST ) JABALPUR
₹1.9 L
Yes
30 Sept 2025
23 May 2025
3 Jul 2025
23 May 2025
27 Jun 2025
13 Jun 2025
23 May 2025 - 7 Jun 2025
Amount
Taking down old Unserviceable LT panel / switch gear / APFC panel of any type and any size complete all as specified and directed.
M&L for Earthing in replacement complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6 mm thick buried directly in ground ,(Earth pit not less than 2.25 metre deep below ground level) with top edge of plate not less than 1.5 metre below normal ground level ,connected to and including galvanised iron earth Strip 32 X 6 mm by means of nut, bolts, check nuts and washers of galvanised iron or steel and provision of charcoal dust and common salt packed all around the earth plate including necessary excavation and earth work in any type of soil and testing complete all as specified and directed and shown in electrical Plate No. 3 of MES SSR part-I(2009) (a) Excavation and earth work for drilling hole for electrode in any type of Soil. (b) PCC pit in cement concrete 1:2:4 type B-1(using 20mm graded crushed stone aggregate), Pre-cast RCC cover with suitable handle 40 mm thick in PCC 1:2:4 type B-1(using 20mm graded crushed stone aggregate), reinforced with welded steel wire fabric weighing not less than 1.87 Kg/ Sq metre. (c) Funnel with watering pipe of GI 20 mm nominal bore light grade and lugs etc complete all as specified and directed
(d) 40 mm nominal bore medium grade GI protection pipe 5 meter long for protection of earthing lead complete all as specified and directed. (e) Requisite quantity of common salt and charcoal. (f) Testing of earthing. Note:- GI strip and protection pipe from earth electrode to test point max upto 7.50M shall be deemed to be included in the unit rate as quoted by the contractor.
Supply, laying or fixing or passing through pipe commissioning and testing of XLPE insulated, armoured heavy duty, electric cable with aluminium conductor, 1100 volts grade of the following cross section area including suitable size lugs including taking out /dismantling of existing cable complete all as specified and directed. (Note:- Excavation & earth work, sand cushioning, brick protection & GI pipe where required shall be measured & paid for separately under relevant items of this BoQ.)
10 Sqmm 2 core
16 Sqmm 4 core
25 Sqmm 4 core
35 Sqmm 3.5 core
50 Sqmm 3.5 core
70 Sqmm 3.5 core
95 Sqmm 3.5 core
120 Sqmm 3.5 core
150 Sqmm 3.5 core
185 Sqmm 3.5 core
240 Sqmm 3.5 core
Supply, erection, commissioning and testing outdoor type LT Panel , platform mounted, suitable for 3 phase 4 wire, 415 volts AC supply and having 4 Nos stepped type main copper bus bars of 1000 Amps, looping & branch connection system shall be made with suitable rating copper bus bar having sleeves colour coded .The chamber shall be painted with powder coated paint (Shade : RAL-7032) after 7 tank pre-treatment of surfaces. The LT Panel shall be provided with suitable Neoprene rubber gasket to make it completely dust and vermin proof and degree of protection not less than IP-55 and general construction conforming to IS : 13947. The LT Panel shall be made of 3.15mm thick CRCA mild steel sheet and 3.00mm thick gland plate , front door (02 layers) and rear Door (01 layer) opening facility and 4 side slanting canopy type roof on top and mild steel channel (ISMC 75) base frame at bottom. All incoming MCCBs shall be marked with location and rating of MCCBs. The Feeder Pillar shall be provided with ventilation facility in the form of louvers for better heat dissipation and including the followings :
CONTROL WIRING : All control wirings shall have to be carried out with 1100 volts rated FR grade PVC insulated multi-flexible type copper wire of cross sectional area 1.50 Sqmm and shall be properly bunched, tied and dressed, ferrule marked for proper identification and crimped with suitable size and type of tinned copper lugs and shall be wrapped with PVC spring type tube near the door hinges. CABLE ALLEY- Cable alley shall be provided in both side of the panel of suitable space for all incoming and outgoing cables. Cable terminals shall be provided for conecting of all incoming and outgoing cables. INCOMING :- MCCB 630 Amps, 4 pole, 415 volts, 50 kA, 50 Hz, micro-processor based electronic release - 01 No
OUTGOING : (a) MCCB 250 Amps, 4 pole, 415 volts, 36 KA, 50 Hz, adjustable thermal and adjustable magnetic release, Ics = 100%Icu, - 02 Nos (b) MCCB 200 Amps, 4 pole, 415 volts, 25 KA, 50 Hz, adjustable thermal and adjustable magnetic release, Ics = 100%Icu, - 02 Nos (c) MCCB 160 Amps, 4 pole, 415 volts, 25 KA, 50 Hz, adjustable thermal and adjustable magnetic release, Ics = 100%Icu, - 02 Nos (d) Digital voltmeter 96mm x 96mm suitable to read 0 to 500 volts, accuracy class 1% - 01 No. (e) Digital Ammeter 96mm x 96mm suitable to read 0 to 630 Amps, accuracy class 1% - 01 No. (f) Current Transformer (CT) of rating 630/5, tape wound, rated burden 5 VA - 03 Nos (g) LED indicator lamps complete with integral circuit and cluster LED, suitable to operate in 230-240 Volts AC supply - 1 set of 03 Nos (Red - 01, Yellow- 01, Blue - 01) (h) Control fuse holder, made of bakellite, 16 Amps rating, stud type, pannel door mounting complete with 01 No 02 Amps HRC fuse of suitable type- 03 Nos. (j) Copper bus bar of suitable size as per Manufacturer's recommendation duly mounted on FRP bus bar insulators and marked with standard colour coded sleeves / tapes for all outgoing MCCBs - 04 Nos.
(k) LED Pilot Lamp of following colours : (i) RED - 01 No, YELLOW - 01 No, BLUE - 01 No. (l) 02 Nos.Danger Notice Plate duly written in Signal Red colour on aluminium plate in English and Hindi language and of size not less than 150mmx100mm shall be fixed on both front & rear door of the bus bar chamber. (m) Panel box made of CRCA mild steel 3.15mm thick, duly powder coated with busbar and internal wiring all as per CPRI approved Manufacturer. Note : Panel shall be manufactured by CPRI approved Manufacturer. The contractor shall submit drawing of the panels to Engr-in-Charge before procurement of LT panel for approval alongwith CPRI approval. Foundation will be provided as per Manufacturer's instruction and cost thereof is deemed to be included in the unit rate quoted against this item.
Supply, erection, commissioning and testing outdoor type LT Panel, platform mounted, suitable for 3 phase 4 wire, 415 volts AC supply and having 4 Nos stepped type main copper bus bars of 600 Amps, looping & branch connection system shall be made with suitable rating copper bus bar having sleeves colour coded .The chamber shall be painted with powder coated paint (Shade : RAL-7032) after 7 tank pre-treatment of surfaces. The LT Panel shall be provided with suitable Neoprene rubber gasket to make it completely dust and vermin proof and degree of protection not less than IP-66 and general construction conforming to IS : 13947. The LT Panel shall be made of 3.15mm thick CRCA mild steel sheet and 3.00mm thick gland plate , front door (02 layers) and rear Door (01 layer) opening facility and 4 side slanting canopy type roof on top and mild steel channel (ISMC 75) base frame at bottom. All incoming MCCBs shall be marked with location and rating of MCCBs. The Feeder Pillar shall be provided with ventilation facility in the form of louvers for better heat dissipation and including the followings :
CONTROL WIRING : All control wirings shall have to be carried out with 1100 volts rated FR grade PVC insulated multi-flexible type copper wire of cross sectional area 1.50Sqmm and shall be properly bunched, tied and dressed, ferrule marked for proper identification and crimped with suitable size and type of tinned copper lugs and shall be wrapped with PVC spring type tube near the door hinges. CABLE ALLEY- Cable alley shall be provided in both side of the panel of suitable space for all incoming and outgoing cables. Cable terminals shall be provided for connecting of all incoming and outgoing cables, INCOMING :- MCCB 400 Amps, 4 pole, 415 volts, 50 kA, 50 Hz, microprocessor based, electronic release.
OUTGOING : (a) MCCB 200 Amps, 4 pole, 415 volts, 25 KA, 50 Hz, adjustable thermal & Adjustable magnetic, Ics = 100%Icu - 01 No (b) MCCB 160 Amps, 4 pole, 415 volts, 25 KA, 50 Hz,adjustable thermal & Adjustable magnetic, Ics = 100%Icu - 01 No (c) MCCB 100 Amps, 4 pole, 415 volts, 25 KA, 50 Hz, adjustable thermal & Adjustable magnetic, Ics = 100%Icu - 04 Nos (d) Digital volt meter 96mm x 96mm suitable to read 0 to 500 volts, accuracy class 1% - 01 No. (e) Digital Ammeter 96mm x 96mm suitable to read 0 to 630 Amps, accuracy class 1% - 01 No. (f) Current transformer (CT) of rating 400/5, tape wound, rated burden 5 VA - 03 Nos (g) LED indicator lamps complete with integral circuit and cluster LED, suitable to operate in 230-240 Volts AC supply - 1 set of 03 Nos (Red - 01, Yellow- 01, Blue - 01) (h) Control fuse holder, made of bakellite, 16 Amps rating, stud type, pannel door mounting complete with 01 No x 02 Amp HRC fuse of suitable type- 03 Nos. (j) Copper bus bar of suitable length duly mounted on FRP bus bar insulators and marked with standard colour coded sleeves / tapes for all outgoing MCCBs - 04 Nos.
(k) LED Pilot Lamp of following colours : (i) RED - 01 No, YELLOW - 01 No, BLUE - 01 No. (l) 02 Nos. Danger Notice Plate duly written in Signal Red colour on aluminium plate in English and Hindi language and of size not less than 150mmx100mm shall be fixed on both front & rear door of the bus bar chamber. (m) Pannel box made of CRCA mild steel 3.15mm thick, duly powder coated with busbar and internal wiring all as per CPRI approved Manufacturer. Note : Panel will be manufactured by CPRI approved Manufacturer as indicated above. The contractor shall submit drawing of the panels to Engr-in-Charge before procurement of LT panel for approval alongwith CPRI approval. Foundation will be provided as per Manufacturer's instruction and cost of foundation is deemed to be included in the quoted rate.
Supply, erection, commissioning and testing outdoor type LT Panel, platform mounted, suitable for 3 phase 4 wire, 415 volts AC supply and having 4 Nos stepped type main copper bus bars of 600 Amps, looping & branch connection system shall be made with suitable rating copper bus bar having sleeves colour coded .The chamber shall be painted with powder coated paint (Shade : RAL-7032) after 7 tank pre-treatment of surfaces. The LT Panel shall be provided with suitable Neoprene rubber gasket to make it completely dust and vermin proof and degree of protection not less than IP-66 and general construction conforming to IS : 13947. The LT Panel shall be made of 3.15mm thick CRCA mild steel sheet and 3.00mm thick gland plate , front door (02 layers) and rear Door (01 layer) opening facility and 4 side slanting canopy type roof on top and mild steel channel (ISMC 75) base frame at bottom. All incoming MCCBs shall be marked with location and rating of MCCBs. The Feeder Pillar shall be provided with ventilation facility in the form of louvers for better heat dissipation and including the followings :
CONTROL WIRING : All control wirings shall have to be carried out with 1100 Volts rated FR grade PVC insulated multi-flexible type copper wire of cross sectional area 1.50 Sqmm and shall be properly bunched, tied and dressed, ferrule marked for proper identification and crimped with suitable size and type of tinned copper lugs and shall be wrapped with PVC spring type tube near the door hinges. CABLE ALLEY- Cable alley shall be provided in both side of the panel of suitable space for all incoming and outgoing cables. Cable terminals shall be provided for connecting of all incoming and outgoing cables, INCOMING :- MCCB 320 Amps, 4 pole, 415 volts, 50 kA, 50 Hz, micro-processor based, electronic release.
OUTGOING :(a) MCCB 160 Amps, 4 pole, 415 volts, 25 KA, 50 Hz,adjustable thermal & Adjustable magnetic, Ics = 100%Icu - 02 No (b) MCCB 100 Amps, 4 pole, 415 volts, 25 KA, 50 Hz, adjustable thermal & Adjustable magnetic, Ics = 100%Icu - 01 Nos (c) MCCB 63 Amps, 4 pole, 415 volts, 25 KA, 50 Hz, adjustable thermal & fixed magnetic, Ics = 100%Icu - 03 Nos (d) Digital volt meter 96mm x 96mm suitable to read 0 to 500 volts, accuracy class 1% - 01 No. (e) Digital Ammeter 96mm x 96mm suitable to read 0 to 630 Amps, accuracy class 1% - 01 No. (f) Current transformer (CT) of rating 630/5, tape wound, rated burden 5 VA - 03 Nos (g) LED indicator lamps complete with integral circuit and cluster LED, suitable to operate in 230-240 Volts AC supply - 1 set of 03 Nos (Red - 01, Yellow- 01, Blue - 01) (h) Control fuse holder, made of bakellite, 16 Amps rating, stud type, pannel door mounting complete with 01 No 02 Amps HRC fuse of suitable type- 03 Nos. (j) Copper bus bar of suitable length duly mounted on FRP bus bar insulators and marked with standard colour coded sleeves / tapes for all outgoing MCCBs - 04 Nos.
(k) LED Pilot Lamp of following colours : (i) RED - 01 No, YELLOW - 01 No, BLUE - 01 No. (l) 02 Nos. Danger Notice Plate duly written in Signal Red colour on aluminium plate in English and Hindi language and of size not less than 150mmx100mm shall be fixed on both front & rear door of the bus bar chamber. (m) Pannel box made of CRCA mild steel 3.15mm thick, duly powder coated with busbar and internal wiring all as per CPRI approved Manufacturer. Note : Panel will be manufactured by CPRI approved Manufacturer as indicated above. The contractor shall submit drawing of the panels to Engr-in-Charge before procurement of LT panel for approval alongwith CPRI approval. Foundation will be provided as per Manufacturer's instruction and cost of foundation is deemed to be included in the quoted rate.
supply, erection, commissioning and testing outdoor type LT Panel, platform mounted, suitable for 3 phase 4 wire, 415 Volts AC supply and having 4 Nos stepped type main copper bus bars of 400 Amps, looping & branch connection system shall be made with suitable rating copper bus bar having sleeves colour coded .The chamber shall be painted with powder coated paint (Shade : RAL-7032) after 7 tank pre-treatment of surfaces. The LT Panel shall be provided with suitable Neoprene rubber gasket to make it completely dust and vermin proof and degree of protection not less than IP-66 and general construction conforming to IS : 13947. The LT Panel shall be made of 3.15mm thick CRCA mild steel sheet and 3.00mm thick gland plate , front door (02 layers) and rear Door (01 layer) opening facility and 4 side slanting canopy type roof on top and mild steel channel (ISMC 75 ) base frame at bottom. All incoming MCCBs shall be marked with location and rating of MCCBs. The Feeder Pillar shall be provided with ventilation facility in the form of louvers for better heat dissipation complete and including the followings :
CONTROL WIRING : All control wirings shall have to be carried out with 1100 Volts rated FR grade PVC insulated multi-flexible type copper wire of cross sectional area 1.50 Sqmm and shall be properly bunched, tied and dressed, ferrule marked for proper identification and crimped with suitable size and type of tinned copper lugs and shall be wrapped with PVC spring type tube near the door hinges. CABLE ALLEY- Cable alley shall be provided in both side of the panel of suitable space for all incoming and outgoing cables. Cable terminals shall be provided for connecting of all incoming and outgoing cables, INCOMING :- MCCB 250 Amps, 4 pole, 415 volts, 50 kA, 50 Hz, micro-processor based, electronic release.
OUTGOING : (a) MCCB 160 Amps, 4 pole, 415 volts, 36 KA, 50 Hz, adjustable thermal & Adjustable magnetic, Ics = 100%Icu - 01 No (b) MCCB 100 Amps, 4 pole, 415 volts, 25 KA, 50 Hz, adjustable thermal & Adjustable magnetic, Ics = 100%Icu - 02 Nos (c) MCCB 63 Amps, 4 pole, 415 volts, 16 KA, 50 Hz, adjustable thermal & fixed magnetic, Ics = 100%Icu - 03 Nos (d) Digital voltmeter 96mm x 96mm suitable to read 0 to 500 volts, accuracy class 1% - 01 No. (e) Digital Ammeter 96mm x 96mm suitable to read 0 to 630 Amps, accuracy class 1% - 01 No. (f) Current Transformer (CT) of rating 630/5, tape wound, rated burden 5 VA - 03 Nos (g) LED indicator lamps complete with integral circuit and cluster LED, suitable to operate in 230-240 Volts AC supply - 1 set of 03 Nos (Red - 01, Yellow- 01, Blue - 01) (h) Control fuse holder, made of bakellite, 16 Amps rating, stud type, pannel door mounting complete with 01 No x 02 Amps HRC fuse of suitable type- 03 Nos.
(j) Copper bus bar of suitable length duly mounted on FRP bus bar insulators and marked with standard colour coded sleeves / tapes for all outgoing MCCBs - 04 Nos. (k) LED Pilot Lamp of following colours : (i) RED - 01 No, YELLOW - 01 No, BLUE - 01 No. (l) 02 Nos.Danger Notice Plate duly written in Signal Red colour on aluminium plate in English and Hindi language and of size not less than 150mmx100mm shall be fixed on both front & rear door of the bus bar chamber. (m) Power contactor four pole with coil voltage 230 volt of capacity 25 Amps 50 cycles. - 01 No (n) Time switch microrex analog time switch -01 No (o) Pannel box made up of CRCA mild steel 3.15mm thick, duly powder coated with busbar and internal wiring all as per CPRI approved Manufacturer (The panel shall not be less than 2.5 Sqm front area) Note : Panel will be manufactured by CPRI approved Manufacturer as indicated above. The contractor shall submit drawing of the panels to Engr-in-Charge before procurement of LT panel for approval alongwith CPRI approval. Foundation will be provided as per Manufacturer's instruction and cost of foundation is deemed to be included in the quoted rate.
Design, supply, erection, commissioning and testing outdoor type LT Panel, platform mounted, suitable for 3 phase 4 wire, 415 volts AC supply and having 4 Nos stepped type main copper bus bars of 250 Amps, looping & branch connection system shall be made with suitable rating copper bus bar having sleeves colour coded .The chamber shall be painted with powder coated paint (Shade : RAL-7032) after 9 tank pre-treatment of surfaces. The LT Panel shall be provided with suitable Neoprene rubber gasket to make it completely dust and vermin proof and degree of protection not less than IP-66 and general construction conforming to IS : 13947. The LT Panel shall be made of 3.15mm thick CRCA mild steel sheet and 3.00mm thick gland plate , front door (02 layers) and rear Door (01 layer) opening facility and 4 side slanting canopy type roof on top and mild steel channel (ISMC 75 ) base frame at bottom. All incoming MCCBs shall be marked with location and rating of MCCBs. The Feeder Pillar shall be provided with ventilation facility in the form of louvers for better heat dissipation in and including the followings :
CONTROL WIRING : All control wirings shall have to be carried out with 1100 volts rated FR grade PVC insulated multi-flexible type copper wire of cross sectional area 1.50Sqmm and shall be properly bunched, tied and dressed, ferrule marked for proper identification and crimped with suitable size and type of tinned copper lugs and shall be wrapped with PVC spring type tube near the door hinges CABLE ALLEY- Cable alley shall be provided in both side of the panel of suitable space for all incoming and outgoing cables. Cable terminals shall be provided for conecting of all incoming and outgoing cables INCOMING :- MCCB 160 Amps, 4 pole, 415 volts, 50 kA, 50 Hz, electronic release
OUTGOING : (a) MCCB 63 Amps, 4 pole, 415 volts, 25 KA, 50 Hz, adj thermal & fixed magnetic, Ics =100%Icu, -04 Nos (b) Pannel box made up of CRCA mild steel 3.15mm thick, duly powder coated with busbar and internal wiring all as per CPRI approved (The panel shall not be less than 2.5 Sqm front area) (c) Digital volt meter 96mm x 96mm suitable to read 0 to 500 volts, accuracy class 1% - 01 No. (d) Digital Ammeter 96mm x 96mm suitable to read 0 to 630 Amps, accuracy class 1% - 01 No. (e) Current transformer (CT) of rating 630/5, tape wound, rated burden 5 VA - 03 Nos (f) LED indicator lamps complete with integral circuit and cluster LED, suitable to operate in 230-240 Volts AC supply - 1 set of 03 Nos (Red - 01, Yellow- 01, Blue - 01)
(g) Control fuse holder, made of bakellite, 16 Amps rating, stud type, pannel door mounting complete with 01No x 02 Amps HRC fuse of suitable type- 03 Nos. (h) Copper bus bar of suitable length duly mounted on FRP bus bar insulators and marked with standard colour coded sleeves / tapes for all outgoing MCCBs - 04 Nos. (j) LED Pilot Lamp of following colours : (i) RED - 01 No, YELLOW - 01 No, BLUE - 01 No. (k) 02 Nos.Danger Notice Plate duly written in Signal Red colour on aluminium plate in English and Hindi language and of size not less than 150mmx100mm shall be fixed on both front & rear door of the bus bar chamber (l) Power contactor four pole with coil voltage 230 volt of capacity 25 Amps 50 cycles - 01 No (m) Time switch microrex analog time switch Cat part No 412814 of Legrand -01 Nos (Note : Panel will be manufactured by CPRI approved firm as indicated above. The contractor shall submit drawing of the panels to Engr-in-Charge before procurement of LT panel for approval alongwith CPRI approval. Foundation will be provided as per Manufacturer's instruction and cost of fondation is deemed to be included in the quoted rate.)
M&L for cable jointing kit LT cable for straight through joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 25 sqmm to 95 sqmm and testing on completion complete all as directed.
M&L for cable jointing kit for LT cable for straight through joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 120 sqmm to 240 sqmm and testing on completion complete all as directed.
Supply, erection, commissioning and testing outdoor type LT Panel size, platform mounted, suitable for 3 phase 4 wire, 415 volts AC supply and having 4 Nos stepped type main copper bus bars of 1000 Amps, looping & branch connection system shall be made with suitable rating copper bus bar having sleeves colour coded .The chamber shall be painted with powder coated paint (Shade : RAL-7032) after 7 tank pre-treatment of surfaces. The LT Panel shall be provided with suitable Neoprene rubber gasket to make it completely dust and vermin proof and degree of protection not less than IP-55 and general construction conforming to IS : 13947. The LT Panel shall be made of 3.15mm thick CRCA mild steel sheet and 3.00mm thick gland plate , front door (02 layers) and rear Door (01 layer) opening facility and 4 side slanting canopy type roof on top and mild steel channel (ISMC 75 ) base frame at bottom. All incoming MCCBs shall be marked with location and rating of MCCBs. The Feeder Pillar shall be provided with ventilation facility in the form of louvers for better heat dissipation and including the followings :
CONTROL WIRING : All control wirings shall have to be carried out with 1100 Volts rated FR grade PVC insulated multi-flexible type copper wire of cross sectional area 1.50 Sqmm and shall be properly bunched, tied and dressed, ferrule marked for proper identification and crimped with suitable size and type of tinned copper lugs and shall be wrapped with PVC spring type tube near the door hinges. CABLE ALLEY- Cable alley shall be provided in both side of the panel of suitable space for all incoming and outgoing cables. Cable terminals shall be provided for connecting of all incoming and outgoing cables. INCOMING :- ACB 800 Amps, manual draw out type 4 pole, 415 Volts, 50 kA, 50 Hz, micro-processor based electronic release - 01 No
OUTGOING : (a) MCCB 630 Amps, 4 pole, 415 volts, 50 KA, 50 Hz, adjustable thermal and adjustable magnetic release, Ics = 100%Icu, - 01 No (b) MCCB 400 Amps, 4 pole, 415 volts, 50 KA, 50 Hz, adjustable thermal and adjustable magnetic release, Ics = 100%Icu, - 02 Nos (d) Digital voltmeter 96mm x 96mm suitable to read 0 to 500 volts, accuracy class 1% - 01 No. (e) Digital Ammeter 96mm x 96mm suitable to read 0 to 630 Amps, accuracy class 1% - 01 No. (f) Current Transformer (CT) of rating 630/5, tape wound, rated burden 5 VA - 03 Nos (g) LED indicator lamps complete with integral circuit and cluster LED, suitable to operate in 230-240 Volts AC supply - 1 set of 03 Nos (Red - 01, Yellow- 01, Blue - 01) (h) Control fuse holder, made of bakellite, 16 Amps rating, stud type, pannel door mounting complete with 01 No 02 Amps HRC fuse of suitable type- 03 Nos. (j) Copper bus bar of suitable size as per Manufacturer's recommendation duly mounted on FRP bus bar insulators and marked with standard colour coded sleeves / tapes for all outgoing MCCBs - 04 Nos.
(k) LED Pilot Lamp of following colours : (i) RED - 01 No, YELLOW - 01 No, BLUE - 01 No. (l) 02 Nos.Danger Notice Plate duly written in Signal Red colour on aluminium plate in English and Hindi language and of size not less than 150mmx100mm shall be fixed on both front & rear door of the bus bar chamber. (m) Panel box made of CRCA mild steel 3.15mm thick, duly powder coated with busbar and internal wiring all as per CPRI approved Manufacturer. (Note : Panel shall be manufactured by CPRI approved Manufacturer. The contractor shall submit drawing of the panels to Engr-in-Charge before procurement of LT panel for approval alongwith CPRI approval. Foundation will be provided as per Manufacturer's instruction and cost thereof is deemed to be included in the unit rate quoted against this item.
(B) Outgoing :- (i) Capacitor 20 KVAr ultra heavy duty 440V cylindrical - 01 No (ii) Capacitor 10 KVAr ultra heavy duty 440V cylindrical - 01 No (iii) Capacitor 05 KVAr ultra heavy duty 440V cylindrical - 06 No (iv) MCB Triple pole 63 Amps, 10 kA, 'C' series - 01 No (v) MCB Triple pole 32 Amps, 10 kA, 'C' series - 01 No (vi) MCB Triple pole 16 Amps, 10 kA, 'C' series - 06 Nos (vii) Capacitor duty contactor 3 pole 20 KVAr - 01 No (viii) Capacitor duty contactor 3 pole 10 KVAr - 01 No (ix) Capacitor duty contactor 3 pole 05 KVAr - 06 No (x) 22.5mm dia Push Button ON/OFF-08 set (xi) 22.5 mm dia LED Red - 08 Nos (xii) 22.5mm dia LED Green-08 Nos (xiii) Armoured 2 core copper cable 1.5sqmm shall be provided for sensing CT
(xiv) Sensing CT as per site load condition shall be provided alongwith APFC Panel (xv ) All power connection shall be done with 1100 volts FRLS copper flexible wire with copper termination of proper size and proper type Notes : (i) GA drawing for APFC panel shall be got approved from the Engr in-Charge before manufacturing of APFC panels (ii) Test report for powder coating shall be provided with panels (iii) The Manufacturer shall have inhouse 8 tanks Powder coating Process Plant to avoid defective process (iv) PCC plateform of suitable size shall be provided after demolition of existing PCC plateform, The cost of all above shall be deemed to be included in unit rate quoted against this item.
(B) Outgoing : (i) Capacitor 20 KVAr ultra heavy duty 440V cylindrical - 02 Nos (ii) Capacitor 10 KVAr ultra heavy duty 440V cylindrical - 02 Nos (iii) Capacitor 05 KVAr ultra heavy duty 440V cylindrical - 08 Nos
(iv) MCB Triple pole 63 Amps, 10 kA, 'C' series - 02 Nos (v) MCB Triple pole 32 Amps, 10 kA, 'C' series - 02 Nos (vi) MCB Triple pole 16 Amps, 10 kA, 'C' series - 08 Nos (vii) Capacitor duty contactor 3 pole 20 KVAr - 02 Nos (viii) Capacitor duty contactor 3 pole 10 KVAr - 02 Nos (ix) Capacitor duty contactor 3 pole 05 KVAr - 08 Nos (x) 22.5mm dia Push Button ON/OFF-12 set (xi) 22.5 mm dia LED Red - 12Nos (xii) 22.5mm dia LED Green-12 Nos (xiii) Armoured 2 core copper cable 1.5sqmm shall be provided for sensing CT (xiv) Sensing CT as per site load condition shall be provided alongwith APFC Panel (xv ) All power connection shall be done with 1100 volts FRLS copper flexible wire with copper termination of proper size and proper type
Notes : (i) GA drawing for APFC panel shall be got approved from the Engr in Charge before manufacturing of APFC panels (ii) Test report for powder coating shall be provided with panels (iii) The manufacturers shall have inhouse 8 tanks Powder coating Process Plant to avoid defective process (iv) PCC plateform of suitable size shall be provided after demolition of existing PCC plateform, The cost of all above shall be demmed to be included in unit rate quoted gainst this item. (v) One 20 KVAr capacitor shall be fixed type (Connected directly ) and others shall be controlled through APFC relay
(B) Outgoing :- (i) Capacitor 20 KVAr ultra heavy duty 440V cylindrical - 02 Nos (ii) Capacitor 10 KVAr ultra heavy duty 440V cylindrical - 04 Nos (iii) Capacitor 05 KVAr ultra heavy duty 440V cylindrical - 08 Nos (iv) MCB Triple pole 63 Amps, 10 kA, 'C' series - 02 Nos (v) MCB Triple pole 32 Amps, 10 kA, 'C' series - 04 Nos (vi) MCB Triple pole 16 Amps, 10 kA, 'C' series - 08 Nos (vii) Capacitor duty contactor 3 pole 20 KVAr - 02 Nos (viii) Capacitor duty contactor 3 pole 10 KVAr - 04 Nos (ix) Capacitor duty contactor 3 pole 05 KVAr - 08Nos (x) 22.5mm dia Push Button ON/OFF-14 set (xi) 22.5 mm dia LED Red - 14 Nos (xii) 22.5mm dia LED Green-14 Nos (xiii) Armoured 2 core copper cable 1.5sqmm shall be provided for sensing CT (xiv) Sensing CT as per site load condition shall be provided alongwith APFC Panel (xv ) All power connection shall be done with 1100 volts FRLS copper flexible wire with copper termination of proper size and proper type
(Notes : (i) GA drawing for APFC panel shall be got approved from the Engr- in-Charge before manufacturing of APFC panels (ii) Test report for powder coating shall be provided with panels (iii) The manufacturers shall have in-house 8 tanks Powder coating Process Plant to avoid defective process (iv) PCC plateform of suitable size shall be provided after demolition of existing PCC plateform, The cost of all above shall be deemed to be included in unit rate quoted against this item. (v) One 20 KVAr capacitor shall be fixed type (Connected directly ) and others shall be controlled through APFC relay
(B) Outgoing :- (i) Capacitor 20 KVAr ultra heavy duty 440V cylindrical - 02 Nos (ii) Capacitor 10 KVAr ultra heavy duty 440V cylindrical - 06 Nos (iii) Capacitor 05 KVAr ultra heavy duty 440V cylindrical - 10 Nos(iv) MCB Triple pole 63 Amps, 10 kA, 'C' series - 02 Nos (v) MCB Triple pole 32 Amps, 10 kA, 'C' series - 06 Nos (vi) MCB Triple pole 16 Amps, 10 kA, 'C' series - 10 Nos (vii) Capacitor duty contactor 3 pole 20 KVAr - 02 Nos (viii) Capacitor duty contactor 3 pole 10 KVAr - 06 Nos (ix) Capacitor duty contactor 3 pole 05 KVAr - 10 Nos (x) 22.5mm dia Push Button ON/OFF-18 set (xi) 22.5 mm dia LED Red - 18 Nos (xii) 22.5mm dia LED Green-18 Nos (xiii) Armoured 2 core copper cable 1.5sqmm shall be provided for sensing CT (xiv) Sensing CT as per site load condition shall be provided alongwith APFC Panel (xv ) All power connection shall be done with 1100 volts FRLS copper flexible wire with copper termination of proper size and proper type
(Notes for Srl item No. 12,13,14&15 : (i) GA drawing for APFC panel shall be got approved from the Engr- in-Charge before manufacturing of APFC panels (ii) Test report for powder coating shall be provided with panels (iii) The manufacturers shall have in-house 8 tanks Powder coating Process Plant to avoid defective process (iv) PCC plateform of suitable size shall be provided after demolition of existing PCC plateform, The cost of all above shall be deemed to be included in unit rate quoted against this item. (v) One 20 KVAr capacitor shall be fixed type (Connected directly ) and others shall be controlled through APFC relay (vi) Cost of control cable required for connecting APFC panel with existing LT panel is deemed to be included in the unit rate quoted against this item
Excavation in trenches, not exceeding 1.5m wide and not exceeding 1.5m in depth for foundation, for laying of pipe, cable etc or n. exc.10 Sqm on plan and n. exc. 1.5m in depth for shafts, cesspits, manholes, pier holes, etc and getting out in any type of soil complete all as specified and directed.
Returning, filling in excavated approved soil, including spreading, levelling, watering and well ramming in layers not exceeding 25cm each complete all as specified and directed.
Removing excavated soil not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point including spreading complete all as specified and directed.
Supply and spreading clean and dry fine sand free from sharp materials (unwashed) laying in trenches around the cable for cushioning in trenches, laid to a uniform thickness of 23cm (15cm under the cable & 8cm over the cable) and gently punned down to 18cm thickness complete all as specified and as directed. (Note: Only punned sand shall be measured and paid.)
Supply and laying the Brick covering with width equal to length of brick as mechanical protection to cable with sub class ‘B’ fly ash bricks laid dry flat complete all as specified and directed by Engr- in- Charge.
M&L in repair GI Tubes light grade ,galvanised , with clamp of 25x3 flat iron welded to pipe fixed to wall/pole/ceiling or laid in floors or under road etc of following size, complete all as specified and as directed.
40 mm bore
50 mm bore
80mm bore
Supply and fixing, in replacement, outdoor type LT Bus Bar Chamber box, platform mounted, suitable for 3 phase 4 wire, 415 volts AC supply and having 4 Nos stepped type Aluminium bus bars 400 A, 4 way) for looping & branch connection system .The chamber shall be painted with powder coated paint (Shade : RAL-7032) after 7 tank pre-treatment of surfaces. The bus bar chamber shall be provided with suitable Neoprene rubber gasket to make it completely dust and vermin proof and degree of protection not less than IP-55 and general construction conforming to IS : 13947. The bus bar chamber shall be made out of 3.00mm thick CRCA mild steel sheet and 3.00mm thick gland plate , front door (01 layer) and rear Door (01 layer) opening facility and 4 side slanting canopy type roof on top and mild steel channel (ISMC 75 ) base frame at bottom. The bus bar chamber shall be provided with ventilation facility in the form of louvers for better heat dissipation. (Note : The bus bar chamber Box shall be designed in such a way that adequate workable space is made available inside the compartments and the size of the chamber shall not be less than 500mm height (without base frame & canopy), 500mm width and 450mm depth).
Supply installation testing & commissioning IP65/54 made of environment friendly polycarbonate PC - GFS Insulation-enclosed power distribution board as power switchgear and control gear assembly (PSC) in accordance with IEC 61439-2 for wall mounting/floor mounting. The enclosures must be suitable for outdoor installation - harsh environment and/or outdoor installation - the climatic effects on the equipment must be considered. Bottom parts and lids of the boxes made from impact-resistant polycarbonate, halogen and silicon-free, colour RAL 7035, transparent lid with quick action fasteners for tool operation. Burning behaviour according to IEC 60695-2-11 glow wire test + 960°C. Maximum water absorption 10 mg in accordance with DIN 53473. Protective measure: totally insulated (protection class II), the enclosure should have mechanical strength equivalent to IK10 (bidder should submit compliance for same for polycarbonate enclosure in OEM letter head to the Engineer-in-Charge).To prevent the condensation in each distribution board “dew guard” to be used in right quantity in each system. including fwg with aluminium bus bar of capacity 400 Amp INCOMING :- MCCB 250 Amps, 4 pole, 415 volts, 50 kA, 50 Hz, microprocessor based, electronic release. OUTGOING : (a) MCCB 160 Amps, 4 pole, 415 volts, 36 KA, 50 Hz, adjustable thermal & Adjustable magnetic, Ics = 100%Icu - 01 No (b) MCCB 100 Amps, 4 pole, 415 volts, 25 KA, 50 Hz,adjustable thermal & Adjustable magnetic, Ics = 100%Icu - 02 Nos
(c) MCCB 63 Amps, 4 pole, 415 volts, 16 KA, 50 Hz, adjustable thermal & fixed magnetic, Ics = 100%Icu - 03 Nos (d) Digital volt meter 96mm x 96mm suitable to read 0 to 500 volts, accuracy class 1% - 01 No. (e) Digital Ammeter 96mm x 96mm suitable to read 0 to 630 Amps, accuracy class 1% - 01 No. (f) Current transformer (CT) of rating 630/5, tape wound, rated burden 5 VA - 03 Nos (g) LED indicator lamps complete with integral circuit and cluster LED, suitable to operate in 230-240 Volts AC supply - 1 set of 03 Nos (Red - 01, Yellow- 01, Blue - 01) (h) Control fuse holder, made of bakellite, 16 Amps rating, stud type, pannel door mounting complete with 01 No 02 Amps HRC fuse of suitable type- 03 Nos.
Notes : 1) Drawing from Original Equipment Manufacturer ( OEM ) to be got approved from Engr-in-Charge before placing order of Panel. 2) Panel should be manufactured and assembled by OEM only. Fabrication / Assembling from any other system house will not be accepted. 3) Inspection by Company Engineer after installation at site is mandatory and cost thereto is deemed to be included it the overall quoted rate. 4) The contractor shall submit all relevant type test certificate / compliance on OEM letter head to the Engineer-in-Charge. 5) The contractor shall submit Routine test certificate on OEM letter head to the Engineer-in-Charge.
Schedule of credit amount of Rs 3,89,755.00 to be deducted during AOC
Leo Network power systems (BID ID -3329653)
C L BHATIA (BID ID -3339000)
New Era Engineers (BID ID -3339218)
Paragon Electrotechnics (BID ID -3323261)
Vijaypower Generators Limited (BID ID -3330799)
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .