| 1.00 | M/L for Repair & Maintenance and servicing of standby DG Set upto capacity 40 KVA, complete including draining out of diesel from tank , cleaning the tank thoroughly and refilling the drained out diesel, draining out engine oil from the sump, cleaning the sump thoroughly and refilling the sump with new engine oil to it’s required level, replacing the fuel filter, lubricating oil filter , check & clean air cleaner , change air cleaner elements, check coolant level & make up the same ,drain the fuel filter & water separator ,filling the starting batteries with electrolyte/distilled water to maintain the required specific gravity, replace the u/s brass connectors for batteries, cleaning of battery terminals & applying petroleum jelly to battery terminal posts & brass connectors, including M & L for V Belts, checking of exhaust leakage, governor, breathers etc, adjust/set the same for proper functioning of DG Set, checking of fuel, oil and water/ coolant level etc, adjusting and keeping the fan belts to the desired tension, tightening all the bolts and nuts to the required torque etc, cleaning the DG Set with accessories as prescribed by the manufacturer and test for satisfactory running of DG set for two hour at connected load and record shall be made in respect of RPM , oil pressure , oil temperature , coolant temperature, voltage , frequency , load current , battery charging , fuel consumption etc complete all as specified and directed by Engineer in Charge.
(a). Engine oil for refilling will be measured & paid separately.
(b). Coolant for make up will be measured & paid separately
(c). The Make of Fuel filter , Oil Filter , V belt & component will be as per manufactures recommendations and quoted item is not inclusive of cost of fuel filter, oil filter, air filter and V belt. Capacity of DG 15 to 50 KVA and Make of DG Set Kirlosker/Cummins/Ashok Layland /CG/Sudhir | 13 | Ecah Job | 5,000 ₹65,000 Lowest | 7,200 ₹93,600 | 8,500 ₹1,10,500 |
| 2.00 | All as per Srl Item No.1 here-in-before but capacity of DG set 62.5/63 KVA and Make of DG Set Kirlosker/Cummins/Ashok Layland/CG/Sudhir | 5 | Ecah Job | 5,200 ₹26,000 Lowest | 7,500 ₹37,500 | 6,500 ₹32,500 |
| 3.00 | All as per Srl Item No.1 here-in-before but capacity of DG set 82.5 KVA and Make of DG Set Kirlosker/Cummins/ Ashok Layland/CG/Sudhir | 2 | Ecah Job | 6,500 ₹13,000 Lowest | 8,800 ₹17,600 | 7,800 ₹15,600 |
| 4.00 | All as per Srl Item No.1 here-in-before but capacity of DG set 125 KVA and Make of DG Set Kirlosker/Cummins/Ashok Layland/CG/Sudhir | 3 | Ecah Job | 10,000 ₹30,000 Lowest | 13,500 ₹40,500 | 10,000 ₹30,000 Lowest |
| 5.00 | All as per Srl Item no.1 here-in-before but capacity of DG set of 160/180/200 KVA Make of DG Set Kirlosker/Cummins/Ashok Layland/CG/Sudhir | 4 | Ecah Job | 12,000 ₹48,000 Lowest | 14,000 ₹56,000 | 14,500 ₹58,000 |
| 6.00 | Repair/maintenance of existing control panel of DG set by replacing the connected items such as leads, copper wire, thimble , Analogue Ammeter, Analogue voltmeter,frequancy meter etc along with other minor parts required for carrying out maintenance complete all as directed by Engineer in Charge.
Note- Ammeter, Voltmeter and frequancy meter shall be measured and paid separately as supply only items below and labour element involve for replacing the same shall deemed to be included in the rate quoted against these item. | 6 | EACH JOB | 1,930 ₹11,580 | 1,500 ₹9,000 | 500 ₹3,000 Lowest |
| 6.01 | Supply only Analogue Ammeter Class 1, 5 A, 3 phase. | 6 | EACH | 1,737 ₹10,422 | 1,500 ₹9,000 | 1,250 ₹7,500 Lowest |
| 6.02 | Supply only Analogue Voltmeter Class 1, 3 Ph. | 4 | EACH | 1,930 ₹7,720 | 1,500 ₹6,000 | 1,450 ₹5,800 Lowest |
| 6.03 | Supply only Frequancy meter single phase, Class 0.20. | 3 | EACH | 1,737 ₹5,211 | 1,500 ₹4,500 | 1,200 ₹3,600 Lowest |
| 7.00Repair/ over hauling of self starter assembly of any type/make/ model including replacement of bearing bushing, washer, bendix pinion, carbon bush etc complete as required for proper functioning for the following capacities of DG sets complete all as directed by Engr-in-Charge:- | ||||||
Tender Value
₹35 L
EMD Value
₹70,000
Closing Date
31 Jul 2025, 6:00 pmClosed
GE SHILLONG
GE SHILLONG SHILLONG PIN 793002
REPAIR/MAINT OF D G SETS AND SOLAR WATER HEATER AND LAUNDARY PLANT AND OTHER MISC SERVICES AT CANTT AREA UNDER GE SHILLONG
2025_MES_717381_1
GE/SHL/TOKEN-46 OF 2025-26
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE SHILLONG
ALL AS PER TENDER DOCUMENT
7 documents required · 7 mandatory
₹500
GE SHILLONG
₹70,000
Yes
13 Sept 2025
28 Jun 2025
2 Aug 2025
28 Jun 2025
31 Jul 2025
12 Jul 2025
Amount
M/L for Repair & Maintenance and servicing of standby DG Set upto capacity 40 KVA, complete including draining out of diesel from tank , cleaning the tank thoroughly and refilling the drained out diesel, draining out engine oil from the sump, cleaning the sump thoroughly and refilling the sump with new engine oil to it’s required level, replacing the fuel filter, lubricating oil filter , check & clean air cleaner , change air cleaner elements, check coolant level & make up the same ,drain the fuel filter & water separator ,filling the starting batteries with electrolyte/distilled water to maintain the required specific gravity, replace the u/s brass connectors for batteries, cleaning of battery terminals & applying petroleum jelly to battery terminal posts & brass connectors, including M & L for V Belts, checking of exhaust leakage, governor, breathers etc, adjust/set the same for proper functioning of DG Set, checking of fuel, oil and water/ coolant level etc, adjusting and keeping the fan belts to the desired tension, tightening all the bolts and nuts to the required torque etc, cleaning the DG Set with accessories as prescribed by the manufacturer and test for satisfactory running of DG set for two hour at connected load and record shall be made in respect of RPM , oil pressure , oil temperature , coolant temperature, voltage , frequency , load current , battery charging , fuel consumption etc complete all as specified and directed by Engineer in Charge. (a). Engine oil for refilling will be measured & paid separately. (b). Coolant for make up will be measured & paid separately (c). The Make of Fuel filter , Oil Filter , V belt & component will be as per manufactures recommendations and quoted item is not inclusive of cost of fuel filter, oil filter, air filter and V belt. Capacity of DG 15 to 50 KVA and Make of DG Set Kirlosker/Cummins/Ashok Layland /CG/Sudhir
All as per Srl Item No.1 here-in-before but capacity of DG set 62.5/63 KVA and Make of DG Set Kirlosker/Cummins/Ashok Layland/CG/Sudhir
All as per Srl Item No.1 here-in-before but capacity of DG set 82.5 KVA and Make of DG Set Kirlosker/Cummins/ Ashok Layland/CG/Sudhir
All as per Srl Item No.1 here-in-before but capacity of DG set 125 KVA and Make of DG Set Kirlosker/Cummins/Ashok Layland/CG/Sudhir
All as per Srl Item no.1 here-in-before but capacity of DG set of 160/180/200 KVA Make of DG Set Kirlosker/Cummins/Ashok Layland/CG/Sudhir
Repair/maintenance of existing control panel of DG set by replacing the connected items such as leads, copper wire, thimble , Analogue Ammeter, Analogue voltmeter,frequancy meter etc along with other minor parts required for carrying out maintenance complete all as directed by Engineer in Charge. Note- Ammeter, Voltmeter and frequancy meter shall be measured and paid separately as supply only items below and labour element involve for replacing the same shall deemed to be included in the rate quoted against these item.
Supply only Analogue Ammeter Class 1, 5 A, 3 phase.
Supply only Analogue Voltmeter Class 1, 3 Ph.
Supply only Frequancy meter single phase, Class 0.20.
Repair/ over hauling of self starter assembly of any type/make/ model including replacement of bearing bushing, washer, bendix pinion, carbon bush etc complete as required for proper functioning for the following capacities of DG sets complete all as directed by Engr-in-Charge:-
DG set 180 to 200 KVA
DG set 125 to 160 KVA
DG set 63 to 82.50 KVA
DG set 10 to 40 KVA Note: Item No 7.01 to 7.04 (i) Make of DG Sets shall be as specified against item No 1 here-in-before. (ii) Repair works shall be carried out by authorised agent / dealer of DG Sets.
Disconnecting the Exhaust Pipe Line with mufler of DG set from Exhaust Manifold of the Engine and removing the Unserviceable Asbestos Rope from the Exhaust Pipe, Cleaning the Exhaust Pipe and cutting the mufler removing all Carbon Particles Inside including wrapping of existing asbestos rope complete all as directed by Engr-in-charge for the following capacities of DG Sets:
DG set 180 to 200 KVA
DG set 125 to 160 KVA
DG set 63 to 82.50 KVA
DG set 10 to 40 KVA
Dismantaling Radiator assembly from DG set Engine from inside and out side , Cleaning and Washing the Radiators & fins by Compressed Air with Chemical Water, removing all dust, etc. from the Radiator and Filling Coolant, re-assemble the same in Original Position with new gaskets, radiator connecting hoses and clamps complete all as directed by Engr-in-charge, for the following capacities DG Sets:- Note:- (i) Coolant shall be measured and paid seperatly under relevnt items of these schudule. (ii) Asbestos rope shall be measured and paid separately under relevant items of these schedule. (iii) Repair works shall be carried out by authorised agent / dealer of DG Sets. (iv) Make of DG Sets shall be as spesified against item No 1 here-in-before.
DG set 180 to 200 KVA
DG set 125 to 160 KVA
DG set 63 to 82.50 KVA
DG set 10 to 40 KVA
Disconnecting the fuel tank including Inlet/Outlet Connections of the following capacities of DG sets and cleaning the Tank properly and removing all dusts, mud, etc. and refixing the fuel tank and Inlet/Outlet Pipe connections in orginal position complete all as directed by Engr-in-charge.
DG set 180 to 200 KVA
DG set 125 to 160 KVA
DG set 63 to 82.50 KVA
DG set 10 to 40 KVA Note: Item No 10.01 to 10.04 (i) Repair/ maintenance & servicing shall be carried out through authorized representative of manufacturer's of DG Sets.
Material and labour for Rewinding of starter armature complete for the following capacities of DG sets With super enamelled copper winding wire including taking out old unserviceable winding :-
DG set 180 to 200 KVA
DG set 125 to 160 KVA
DG set 63 to 82.50 KVA
DG set 10 to 40 KVA Note: Item No 11.01 to 11.04 (i) Make of DG Set shall be as specified against item No 1 here-in-before. (ii) Repair/ maintenance & servicing shall be carried out through authorized representative of manufacturer's of DG Sets.
Repair / over hauling of automatic/manual, Governor assembly of any make/type/model complete including calibration and replacement of spare parts as required to make the governor 100 % trouble free complete all as directed by Engr-in-Charge:-
DG set 180 to 200 KVA
DG set 125 to 160 KVA
DG set 63 to 82.50 KVA
DG set 10 to 40 KVA Note: Item No 12.01 to 12.04 (i) Make of DG Set shall be as specified against item No 1 here-in-before. (ii) Cost of spare parts shall deemed to be included in the rate quoted .
M & L in repair to taking down demage/unserviceble Battery of 12 Volts 180 AH by replace new battery of same capcity complete all as required including charging etc for proper functioning complete all as specified and directed by Engr-in-Charge. Make- Exide/Luminous/Amaron.
All as per item No. 13 above but for 80 to 120 AH Battery as per requirement Make- Exide/Luminous/Amaron.
Repair/ over hauling, servicing of alternator for battery charger of 12 Volt Battery of any make / type / rewinding of armature and field coil including replacement of bearing / bushing etc and make the alternator 100% serviceable complete all as directed by Engineer-in-Charge.
S&F MCCB 4 pole 400 Amps, 36 KA,415 Volts, with thermal magenetic release, etc complete including taking down old unserviceable MCCB. Make- L&T Cat No CM98403OOROOG or equivalent model from make legrand/Siemens/ Havells
S&F MCCB 250 Amps Four pole 25 KA 415 Volts ,adjustable thermal & fixed Magnetic setting Make including taking down old unserviceable MCCB : Havells Cat No IHLANF0250 or L&T cat NO-CM90642OOPO equvalent model from Legrand/Siemens / Havells
Repair/ servicing of alternator of any make/type/model including grinding/polishing of slip rings assembly cleaning and re-tensioning of carbon bush holder including replacement of carbon bush for the alternators of following DG Sets :
DG set 125 to 200 KVA
DG set 40 to 82.5 KVA
DG set 10 to 30 KVA Note: Item No 18.01 to 18.03 (i) Make of DG Set shall be as specified against item No 1 here-in-before. (ii) Cost of spare shall demand to be included in the rate quoted by the tender
Taking out of defective automatic voltage regulator (AVR) of DG set (alternator side) and supply and fix New automatic voltage regulator (AVR) including necessary connection, testing and cable work etc complete all as directed by Engr-in-charge for the following capacities of DG Sets :-
(a) DG set 160 to 200 KVA
(b) DG set 30 to 140 KVA
Supply only the following spare parts (if required) for DG set 180/200 KVA as specified against item No 1 here-in-before.
Gasket set.
Head gasket
Valve steam seal
Rear oil seal
Front oil seal
Hose pipe set
Hose clamp set
Flexible pipe set
Copper washer set.
Air filter set.
Diesel filter set.
Oil filter set.
Fan belt.
Solonied switch.
Oil temperature gauge
Oil pressure gauge
Lube oil pump
Stop Solonied assy
High Pressure pipe
Door Lock
Supply only the following spare parts for DG set 63 to 160 KVA as specified against item No 1 here-in-before.
Gasket set.
Head gasket
Valve steam seal
Rear oil seal
Front oil seal
Hose pipe set
Hose clamp set
Flexible pipe set
Copper washer set.
Air filter set.
Diesel filter set.
Oil filter set.
Fan belt.
Solonied switch.
Oil temperature gauge
Oil pressure gauge
Lube oil pump
Stop Solonied assy
High Pressure pipe
Door Lock
Supply only the following spare parts for DG set 10 to 40 KVA as specified against item No 1 here-in-before.
Gasket set.
Head gasket
Valve steam seal
Rear oil seal
Front oil seal
Hose pipe set
Hose clamp set
Flexible pipe set
Copper washer set.
Air filter set.
Diesel filter set.
Oil filter set.
Fan belt.
Solonied switch.
Oil temperature gauge
Oil pressure gauge
Lube oil pump
Stop Solonied assy
High Pressure pipe
Door Lock
Supply only Engine Oil (20 W 40) Make- Servo/Castrol /BPCL.
Supply only Coolent Make- Fleet Guard or equivalent Make as approved by GE.
Supply only Distilled water for Battery as per sample
Supply and Fix Asbestos rope of required size.
S&F in repairs Battery connection cable of length 1.2 Mtr with solid brass clamp lugs for "+" terminals at one side and copper lug on other side.
S&F in repairs Battery connection cable of length 1.2 Mtr with solid brass clamp lugs for "-" terminals at one side and copper lug on other side.
M&L Earthing with galvanized steel earth plate electrode of size 600 mm x 600 mm x 6.00 mm buried directly in ground connected to galvanized earth lead strip of size 32 mm x 6 mm by means of bolts, nuts, check nuts and washers of galvanized iron or steel including 40mm dia medium grade GI tubing for protection of earth lead, MS sheet metal funnel with wire mesh, watering pipe light grade 20mm dia, charcoal or coke and common salt in alternative layer of 15 Cm compacted thickness all around the electrode with concrete earth pit of PCC type C1 (1:3:6, using 20mm graded crushed stone aggregates) 50mm thick precast RCC type B1, (1:2:4, using 20mm graded crushed stone aggregates) pit cover reinforced with 8mm dia deformed bar and suitable handle made of 10mm dia round bar including galvanised strip of size 32mm x 6mm for extension of earth lead and necessary excavation, earth work, in soft/loose soil and disposal of spoils to a distance n.exc 50m and necessary connection and testing complete all as shown in electrical plate No 3 of SSR Part-I, 2009 and all as specified and directed including taking down old unserviceable earth pit and accessories. Note : GI Strip upto 7.5m length shall be deemed to include in the cost of above item. This quantity required over and above shall be measured under relevant items of these schedule.
S&F, GI strip 32 x 6 mm as eath continuity conductor or main earthing lead buried in ground or drawn through pipes or fixed to wall or poles or any other situation for loop earthing etc including dismantling old unserviceable strip complete all as specified and directed by Engr-in-Charge.
Excavation In trenches not exceeding 1.5m wide and not exceeding 1.5m deep and getting out in soft/soil for laying/removing of UG cables complete all as specified and directed.
Returning, filling in, including, spreading, levelling, watering and wall ramming, in layers not exceeding 25Cm in soil obtained from excavation complete all as specified and directed.
Removal of surplus soil to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above starting point
M & L for providing dry river sand as in sand cushioning to UG cable including punning gently complete all as specified and directed.
M & L Sub class'B' old size well burnt brick laid flat in trenches as protection to LT cable complete all as specified and as directed.
S&F XLPE insulated, screened, PVC bedded, galvanized steel strip of wire armoured, electric power cables (heavy duty) 1100 Volts grade, with stranded aluminium conductor of size 150 Sqmm 3.5 core, including taking out old unserviceable cable complete all as specified and as directed.
All as per item No. 42 above but size of XLPE cables 120 Sqmm 3.5 core.
All as per item No. 42 above but size of XLPE cables 95 Sqmm 3.5 core.
All as per item No. 42 above but size of XLPE cables 70 Sqmm 3.5 core.
All as per item No. 42 above but size of XLPE cables 50 Sqmm 3.5 core.
S&F Changeover switch 400 Amps, in sheet steel enclosure, 4 Pole, side handle operated complete including taking down old unserviceable one. Make:- L&T Cat Part No. CO44000OSOO or equivalent model from Make:- Schneider / Siemens / Legrand / Havells
S&F Changeover switch 250 Amps, in sheet steel enclosure, 4 Pole, side handle operated complete including taking down old unserviceable one. Make:- L&T Cat Part No. CO32500OSOO or equivalent model from Make:- Schneider / Siemens / Legrand / Havells
S&F Changeover switch 160 Amps, in sheet steel enclosure, 4 Pole, side handle operated complete including taking down old unserviceable one. Make:- L&T Cat Part No. CO21600OSOO or equivalent model from Make:- Schneider / Siemens / Legrand / Havells
S&F Changeover switch 63 Amps, in sheet steel enclosure, 4 Pole, side handle operated complete including taking down old unserviceable one. Make:- L&T Cat Part No. CO10630OSOO or equivalent model from Make:- Schneider / Siemens / Legrand / Havells
S&F MCCB, 3 pole, 415 Volts,160 Amps, 36 kA breaking capacity with thermal and magnetic release including taking down old unserviceable one. Make :- 'L&T' Cat part No. CM92008OOM1OG or equivalent model from make:- Legrand / Schneider / Legrand / Havells
S&F MCCB, 3 pole, 415 Volts,125 Amps, 16 kA breaking capacity with thermal and magnetic release including taking down old unserviceable one. Make :- 'L&T' Cat part No. CM90676OOLO or equivalent model from make:- Legrand / Schneider / Legrand / Havells
S&F MCCB, 3 pole, 415 Volts,100 Amps, 16 kA breaking capacity with thermal and magnetic release including taking down old unserviceable one. Make :- 'L&T' Cat part No.CM90517OOKO or equivalent model from make:- Legrand / Schneider / Legrand / Havells
Supply only MCCB, 3 pole, 415 Volts, 63 Amps, 16 kA breaking capacity with thermal and magnetic release including taking down old unserviceable one. Make :- 'L&T' Cat part No.CM90517OOHO or equivalent model from make:- Legrand / Schneider/ Havells Note:- Materials shall be fixed to panel board as mentioned here in after.
M&L 25mm thick PCC type B2 ( 1:2:4, using 40 mm graded aggregates) as in floor, finished even and smooth without using extra cement including demolition of old unserviceable concrete complete all as specified and as directed.
Supply only First aid Kit with all accessories including necessary medicines complete all as directed.
Supplying and laying insulated Electrical matting class 1, proof voltage tested upto 10 KV, 2mm thick ness of size 1.00 mtr (wide) with one side fabric and other side plain finish as per IEC 61111 including taking out old unserviceable rubber matting. Make:- Raychem or equivalent as approved by Accepting officer.
Excavation in trenches not exceeding 1.5m wide and not exc. 1.5m depth and getting out in soft/loose soil complete all as specified and as directed.
Excavation in trenches not exceeding 1.5m wide and exc. 1.5m depth not exc 3.0m depth and getting out in soft/loose soil complete all as specified and as directed.
Returning, filling, including spreading, leveling, watering and well ramming in layers not exc. 25cmin soft/loose soil complete all as specified and as directed.
Removal of excavated soil to a distance not exc 50 m and depositing where directed at a level not exc 1.5 mtr above the starting point complete all as directed.
Supply and lay for dry river sand filling for cable protection with a layer of 8cm deep before laying and 15cm covering above the top edge of cable after laying complete all as specified and as directed. (Note : Punned thickness shall be measured).
Laying only serviceable bricks for protection of cable obtained during excavation from item No. 5 here-in-before.
Supply, laying & testing cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminiium conductor, 1100 volts grade cross sectional area 150 sq. mm 3½ Core complete all as directed by Engr-in-Charge.
All as per item No 12 above but 120 Sqmm 3½ Core
All as per item No 12 above but 95 Sqmm 3½ Core
All as per item No 12 above but 70 Sqmm 3½ Core
All as per item No 12 above but 50 Sqmm 3½ Core
All as per item No 12 above but 25 Sqmm 4 Core
All as per item No 12 above but 16 Sqmm 2 Core
Shifting of DG set any capacity/location to another location with the half of recovery van including disconnecting of earth wire, cables and connection at new location complete all as specified and directed by engr-in-charge. Note : Any damaged cause during shifting shall be contractors responsibility and to be made good without any extra cost to be department.
Material and labour, for testing and full servicing of Washing Machine front loading open pocket capacity 50kg with replacement of following spare part and wash room trolly sheet of size 1016x761x863 mm with roller and dry lines trolly size 930x630x80mm with roller. Washing Machine No 1, 2 & 3 including taking down old one complete including small spare part all as specified and directed. Make- BTC (NOTE : All Work shall be done by OEM and shall produce fitness certificate of machine)
Main Bearing Make- ZKL , SKF , TATA
Counter Bearing Make - ZKL & SKF , TATA
Control panel Make- L&T , MUKAND , BCH
Temperature controller Make- INSTAMES
Drain valve Make- SOCLA , AUDCO , KEYSTONE VALVE
V-Belt Make- GIMPEX , ISCOKON , EMCON
Material and labour for testing and full servicing of Drying tumblar front loading auto timed 50 kg and replacement of following spare part Drying tumblar- 1 & 2. including taking down old one complete including small spare part all as specified and directed. Make- BTC (NOTE : All Work shall be done by OEM and produce fitness certificate of machine)
Steam Readiater Make- CUSTMIZED
Main Bearing Make- ZKL , SKF , TATA 2
Counter Bearing Make- ZKL & SKF , TATA
Temperature controller Make- INSTAMES
Contractor Make- L&T & ELTEK , BCH
Material and labour for testing and full servicing of Hydro extractor M/C top loading 25 Kg and replacement of following spare part Drying tumblar- 1 & 2, including taking down old one complete including small spare part all as specified and directed. Make- BTC (NOTE : All Work shall be done by OEM and shall produce fitness certificate of machine)
Rubber Buffer Bush Make- CUSTMIZED
Control panel Make- L& T , MUKAND , BCH
Timer Make- DEHL ,OZO , MINILEC
Bearing set Make- ZKL & SKF , TATA
Contractor Make- L & T , SKF , TATA
Material and labour for testing and servicing of flat Work Ironer and replacement of following spare part, including taking down old one complete including small spare part all as specified and directed. (NOTE : All Work shall be done by OEM and produce fitness certificate of machine)
Pading + cloth
chest rabbing polish buffiing
Material and labour for testing and servicing of steam heater for drying chamber including all necessary spare part / item size 29" x 8.3" x 18.5 : (SS Pipes ) including taking down old one complete including small spare part all as specified and directed. (NOTE : All Work shall be done by OEM and shall produce fitness certificate of machine)
Material and labour for testing and servicing of full D-scaling (Chemical wash) of Boiler tube for Boiler No. 1 & 2 and replacement of following spare part Burner, Pump ,Inspection, Fire kit, Water Pump, Temperature Controller & indicator lamp etc. including small spare part or Boiler No. 1 & 2 with ( Note : After completion of work Calibration Certification for Boiler Nos. 1 & 2 should be produced to department) including taking down old one complete all as specified and directed. Make- M/s A S Thermofeed Pvt. Ltd (NOTE : All Work shall be done by OEM and shall produce fitness certificate of machine)
New coil including asbestor tape, rope, gasket and reactors along with new NRV, diffuser plate with pump. Make- KIRLOSKER , CROM
Full set economizer. Make- BABA THRUM ,MEXOTHERM SUNMAX
New fuel pump along with fuel hose, fuel pressure gauge, steam pressure guage and pressure switch. Make- KIRLOSKER ,CROMPTON, EVEREST
Electrical Control Panel Make- L &T , ELTEK , MUKAND 1
Relay & Breaker, timer, burner sequence controller. Make- L&T,ELTEK , MUKAND 1
Temperature Controller Make- ELTEK , MUKAND 1
indicator lamp Make- L&T,ELTEK , MUKAND
Material and labour for testing and full servicing of Flat Bed Press automatic temp control -1 & 2 and replacement of following spare part Flat Bed Press - 1 & 2, including taking down old one complete including small spare part all as specified and directed. Make- BTC (NOTE : All Work shall be done by OEM and shall produce fitness certificate of machine)
Synchronous timer Make- L&T , ELTEK , BCH
Contractor Make- L & T , ELTEK , BCH
Cylinder Make-GANPATI , COSTMIZED
Material and labour for testing and full servicing of AZR Compressor with 7.5 HP Motor , 10kg/cm2 and replacement of following spare part for AZR Compressor- 1 & 2, including taking down old one including small spare part complete all as specified and directed. Make- M/s Khosla (NOTE : All Work shall be done by OEM and shall produce fitness certificate of machine)
Piston Make- EVEREST ,POWER HOUSE
Cylinder Make- EVEREST ,POWER HOUSE
Material and labour for testing and full servicing of MS Steam pipe bounded mineral wool sanp on lagging with aluminum etc including taking down old one including small spare part complete all as specified and directed (NOTE : All Work shall be done by OEM and shall produce fitness certificate of machine)
Material and labour for testing and full servicing of Water softener plant (up flow) hydrion packed with all necessary spare part etc. including taking down old one including small spare part complete all as specified and directed (NOTE : All Work shall be done by OEM and shall produce fitness certificate of machine)
Dismantling complete solar water heating of capacity 100 ltr per day including hot & cold water pipes and hot water tank complete. Repairing the sys fixing back in position and testing complete all as specified and as directed. Note:- Rate quoted by the contractor shall deemed to be included for :- (a) Making good the worn out missing nuts bolts, washers, union socket, flanges and screws etc. (b) Dismantling the solar panel descaling of hot water pipes by using appropriate chemicals, cleaning and washing all copper tube throughly cleaning the complete panel, making the tubes scale free and reassembling the panel. (c) Cleaning cold water tanks. (d) All other materials shall be measured and paid separately under respective item.
All as per item No 106 but cap 500 LPD
S & F in repairs solar energy collector panel complete of cap 100 Ltrs per day camplete all as specified and as directed. Make- Solchrome
Supply only Hi strenth granular chlorination chemical based with CIAS to be ratified by E-in C's branch,dry free flowing constant white granulesand without hard lumps or impurities should not induce substances beyound acceptable limit as give in IS 10500: 2012 intreated and disinfactant water, cholorine content by mass packed in 45 Kgs PVC sealed container, 5-10% moisture content up to 4% calicium Hydrooside upto 15% sodium chloride suitable for treatment of drinking water and swimming pool all as specified and as directed. (Make : Conforming to generic BIS specifications as approved by GE).
Supply only Alum Ferric( brick type) TI BIS 260-2001 complete all as specified and directed.
S K Construction (BID ID -3376765)
MAHINDER ELECTRICALS (BID ID -3363998)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .