Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹17.3 CrAccepted-AOC | ₹17.3 Cr | L1 | Accepted-AOC Being lowest |
| 2 | L2₹18.2 CrRejected-Finance | ₹18.2 Cr | L2 | Rejected-Finance Other than lowest. |
| 3 | L3₹18.8 CrRejected-Finance B 604 VASUNDHRA APARTMENTS PLOT NO 16 SECTOR 6 DWARKA NEW DELHI 110075 | NEW DELHI | SOUTH WEST DELHI | DELHI | 110075 | ₹18.8 Cr | L3 | Rejected-Finance Other than lowest. |
| 4 | L4₹20.5 CrRejected-Finance | ₹20.5 Cr | L4 | Rejected-Finance Other than lowest. |
| 5 | L5₹21.1 CrRejected-Finance F 18 ANSAL COMPLEX OPP JWALA HARI MARKET PASCHIM VIHAR NEW DELHI 110063 | NEW DELHI | WEST DELHI | DELHI | 110063 | ₹21.1 Cr | L5 | Rejected-Finance Other than lowest. |
Tender Value
₹17.8 Cr
EMD Value
₹12.1 L
Closing Date
26 Jul 2023, 6:00 pmClosed
Chief Engineer Delhi Zone
HQ Chief Engineer Delhi Zone Delhi Cantt-10
PROVN OF KLP OF ARTY UNIT AT DELHI CANTT-10 PHASE I UNDER GE NORTH
2023_MES_596359_1
CA No CEDZ/TOKEN-10 of 2023
Open Tender
Civil Works
545 days
Delhi Cantt-10
As per NIT
9 documents required · 9 mandatory
₹3,000
GE North
₹12.1 L
Yes
HQ Chief Engineer Delhi Zone
5 Aug 2023
18 May 2023
28 Jul 2023
18 May 2023
26 Jul 2023
12 Jul 2023
22 May 2023 - 27 May 2023
29 May 2023
Amount
Lump sum price worked out by the contractor for Schedule 'A' Section-I (Bldg Work)(Ref pre priced Schedule attached seperately)
Lump sum price worked out by the contractor for Schedule 'A' Section-II (Internal Water supply) (Ref pre priced Schedule attached seperately)
Lump sum price worked out by the contractor for Schedule 'A' Section-III (Exacavation and Earth Work) (Ref pre priced Schedule attached seperately)
Lump sum price worked out by the contractor for Schedule 'A' Section-IV (Internal Electric supply) (Ref pre priced Schedule attached seperately)
Lump sum price worked out by the contractor for Schedule 'A' Section-V (Site Clearance) (Ref pre priced Schedule attached seperately)
Lump sum price worked out by the contractor for Schedule 'A' Section-VI (Demolition and Dismantling) (Ref pre priced Schedule attached seperately)
Lump sum price worked out by the contractor for Schedule 'A' Section-VII (DG Set) (Ref pre priced Schedule attached seperately)
Lump sum price worked out by the contractor for Schedule 'A' Section-VIII (Summer Appliances) (Ref pre priced Schedule attached seperately)
Lump sum price worked out by the contractor for Schedule 'A' Section-IX (Hot Water Supply) (Ref pre priced Schedule attached seperately)
Lump sum price worked out by the contractor for Schedule 'A' Section-X (Lightning protection) (Ref pre priced Schedule attached seperately)
Lump sum price worked out by the contractor for Schedule 'A' Section-XI (Conduit for TV/Tele) (Ref pre priced Schedule attached seperately)
Lump sum price worked out by the contractor for Schedule 'A' Section-XII (Road, path and culvert) (Ref pre priced Schedule attached seperately)
Lump sum price worked out by the contractor for Schedule 'A' Section-XIII (External Water Supply) (Ref pre priced Schedule attached seperately)
Lump sum price worked out by the contractor for Schedule 'A' Section-XIV (External Electric Supply) (Ref pre priced Schedule attached seperately)
Lump sum price worked out by the contractor for Schedule 'A' Section-XV (Sewage Disposal) (Ref pre priced Schedule attached seperately)
Lump sum price worked out by the contractor for Schedule 'A' Section-XVI (Area Drainage) (Ref pre priced Schedule attached seperately)
Lump sum price worked out by the contractor for Schedule 'A' Section-XVII (Boundary Wall) (Ref pre priced Schedule attached seperately)
Lump sum price worked out by the contractor for Schedule 'A' Section-XVIII (Rain Water Harvesting) (Ref pre priced Schedule attached seperately)
Description of Work / Item(s)
Amount
INTERNAL WATER SUPPLY
S&F 15mm bore long body bib taps cast copper alloy chromium plated with crutch or butterfly handle screwed down, complete all as specified and directed.
INTERNAL ELECTRIC SUPPLY
S&F surface mounted LED building security light fitting in high pressure die cast aluminium housing not less than 25 watt fixture should have minimum efficiency at level >=120lumens/watt, life of fixture not less than 50K Hrs, Ripple<5%, UGR<19, Minimum surge protection level of 4 KV, CCT 4000-6500K with same lumens/w CRI>80, PF>0.95, THD<10%@240V AC, an operating voltage range of 140-270V including light grade GI tube mounting size 40MM bracket of suitable size & length, bend to shape and fixed to wall by means of 02 nos. of 40 x 5 mm flat iron clamps, nuts, bolts and washers etc complete and one coat of primer and one coat of synthetic enamel paint after coating of primer on GI bracket and pre-wired incl connecting up with PVC insulated copper conductor cable 1.5 Sqmm, 3 core complete all as specified and as directed.
S&F energy saving rotating security search light fitting of 50 watts, pressure die-cast aluminium IP 66 with high power LED as light source comprising with electronic driver and all accessories pre-wired incl connecting up with PVC insulated copper conductor cable 1.5 Sqmm, 3 core as required for connections complete .
Suppy & fixing DBOXx MCB Protected Socket 15 Amps , PVC Plastic Base (white) with Plug top 25 Amps & MCB SP 32 amps complete all as specified and directed.
Supply, installation, testing & commissioning LT distribution cubical panel indoor type, double door with rigid hinges, door handle locking arrangement back side openable, compartmentalized design, mounted on suitable PCC blocks, fabricated out of CRCA sheet 2.0 mm thick, suitably spaced, totally enclosed in chamber for reception of 3 phase, 440 volt, 50 HZ, AC supply including all connection with aluminium strips, internal wiring with suitable size of PVC copper conductor wire with lugs panel shall be effectively PVC gasketed and sealed, glands to be provided at cable entries, powder coated painting and sign writing for in/out going connections and bottom support by MS channel MC-75 grouting in PCC 1:2:4, height 450 mm from ground level complete & having IP54 ingress protection all as specified and directed and comprising of following (i)4 Nos bus bars of high conductivity aluminium alloy, 3 Nos for phase (R,Y,B) rating 300 amp rating and 1 No for neutral rating 150 amp, mounted on DMC support with heat shrink sleeve - 01 set. (ii) MCCB 4 pole, 125 amp, 415 volts, 16 KA - 01 No (Incoming) (iii) MCCB 4 pole, 63 amp, 415 volts, 16 KA - 05 Nos (Outging) (iv) Multifunction energy meter ; three phase to Measure V, I, Hz, Kw, KVAr, KVA, PF, PA, I/E, KWH &KVArh, KVAh, Demand & Max Demand - A, Kw & KVA, etc. with inbuilt RS 485/ MODBUS Card along with necessary CTs acc class 0.5,10 VA Aux Supply: 230 V :- 01 Sets (v) Indication lamp (R,Y,B), LED type - One set of three
DG SET
(b) AC Alternator (Brush Less) : The AC alternator (Generator) shall be designed for an output of 50 KVA/ 40 KW at ful load for continous rating 10% for over load for one hour at 0.8 (lag) PF conforming to IS-4722 & 13364 or BS-5000 RPM 1500 including self excited and self regulating Electronic voltage panel with all accessories cable termina bo suitable size of glands earth terminal etc complete all as per OEM specifictions.
(c) Diesel Engine : The engine shall be vertical multi cylinder four stroke 1500 RPM water cooled with water pump asembly battery charging alternator of suitable instrument panel, electronic in built governor starting bateries heavy duty with leads (as recommended by the manufacturer) suitable size and length of exhaust pipe with necessary clading materials, exhaust coupling inside accousitc enclosure/ canopy, silencer and exhaust pipe above canopy al as fixtures all as per OEM specification complete as per IS 1602 or BSS-649 & suitale BHP for the generator, (BHP not less than 75 BHP) according to IS-10002, BS 5514, supply and installation of diesel engine driven generating set in cooperating engine of minimum 75 BHP/1500 RPM turbocharged after cooled water cooled with alternator of 50 KVA/ 40 KW, 415 V, 0.8 PF, 50 Hz, AC, brushless alternator mounted on a common base frame alongwith all standard accessories i.e. fuel tank, electric reinforcement of 8mm TMT bars & 100mm c/c borth directions including MS angle in frame of 40 x 40 x 3mm etc to acheive earth resistance less than 01 Ohm including testing comlete a complete relay panel for noise free compartment (acoustic enclosure) housing all as directed
(d) The tools as per the manuacturer's list shall be provided by the contractor alongwith the set at no extra cost. (e) Unit rate quoted shall deemed include the control cable from DG set to AMF panel, Diesel oil, Lub Oil, Coolant for Radiator etc for smooth functioning of DG Set during PH I & PH II complete testing (at factory premises before dispatch & at site after commissioning) and full tank filling of Diesel oil after PH I & II testing (at factory premises before dispatch & at site after commissioning) topping of Lub Oil, Coolant for Radiator etc required for commissioning and testing of DG Set
COOLING APPLIANCES
Supply and fix refrigerator, electric driven (single phase), capacity upto to 195/ 198 Litres BEE 5 star rated complete
S&F voltage stabilizer for automatic operation, single phase naturally air cooled, indoor wall mounted type, fully elecronic controlled & designed for input variation between 170 V to 250 V with output voltage stabilized at 230 V with accuracy of ± 2.5 % and of capacity 1.0 KVA complete all as directed (Make : Microtech/Blue Bird/V-Guard/Zenith/Sinetrac)
S&F voltage stabilizer for automatic operation, single phase naturally air cooled, indoor wall mounted type, fully elecronic controlled & designed for input variation between 170 V to 250 V with output voltage stabilized at 230 V with accuracy of ± 2.5 % and of capacity 2.0 KVA complete all as directed (Make : Microtech/Blue Bird/V-Guard/Zenith/Sinetrac)
Supply and fix desert air cooler electric driven (single phase), Plastic Body, water tank capacity not less than 100 ltr, having nominal air flow/ delivery rate capacity of 4000 CuM per hour (or nearest size) with pump and all accessories cpmplete all as specified & directed (Make : Crompton / Usha / Croma / Bajaj / Symphony)
CONDUIT FOR TV/TELE
Supply and fixing RJ112 Tel jack with shutter modular type Complete
EXTERNAL WATER SUPPLY
M&L for Boring holes under road pavement by bocky manually, in any type of soil upto 100 mm bore complete all as specified and as directed
M&L for provision of MS header of size 200mm bore with end plate and length 3 mtr inclduing incoming supply 2 nos with MS pipe 80 mm and outgoing with 2 Nos MS pipe 80 mm & 1 No 50 mm with flanged end and end plate cover, nuts bolts, etc for provision of sluice valve complete
M&L for pipe ductile Iron, S/S including specials, Class “K7” ,100 mm (4”) dia complete all as specified and directed
Material and labour for DI specials such as Tees, bends of any size and radius, collars, tapers, tail pieces, caps and plugs etc upto 150mm bore
M&L Rubber Gasket Joint (Tyton Joint) including jointing material for DI/CI pipe of 100 mm size/ bore complete all as specified & directed.
Supply,installation,testing and commissioning SITC of motor actuated butterfly valves with the following specification including all accessories as required complete all as specified and directed Butterfly valve specification:-(a)Valve size: 100 mm (b) design pressure: PN1.6 (c) operating angle: 90 degree; (d) MoC: body & disc-Cl, body seat ring :SS AISI 304, Disc seal- nitrile/EPDM rubber, clamping ring- cast steel (WCB/MS).Shaft-SS AISI 410: (e) Design & manufacturing standard: IS: 13095 /BS EN 593(BS 5155), testing standard: IS:13095/BS EN 12266, Pressure rating Standard-IS:13095, BS EN593 (BS 5155) (f) Low friction self-lubricated sleeve type bearings Actuator Specification: (a) Enclosure: IP68 watertight; (b) Power supply: 230V AC, 50 Hz / 400 V AC (3 Phase), 50 Hz/24 V DC (c) travel angle :90'+ 5; (d) Casing Material: Aluminum Alloy. Dry power polyester coated; (e) Motor: totally enclosed non ventilating type, insulation -IEC 85 Class F (155 C), totally separated from lubricant filled gearing of Actuator, protected by 3 monitoring device embedded in motor winding: (f) Limit Switches: 2 X open / 2 X close, SPDT, 230V AC; (g) Space heater: 230V AC anti condensation; Ambient temp: -20 to 60 Celsius : (h) hand wheel for manual operation : (i) hall sensor based absolute encoder for limit sensing with a resolution of 3' or better in case of power failure, Actuator shall not be equipped with battery: Make: RotorkPlc, Festo AG & Co. KG, Pentair Plc, Honey well, Emerson electric, Cameron international corporation, Marsh automation pvt. Ltd., Sdtrok, Auma actuators, Johnson Valves, Kirloskar ( Note: Valve & Actuator assembly unit to be supplied as 1 package tested & issued with certification confirming the actuator functionality before dispatch).
Supply,installation,testing and commissioning of open well submersible pump set having CI casing impeller & SS shaft, electric driven,415 volts,50 Hz, suitable for head 40 mtr,discharge 650 LPM complete all as specified and directed.
Construction of underground sump of capacity 1 lakh ltrs complete.
Supply installation, testing and commissioning of ultra-sonic level sensor with following specifications : Rust proof, maintenance free suitable for up to 6 meter water level depth of U/G sump, with dead band of less than 0.6 meter, IP67 protection, accuracy of 0.25% o F.S and 4-20mA current output, No of wires, Beam angle less than 7.5 degree capable for working in ambient temperature of 0 degree Centigrade to 75 degree Centigrade, non-condensing at 25 degree centigrade and humidity up to 95% with response time of less than 1 sec with 230 VAC to 24VDC, 50Hz power supply, Non display type, in built temperature & voltage variation compensation, vertical type mounting on top of Sump suitable for measuring water / waste water in sump, with al connection and fixing including clamp, nut bolt etc. complete all as specified and as directed make, ABB Endress + Hauser MgtsiemensKrohnePepperl + fuchs, continental Vega grieshaber Hans, turck, Gems sensors Omega engineering Keyence Texas instruments Migatron, Honeywell (Scope of work include all accessories required for the correct operation of the sensor).
Supply, Installation, Testing and Commissioning of pressure transmitters in the water supply lines. The Pressure Transmitter needs to be with proper wiring including necessary with following specification all as specified and directed by Engg -in-charge.:- Pressure Range: 0 bar to 16 bar Enclosure: whether proof IP 65 Ambient temperature: -40°C to 70°C Accuracy: 0.5 % Must have RS485 Modbus enabled communication
Supply, Installation Testing & Commissioning of Indoor type PLC ( Programmable Logic Controller ) /RTU (Remote terminal Unit) based Automation, Protection Panel for Pump and Valve with modem having feature of dual sim card, suitable for control and monitoring of 03 Nos. Centrifugal Pumps (40HP), 03 Nos. Energy Meters, 3 Nos. Motorized Butterfly Valves, 2 Nos. Pressure Transmitter, 01 Nos Ultrasonic sensor, 03 Nos. Flow Meters. The panel should be of minimum size 1200 X 950 X 300 mm front opening type, fabricated from 2.00 mm thick CRCA Sheet & mounting channel 40x40x5mm made out of Angle iron with proper ferrule & cable gland, internal wiring with PVC insulated multistranded copper conductor FRLS cable of adequate size. The Panel should comprise the following items complete all as specified and directed:- (a) Water Level Sensing & Display (b) Automatic Pump On/Off, Automatic Priming and Air Release (if required) (c) Automatic Operation of Motor Actuated Butterfly Valves (d) Automatic Toggling of Pumps or time based operation (e) Auto Change Over In Case of Pump Failure (f) Single Phasing Prevention, phase sequence corrector (g) Manual Mode Operation (all connected sub systems including all valves in pump houses and connected buildings / overhead tanks and pumps) from the PLC based Control Panel.
Supply, installation, testing and commissioning factory made and tested (incl proto type being CPRI test certified) LT feeder piller box, outdoor type, suitable for 415 volts, 3 phase 4 wire, 50 Hz AC supply system having bus bar chamber fuly insulated & neutral, installed on epoxy/SMC type insulator. The panel shall be dust and vermin proof IP-65 class protection and made of 3.15 mm thick CRCA MS sheet and powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside both side opening bype with approx of 65 mm Godrej Natural) lock with 2 keys, internal wiring with PVC insulated, solid copper conductor, FRLS cables IS-694 marked of adequate size but not less than 2.5 sqmm including installation on foundation complete. the scope of work includes the following :-
(i) MCCB 4 Pole 63 Amp 415 V,16 KA rupturing capacity with adjustable Thermal and Magnetic setting releases. - 01 No (ii) Aluminium bus bar 100 Amps with insulator - 04 Nos (iii) Digital VAF meter - 01 No (iv) LED indication lamp -01 (R Y B, set of three) (v) MCB TPN, 25 Amps ,breaking cap 16 KA - 02 Nos (vi) MCB DP, 10 Amps ,breaking cap 10 KA - 01 No (vii) Providing single phase preventer - 01 Nos (viii) Star delta motor starter suitable for pump , 415 V - 02 Nos (ix)CT: 250/5A, 5VA CL.1- 3 Nos (x) Relay for thermal protection/overheating
EXTERNAL ELECTRIC SUPPLY
Supply, installation, testing & commissioning of package type/unitised 11kV / 433 V Outdoor sub-station ,315KVA made from G. I. enclosure complete as required conforming to IEC 62271-202 only and relevant IS specifications including K-10 Temperature Class as applicable for the rating, Internal Arc of 21 KA/1 Sec. IAC AB on 1:2:4 (1 cement :2 cores and : 4 Graded stone aggrregate of 40 mm nominal size) PCC foundation of suitable size extending 500 mm all around the outdoor enclosure and 1000 mm height (above ground level) complete with suitable sizes of GI Pipes for incoming/outgoing cables/earthing strips etc. and consisting of following complete as required. Angle iron frame of size 40x40x5mm NS all along the corner of the foundation CSS shall be from OEMs only . Licensed System Integrators of approved OEM are not allowed to supply . Package substation will have the following equipment :-
HT SWITCHGEAR 11kV 630Amps 21KA/3 sec. Non-Extensible Ring Main Unit Compact switchgear consisting of 1 nos. fixed motorized Vacuum Circuit Breaker Module with a direct cable module in SF6 insulated stainless steel enclosure with series trip, self powered microprocessor based numerical over current and earth fault relay protection. HT RMU shall preferably have site replaceable bushings to have very less downtime in the event of bushing breakage and restoration can be done immediately without sending the RMU to OEM Works. Interconnection between HT Switchgear and primary of transformer shall be done through 1C x 3R x 95 sq.mm Aluminium XLPE cable. - 1 No. Vacuum Interrupter,RMU,LT Switchgear and CSS Enciosure shall be of same make to ensure life cycle optimization. Capacitive voltage indication fixed type system with LED for all feeder and FPI in all load break switch feeder. SF6 Gas pressure indicator. Operating sequence of VCB must be O-0.3Sec-CO-3 Mins-CO Protection CT shall be minimum 40/1A ,2.5VA ,5P10. - 3 nos. All modules of the RMU shall be suitable for cable termination of 3C x 300 sq.mm Al XLPE Cable, incoming cable termination is included within the scope of work - 1 Set
TRANSFORMER 315 KVA 11KV/433V DYN-11 Oil type, hermetically sealed energy efficiency level-2 transformer (BEE Star Rated-2) with corrugated wall, without conservator, type of design & Top Bushings for HT & LT with Off load tap switch of rating +5% to -5% @2.5%. Temp Rise - Oil/Winding 40/45 Deg cel. Losses (As per IS-1180 amended up to date) Max Losses @ 50% Load 955W and Max Losses @ 100% Load 2750 KW and Impedance of 4.5% (Subject to IS Tolerance (as per IS1180-2014) The transformer shall be confirming to IS: 2026 and IS: 1180(part-I). amended up to date. -One No. Winding Temperature Indicator with Alarm and trip Contact
LT PANEL LVS PANEL 630 AMPS 4 pole Aluminium BUSBAR (100% FOR PHASES AND 100% FOR NEUTRAL) - CURRENT DENSITY OF Aluminum as 1 A/sq.mm. ; LT panel made up of 2 mm thick CRCA sheet 630 Amps 433V 4P 50Hz 50KA, Manual Type with microprocessor release Air Circuit Breaker (ACB) MCCB 63 Amp,4 pole 415 V, 16 KA rupturing capacity with adjustable Thermal and Magnetic setting releases - 04 Nos MCCB ,200 Amp ,4 pole 415 V , 25 KA rupturing capacity with adjustable Thermal and Magnetic setting releases - 01 Nos MCCB,160 Amp,4 pole 415 V, 25 KA rupturing capacity with adjustable Thermal and Magnetic setting releases”. . - 02 Nos MCB 4 pole,25 Amp,415 V, rupturing cap 10 KA - 01 Nos MCCB 100 Amp, 4 pole,415V, 25 kA rupturing capacity with adjustable Thermal and Magnetic setting releases”., 415V -01 Nos LED indication lamp -01 (R Y B, set of three) Multifunction energy meter (Make: Schneider, L&T, El measure); three phase to Measure V, I, Hz, Kw, KVAr, KVA, PF, PA, I/E, KWH &KVArh, KVAh, Demand & Max Demand - A, Kw & KVA, etc. with inbuilt RS 485/MODBUS Card along with necessary CTs acc class 0.5 ,10 VA Aux Supply: 230 V :- 01 Sets 100KVAR APFC panel with minimum 12 steps as per following tentive steps ( 5KVARX4, 10KVARX8) through 250A MCCB All Civil works such as PCC/RCC foundation, Plateform, Filling trench and pedestal etc as per CSS manufacturer's recomandation are included in scope of work.
OUTDOOR ENCLOSURE Outdoor type encloser of 1.5 mm (For non load bearing members) & 2.0 mm (For load bearing members) thickness having modular construction of Galvanised Sheet Steel in suitable design for better heat dissipation and providing robust construction. The Enclosure shall have IP54 degree of protection for HT & LT switchgear compartment & IP 23 degree of protection for transformer compartment. The enclosure exterior shall be painted with epoxy based powder paint (colour RAL 7032). Each compartment will be provided with the door and pad locking arrangement. The design of the enclosure should be type tested for suitablly handling any arcing inside the compartment for providing better safety to the operator. The compartment illumination lamp with door operated switch shall be provided for each compartment. Vacuum Interrupter,RMU,LT Switchgear, Multifunction meter and CSS Enclosure shall be of same make to ensure life cycle optimization.
Supply, installation, testing and commissioning of factory made powder coated compartmentalized cubicle type LT Panel outdoor type of appropriate size and fabricated from 3.15 mm thick CRCA sheet steel with necessary MS angle iron frame work(50X50X6mm), weather proof, vermin proof, suitable rating aluminium bus bar chamber for operation on 415 volts, 50Hz, 3 Phase 4 wire AC supply complete with gland plates, lifting hooks, ventilating louvers, bus bars, inter connections, earthing terminals, labeling , cable alley suitable for termination of cables including supply and fixing of following switchgear and accessories in the panel complete as required size conforming specification as per IS 5039. The panel should be CPRI approved and having IP 65 ingress protection including necessary foundation for mounting all as specified and directed by Enginer in charge.
Incoming MCCB 200 Amps 4 pole 415 V, 25 KA rupturing capacity with adjustable Thermal and Magnetic setting releases. Outgoing :- (i) MCCB 4 pole 40 Amp,415 V, 16 kA rupturing capacity with adjustable Thermal and Magnetic setting releases - 03 Nos (ii) MCB 4 pole 25 Amp,415V, 10 kA rupturing capacity - 01 Nos (iii) MCCB 4 pole 63 Amp,415 V, 16 kA rupturing capacity with adjustable Thermal and Magnetic setting releases - 01 Nos (iv) MCCB 4 pole 125 Amp,415V, 25 kA rupturing capacity with adjustable Thermal and Magnetic setting releases - 02 Nos (v) Multifunction energy meter (Make: Schneider, L&T, El measure); three phase to Measure V, I, Hz, Kw, KVAr, KVA, PF, PA, I/E, KWH &KVArh, KVAh, Demand & Max Demand - A, Kw & KVA, etc. with inbuilt RS 485/MODBUS Card along with necessary CTs acc class 0.5 ,10 VA Aux Supply: 230 V :- 01 Sets (vi) LED indication lamp -01 (R Y B, set of three) (vii) Busbar: 400 Amps, System Voltage: 415V, 50 Hz,
Supply, installation, testing and commissioning of factory made powder coated compartmentalized cubicle type LT Panel outdoor type of appropriate size and fabricated from 3.15 mm thick CRCA sheet steel with necessary MS angle iron frame work(50X50X6mm), weather proof, vermin proof, suitable rating aluminium bus bar chamber for operation on 415 volts, 50Hz, 3 Phase 4 wire AC supply complete with gland plates, lifting hooks, ventilating louvers, bus bars, inter connections, earthing terminals, labeling , cable alley suitable for termination of cables including supply and fixing of following switchgear and accessories in the panel complete as required size conforming specification as per IS 5039. The panel should be CPRI approved and having IP-65 ingress protection including necessary foundation for mounting all as specified and directed by Enginer in charge.
Incoming MCCB 4 pole,160 Amp,415 V, 25 KA rupturing capacity with adjustable Thermal and Magnetic setting releases. Outgoing :- (i) MCCB 4 pole 125 Amp,415V, 25 kA rupturing capacity with adjustable Thermal and Magnetic setting releases. - 02 Nos (ii) MCB 4 pole 25 Amp,415V, rupturing capacity 10 kA - 03 Nos (iii) MCCB 4 pole 100 Amp,415V,25 kA rupturing capacity with adjustable Thermal and Magnetic setting releases. - 01 Nos (iv) Multifunction energy meter of approved make; three phase to Measure V, I, Hz, Kw, KVAr, KVA, PF, PA, I/E, KWH &KVArh, KVAh, Demand & Max Demand - A, Kw & KVA, etc. with inbuilt RS 485/MODBUS Card along with necessary CTs acc class 0.5 ,10 VA Aux Supply: 230 V :- 01 Sets (v) LED indication lamp -01 (R Y B, set of three)) (vi) Busbar: 300 Amps, System Voltage: 415V, 50 Hz,
Supply, installation, testing and commissioning of factory made powder coated compartmentalized cubicle type Bus bar Panel outdoor type of appropriate size and fabricated from 3.15 mm thick CRCA sheet steel with necessary MS angle iron frame work(50X50X6mm), weather proof, vermin proof, suitable rating aluminium bus bar chamber for operation on 415 volts, 50Hz, 3 Phase 4 wire AC supply complete, provision for cables bottom entry ,insulated with PVC sleeves and coloured with (Red,Yellow,Blue and black) CTR and internal wiring with suitable size of PVC insulated copper wire,,grouted by using PCC foundation 1:2:4 type C1 using 20 mm graded stone aggregate The panel should be CPRI approved and having IP 65 ingress protection including necessary foundation for mounting all as specified and directed by Enginer in charge. (i) MCCB 4 pole 63 Amp,415V, 16 kA rupturing capacity with adjustable Thermal and Magnetic setting releases. - 01 Nos (ii) Multifunction energy meter (Make: Schneider, L&T, El measure); three phase to Measure V, I, Hz, Kw, KVAr, KVA, PF, PA, I/E, KWH &KVArh, KVAh, Demand & Max Demand - A, Kw & KVA, etc. with inbuilt RS 485/MODBUS Card along with necessary CTs acc class 0.5 ,10 VA Aux Supply: 230 V :- 01 Sets (iii) LED indication lamp -01 (R Y B, set of three) (iv) Busbar: 100 Amps, System Voltage: 415V, 50 Hz,
M&L HDPE pipe with all necessary fittings laid in trenches/under road crossing/fixed on pole/wall/under floor including suitable mild steel FI clamps of required size complete for following sizes :-
Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including HDPE pipe of upto 100 mm dia suitable for 0.4 mpa working pressure.
S&F RCC HT cable route indicator of dimension 700x300x100mm complete all as specified and directed .
SEWAGE DISPOSAL
S & F in repair precast fibre reinforced cement concrete Manhole cover (Ist quality) including grove and hook arrangement for lifting and placing in position and sides covered by MS sheet medium duty of overall Size 500mm x1000mmx80mm omplete all as specified and as directed.
Supply and laying, jointing 200 mm internal dia of Double wall corrugated DWC (HDPE pipes) pipes incl testing and laid in trenches to a level on concrete bed complete all as specified.
Supply and laying, jointing 400 mm internal dia of Double wall corrugated DWC (HDPE pipes) pipes incl testing and laid in trenches to a level on concrete bed complete all as specified.
AREA DRAINAGE
S&F steel fiber reinforcement concrete (SFRC) drain cover with perforated holes factory made of size 0.5m x 1m x 0.075mm thick complete all as specified and directed.
RAIN WATER HARVESTING
M&L for drilling 300mm dia bore hole by DTH cum rotary at any depth below the ground level in any kind of rock/soil upto 100 m depth including disposal of surplus soil to a distance not exc. 50 m away all as specified and directed.
S&F self perforated UPVC pipe 160mm dia for pressuring rating 10 kg/sqcm fixed complete to floors lowering and jointing self perforated in bore hole all as specified.
S&F PVC web cap 160mm dia all as spd and directed.
SEWAGE TREATMENT PLANT
Designing (hydraulicaly, structurally & aesthetically), providng, construction, hydraulic testing, commissioning and giving satisfactory trials of STP (MBBR) of capacity 50 Cum/day with tertiary treatment consisting of Inlet chamber (RCC) , Fine bar screen chamber (manual) RCC with steel screen , oil & grease remover (RCC), grit separator, equalization tank ( 2 tanks of 50% capacity each), Air grid for equalization tanks, feed pumps (2 No), moving bed bio reactor (s) with plastic media (of appropriate density, size and quantity to keep very high MLSS >15,000 mg/lit), air blowers for MBBR(02 Nos), tube settler assembly, sludge drying bed of appropriate size, chlorine dozing system, chlorine contact tank foundation for all E/M quipments, associated piping work with required valves, gates, drains, pathways, electrical control panel with interconnecting cable, spare parts for 2 years of operation, etc. complete as turn key job with all involved civil, electrical, digital and mechanical works as per detailed specifications for civil, electrical and mechanical components with all duties and taxes complete. (Also ref imp notes below). For tertiary treatment it also includes filter feed tank of RCC, Filter feed pumps (02 Nos), dual media filter, activated carbon filter, treated water tank in RCC. Treated sewage can be used for irrigation, horticulture, fire fighting and MT wash. Note : Treated water characteristic should be as per guidelines of CPHEEO (Chapter 5, table 5.3) for STP
Designing (hydraulically, structurally & aesthetically) and construction of lift well RCC sump of capacity 5 KLD , with invert level 3 meter including excavation of all types of strata,foundation concrete,container walls,bottom slab,with plaster and water proofing as per zonal specification including epoxy paint inside ,refilling of earth and disposal of surplus earth within 50 m radius,including all piping connections,
S&F non-clog submersible pump set of capacity 1 HP including DOL starter panel and all connection and testing complete all as specified and directed.
S&F open well submersible pump set having CI casing, impeller & SS shaft ,415 V, 3 phase of capacity 2 HP including all connection and testing complete all as specified and directed.
Supply and laying 3 layer ( inner antimicrobial, outer UV stabilized) ISI marked, IS-15801, PP-R pipes SDR 11 (PN-10) including PP-R fittings in trenches/walls/celling or laying in floors including all fittings for complete of following sizes.
50 mm dia
25 mm dia
Supply and fix PP-R Gate Valves of following sizes all as specified and directed.
50 mm dia
25 mm dia
Supply installation, testing and commissioning of ultra-sonic level sensor with following specifications : Rust proof, maintenance free suitable for up to 3 meter water level depth of sewage sump, with dead band of less than 0.6 meter, IP67 protection, accuracy of 0.25% o F.S and 4-20mA current output, No of wires, Beam angle less than 7.5 degree capable for working in ambient temperature of 0 degree Centigrade to 75 degree Centigrade, non-condensing at 25 degree centigrade and humidity up to 95% with response time of less than 1 sec with 230 VAC to 24VDC, 50Hz power supply, Non display type, in built temperature & voltage variation compensation, vertical type mounting on top of sewage Sump suitable for measuring water / waste water in sewage sump, with all connection and fixing including clamp, nut bolt etc complete all as specified and as directed make, ABB Endress + Hauser MgtsiemensKrohnePepperl + fuchs, continental Vega grieshaber Hans, turck, Gems sensors Omega engineering Keyence Texas instruments Migatron, Honeywell (Scope of work include all accessories required for the correct operation of the sensor).
ARBORICULTURE
Supply only fine sand at site including royality and carriage for preparing compost at site (sand shall be brought at site and stacked for measurement before incorporating in the work) complete all as specified.
Supply only sweet / good earth at site including royality and carriage for preparing compost for ots pits/required for planting treees and shrubs ets free from objectionable extraneous matter, toxic material and termites shall be brought at site and stacked for measurement before incorporating in the work. 20% of computed volume shall be reduced for loose stacking. complete as specified.
Supply only manure at site including royalty and carriage for preparing compost at site. Manure shall be brought at site and stacked for measurement before incorporating in the work. 8% computed volume shall be reduced for loose stacking completely all as specified
Preparing compost pits of size 0.60mx0.60mx0.60m by excavation in ordinary soil carrying out antitermite, planting trees & refilling of the pit with compost (manure, sand and sweet eart mised in ratio 1:1:4 BREAKING MOULDS, RAMMING AND FLOODING WITH WATER filling with more compost if necessary and fine dressing including removal of rubbish unserviceble materials and surpus soil to a distance n exc 100m. ATT shall be in form of 200 gms neem cake mixed with every cum of compost followed by dursban or equivalent applied at 2 ml per litre in the first watering of 20 litres per pit, colmplete as specified. Note (i) The rate for excacation and getting out soil shall be deemed to be included in the rate of this item. (ii) The rate for mixing only earth, manure and sand is deemed to be included in the unit rate of this item supply of sweet earth manure and sand hall be paid under respective item of this schedule.
Preparing compost pits of size 0.90mx0.90mx0.90m by excavation in ordinary soil carrying out antitermite, planting trees & refilling of the pit with compost (manure, sand and sweet eart mised in ratio 1:1:4 BREAKING MOULDS, RAMMING AND FLOODING WITH WATER filling with more compost if necessary and fine dressing including removal of rubbish unserviceble materials and surpus soil to a distance n exc 100m. ATT shall be in form of 200 gms neem cake mixed with every cum of compost followed by dursban or equivalent applied at 2 ml per litre in the first watering of 20 litres per pit, colmplete as specified. Note (i) The rate for excacation and getting out soil shall be deemed to be included in the rate of this item. (ii) The rate for mixing only earth, manure and sand is deemed to be included in the unit rate of this item supply of sweet earth manure and sand hall be paid under respective item of this schedule.
Supply and planting following trees in location where shown on drwng and described in sch A and specifications/directed by engr-in-charge, girth 80mm to 100mm minimum (measured at 150mm top of roots) and complete provided necessary pots whereas req as per plants and height as shown under.
Bottle Palm 4' height
Cycus palm 4' ht
Kachnar 4' ht
Champa 4' ht
Jacoranda mimosifolia 4' ht
Deloniox Regia (gulmohar) 4' ht
Cassia fistula (armaltas) 4' ht
Chinese Palm 4' ht
Bouganvillea Variegata 4' ht
Supply and planting shrubs i.e. Acylpha 2' , Calliandraz, Crotons 3' , Hamcha, Jasminum capensis Hibisew, Ticoma, Golden Dorangta, Red Hdge and complete provided necessary pots whereas req as per plants as directed by Engr-in-charge.
(i) Ploughing of whole site in soft/ordinary soil upto the depth of 20 cm and removing all the unwanted material such as stones, weeds, tree root etc which are not suitable for healthy growth of grass. (ii) Dressing and leveling the soil to a required gradient and slope on completion of work mentioned in Note (a) above after loosening the soil. Manure:- Old cow dung or Okhla sludge at the rate of 2.25 cuts foot for 10 sqm Fertilizers (i) Neem Kholi @ 2 kg for 10 sqm (ii) Benemeal @ 1 kg for 10 sqm (iii) D.A (16.42) @ 0.15 kg for 10 sqm (iv) BHC dust 10% or lindance dust @ 0.15 kg for 10 sqm (d) Fine dressing a top soil after mixing the manure and fertilizers to requisite slope (e) Fine dressing a top soil after mixing the manure and fertilizer to requisite slope (f) Fine dressing of surfaces of top soil to rquire slope and gradient towards the manholes. (g) Plantation of grass @ 10 cm do both way by dibbling root method.
B D Raizada Projects Pvt Ltd
Pooja Singla Builders And Engineers Pvt Ltd
City Promoter and Buildwell Pvt. Ltd.
NITYA NAND AND SONS CONTRACTORS PVT LTD
GEMINI PROMOTERS AND BUILDERS PVT. LTD.
MAGO CONSTRUCTION PVT. LTD.
NITYA NAND AND SONS CONTRACTORS PVT LTD
MAGO CONSTRUCTION PVT. LTD.
GEMINI PROMOTERS AND BUILDERS PVT. LTD.
Global Enterprises
B D Raizada Projects Pvt Ltd
City Promoter and Buildwell Pvt. Ltd.
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.05 MB
Download all tender documents and submit your bid