Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹26.3 LAccepted-AOC 901 GH 83 SECTOR 20 PANCHKULA 134116 | PANCHKULA | HARYANA | 134116 | L1 | Accepted-AOC L1 | |
| 2 | L2₹28.4 L+₹2.0 L (7.50%)Rejected-Finance 186 GANDHI MARKET AMBALA CANTT 133001 | AMBALA CANTT | AMBALA | HARYANA | 133001 | L2 | Rejected-Finance L2 | |
| 3 | L3₹30.0 L+₹3.5 L (13.4%)Rejected-Finance | L3 | Rejected-Finance L3 | |
| 4 | L4₹30.0 L+₹3.6 L (13.5%)Rejected-Finance 195 MAHESH NAGAR AMBALA CANTT 133001 | AMBALA | HARYANA | 133001 | L4 | Rejected-Finance L4 | |
| 5 | L5₹32.1 L+₹5.6 L (21.3%)Rejected-Finance BOOTH NO 119 SECTOR 9 PANCHKULA 134109 HARYANA | PANCHKULA | PANCHKULA | HARYANA | 134109 | L5 | Rejected-Finance L5 |
Tender Value
Refer Docs
EMD Value
₹82,000
Closing Date
15 Dec 2023, 6:00 pmClosed
CWE PATIALA
HQ COMMANDER WORKS ENGINEER BLDG No 26 NEW LALBAGH PATIALA 147001 Contact 01712200082
SPECIAL REPAIR TO LT DISTRIBUTION NETWORK UNDER AGE(I) AT DAPPAR MIL STN
2023_MES_628319_1
CWE/PAT/T-45/2023-24
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
DAPPAR
Please refer Tender documents.
6 documents required · 6 mandatory
₹500
AGE(I) DAPPAR
₹82,000
15 Jan 2024
15 Nov 2023
18 Dec 2023
15 Nov 2023
15 Dec 2023
1 Dec 2023
15 Nov 2023 - 30 Nov 2023
Amount
Material and Labour for dismantling old feeder pillar boxes any size or any shape all as directed and specified.
Material and Labour for dismantling old unserviceable LT panel along with disconnecting connected cables, supplying, installing, testing and commissioning of 415 Volts 3 Phase 4 Wire factory fabricated and tested all as per existing IEC 60439 Part 1, floor mounted, IP 55 grade, Outdoor double door Partially Type Tested Assembly Type (PTTA) Bus Coupler LT cubical panel made out of CRCA 3.15mm thick MS sheet duly powder coated with Seimens grey shade RAL 7032, dust and veremin proof with suitable size TPN PVC sleeved aluminium bus bar including. angle iron base frame of 40mmx40mmx6mm size. Panel should be mounted/grouted on 150 mm thick PCC (1:4:8) type D2 above nearest ground level and should be with 400 mm offsets on all 04 sides of the panel complete and should be inclusive of following accessories fitted in:-
A. INCOMING :- (i) MCCB 200 Amps, 415 V 4 pole 36 KA 50 Hz with Ics =100% Icu & thermal magnetic adjustable type including spreader terminals - set of 04 and direct rotary handle -01 No, Current transfomer 200/5A -01 Nos, Shunt Release as per OEM specifications. B. OUTGOING - (ii) MCCB 125 Amps ,415 V 4 pole 25 KA 50 Hz with Ics =100% Icu & thermal magnetic adjustable type including spreader terminals - set of 04 and direct rotary handle -01No as per OEM specifications. (iii) MCCB 63 Amps , 415 V 4 pole 25 KA 50 Hz with Ics =100% Icu & thermal magnetic adjustable type including spreader terminals - set of 04 and direct rotary handle -01No as per OEM specifications.. (iv) MCB TPN 6-32 Amps - 01 No. (v) Spare cubicles for expansion as per MCCB 4P 125 Amps - 02 Nos.
(vi) LED indicators - R/Y/B 240 V AC - 03 Sets of 03 Nos. per incoming & outgoing (vii) Multifunction meter with accuracy Class 1.0, Flush mounting 96 x 96 mm, CT/PT site programmable for measurement of V, A, PF, kW, kVA, Load hours all as per L&T make, Cat No. - WL440010OOOO or equivalent from the makes as specified in list of makes or as per existing make as approved by AGE (I) and including suitable size CTs (set of 3) - 01 No. (01 NO. for Incoming feeder) (viii) MCB SP 'C' series 10kA 60-32 Amps as protection for LED lamps (01 No. each for set of 03 Nos. LED lamps, multifunction and single function meters) and multifunction meter - 2 Nos. (ix) Control wiring with suitable size PVC insulated single core copper conductor cable for LED lamps, MFMs, etc.
All as per Srl Item No. 2 here-in-before but :-
INCOMING (i) MCCB 4 pole 25 kA 63 Amp with Ics =100% Icu & thermal magnetic adjustable type including spreader terminals - set of 04 and direct rotary handle - 01 No (ii) Current transfomer 100/5A -01 No, (iii) Shunt Release all as per OEM specifications - 01 No. OUTGOING (iv) MCB TPN 40 Amp - 01 No. (v) MCB TPN 6-32 Amps - 02 Nos. (vi) LED indicators - R/Y/B 240 V AC - 03 Sets of 03 Nos. per incoming & outgoing (vii) Multifunction meter with accuracy Class 1.0, Flush mounting 96 x 96 mm, CT/PT site programmable for measurement of V, A, PF, kW, kVA, Load hours all as per L&T make, Cat No. - WL440010OOOO or equivalent from the makes as specified in list of makes or as per existing make as approved by AGE (I) and including suitable size CTs (set of 3) - 01 No. (01 NO. for Incoming feeder)
(viii) MCB SP 'C' series 10kA 60-32 Amps as protection for LED lamps (01 No. each for set of 03 Nos. LED lamps, multifunction and single function meters) and multifunction meter - 2 Nos. (ix) Control wiring with suitable size PVC insulated single core copper conductor cable for LED lamps, MFMs, etc.
All as per Srl Item No. 2 here-in-before but :-
INCOMING (i) MCCB 4 pole 25 kA 63 Amp with Ics =100% Icu & thermal magnetic adjustable type including spreader terminals - set of 04 and direct rotary handle - 01 No, (ii) Current transfomer 100/5A -01 No, (iii) Shunt Release all as per OEM specifications - 01 No. OUTGOING (iv) MCB TPN 40 Amp - 01 No. (v) MCB TPN 6-32 Amps - 03 Nos. (vi) LED indicators - R/Y/B 240 V AC - 01 Set of 03 Nos. per incoming and outgoing (vii) Multifunction meter with accuracy Class 1.0, Flush mounting 96 x 96 mm, CT/PT site programmable for measurement of V, A, PF, kW, kVA, Load hours all as per L&T make, Cat No. - WL440010OOOO or equivalent from the makes as specified in list of makes or as per existing make as approved by AGE (I) and including suitable size CTs (set of 3) - 01 No. (01 NO. for Incoming feeder)
(viii) MCB SP 'C' series 10kA 60-32 Amps as protection for LED lamps (01 No. each for set of 03 Nos. LED lamps, multifunction and single function meters) and multifunction meter - 2 Nos. (ix) Control wiring with suitable size PVC insulated single core copper conductor cable for LED lamps, MFMs, etc.
All as per Srl Item No. 2 here-in-before but :-
INCOMING (i) MCCB 4 pole 25 kA 63 Amp with Ics =100% Icu & thermal magnetic adjustable type including spreader terminals - set of 04 and direct rotary handle - 01 No, (ii)Current transfomer 100/5A -01 No, (iii) Shunt Release all as per OEM specifications - 01 No. OUTGOING (iv) MCB TPN 32 Amps - 02 Nos. (v) LED indicators - R/Y/B 240 V AC - 01 Set of 03 Nos. per incoming and outgoing (vi) Multifunction meter with accuracy Class 1.0, Flush mounting 96 x 96 mm, CT/PT site programmable for measurement of V, A, PF, kW, kVA, Load hours all as per L&T make, Cat No. - WL440010OOOO or equivalent from the makes as specified in list of makes or as per existing make as approved by AGE (I) and including suitable size CTs (set of 3) - 01 No. (01 NO. for Incoming feeder) (vii) MCB SP 'C' series 10kA 60-32 Amps as protection for LED lamps (01 No. each for set of 03 Nos. LED lamps, multifunction and single function meters) and multifunction meter - 2 Nos. (viii) Control wiring with suitable size PVC insulated single core copper conductor cable for LED lamps, MFMs, etc.
All as per Srl Item No. 2 here-in-before but :-
INCOMING (i) MCCB 4 pole 25 kA 63 Amp with Ics =100% Icu & thermal magnetic adjustable type including spreader terminals - set of 04 and direct rotary handle - 01 No, (ii) Current transfomer 100/5A -01 No, (iii)Shunt Release all as per OEM specifications - 01 No. OUTGOING (iv) MCB TPN 32 Amps - 02 Nos. (v) LED indicators - R/Y/B 240 V AC - 01 Set of 03 Nos. per incoming and outgoing (vi) Multifunction meter with accuracy Class 1.0, Flush mounting 96 x 96 mm, CT/PT site programmable for measurement of V, A, PF, kW, kVA, Load hours all as per L&T make, Cat No. - WL440010OOOO or equivalent from the makes as specified in list of makes or as per existing make as approved by AGE (I) and including suitable size CTs (set of 3) - 01 No. (01 NO. for Incoming feeder) (vii) MCB SP 'C' series 10kA 60-32 Amps as protection for LED lamps (01 No. each for set of 03 Nos. LED lamps, multifunction and single function meters) and multifunction meter - 2 Nos. (viii) Control wiring with suitable size PVC insulated single core copper conductor cable for LED lamps, MFMs, etc.
All as per Srl Item No. 2 here-in-before but :-
INCOMING (i) MCCB 4 pole 25 kA 63 Amp with Ics =100% Icu & thermal magnetic adjustable type including spreader terminals - set of 04 and direct rotary handle - 01 No, (ii) Current transfomer 100/5A -01 No, (iii) Shunt Release all as per OEM specifications - 01 No. OUTGOING (iv) MCB TPN 32 Amps - 07 Nos. (v) LED indicators - R/Y/B 240 V AC - 01 Set of 03 Nos. per incoming outgoing (vi) Multifunction meter with accuracy Class 1.0, Flush mounting 96 x 96 mm, CT/PT site programmable for measurement of V, A, PF, kW, kVA, Load hours all as per L&T make, Cat No. - WL440010OOOO or equivalent from the makes as specified in list of makes or as per existing make as approved by AGE (I) and including suitable size CTs (set of 3) - 01 No. (01 NO. for Incoming feeder) (vii) MCB SP 'C' series 10kA 60-32 Amps as protection for LED lamps (01 No. each for set of 03 Nos. LED lamps, multifunction and single function meters) and multifunction meter - 2 Nos. (viii) Control wiring with suitable size PVC insulated single core copper conductor cable for LED lamps, MFMs, etc.
All as per Srl Item No. 2 here-in-before but :-
INCOMING (i) MCCB 4 pole 25 kA 63 Amp with Ics =100% Icu & thermal magnetic adjustable type including spreader terminals - set of 04 and direct rotary handle - 01 No, (ii)Current transfomer 100/5A -01 No, (iii) Shunt Release all as per OEM specifications - 01 No. OUTGOING (iv) MCB TPN 6-32 Amps - 06 Nos. (v) LED indicators - R/Y/B 240 V AC - 01 Set of 03 Nos. per incoming and outgoing (vi) Multifunction meter with accuracy Class 1.0, Flush mounting 96 x 96 mm, CT/PT site programmable for measurement of V, A, PF, kW, kVA, Load hours all as per L&T make, Cat No. - WL440010OOOO or equivalent from the makes as specified in list of makes or as per existing make as approved by AGE (I) and including suitable size CTs (set of 3) - 01 No. (01 NO. for Incoming feeder) (vii) MCB SP 'C' series 10kA 60-32 Amps as protection for LED lamps (01 No. each for set of 03 Nos. LED lamps, multifunction and single function meters) and multifunction meter - 2 Nos. (viii) Control wiring with suitable size PVC insulated single core copper conductor cable for LED lamps, MFMs, etc.
All as per Srl Item No. 2 here-in-before but :-
INCOMING (i) MCCB 4 pole 25 kA 63 Amp with Ics =100% Icu & thermal magnetic adjustable type including spreader terminals - set of 04 and direct rotary handle - 01 No, (ii) Current transfomer 100/5A -01 No, (iii) Shunt Release all as per OEM specifications - 01 No. OUTGOING (iv) MCB TPN 6-32 Amps - 04 Nos. (v) LED indicators - R/Y/B 240 V AC - 01 Set of 03 Nos. per incoming and outgoing (vi) Multifunction meter with accuracy Class 1.0, Flush mounting 96 x 96 mm, CT/PT site programmable for measurement of V, A, PF, kW, kVA, Load hours all as per L&T make, Cat No. - WL440010OOOO or equivalent from the makes as specified in list of makes or as per existing make as approved by AGE (I) and including suitable size CTs (set of 3) - 01 No. (01 NO. for Incoming feeder) (vii) MCB SP 'C' series 10kA 60-32 Amps as protection for LED lamps (01 No. each for set of 03 Nos. LED lamps, multifunction and single function meters) and multifunction meter - 2 Nos. (viii) Control wiring with suitable size PVC insulated single core copper conductor cable for LED lamps, MFMs, etc.
Material and Labour for dismantling, disconnecting connected cables of old unserviceable LT FPB, supplying, installing, testing and commissioning of factory fabricated CPRI approved, floor mounted, IP 55 grade, outdoor type LT cubical panel made out of 3mm thick CRCA MS sheet duly powder coated with Seimens grey shade RAL 7032 of size not less than LBW-0.60mX0.60mX0.40m, dust and veremin proof with suitable size TPN PVC sleeved aluminium bus bar, including. aluminium bus bars for incoming and outgoing connections supported on glass fiber reinforced thermosetting plastic insulated support with lifting lugs of 40mmx40mmx6mm size. Panel should be mounted/grouted on 150 mm thick PCC (1:4:8) type D2 with 200 mm offsets complete. The bottom of the panel (space between bottom of panel and top of PCC foundation) shall be covered with 3 mm thick CRCA sheet covering all the sides of the base frame duly painted with two coats of synthetic enamel paint of approved shade over one coat of red oxide primer. The panel should have following accessories fitted in :-
Material and Labour for making bore up to 100 mm dia of road width for providing GI pipe medium grade both end socketed for passing armoured cable complete all as specified.
Material and Labour for 50 mm bore galvanized steel tubing light garde (ISI marked) protection of cable fixed to pole/walls or laid in floors, road crossing ducts with all necessary fittings and fittings and fixed with clamps, bolts, nuts and washers etc complete all as specified and directed.
Supply and fix XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 16 sqmm 4 core all as specified and directed by Engr-in-charge.
Supply and fix XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 50 sqmm 3.5 core all as specified and directed by Engr-in-charge.
Supply and fix XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 70 sqmm 3.5 core all as specified and directed by Engr-in-charge.
Excavation in trenches in soft/loose soil n exc 1.5m wide and not exc1.5m deep and getting out includingforming bottom surfaces to required level or slope for taking out embeded cables,brick/ PCC protective tiles complete all specified and all as directed by Engineer-in-Charge.
Material and Labour for sand cushioning (dry sand) to under ground cable for cable protection provided with layers 8cm deep before laying and 15 cm after laying the cable complete all as specified and directed. Note :- Punned thickness will be measured only.
Material and Labour for laying in trenches as PCC cable protection cover class LV, type 2, flat size 300mm x 180mm x 40mm complete all as specified and directed.
Removal of surplus excavated soil to a distance exc 50 m but not exc in 100 m and deposited where directed at a level not exc 50 m above the starting point complete all as specified and directed.
Returning filling in soft/ loose soil in trenches including spreading, leveling watering and well ramming in 25mm thick layer complete all as specified and as specified.
Material & Labour for cement concrete 1:4:8 type D- 2 using 40mm graded crushed stone aggregate in foundation filling & mass concrete for poles/struts/stay assembly complete all as specified and directed by Engr-in-Charge.
Material & Labour for cement concrete 1:2:4 type B - 1 using 20mm graded crushed stone aggregate in coping pedestal to poles including provision of necessary form work finishing the expossed surface even and smooth complete all as specified and directed by Engr-in-Charge.
Supply and fix in replacement for earthing complete with galvanized steel earth plate electrode 600mm x 600mm x 6mm thick buried directly in ground (earth pit not less than 2.25 meters deep below normal ground level) with top edge of plate not less than 1.5 meter deep below normal ground level connected to galvanized earth strip of size 25 x 4 mm, 7.5m long means of bolts, nuts, check nuts and washers of galvanized iron or steel all as shown in electrical plate No 3 of SSR part I connecting to earthing test point and testing on completion with and including PCC pit in mix 1:3:6 type c1 with RCC 1:2:4 type B-1, 40mm thick cover reinforced with 6mm dia MS bars 3 Nos both ways with lifting book made out of 6mm dia bar, watering arrangement with funnel and wire mesh and 20mm bore light grade GI watering pipe, common salt and charcoal filling, necessary excavation and earth work, complete all as directed.
Material and labour for LT cable route indicator/marker with engraving "LT CABLE" on block made out of RCC of size 800x150x80mm with 6mm round bar fixed in ground at a distance 05 Mtrs complete all as directed by Engr-in-charge.
M/S Sonu Traders
Sukhdev Ram
Raman Electric Trading Co
SHARMA ELECTRICAL ENGINEERS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .