CWE Jalandhar Cantt
HQ CWE Jalandhar Cantt, PIN 144005
Spl repair of fire fighting system and allied works at FF Installation No 1 and 2 at FAD under AGE I Suranussi
2026_MES_752086_4
8325/91/E8
Open Tender
Civil Works
Item Rate
180 days
HQ CWE Jalandhar Cantt
Class E Category c (vi) for contractors enlisted with MES
9 documents required · 9 mandatory
₹500
Yes
AGE (I) Suranussi
₹45,900
Yes
21 Aug 2026
21 Aug 2026
4 Sept 2026
21 Aug 2026
3 Sept 2026
29 Aug 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply,installation, testing and commissioning new LT panel box " CPRI type tested" cubicle type,with angle & frame, free standing, floor mounted, indoor, weather proof type, Double door, front and rear openable type working on 415 V 3-phase, 50 Hz, AC supply with copper bus bars-600 Amp Copper bus bar- 04 Nos, 600 amp rating considering current carrying cap 1.5 Amp/sqmm duly having colour coated heat shrinkable sleeves mounted on insulators weather proof, dust-proof and vermin proof with canopy on top, 3mm thick CRCA sheet steel enclosure,power coated CRCA-IP-55,Light grey painted as per the 7-tank process, weather proof IP-55 protection compartalized as per specification incl MS angle iron legs of height 900 mm made out of angle iron 50x50x6mm and including following component complete all as specified and as directed:-
(1) Main Incomer section : MCCB with suitable rating for panel load 100 HP Pump e.g. 4 Pole, 400A, breaking cap 36kA.(I/C) Ics=100% Icu with phase separator & phase extender/copper links. | 2 | Each | - | - |
| 1.01 | Individual feeder section
(A) 100 HP main fire pump star delta starter-01 Nos
(i) 3 pole contactor e.g. 150 A AC-3 phase heavy duty-03 Nos
(ii) Thermal overload relay-(78-130 A)-01 Nos
(iv) Pressure switches interface (auto start on pressure drop)-01 Nos
(v) Manual and auto selector switch-01 Nos
(vi) Start/stop push button (Green and red)-02 Nos
(vii) Indicating lamp (Running,Stopped,Trip,Auto mode)-04 Nos
(viii) Digital Ammeter(0.200A) 01 Nos and Digital Voltmeter CT operated (0-500V) 01 Nos with selector switch
(ix) Single phase preventor - 01 Nos
(x) Star/Delta electronic timer (0-30 sec)-01 Nos
(xi) Control MCCB 250 Amp 4 pole 36 KA with thermal and magnetic adjustable type, Ics=100%Icu with phase seperator & phase extender-01 Nos
(xii) Power wiring, control wiring, with suitable size copper wire. | - | - | - | - |
| 1.02 | (B) 25 HP Jockey pump star delta starter
(i) 3 pole contactor e.g. 45 A AC-3 phase heavy duty-03 Nos
(ii) thermal overload relay (22-40 A)-01 Nos
(iv) pressure switches interface for auto start/stop on pressure drop from preset limit (auto start on pressure drop)-01 Nos
(v) Manual and auto selector switch-01 Nos
(v) Start/stop push button (Green and red)-02 Nos
(vii) Indicating lamp (Running,Stopped,Trip,Auto mode)-04 Nos
(viii) Digital Ammeter (0-100A) 01 Nos and Digital Voltmeter (0-500V)-01 Nos with selector switch.
(ix) single phase preventor-01 Nos
(x) star delta electronic timer (0-30 sec)-01 Nos
(xi) control MCCB 100 Amp 4 pole 25 KA-01 Nos
(xii) Power & Control wiring with suitable size copper wire. | - | - | - | - |
| 1.03 | (C ) 20 HP Standby pump star delta starter
(i) 3 Pole contactor e.g. 40 A AC-3 phase heavy duty-03 Nos
(ii) thermal overload relay(22-35 A)-01 Nos
(iii) over current protection relay (MCCB/MCB)-40 Amp-01 Nos
(iv) Auto start start on main pump(25 HP jockey Pump) failure -01 Nos
(v) Start/stop push button (Green and red)
(vi) Indicating lamp (Running ,trip,auto,stand by active)
(viii) single phase preventor
(ix) star delta timer (0-30 sec)
(xi) control MCCB 100 Amp 4 pole 25 KA 01 Nos with phase seperator & phase extender/copper links.
(xii) Power & Control wiring with suitable size copper wire. | - | - | - | - |
| 1.04 | DIESEL ENGINE PUMP 12/24 Volt
1.MCB, 32 Amp ,DP -Make-L&T-01 Nos
2.DC Contactor Start 150 Amp -01 Nos
3.DC Contactor Stop 150 Amp-01 Nos
4.Push Botton-Make- L&T-02 Nos
5. Amp Meter DC-Make-AE -01 Nos
6.Volt meter DC-Make-AE-01 Nos
7.Auto Manual Switch -Make-L&T-01 Nos
8.Battery Charger 12/24 Volt 10 Amp with trickle float & boost facility -01 Nos
9.Timer 12 Volt -Make-Selection -02 Nos
10. Connection Terminal 6 way -Make-FTC-01 Nos
11.On off Light-Make-L&T-02 Nos
Note:-above Scope includes the supply, installation, testing and commissioning of complete internal wiring for electrical control panels, including all accessories etc. Anything not specifically mentioned here-in-before but reqd for satisfactory functioning of starters, auto ON/OFF of Jockey Pumps, Fire Pumps, same deemed to the included in quoted rates. | - | - | - | - |
| 2 | M&L for maintenance and servicing at site of existing diesel engine Set of capacity 113/153 BHP, installed at fire fighting No1 & 2 FAD complete including draining out & starting of diesel from tank, cleaning the tank thoroughly and refiling the drained out diesel, draining out engine oil from the chamber, cleaning the chamber thoroughly and replacing the engine oil with new to required level, replacing the fuel filter, check & clean air cleaner, check coolant level & make up to required level the same, drain the Fuel filter & water separator, filling the starting batteries with electrolyte/distilled water to maintain the required specific gravity, cleaning of battery terminals & applying petroleum jelly to battery terminal posts & brass connectors, replacement of V-belts, changing clips of air cleaner, checking of exhaust leakage, governor, breathers etc, adjust/set the same for proper functioning , checking of fuel, oil and water/coolant level etc, adjusting and keeping the fan belts to the desired tension, tightening all the bolts and nuts to the required torque etc, cleaning the diesel engine with accessories for satisfactory running and testing at connected load. complete all as directed. Note:- The quoted rate include the required engine oil distiled water as mentioned above. | 2 | Each | - | - |
| 3Supply and fixing the following items for 113/153 BHP Diesel engine incl old removing UNSV parts. | |||||
| 3.01 | (a) Control Safety for (Water) Temp, | 2 | Each | - | - |
| 3.02 | (b) Control Safety for (Lub Oil) Pressure , | 2 | Each | - | - |
| 3.03 | (c) Water Temp Guage. | 2 | Each | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.25 MB
TENDERDOC91.pdf
Tender Documents • 1.49 MB
BOQ_880365.xls
BOQ • 0.32 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].