Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Tender Value
₹50.9 L
EMD Value
₹1.0 L
Closing Date
14 Oct 2024, 5:30 amClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Facilities Management Division, Bangalore
HINDUSTAN AERONAUTICS LIMITED Facilities Management Division, Bangalore
Providing air conditioning facility for admin building 2nd floor IMM office at MRO division HAL HC
9748
FM/NE-P/Advt./11/24-25
Works
Electrical Planning and Contract Section-E and M Dept-FMD-Bangalore
₹0
₹1.0 L
14 Oct 2024
20 Sept 2024
20 Sept 2024
14 Oct 2024
Name of the Individual / Firm / Company: * Mandatory
Type of ownership
Details of Constitution or Legal Status such as certificate of incorporation, shops and establishments, etc.,
Address for correspondence:
Bank(s) details: [Copy of the cheque leaf to be uploaded]
Related Document to be Uploaded to eProcurement Portal (Note Cancelled cheque leaf to be uploaded)
PAN No.:
Average annual financial turn over during the last 3 years, ending 31st March of the previous financial year [ should not be less than 30% of Amount put to tender]
TURN OVER IN Rs:
Please Enter Turn over in Rupees for all the 3 years
Details of Registered Contractor
ESI No.:
GST Detail:
Please Enter GST Details
Related Document to be uploaded in ePortal
Contact details
Please Enter Contact person Name
Please Enter Mobile No
Valid Electrical contractor licence of appropriate voltage issued by any state Govt. under clause 45 of Indian Electricity Rules 1956 and as amended from time to time or to declare engage an electrical contractor who has the above mentioned licence and requisite experience.
Latest Bankers Solvency Certificate from Nationalized/ scheduled Bank issued within a period 12 months from the final date of submission of tender.
Please Enter Details to 'Name of the Bank' , 'Date of Issue','Value in C89``Rs. in Lakhs
Experience of having successfully completed similar works during last 7 years ending on the previous day of submission of tender should be either of the following: [Work completion certificates along with LOA/PO/WO should be uploaded] (i) THREE similar completed works each costing not less than the amount equal to 40% of the estimated amount put to tender. (ii) TWO similar completed works each costing not less than the amount equal to 50% of the estimated amount put to tender. (iii) ONE similar completed work costing not less than the amount equal to 80% of the estimated amount put to tender.
Type of Work: [Incase of private works the same shall be supported with TDS certificate]
Type of Work: [Incase of private works the same shall be supported with TDS certificate]
Please Enter Details for Work No II
work done
Type of Work: [Incase of private works the same shall be supported with TDS certificate]
Please Enter Details for Work No III
Details of person holding the power of Attorney :
Related Document to be Uploaded to eProcurement Portal
Please Enter Details for Person holding Power of Attorney
DECLARATION I
Please Accept the Declaration I
DECLARATION II
Please Accept the Declaration II
The payment terms shall be governed as per the terms indicated in General conditions of contract.
Basic Rate to be quoted for each item.Subject work is called on works contract basis and prevailing GST of 18% has been added in the BOQ on overall total. Any revision on this GST rate is to HAL account.
Sucessful offer that is L-1 (Lowest offer) will be determined including GST.
Amount towards GST will be paid along with RAR payment against invoice.
The tenderers are requested to abide by the rules of prevailing GST act.
This BOQ specification has to be read in conjunction with technical specifications and tender drawings. Any ambiguty in these have to be brought to the knowledge of contract section before submission of tender to avoid future claims/dispute.
Specification of item
Design, Supply, erection, testing and commissioning of 24HP capacities Air-cooled variable refrigerant volume/variable refrigerant flow(VRV/VRF) modular type Outdoor unit mounted on suitable MS angle frame for connecting multiple indoor units of different capacities including suitable size communication copper control wiring up to each indoor units, energy efficient inverter driven rotary/ Scroll compressors, 380-415 V, 50Hz AC power supply input including microprocessor control panel, starter controls for all compressors and condenser fan motors along with internal control and power wiring, cooling coil with internally interconnected refrigerant pipes for interconnecting various capacity modules (to make unit of 48 HP), charging port and the entire unit shall be with weather resistant powder coating paint for continuous outdoor operation, all other required accessories, & hardware’s, full charge of eco friendly R 410A/R407 /R32 Refrigerant, safety devices and all other standard accessories etc., complete in all respect as per technical specification and as instructed by the Engineer-in-charge. MS frame work for mounting unit will be included in the scope. Note: 1)Power supply to individual units shall be provided near ODU to tap power supply.
Design, Supply, erection, testing and commissioning of minimum 2.0TR capacity, Four directional/ Rounded air flow Cassette type Indoor Air Conditioning Units suitable for mounting inside false ceiling, each comprising of cooling coil, blower with multi speed motor, electronic expansion valve, supply & return air grilles, filter, insulated connection of refrigerant circuit, provision for fresh air intake, condensate water drain pump with electronic level sensor, including suitable size LT copper cable connecting to the nearest existing plug & socket, necessary mounting arrangement for suspending the unit from ceiling etc. All the indoor units shall be compatible to work with VRV / VRF type above condensing unit. Scope includes Remote controller (Cordless) for each following units including batteries and necessary cutting of existing false ceiling Note: Power supply to individual indoor unit will be provided near to IDU to tap power supply.
Design, Supply, erection, testing and commissioning of suitable size hard/soft refrigerant copper pipe as required with required pipe fittings and accesories like bends,Tees, reducers, Y-Joints/Refnets, suction filters, filter drier and couplings by good quality pipe joints which laid between ODU and IDU (AHU/Cassette). The Minimum copper pipe gauge shall be as per the gauges indicated by manufacturer. The Pipe sizes to be used as per OEM design recommendation. The Refrigerant pipe shall be insulated with Class O nitirle rubber of 19 mm thick for Gas line and 19 mm thick for liquid line. The piping shall be laid on walls / roof / ceiling well supported at specific intervals with metallic support, Cable tray with cover and required hardwares etc., for fixing copper pipes. All the necessary accessories, jointing / brazing etc shall be carried out as required..The pressure testing of refrigerant piping has to be done as per manufacturer design recommendation. All the copper fittings shall be suitable for R 410 A/R 407/R-32 refrigerant. Refer IDU/ODU layout tender drawing. Make: Mandev/Piyush/Totaline
Design,supply,Installation testing & commissioning of suitable sizes as per OEM recommonadation not less than 2mm thick CPVC drain water / fresh air arrangement pipe including U-traps, valves for AHU drain,reducer, bends, collars & elbow etc, all complete and duly insulated with 9 mm thick tubular insulation of closed cell elastomeric nitrile rubber as required.The PVC drain water pipe/fresh air pipe shall be complete with fittings, accessories and duly insulated using bends, elbows, tees, wall sleeves, hangers, supports, anchors etc.(Note:.1 Pipe used for fresh air intake to IDU shalll be coverd with mesh. 2. Necessary wall openings and closing the same using cement mortar and matching paint finish after taking out pipes is included in the scope of work.) Make: SUPREME/HYCOUNT/FINOLEX/SEROPLAST
Supply, Installation, Testing & commissioning of Indoor(IP54) LT Panel-1.(PTTA)
Incoming
1No- 250A, 415V gr. 50KA 4P MCCB with Thermomagnetic release.
Lot - 300A TP + 150A N, 415V, short circuit rated 50KA for 1sec, Aluminium bus bars with busbar insulators, heat shrinkable PVC sleeves etc.
1Nos- Multi function meter (MFM/MDM) suitable for 3ph, 4 wire, 240V(L-N), 5A, CL-1, RS 485 Port Digital MFM/MDM of EM6400NG of Schneider or any equivalent make meeting technical specification of above MFM complete in all respect.
1 Set-250/5A current transformers of class 1 and suitable VA burden for metering.
1No 16 A 415V gr TP 50KA MPCB of for tapping power for metering and control circuit
1Set - RYB indicating lamps of LED module with 6A, 230V,10KA, SP MCB.
1Set- 6A, 230V, 10KA SP MCB for the protection of measuring instruments.
Outgoings:
4Nos - 125A, 415V gr. 50KA breaking capacity, TPN MCCB with Thermomagnetic release.
1No - 63A, 415V gr. 10KA breaking capacity, TPN MCB
1No - 32A, 240V gr. 10KA breaking capacity, TPN MCB
Supply, fixing, testing & commissioning of the following factory built powder coated Double door MCB DB of any approved make fabricated out of M.S. sheet steel enclosure & necessary cutouts for operating the MCB knobs & comprising of suitable rating tinned copper busbars & earthing bus with tapped holes including internal wiring with stranded copper PVC wires or suitable size copper strips etc. & fixing the DB in flush with wall/ on wall as per site requirement with necessary M.S. angle supports, chipping the wall and replastering to smooth finish etc., wherever required as per site condition, complete in all respects, as directed by Engineer-in-charge and comprising the following as detailed below:
8 WAY Double door Vertical MCCB DB
Supply and fixing 125A rating, FP 415V 36kA, MCCB.
Supply and fixing 5A to 32 A rating, TP 240/415V 10kA, "C" curve, miniature circuit breaker suitable for inductive load in the existing MCB/MCCB DB complete with connections, testing and commessioning etc., as required.
Supply and fixing 6A to 32 A rating, SP 240V 10kA, "C" curve, miniature circuit breaker suitable for inductive load in the existing MCB/MCCB DB complete with connections, testing and commessioning etc., as required.
Supplying and fixing 20A, 240 V, SPN Industrial type socket outlet, with 2 pole and earth, metal enclosed plug top along with 20 A "C" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required
Supply & laying in the already excavated cable trench/cable tray/ fixing on wall/duct wall with necessary M.S clamps/encasing in pipes etc., testing & commissioning of following size XLPE insulated Aluminium(Al)/Copper(cu) conductor 1.1 KV grade confirming to IS:7098(part I)/1998 with upto date amendment earthed Armoured(Arm)/ unArmoured(unArm) U.G cables and as per technical specfication including stacking at site, proper storage complete etc. as required.(Note: Excavation, sand & Brick Protection, concretecutting, reconcreting, casing pipes will be measured separately.)
3.5CX 185 Sqmm Aluminium armoured conductor
3.5 CX 50 Sqmm Aluminium armoured conductor.
3CX 4 Sqmm Copper armoured conductor.
4 CX 10 Sqmm Aluminium armoured conductor
Supplying and making end termination with brass compression gland and aluminium/Copper lugs for following size of PVC/XLPE insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required
3.5 CX 185 Sqmm Aluminum armoured conductor
3.5 CX 50 Sqmm Aluminum armoured conductor
3CX 4Sqmm Copper armoured conductor
4CX 10 Sqmm Aluminum Armoured conductor.
Supply, fabricating and installing following size of perforated painted with hot dipped galvanized iron cable tray(Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, joined with connectors, including suspensions from the ceiling with GI suspenders/MS angle support on floor/wall, bolts & nuts, painting supports etc as required.
300mm width x50mm depth x2mm thick size perforated GI cable trays with cover
225 mm width X 50 mm depth X 1.6 mm thickness without cover
Providing and fixing factory made Three track three panels uPVC sliding glazed window upto 1.50 m and balance height as fixed in height dimension comprising of lead free uPVC multi-chambered frame,sash and mullion/coupler(where ever required) extruded profiles having approximate wall thickness of 2.10mm with frame of approximate size (98mm x 40mm) & both glazed and fly screen sash of approximate size (30mm X 55mm) with zinc alloy powder coated handle on every glazed panel along with multi-point locking system confirming to EN:12608 in any shape,colour and design duly reinforced with galvanized mild steel section made of required shape & size as per CPWD specification, uPVC extruded glazing beads,interlocks and inline sash adaptor (where ever required) of approriate dimension, EPDM gasket, hadrwares,SS304 fastners of approximate 8mm dia with countersunk head,comprising of matching polyamide PA6 grade sleeve for fixing frame to finished wall as per IS1367:Part I to 14,Plastic packers,plastic caps and necessary stainless steel screws etc. Profile of frame,sas & mullion shall be mitred cut and fusion welded/mechanically jointed duly sealed at all corners, including drilling of holes for fixing hardware's and drainage of water etc. After fixing frame the gap between frame and adjacent finished wall shall be filled with weather proof silicon sealent over backer rod of required size and of approved quality, all complete as per approved drawing & direction of Engineer-in-Charge. Note: For uPVC frame and sash extruded profiles minus 5% tolerance in dimension i.e. in depth & width of profile shall be acceptable.(Glass to be paid separately). Approved makes for uPVC frames:Fenesta,SaintGobian,Encraft,Deccan woodmate,LG,Madhu Indutsries.
Dismantling aluminium/ Gypsum partitions, doors, windows, fixed glazing and false ceiling including disposal of unserviceable material and stacking of serviceable material with in 50 meters lead as directed by Engineer-in-charge.
Providing and fixing glazing in aluminium/UPVC (door, window, ventilator,louvers,shutters and partitions) etc. With float glass panes of minimum 5mm thickness (weight not less than 12.50 kg/sqm) along with EPDM rubber / neoprene gasket etc. all complete as per the architectural drawings and the directions of engineer-in-charge.
Providing and fixing mineral fibre false ceiling tiles (of approved brand/make) with 16 mm thick beveled tegular edge with (NRC 0.55 to 0.60) at all heights of size 595X595mm of approved texture,design and pattern. The tiles should have Humidity Resistance (RH) of 99%, Light Reflectance ≥ 85%,Thermal Conductivity k = 0.052 - 0.057 w/m K, Fire Performance as per (BS 476 pt - 6 &7)in true horizontal level suspended on interlocking T-Grid of hot dipped all round galvanized iron section of 0.33 mm thick (galvanized @120 gsm) comprising of main T runners of 15x32 mm of length 3000 mm, cross T of size 15x32mm of length 1200 mm and secondary intermediate cross T of size 15x32 mm of length 600 mm to form grid module of size 600x600 mm suspended from ceiling using galvanized mild steel item (galvanised@80gsm) 50 mm long 8mm outer diameter M-6 dash fasteners, 6 mm diameter fully threaded hanger rod up to 1000 mm length and L-shape level adjuster of size 85x25x2 mm, spaced at 1200 mm centre to centre along main ‘T’. The system should rest on periphery walls /partitions with the help of GI perimeter wall angle of size24x24X3000 mm made of 0.40 mm thick sheet, to be fixed to the wall with help of plastic rawl plug at 450 mm centre to centre & 40 mm long dry wall S.S. screws. The exposed bottom portion of all T-sections used in false ceiling support system shall be pre-painted with polyester baked paint, for all heights. The work shall be carried out as per specifications, drawings and as per directions of the Engineer-In-Charge. Standard approved makes for Ceilng Grid and Tiles: Saint Gobain(Gyproc),Armstrong,Shera,Hunter Douglav,Metalium,USG Borel.
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
raw.json
RAW_JSON
Tender_Notice_EC2936.pdf
TENDER_DOCUMENT • 0.46 MB
Tender_Drawing_No_1.pdf
TENDER_DOCUMENT • 0.04 MB
PB_Freeview_EC2936.pdf
TENDER_DOCUMENT • 0.31 MB
Tender_Drawing_No_2.pdf
TENDER_DOCUMENT • 0.21 MB
PQ_Freeview_EC2936.pdf
TENDER_DOCUMENT • 0.21 MB
TechnicalBidEC2936.pdf
TENDER_DOCUMENT • 3.54 MB
Pre_Qualification_EC_2936.xlsm
TENDER_DOCUMENT • 0.03 MB
Price_Bid_EC2936.xlsm
TENDER_DOCUMENT • 0.11 MB
Check_List_EC2936.pdf
TENDER_DOCUMENT • 0.11 MB
ECS_Format.pdf
TENDER_DOCUMENT • 0.19 MB
Undertaking_Letter_EC2936.pdf
TENDER_DOCUMENT • 0.28 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .