| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹34.2 LAccepted-AOC AZARA GUWAHATI ASSAM 781017 | KAMRUP METRO | ASSAM | 781017 | L1 | Accepted-AOC Lowest Bid | |
| 2 | L2₹36.3 L+₹1.8 L (5.34%)Rejected-Finance 0 PRAGATIPUR DHARMA SARMA PATH BIRUBARI KAMRUP ASSAM 781016 | KAMRUP METRO | ASSAM | 781016 | L2 | Rejected-Finance Other than L1 | |
| 3 | L3₹40.1 L+₹5.7 L (16.4%)Rejected-Finance SHREE KUNJ HOUSE NO 22B JIBAN KRISHNA PATH NEAR L P SCHOOL HENGRABARI GUWAHATI PIN 781036 | GUWAHATI | KAMRUP | ASSAM | 781036 | L3 | Rejected-Finance Other than L1 |
Tender Value
₹40 L
EMD Value
₹80,000
Closing Date
3 Dec 2022, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE (AF) Borjhar
Garrison Engineer (AF) Borjhar, Military Engineer Services, Guwahati Airport- PO, Borjhar Airport, Guwahati, Assam, Pin- 781015 Tele 0361 - 2840127
Repair/Maint of Electrical Distribution System and other allied works at 19 Wing and 14 BRD under GE (AF) Borjhar
2022_MES_560070_1
8305/BOR/E8
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
GE (AF) Borjhar
MES Contractor enlisted as Class D category b(i) having deposited Standing Security of Rs 100000.00 with dept. Contractors not enlisted in MES should meet the MES enlistment criteria corresponding to appropriate class and category.
7 documents required · 7 mandatory
₹500
Yes
GE (AF) Borjhar
₹80,000
Yes
30 Jan 2023
27 Oct 2022
5 Dec 2022
27 Oct 2022
3 Dec 2022
10 Nov 2022
Amount
Excavating in trenches not exceeding 1.5m wide and not exceeding1.5m in depth/width for laying under ground cable/foundations and getting out in soft/loose soil complete all as specified and as directed. Note: During excavation, no mechanical excavator is permitted to use at site,
Returning, filling in including spreading, leveling, watering and well ramming in layers not exceeding 25cm complete all as specified and as directed.
Removing of surplus excavating material not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and as directed.
M&L for sand cushioning for protection of LT under ground cable with screen wash sand and punning to proper required cover complete all as specified and as directed.
M&L brick protection with old size sub class ‘B’ brick for PVC under ground cable protection in trench with width equal to length of brick, laid dry and flat joining each other with gap between adjacent brick not exceeding 10mm over LT under ground cable complete all as specified and as directed.
Laying only old bricks for PVC under ground cable protection in trenches with width equal to length of brick laid dry and flat joining each other with gap between adjacent brick not exceeding 10mm over LT under ground cable complete all as specified and as directed. Note : Old serviceable retrived during taking out bricks shall re-use.
M&L excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m in depth for making foundation or any other works in hard/dense soil including removing excavated materials not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the staring point complete all as specified and as directed.
M&L for cement concrete (1:3:6) type C-2 (using 40mm graded stone aggregate) as in foundations, filling and mass concrete, etc complete all as specified and as directed.
M&L for PCC (1:3:6) type C-1 (using 20mm graded stone aggregate) as in foundation or any other works complete all as specified and as directed. Note: Form work if so required for PCC works are deemed to be inclusive with quoted rate.
M&L for rendering 10mm thick in CM (1:6) on fair faces of brick works or concrete surfaces complete all as specified and as directed.
M&L for dismantling of ACSR or AAC conductors of any sizes or types etc. complete, setting aside for taking credit complete all as specified and as directed.
M&L for dismantling of cross arms of M.S. channels or angle sections, etc. complete and depositing to MES Store Yard for re-use the serviceable steel sections complete all as specified and as directed.
M&L for dismantling of insulators of any type and sizes and depositing to MES Store Yard for re-use the serviceable insulators complete all as specified and as directed.
M&L for dismantling of earth wire or copper conductor, service feeder or distributor span of any type and sizes and depositing to MES Store Yard for re-use the serviceable conductors complete all as specified and as directed.
M&L for taking out of old unserviceable cable of any sizes or types for replacement with new cable complete all as specified and as directed.
M&L for relaying of heavy duty LT under ground cable of any sizes and types in pipe/trench /cable duct/fixed on wall by proper size shaped GI clamps with nuts, bolts, etc. and making good the disturbed surfaces by cement mortar/paint to match with the existing surface complete all as specified and as directed.
M&L for connection to Feeder Pillar Box, panel, DB or any other indicatated location by heavy duty round wire armoured LT under ground cable of size 300 Sq.mm, 3.5 Core, 1100 volt grade, XLPE insulated, PVC sheathed, multi stranded aluminium cable conforms to IS 7098 (Part-I) 1988 with latest ammendments in pipe/trench/cable duct/fixed on wall by proper size shaped GI clamps with nuts, bolts, etc. and making good the disturbed surfaces by cement mortar/paint to match with the existing surfaces including taking out old unseviceable cable and depositing the same in MES E/M Store Yard complete all as specified and as directed.
All as per Serial item No. 17 here-in-before but cable of size 240 Sq.mm, 3.5 Core, 1100 volt grade.
All as per Serial item No. 17 here-in-before but cable of size 185 Sq.mm, 3.5 Core, 1100 volt grade.
All as per Serial item No. 17 here-in-before but cable of size 150 Sq.mm, 3.5 Core, 1100 volt grade.
All as per Serial item No. 17 here-in-before but cable of size 120 Sq.mm, 3.5 Core, 1100 volt grade.
All as per Serial item No. 17 here-in-before but cable of size 95 Sq.mm, 3.5 Core, 1100 volt grade.
All as per Serial item No. 17 here-in-before but cable of size 70 Sq.mm, 3.5 Core, 1100 volt grade.
M&L connection to Feeder Pillar Box, Panel, DB or any other indicatated location by heavy duty round wire armoured LT under ground cable 50 Sq.mm, 3.5 Core, 1100 V grade HR PVC insulated, HR PVC inner & outer sheathed, multi stranded aluminium cable conforms to IS 7098 (Part-I) 1988 with latest ammendments in pipe/ trench/cable duct/fixed on wall by proper size shaped GI clamps with nut, bolts, etc. and making good to the disturbed surfaces by cement mortar/paint to match with the existing surfaces complete all as specified and as directed.
All as per Serial item No. 24 here-in-before but cable of size 35 Sq.mm, 3.5 Core, 1100 volt grade.
All as per Serial item No. 24 here-in-before but cable of size 25 Sq.mm, 3.5 Core, 1100 volt grade.
All as per Serial item No.24 here-in-before but cable of size 16 Sq.mm, 4 Core, 1100 volt grade.
All as per Serial item No. 24 here-in-before but cable of size 10 Sq.mm, 4 Core, 1100 volt grade.
All as per Serial item No. 24 here-in-before but cable of size 10 Sq.mm, 2 core, 1100 volt grade.
Supply and use of corrosion inhibiting compound during fixing the cable end in aluminium reducer terminals or any other specified location complete all as specified and as directed.
M&L for boring of holes under road, pavement, hard standing, etc. by trenchless technology using ultra sounding techinque and necessary machine for insertion of pipes, suitable for 50mm to 100mm dia GI pipes complete all as specified and as directed.
M&L for 100mm bore GI pipe, light grade, with all fittings, laid in trenches/wall/pole through MS flat iron of size 25x3mm, including nuts, bolts & washers, etc. of proper sizes for cable protection complete all as specified and as directed.
All as per Serial item No. 32 here-in-before but 80mm bore.
All as per Serial item No. 32 here-in-before but 50mm bore.
All as per Serial item No. 32 here-in-before but 40mm bore.
Taking down old unsv/corroded LT feeder pillar box/ Busbar Chamber/DB's of any sizes or types (after disconnection of all electrical connections) complete for replacement with new one complete all as specified and as directed.
Supply, install, testing, commissioning LT feeder pillar box, IP-54 type (from CPRI type tested manufacturer ) of size 1300mm x 800mm x 500mm (leg of the feeder pillar should not be less than 600mm length) out door type made out of 3.15 mm thick CRCA sheet supported and fixed on structural frame, factory made duly fixed on the ground foundation by PCC (1:2:4) type B-1(using 20mm graded stone aggregate) of size 700mm x 300mm x 600mm on the adjacent pairs of leg and net cementing the same. The feeder pillar box shall be enamelled danger notice plate of 1.6 mm thick, duly painted with two coats of enamel paint over a coat of red oxide primer (internally & externally) on the surface complete all as specified and as directed comprising with the following Electrical components/items :- NOTE : The feeder pillar box is cubicle shaped, roof canopy type, with special type of heavy duty stainless steel door hinges and totally enclosed dust proof and vermin proof front and back opening with locking arrangements and arrangement of fixing padlock on the front door with one No 7 levers Pad Lock (Type Nav-Tal, 6 levers, 3 Keys, Make- Godrej).
(A) INCOMING/OUT GOING : (i) Aluminium bus bar 4 strips (covered with PVC insulated sleeves) 600 Amps capacity, 60-70 cm long including connection etc complete – 01 Set (ii)Moulded case circuit breaker 250 Amps 415 Volts, Adjustable Thermal Magnetic Trip Unit, Ics = 100%Icu, 4 pole, 25KA breaking capacity = 01 No (Incoming to FP Box) (iii) Moulded case circuit breaker 250 Amps 415 Volts, Adjustable Thermal Magnetic Trip Unit, Ics=100%Icu, 4 pole, 25 KA breaking capacity with incoming and outgoing spreader sets = 01 No (Outgoing to another FP Box) Note- The connection between the MCCB and bus bar shall be done by aluminium bar or cable of suitable rating with nut, bolt & washer.
(B) OUT GOING (i) MCB FP 40 to 63 Amps,415 Volts, 50 HZ, 10 KA breaking capacity (DIN rail mounted) Type ‘C’ Characteristic = 06 Nos (ii) DP 20 to 32 Amps, 240 Volts, 50 HZ, 10 KA breaking capacity (DIN rail mounted) Type ‘C’ Characteristic. Note- (i) All cables in the feeder pillar box shall be properly glanded and thimbled as specified and directed. (ii) Cable Lugs or thimbled will be measured and paid separately.
Taking down old unsv/ corroded LT feeder pillar box/ Busbar Chamber/ DB's of any sizes or types (after disconnection of all electrical connections) complete for replacement with new one complete all as specified and as directed.
Supply, installation, testing and commissioning LT cubicle type distribution panel, IP-54 type (manufactured from CPRI type tested manufacturer i.e. Parbati Engineers/ Kratos/ Bramhaputra Power & Control) indoor type made out of 2.00 mm thick CRCA sheet supported on structural frame, angle or channel, factory made, fixed on the ground by galvanised nut & bolts, PCC works in cement concrete (1:2:4) type B-1 (using 20mm graded stone aggregate). The LT cubicle type distribution panel should have enamelled danger notice plate of 1.6 mm thick, duly painted with powder coated paint of shade RAL 7032 (internally & externally) complete all as specified and as directed comprising with the following Electrical components/items :- NOTE : The LT distribution panel must have stainless steel hinges, with special type of heavy duty stainless steel front & back door opening, locking arrangements. INDICATING DEVICES (a) Three Phase LED Ammeter, Class - 1 with CT (size 96mm x 96mm) = 01 No (b) Three Phase LED Voltmeter, Class - 1 (size 96mm x 96mm) = 01 No (c) LED type panel indicator lamp = 03 Nos
BUS BAR (a) Aluminium bus bar 4 strips (covered with PVC insulated sleeves as per colour code) 600 Amps capacity, including connection etc complete = 01 Set INCOMING (b) Moulded case circuit breaker 200 - 250 Amps 415 Volts (Vertically Placed), 4 pole 25 KA breaking capacity, Ics=100% Icu, adjustable overload settings 0.8 - 1.0 x In, adjustable short circuit settings 6 - 10 x In = 02 Nos OUTGOING (c) On-Load Manual Change Over Switch (Open Execution Type) 250 Amps 415 Volts, 4 pole = 01 No (d) Moulded case circuit breaker 100 - 125 Amps 415 Volts (Vertically Placed), 4 pole 25 KA breaking capacity, Ics=100% Icu, adjustable overload settings 0.8 - 1.0 x In, adjustable short circuit settings 6 - 10 x In = 02 Nos
(e) Moulded case circuit breaker 63-80 Amps 415 Volts (Vertically Placed), 4 pole 25 KA breaking capacity, Ics=100% Icu, adjustable overload settings 0.8 - 1.0 x In, adjustable short circuit settings 6 - 10 x In = 03 Nos (f) Moulded case circuit breaker 40 - 50 Amps 415 Volts (Vertically Placed), 4 pole 25 KA breaking capacity, Ics=100% Icu, adjustable overload settings 0.8 - 1.0 x In, adjustable short circuit settings 6 - 10 x In = 02 Nos Note- The connection between the MCCB and bus bar should be done by aluminium bar of suitable rating.
Supply and installation on wall/ floor fire extinguisher including painting as " MES “ on the extinguisher of undermentioned specification :- ABC stored pressure type fire extinguisher capacity 09 Kg with squeeze lever discharge valve fitted with pressure indicating gauge with internal discharge tube, discharge hose and nozzle, suspension bracket conforming to IS : 15683:2006 duly charged with ISI marked mono ammonium phosphate base ABC powder conforming to IS : 4308:2019 and pressurize with nitrogen gas complete all as specified and as directed. Make : Fire Shield / Eversafe.
M&L for brickwork with sub class ‘B’ bricks, straight or curved on plan exc 6m mean radius, set in cement mortar (1:6) complete all as specified and as directed.
M&L for dismantling / taking down angle sections / cable duct cover, etc. complete and setting aside for taking credit complete all as specified and as directed.
M&L for replacement of cable duct cover or any other works made up of chequered plate with lifting handle (whereever required) including fabrication works such as cutting, welding & bent to shape and painting with two coats of black japan paint over one coat of red oxide primer on steel surfaces of any description over 10cm in width or girth including preparation of new untreated surfaces complete all as specified and as directed.
M&L angle iron / flat bar of required sizes with locking arrangements including fabrication works such as such as cutting, welding & bent to shape and painting with two coats of black japan paint over one coat of red oxide primer on steel surfaces of any description over 10cm in width or girth including preparation of new untreated surfaces complete all as specified and as directed.
M&L for fixing the aluminium terminal in cable end (through corrosion inhibiting compound) of cable size 300 Sq.mm complete all as specified and as directed. Note: Corrosion inhibiting compound which shall be used during crimping of terminal shall be measured and paid separately.
All as per Serial item No. 45 here-in-before including Note but cable size 240 Sq.mm
All as per Serial item No. 45 here-in-before including Note but cable size 185 Sq.mm
All as per Serial item No. 45 here-in-before including Note but cable size 150 Sq.mm
All as per Serial item No. 45 here-in-before including Note but cable size 120 Sq.mm
All as per Serial item No. 45 here-in-before including Note but cable size 95 Sq.mm
All as per Serial item No. 45 here-in-before including Note but cable size 70 Sq.mm
All as per Serial item No. 45 here-in-before including Note but cable size 50 Sq.mm
All as per Serial item No. 45 here-in-before including Note but cable size 35 Sq.mm
All as per Serial item No. 45 here-in-before including Note but cable size 25 Sq.mm
All as per Serial item No. 45 here-in-before including Note but cable size 16 Sq.mm
All as per Serial item No. 45 here-in-before including Note but cable size 10 Sq.mm
Supply only fixing decorative PC diffuser type LED Bollards made up of extruded aluminium 9 - 10 W, 230V and all accessories internally pre-wired with installation screws & rawl plug and connection cable of suitable size and lenth (not less than 0.8m) complete all as specified and as directed. Make : Philips/Surya (Blink type)/Crompton (Liara type)
Supply only aesthetically designed decorative LED post top lantern with four nos die cast aluminium arms to support the housing 45W, 230V, IP 65 with 3.5 KV internal 10 KV external SPD and all accessories internally pre-wired with connection cable of suitable size and lenth (not less than 2.0m) complete all as specified and as directed. Make : Philips/Orient (Type Crestline)/ Havells (Type Victoria)/Jaquar
M&L for fixing the cable junction boxes of size 225 x 295 x 122mm with terminals for 35 Sq.mm, 3.5 core, 1100 volt cable, IP 66/69, weather proof, outdoor installation type with threaded cable glands and pole mounting brackets, etc. complete all as specified and as directed.
M&L for fixing the cable junction boxes of size 205 x 255 x 112mm with terminals for 10 - 25 sq.mm, 4.0/3.5 core, 1100 volt cable, IP 66/69, weather proof, outdoor installation type with threaded cable glands and pole mounting brackets, etc complete all as specified and as directed.
M&L for making two nos holes (one at top portion of the pole and one at bottom portion of the pole) for throughing 1.5 sq.mm, 3 single core, 1100 volt cable with in steel tubular swaged pole of type SP 31/ 55 through drill or other required T&P complete all as specified and as directed.
M&L for 3 single core PVC insulated multi stranded copper conductor cable 1.5 sq.mm 1100 volt unarmoured for connection from loop /junction box to street lights/security lights,etc. complete all as specified and as directed.
Supply only multipurpose lubricating & rust remover aerosol in 420 ml container complete all as specified and as directed. Make- Pidilite (Type- WD- 40)/equivalent from approved make.
Supply only high tension pressure sensitive self bonding electrical cable repair tape (38mm width, 900cm long) for XLPE insulated cable complete all as specified and as directed. Make- Jonson/equivalent from approved make.
Supply only maintenance type microfibre cloth, 340 GSM (set of ten) of approx size 40cm x 40cm) Make : 3M/Softspun/Gala
M&L for triming the tree branches of girth 10 to 20cm, falling/touching the HT/LT overhead line in various area of AF Station Borjhar with skilled labours and cutting tools and disposed the branches to a distance not exceeding 50m from starting point complete all as specified and as directed.
All as per Serial item No. 66 here-in-before but girth 20 to 30cm
M&L for replacement of damage/corroded hinges with new hinges throgh necessary gas / arc welding works complete on the outdoor feeder pillar box/LT panel/ or any other works complete all as specified and as directed.
M&L for replacement of corroded sheet metal doors of outdoor/ inddor feeder pillar box or LT panel with new CRCA sheet of 2 or 3mm thick including painting the same with two coats of synthetic enamel paint of existing shade over one coat of red oxide primer including treatment of new surfaces complete all as specified and as directed.
M&L for writing letter, figures, index, arrows, etc. not exc 30 cm in height on LT Panel or any other specified location complete all as specified and as directed.
M&L for painting of LT Feeder Pillar Box/Panel Board or any other plant or equipments by two coats of synthetic enamel paint of existing shade after treating old painted surfaces complete all as specified and as directed.
M&L for cable jointing kit for 1.1KV grade for outdoor end termination heat shrink type joint complete with jointing material and accessories suitable for 4 core PVC/ XLPE armoured aluminium conductor cable of size 25 - 50 sq.mm complete all as specified and as directed.
M&L for cable jointing kit for 1.1KV grade for outdoor end termination heat shrink type joint complete with jointing material and accessories suitable for 4 core PVC/ XLPE armoured aluminium conductor cable of size 70 - 120 sqmm complete all as specified and as directed.
M&L for cable jointing kit for 1.1KV grade for outdoor end termination heat shrink type joint complete with jointing material and accessories suitable for 4 core PVC/ XLPE armoured aluminium conductor cable of size 150 - 185 sqmm complete all as specified and as directed.
M&L for cable jointing kit for 1.1KV grade for outdoor end termination heat shrink type joint complete with jointing material and accessories suitable for 4 core PVC/ XLPE armoured aluminium conductor cable of size 240 - 300 sqmm complete all as specified and as directed.
Supply only electrical insulating gloves manufactured from natural rubber latex conforms to EN 60903:2003, IEC 60903:2014, Type Class 2 having withstanding voltage 30KV AC and proof test voltage 20KV AC having length 360mm and red color complete all as specified and as directed. Make : Raychem RPG (Kamfet)/ 3M
Supply & laying electrical mat with fabric finish, Rohs 2 compliant conforms to EN 61111 standards, Type Class 0 having withstanding voltage 10 KV AC and proof test voltage 5 KV AC having size 1.0 x 0.6 m² mm and dark grey color complete all as specified and as directed. Make : Raychem RPG (Kamfet)/ 3M
Supply and laying electrical mat with fabric finish, Rohs 2 compliant conforms to EN 61111 standards, Type Class 0 having withstanding voltage 10 KV AC and proof test voltage 5 KV AC having size 2.0 x 0.6 m² mm and dark grey color complete all as specified and as directed. Make : Raychem RPG (Kamfet)/ 3M
Supply and laying electrical mat with fabric finish, Rohs 2 compliant conforms to EN 61111 standards, Type Class 0 having withstanding voltage 10 KV AC and proof test voltage 5 KV AC having size 1.0 x 1.0 m² mm and dark grey color complete all as specified and as directed. Make : Raychem RPG (Kamfet)/ 3M
Supply and laying only electrical mat with fabric finish, Rohs 2 compliant conforms to EN 61111 standards, Type Class 2 having withstanding voltage 30 KV AC and proof test voltage 20 KV AC having size 1.0 x 1.0 m² mm and dark grey color complete all as specified and as directed. Make : Raychem RPG (Kamfet)/ 3M
S&F On-Load Manual Change Over Switch (in sheet steel enclosure) 100 Amps 415 Volts, 4 pole after disconnecting all electrical connection including taking down old unserviceable one complete all as specified and as directed.
S&F On-Load Manual Change Over Switch (in sheet steel enclosure) 160 Amps 415 Volts, 4 pole after disconnecting all electrical connection including taking down old unsericeable one complete all as specified and as directed. Make - L&T/ Siemens/ABB = 01 No
S&F outdoor type strip light (RGB type) of 5m length 40W, 24V DC with RGB controller, amplifier and power supply unit 60W, 24V complete all as specified and as directed. Make : Jaquar/ Havells/ Philips/manufactured by Jaquar or Philips or Orient
S&F moulded case circuit breaker 80 - 100 Amps 415 Volts (with thermal magnetic release), 4 pole 25 KA breaking capacity, Ics=100% Icu, adjustable overload settings 0.8 - 1.0 x In, adjustable short circuit settings 6 - 10 x In after disconnecting all electrical connection including taking down old unserviceable one complete all as specified and as directed.
S&F moulded case circuit breaker 125 - 160 Amps 415 Volts (with thermal magnetic release), 4 pole 25 KA breaking capacity, Ics=100% Icu, adjustable overload settings 0.8 - 1.0 x In, adjustable short circuit settings 6 - 10 x In after disconnecting all electrical connection including taking down old unserviceable one complete all as specified and as directed.
S&F moulded case circuit breaker 200 - 250 Amps 415 Volts (with thermal magnetic release), 4 pole 25 KA breaking capacity, Ics=100% Icu, adjustable overload settings 0.8 - 1.0 x In, adjustable short circuit settings 6 - 10 x In after disconnecting all electrical connection including taking down old unserviceable one complete all as specified and as directed.
D.B ENTERPRISE
M/S PRASANTA MAHANTA
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .