Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹13.6 LAccepted-AOC 3082 SECTOR 20D CHANDIGARH 160 020 | CHANDIGARH | CHANDIGARH | 160020 | L1 | Accepted-AOC Being lowest | |
| 2 | L2₹18.9 L+₹4.3 L (29.1%)Rejected-Finance ASHOKA PARK PALLAVA PARK BVT INS VISHWAKARMA INDIAN NAVY OF GE ND VISAKHAPATNAM | VISAKHAPATANAM | ANDHRA PRADESH | 530001 | L2 | Rejected-Finance Being other than lowest |
Tender Value
₹28.5 L
EMD Value
₹57,000
Closing Date
31 Aug 2020, 6:00 pmClosed
GE Chandigarh
GE Chandigarh
REPAIR /MAINTENANCE OF SUMMER AND WINTER APPLIANCES INCLUDING REPAIRS OF INTERNAL WIRING AND FITTINGS AT PCDA (WC) AND DAD COLONY UNDER GE CHANDIGARH.
2020_MES_366267_1
GE/CHD-42/2020-21
Open Tender
Civil Works
Item Rate
270 days
Chandigarh
Class D Cat b i
7 documents required · 7 mandatory
₹500
GE Chandigarh
₹57,000
Yes
15 Sept 2020
4 Aug 2020
2 Sept 2020
4 Aug 2020
31 Aug 2020
19 Aug 2020
4 Aug 2020 - 10 Aug 2020
Amount
Taking down Ceiling fan of Sweep,1200 to 1400mm, 230 volts of any make & size from any height of the building for finding out the defects such as Capacitor, winding, bearing etc and servicing / overhauling the same, including replacing minor accessories like split pins, rubber reel, PVC sleeve, greasing, clamps, etc as required, and fixing back the same in its original position along with necessary fixing materials such as nut, bolts and washers etc all as specified and as directed by Engineer-in-charge. Note:- The spares referred / mentioned here-In- after shall only be paid under supply only. Rest of the spares required for functioning of the fans is deemed to be included in the unit rate quoted. The labour element required for replacing the spares listed here-In -after shall be deemed to be included in the unit rate quoted.
Taking down Exhaust fans heavy duty of Sweep 225 to 450mm, 230 volts of any make & size from walls/ trusts for finding out the defects such as Capacitor, winding, bearing etc and servicing/ overhauling the same and fixing back the same in its original position along with necessary fixing materials such as nut, bolts and washers etc all as specified and as directed by Engineer-in-charge. Note:- The spares referred / mentioned here-In- after shall only be paid under supply only. Rest of the spares required for functioning of the fans is deemed to be included in the unit rate quoted. The labour element required for replacing the spares listed here-In -after shall be deemed to included in the unit rate quoted.
Taking down Wall mounted/Pedestal fans of Sweep 350 to 450mm, 230 volts of any make & size from walls/floors for finding out the defects such as Capacitor, winding, bearing etc and servicing/ overhauling the same and fixing back the same in its original position along with necessary fixing materials such as nut, bolts and washers etc all as specified and as directed by Engineer-in-charge. Note for Item Sl No 1 to 3 : (i). Cost of Bearing, Capacitor and rewinding will be measured and paid separately under the respective item of the Schedule. (ii) Labour element for removing and refixing the Bearing and removing and rewinding the winding will be measured in the respective of the schedule. (iii) Misc items such as nut & bolts, Rubber bush & locking pin etc required for satisfactory completion of job deemed to be inclusive of the unit rate.
Supply and fix of Capacitor 2.5 mfd/3.15 mfd, AC 250 volts capacity all as directed. Make :Usha / Bajaj / Tibco / CG/EPCOS
All as item No 4 here in above but of Capacity 4.0 MFD, AC 250 volts Make :- Usha / Bajaj / Tibco / CG/EPCOS
Rewinding of fan motor of any make Sweep 1200 to 1400mm and rewinding the same with single strand fine enamel copper conductor of same guage weight and turns and keeping the windings into hot air oven till the moisture evaporates including testing and commissioning complete. Make : (i) ICC (ii) DEVY DAYAL (iii) USHA Note : (1) All the misc items such as impregranted paper, warnising, cotton tape and other misc items required for satisfactory completion of job deemed to be included in the unit rate. (2) The above repairs are considered to meet the anticipated requirement if any and based on the site requirement the scope will be handed over to the Contractor.
All as item No 06 here in above but for Exhaust fan 225 to 300mm sweep.
All as item No 06 here in above but for Exhaust fan 350 to 450mm sweep.
All as item No 06 here in above but for Pedestal / Wall mounted fan upto 450mm sweep.
Supply only Ball bearing suitable for 1200mm to1400 mm sweep ceiling fans
Supply only gun metal bush suitable for 1200mm to 1400 mm sweep ceiling fans
Supply only Mild steel shaft suitable for 1200 to 1400 mm sweep ceiling fans
Supply only Ball bearing suitable for 225 to 450 mm sweep Exhaust / Wall mounting fan/Pedestal fan.
Supply only gun metal bush suitable for 225mm to 450 mm sweep Exhaust / Wall mounting fan
Supply only Mild steel shaft suitable for 225mm to 450 mm sweep Exhaust / Wall mounting fan
Supply only Rubber reel for ceiling fan any type any description.
Supply and fix in repair M.S rod including clamp , nut & split pin suitable for 1200/1400/1500mm sweep fan complete all as specified and as directed by Engineer-in-charge.
Supply and fix in repair PVC canopy suitable for 1200/1400/1500mm sweep fan complete all as specified and as directed by Engineer-in-charge.
Supply and fix in repair fan blades (set of three blades) for 1200 mm sweep and 1400 mm sweep ceiling fans complete all as specified and as directed by Engineer-in-charge.
Preparation of surface and painting the Ceiling fan unit of sweep 1200 to 1400mm (consisting of Fan motor, blades, canopy and downrod) with one coat of synthetic enamel paint of existing colour and marking the MES number on the fan motor with suitable paints all as directed by the Engg-in-Charge complete. Make :- Asian / Berger / Jenson & Nicholson.
M&L for lathe work to any type of fan for taking out bush from the lower body part of Ceiling/Exhaust fan and replacing it with suitable size of ball bearing as per matching size to shaft making necessary bearing boring, cutting, greasing, polishing of shaft Complete all as specified and as directed by Engineer-in-charge. Note : - Supply & fixing to Bearing shall be measured and paid separately under respective item of this Schedule.
Supply and fix in repair AC ceiling fan 1200 mm sweep with Accessires Complate with set of lades, down rod and set of canopy. Make :USHA/Crompton/Havells.
Supply and fix in repair AC Exhaust fan 250 mm sweep high air delivery low noise complete with diffusers Make : USHA/Crompton Havells.
Disconnecting and removing the unserviceable Geyser electrically operated of capacity 25 to 50 litres from its original position including disconnecting the electrical and water connections and to finding out the defects and refixing the same after making the same in serviceable condition in its original position connecting up of Electric and water connections, testing and commissioning complete all as specified and directed by Engg-in-Charge. Note : (i) Spare parts such as Inner copper container, thermostat, element, hot & cold water inter connected pipes and cord flexible will be measured and paid separatley. (ii) Misc items and brazing to the Inner copper container and welding to the outer container as required for satisfactory completion of Job deemed to be included in the unit quoted rate. (iii) Existing glass wool to be used after repairs.
All as per above item No 24 here-in-before but 50 ltr capacity.
S&F thermostat for Geyser 0 to 80 degrees 230 volts as suits the existing geyser of any type and capacity all as specified and directed by Engg-in-Charge. Make :- Bajaj / Racold / Venus / usha
Supply only glass wool of good quality as approved for 25 litre capacity of geyser complete all as specified and as directed by Engineer-in-Charge.
All as per above item No 27 here-in-before but 50 litre capacity.
Supply and fix in repairs Stain less steel inner tank of 25 liter capacity geysers of existing make & model including testing after assembled & fixed at site complete all as specified and as directed by Engineer-in-Charge.
All as per above item No 29 here-in-before but 50 ltr capacity.
Supply and fix in repairs Heating element 2 KW ISI Marked complate all as specified and as directed. MAKE:-RECOLD / VENUS / GILCO / PREMIER / THEETA
Supply and fix in repairs Heating element 1.5 KW ISI Marked complate all as specified and as directed. MAKE:-RECOLD / VENUS / GILCO / PREMIER / THEETA
Supply and fix in repairs Safety valve
Supply and fix in repairs Indicating Lamp Round /Square
Supply and fix in repairs 23 to 30 cm long ,10 mm bore C.P Connection with brass union
Supply and fix in repairs Gun metal non return valve ,15 mm bore
S&F for inter connected PVC flexible pipe 60 cm long with both ends check nuts suitable for hot water and connecting the same between the geyser and pipe line. Make : Pressfit/Modi/Prestolast
Supply and fix in repairs Apparatus plate for 25 litre / Syphon Assy
Supply and fix in repairs Apparatus plate for 50 litre / Syphon Assy
Supply and fix in repairs Bottom plates in two halves for 25/50 liter.
Supply and fix in repairs Plug top 3-pin, 16 Amp
Supply and fix in repairs Rubber O ring /gasket for 25 ltrs
Supply and fix in repairs Electric water storage Heater (vertical type Geysers) 25 Ltrs 230 volts, AC single phase with and including grouting with high tensile rag bolt, nut & washer etc as directed as per site requirement .Geysers to have glass lines tank, fero glass coated container,PUF insulation, glass coated heating element, 8 BAR rated pressurer, thermostat cut off etc.including cutting holes and making good the disturbed surface complete all as specified and as directed by Engineer-in-charge. Make : Havells/Venus/AO Smith
M&L for preparation of surface of geyser of 25 ltrs capacity of any make by scrapping to existing paint, filling cavities with filler (Putty) after cleaning of dust etc and applying two coats of synthetic enamel paint over a coat of red oxide primer and writing the MES No with black paint complete all as specified and as directed by Engineer-in-Charge.
M&L for preparation of surface of geyser of 50 ltrs capacity of any make by scrapping to existing paint, filling cavities with filler (Putty) after cleaning of dust etc and applying two coats of synthetic enamel paint over a coat of red oxide primer and writing the MES No with black paint complete all as specified and as directed by Engineer-in-Charge.
S&F for replacement to unserviceable flexible PVC insulated lead in lieu of provided with new flexible PVC insulated sheathed copper conductor connection lead 3- core ,size 40/0.0076 cable suitable for geyser Complete all as specified and as directed by Engineer-in-Charge. MAKE :- HAVELL’s / FINOLEX/PLAZA/RR KABEL
Cutting chasing in bricks/walls or concrete surfaces for GI tubing 15/20mm bore including making good with cement mortar 1:3, cutting not exceeding 10cm girth complete all as specified and directed by Engineer-in-charge
S&F for sheet metal enclosure with single pole and neutral with two pin and earth plug socket including 20Amp 240 Volt including MCB SP,20Amp(C-series) as in repair complete all as specified and as directed by Engineer-in-Charge.Make :-- INDO-AISIAN / Havells/ Legrand
S&F for 15mm bore stop valve cast copper alloy chromium plated fancy type, high pressure with crutch or butterfly handle screwed both ends for iron pipe or union and fixed as in repair complete all as specified and as directed by Engineer-in-Charge.Make :Kiran/Leader/Prayag
S&F for 20mm bore stop valve cast copper alloy, high pressure with crutch or butterfly handle screwed both ends for iron pipe or union and fixed as in repair complete all as specified and as directed by Engineer-in-Charge.Make :KIRAN/LEADER/Prayag.
Taking down to 15mm bore steel tubing and connection including cleaning for re-fixing or remove from site complete all as directed by Engineer-in-Charge.
S & F for 15mm bore steel water tubing medium grade, galvanised with all fittings and fixture fixed & concealed in wall/ceiling or laid in floors complete all as specified and directed by Engineer-in-charge. Make - JINDAL/SWASTIK/SURYAPARKASH.
Unservicable sealed compressor of water cooler of capacity 150/180liters and replaceed with new sealed compressor of existing capacity & model including soldering of liquid/gas pipe cleaning the system arresting the leaking etc complete all as specified and as directed by Engineer-in Charge. Make: Sri Ram/Tikamshah/Kirlosker. NOTE:- Recharging of refrigerant gas shall be measured & paid separately under respective item of this schedule 'A'.
All as per above item No 53 here in before but water cooler of capacity 40/80Liters.
Cleaning the system with CTC and charging the refrigerant gas R-22/134 including replacing strainer and rectification of leakage of the system from water cooler of 150 litres capacity complete all as specified and as directed by Engineer-in-charge.
All as per above item No 55 hereinbefore but water cooler of capacity 40/80 liters
S&F for internal wiring for water coolers 150/80/40 ltr capacity with PVC insulated unsheathed flexible copper conductor cable single core size 40/0.0076 fixed with terminal clips etc including replacement of screws, washers etc required for fastening to body etc complete all as specified and as directed by Engineer-in-charge.Make :-- KALINGA/ FINOLEX/PALAZA
Supply and fix in repairs starting relay assembly suitable for water cooler of 150 liter capacity Complete all as specified and as directed by Engineer-in-Charge . Make :-- RENUTRAL/ INDFOS/DANFOS
All as per above item No 58 hereinbefore but water cooler of capacity 40/80 liter
Supply and fix in repairs over load protector suitable for water cooler of 150 liter capacity Complete all as specified and as directed by Engineer-in-Charge. Make :-- RENUTRAL/ INDFOS/DANFOS
All as per above item No 60 hereinbefore but water cooler of capacity 40/80 liter
S&F in repair fan motor suitable for water cooler of 150 liter capacity Complete all as specified and as directed by Engineer-in-Charge. Make :- COOL-HOME/ AUE
All as per above item No 62 hereinbefore but water cooler of capacity 40/80 liter
Replacement to unserviceable condenser unit with new condenser unit of existing make and model suitable for water cooler of capacity 150/180 liters, complete all as specified and as directed.
All as per above item No 64 here in before but water cooler of capacity 40/80Liters.
S& F for 15 mm bore self closing tap push type cast copper alloy chromium plated fixed to water cooler as in repair Complete all as specified and as directed by Engineer-in-Charge.
M&L for cleaning to water coolers upto 150 ltrs capacity internal & external surfaces of suitable repairs to body & stop leakage etc, replacing unserviceable nut bolts & washers etc including preparation of external surfaces of bottom body and painted with anticorrosive synthetic enamel paint with help of spray gun machine over a coat of red oxide primer Complete all as specified and as directed by Engineer-in-Charge.
All as per above item No 67 hereinbefore but water cooler of capacity 40/80 liter
S&F for replacement to unserviceable thermo-state switch in lieu of provided with new thermo-state switch suitable for water cooler any capacity Complete all as specified and as directed by Engineer-in-Charge. Make :- RENUTRAL/ INDFOS
Supply and fix in repairs sealed compressor for refrigerator of capacity 180/210 liter of existing capacity & model including soldering of liquid /gas pipe ,cleaning the system & the leakage etc complete all as specified and as directed by Engineer-in-charge. Make :- SHRI-RAM/ TIKAMSHAH/ KIRLOSKER / WHIRLPOOL .
Recharging of gas R-10/12/134a in refrigerant cap 180/210 litre complete including testing of leakage and testing the unit for satisfactory performance Complete all as specified and as directed by Engineer-in-Charge.
Supply and fix in repairs Freezer door plastic with tension spring as per existing model suitable 160/210 liter cap.
Supply and fix in repairs Door liner ( Plastic ) for upto 310 liter capacity
Supply and fix in repairs Door magnetic gasket for upto 310 litre capacity.
Supply and fix in repairs Relay box type for any cap.
Supply and fix in repairs over load protector for any Cap.
Disconnection and removing the unserviceable Split AC Outdoor & Indoor Unit/ window type of Capacity 1.5 Ton to 4 Ton from the existing position carefully for finding of the defects and to replace the unserviceable spare parts such as Compressor, Condensor Fan Motor, Condensor Coil, Suction & Discharge valves, mother plates including carry out leak detection test, Gas charging, servicing such as cleaning and removing the dust particles accumulated in the unit and filters carefully and washing the cooling unit and Indoor unit with water and refixing the same in its original position complete including connecting up of the Copper Tubes and cable connections, testing and commissioning complete all as specified and as directed by Engineer-in-charge. Make of existing ACs . Make:- LG/Blue Star/Hitachi/Voltas . (i) Cost of spares such as Compressor, Condensor Fan Motor, Condensor Coil, Suction & Discharge valves, mother plates, leak detection test, Gas charging shall be measured and paid separately under the respective Schedule 'A' Item. (ii) Makes & Specifications of the spare parts for replacement should be identical equivalent to the spares suitable for existing ACs. (NOTE :- Labour element included in Item No 80 to 98)
Supply only Outdoor hermatically sealed Compressor Unit of Capacity 1.5 Ton Single Phase for Split Type ACs complete all as specified and as2) directed by Engineer-in-charge. Make : LG/Hitachi/Voltas/Blue Star
Supply only indoor sealed Compressor Unit of Capacity 1.5 Ton Single Phase for window ACs complete all as specified and as directed. Make : LG/Hitachi/Voltas/Blue Star
Supply only Outdoor hermatically sealed Compressor Unit of Capacity 2 Ton Single Phase for Split Type ACs complete all as specified and as directed. Make : LG/Hitachi/Voltas/Blue Star
Supply only indoor sealed Compressor Unit of Capacity 2.0 Ton Single Phase for window ACs complete all as specified and as directed. Make : LG/Hitachi/Voltas/Blue Star
Supply only sealed Compressor Unit of Capacity 4 Ton Single Phase for Standing Split Type ACs complete all as specified and as directed. Make : LG/Hitachi/Voltas/Blue Star
Supply only Condensor Fan Motor 230 Volt suitable for 1.5 Ton Outdoor Split Type Air Conditioning Unit complete all as specified and as directed. Make : LG/Hitachi/Voltas/Blue Star
Supply only Condensor Fan Motor 230 Volt suitable for 2 Ton Outdoor Split Type Air Conditioning Unit complete all as specified and as directed. Make : LG:/Hitachi/Voltas/Blue Star
Supply only Fan Motor 230 Volt suitable for window type AC of 1.5 Ton capacity complete all as specified and as directed. Make : LG/Hitachi/Voltas/Blu::e Star
Supply only Fan Motor 230 Volt suitable for window type AC of 2.0 Ton capacity complete all as specified and as directed. Make : LG/Hitachi/Voltas/Blue Star
Supply only Fan Motor 230 Volt suitable for Standing Split type AC of 4.0 Ton capacity complete all as specified and as directed. Make : LG/Hitachi/Voltas/Blue Star
Supply only blower motor suitable for Split type AC of 1.5/2 Ton capacity complete all as specified and as directed. Make : LG/Hitachi/Voltas/Blue Star
Supply only blower motor suitable for window type AC of 1.5/2 Ton capacity complete all as specified and as directed. Make : LG/Hitachi/Voltas/Blue Star
Supply only blower motor suitable for Standing Split type AC of 4 Ton capacity complete all as specified and as directed. Make : LG/Hitachi/Voltas/Blue Star
Supply only Condensor Coil Unit consisting of Copper tubing suitable for 1.5 Ton Outdoor Unit of Split Type Air Conditioning complete all as directed.
Supply only Condensor Coil Unit made out of Copper tubing suitable for 2 Ton Outdoor Unit of Split Type Air Conditioning complete all as directed.
Supply only Condensor Coil Unit consisting of Copper tubing suitable for 1.5 Ton Outdoor Unit of window Type Air Conditioning complete all as directed.
Supply only Condensor Coil Unit consisting of Copper tubing suitable for 2 Ton Outdoor Unit of window Type Air Conditioning complete all as directed.
Supply only Condensor Coil Unit made out of Copper tubing suitable for 4 Ton Outdoor Unit of Split Type Air Conditioning complete all as directed.
Supply only PCB/ Mother Board Unit alongwith Remote Control Unit suitable for 1.5/2/4 Ton Indoor Unit of Split Type Air Conditioning complete all as directed.
Disconnection and Removing the unserviceable /broken Fan Blade from the Outdoor units of Split AC Unit 1.5 / 2 /4 Ton Capacity and S&F New Fan Blade Unit complete suitable for existing AC Unit.
Disconnection and Removing the unserviceable Running/Starting Capacitors from the Outdoor units of Split Type AC Unit 1.5/2/4 Ton Capacity and S&F New Capacitors of capacity 36/46/50 MFD, 230 Volts, ISI Marked.
Disconnection and removing the unserviceable Display Unit and S&F Digital Display for indicating Temperature, Temperature Sensor for 1.5/2/4 Ton Split AC Unit complete all as directed. Make :- LG/Hitachi/Voltas
Supply and Charge Refrigerant (R-22)/410a/407C Suitable for existing 1.5 Ton Capacity Split / Window type air conditioning unit complete all as directed.
Supply and Charge Refrigerant (R-22)/410a suitable for existing 2 Ton Capacity Split / Window type air conditioning unit complete all as directed.
Supply and Charge Refrigerant (R-22)/410a suitable for existing 4 Ton Capacity Standing Split type air conditioning unit complete all as directed.
Disconnection and Removing the damaged Flexible PVC Drain Pipe of dia 25mm and S&F New Standard Flexible PVC Drain Pipe of dia 25mm for capacity 1.5 ton, 2.0 ton & 4 Ton capacity.
Disconnection and removing the old unserviceable Copper Pipe between Indoor & Outdoor Unit and S&F New Copper Pipe of 1/2" dia and connecting alongwith Insulation Sleeves to the existing position incl leak testing complete all as directed by Engineer-in-charge.
All as per Item No 104 here in above but of 1/4" dia
Supply only Suction Valve made of Brass suitable for 1.5 Ton Outdoor Unit of Split Type Air Conditioning complete all as directed. (Note : Labour to element included in Item No 77)
Supply only Suction Valve made of Brass suitable for 2 Ton Outdoor Unit of Split Type Air Conditioning complete all as directed. (Note : Labour to element included in Item No 77)
Supply only Suction Valve made of Brass suitable for 4 Ton Outdoor Unit of Standing Split Type Air Conditioning complete all as directed. (Note : Labour to element included in Item No 77)
Supply only Discharge Valve made of Brass suitable for 1.5 Ton Outdoor Unit of Split Type Air Conditioning complete all as directed. (Note : Labour to element included in Item No 77)
Supply only Discharge Valve made of Brass suitable for 2 Ton Outdoor Unit of Split Type Air Conditioning complete all as directed. (Note : Labour to element included in Item No 77)
Supply only Discharge Valve made of Brass suitable for 4 Ton Outdoor Unit of Standing Split Type Air Conditioning complete all as directed. (Note : Labour to element included in Item No 77)
Disconnection and Removing the defective / damaged Industrial Plug & Socket Board and supply & fix Industrial Plug & Socket controlled by 01 No 20 Amp Single Pole ISI Marked in and including sheet metal enclosure suitable for 1.5/2 Ton capacity
Disconnection and Removing the Cable connections and Copper Pipe alongwith all connected items carefully from the existing indoor and out door units and Pumpdown the refriegerant from Outdoor Unit of tonnage 1.5/2/4 Ton including stabilizer from the existing positions and shifting the AC unit at new place and refixing the outdoor and indoor units with necessary copper tubing including topping up of gas and connecting stabilzer etc for its proper functioning all as directed and specified by Engineer-in-charge.
Carry out of Leak Proof Test for detection of leakage of gas from the cooling unit & Copper Tubing for Indoor/Outdoor Unit of Air conditioner, Refrigerator, Water Cooler with liquid nitrogen gas and arresting by gas welding method complete and charging of refrigerant into the Air conditioner/Refrigerator/Water Cooler complete. Note :- 1 The leakage to be observed for 24 Hours and after confirmation only the refrigerant is to be provided to the unit. 2 The cost of refrigerant will be measured and paid separately under rhe respective Schedule A Item.
Disconnection and removing the unserviceable / burnt out Copper Cable between Indoor & Outdoor Unit and S&F PVC Insulated, PVC Sheathed, Multistranded Copper Cable 3 Core 4 Sqmm, ISI Marked, 1100 volts Grade and connecting to the unit along with necessary fixing materials complete. Make: Polycab/Finolex/Havells
Supply, Install, testing and commissioning of capacitor bank built in APFC Panel suitable for 3 phase 415V indor type made out of 2.0mm thick CRCA sheet and suitable for fixing capacitor 100 KVAR contactor, APFC relay and power factor meter, making bank connection with suitable size of copper wire, CTR, Aluminium bus bar, using with angle iron 50x50x6mm frame (bottom portion of panel), grouted by PCC foundation with 1:2:4 type C1 with 20mm graded stone aggregate, thumbing and cable entry boxes with cable gland incl locking arrangement, painting with two coat of synthetic enamel paint over a coat of red oxide primer complete with the following:-(a) MCCB three pole 250Amp 35KA -01Nos (Incomming) (b) Normal duty capacitor (01 to 20Kvr) in 05 step.(c ) Power factor meter digital type -01Nos Make: BCH/Siemens(d) Indicator lamp LED type for three phase.(each seat of three)(e) Capacitor bank with heavy duty cylinder type capacitor of capacity (25+25+20+20+10)KVAR Make: L&T/BCH /Siemens.(f) Power Contactor MNX-32 type, 3 pole, coil, coil voltage 415/440Volts, 50 HZ with 2 No+ 2NC auxiliary contacts, having current rating (AC3) of 32Amp at 440Volts. Make: Siemens/C&S/GE/BCH. Nos- 02(g) Power Contactor MNX-18 type, 3 pole, coil, coil voltage 415/440Volts, 50 HZ with 2 No+ 2NC auxiliary contacts, having current rating (AC3) of 18Amp at 440Volts. Make: Siemens/C&S/GE/BCH. Nos- 02
Taking down carefully aluminum/copper point wiring (light, fan, socket or power) complete along with fittings such as switches, ceiling roses, pendants, regulators sockets etc, and removing from site and making good disturbed surfaces of walls, floors etc all as directed by Engineer in Charge.
Taking down existing unserviceable MCB DB along with MCBS complete by disconnecting all as directedby Engineer in Charge.
Taking down existing unserviceable T/Light fitting any type & Capacity
Taking down existing unserviceable sub main wiring with upto 2X6Sqmm aluminum/Copper cable all as directed by Engineer in Charge.
M&L for Point wiring complete with 1.5 Sqmm single core, PVC insulated unsheathed, FRLS cable, 1100 volts grade, multistranded copper conductor, drawn through and including rigid non-metallic PVC conduit and conduit accessories fixed on surface of walls/ceilings or concealed etc., including provision of PVC insulated 1.5 Sqmm FRLS cable copper conductor for earth continuity and connected to common earth dolly connected including necessary MS terminal box with 3mm thicknes plastic laminated sheet cover of required size for one light point controlled by one, one way 5 Amps switch housing the switches, socket outlet etc. all as specified and as directed by Engineer in Charge.
All as per item 121.00 but for One ceiling fan/ exhaust fan point controlled by one, one way 5 Amps switch
All as per item 121.00 but for One 3 pin socket outlet 5 Amps on independent board
All as per item 121.00 but for One 3 pin socket outlet 5 Amps on same board
All as per item 121.00 but for One light point controlled by two, two way 5 Amps switches.
All as per item 121.00 but for One bell/ buzzer point controlled by one bell push on same board with other switches or on independent board.
M&L for Point wiring complete with 2.5 Sqmm single core, PVC insulated unsheathed, FRLS cable, 1100 volts grade, multistranded copper conductor, drawn through and including rigid non metallic PVC conduit and conduit accessories fixed on surface of wall/ceilings or concealed etc., including provision of PVC insulated 2.5 Sqmm FRLS cable with copper conductor for earth continuity and connected to common earth dolly and modular type metal boxes concealed in wall , modular cover plates with frames on top for housing the switches, socket outlet etc., all as specified and as directed for one switch socket outlet 16 Amps on independent board. MAKE : Polycab / Finolex / havells/plaza
M&L for Sub main wiring/power wiring complete with two runs of 4.0 Sqmm, single core, PVC insulated, unsheathed FRLS cable, 1100 Volts grade, multistranded with copper conductor, drawn through and including suitable size of rigid non metallic PVC conduit pipe and accessories on surface wall/floors/concealed etc., with one run of PVC insulated, 4.0Sqmm FRLS copper conductor for earth continuity all as specified and as directed. MAKE : Polycab / Finolex / havells NOTE :- Two runs of main copper conductor, one run of copper conductor for earth continuity and one run of conduit shall be measured as one unit length.
All as per item No 128.00 here in above but with 2x6 Sqmm for phase and neutral and 1x6 Sqmm for earth wire complete. MAKE : Polycab / Finolex / havells/Plaza.
Disconnection and removing the u/s 3x1.5 Sqmm PVC insulated unsheathed cable from the existing conduit and M&L for 3x1.5 Sqmm PVC insulated, unsheathed FRLS cable, 1100 Volts grade, multistranded with copper conductor drawn in the existing metal/ PVC conduit & Casing capping including connecting of the ends into the switch / socket/ DB complete. Note : Three runs of cable measured as one unit.
All as per Item No 130.00 here in above but of 3x2.5 Sqmm.
All as per Item No 130.00 here in above but of 3x4 Sqmm.
All as per Item No 130.00 here in above but of 3x6 Sqmm. Note for Sl No 122 to 134 : Make of PVC cables : Finolex/Polycab,Havells, Make of PVC Conduit : Mecury/Sudhaker/Avon Plast
Supply and fixing switch piano flush type single pole one way 5 Amps, 230 volts. Makes :- Anchor/SSK/Leader/Bajaj
Supply and fixing socket piano flush type universal 2 in 1,3/2 pin 5 Amps, 230 volts .Makes:-Anchor/SSK/Leader/Bajaj
Supply and fixing switch piano flush type single pole one way 15 Amps, 230 volts. Makes :- Anchor/SSK/Leader/Bajaj
Supply and Fixing socket flush type universal 2 in 1, 3/6 pin 15 Amps 230 volts. Makes :- Anchor/Cona/Leader/SSK
Supply and Fixing Ceiling rose 3 terminal 5 Amps 230 volts PVC/Polycarbonate, insulated body. Makes :- Anchor/Cona/Leader/SSK
Supply and Fixing step type electronic fan regulator of capacity 100 watts 230 volts for ceiling / exhaust fan flush type. Makes :- Anchor/Cona/Leader/SSK
Supply and Fixing Ding Dong bell AC. 230 volts. Makes :- Anchor/Cona/Leader/SSK
Supply & Fixing 6 Amps 1 way one module switch complete. Makes :- Anchor/Cona/Leader/SSK
Supply and Fixing 6 Amps 2 way module switch complete. Makes :- Anchor/Cona/Leader/SSK
Supply and Fixing 16 Amps one way one module switch complete. Makes :- Anchor/Cona/Leader/SSK
Supply and Fixing 6 Amps bell push one module switch complete. Makes :- Anchor/Cona/Leader/SSK
Supply and Fixing 6 Amps three pin socket two module complete. Makes :- Anchor/Cona/Leader/SSK
Supply and Fixing modular multi socket outlet 16 Amps three pin socket complete. Makes :- Anchor/Cona/Leader/SSK
Disconnection and removing the u/s casing caping conduit and S&F PVC casing caping of size 20mm including cut to shape and size to match the existing conduits suitable for LT electric supply along with necessary fixing arrangements complete. Make : Pressfit/Modi/Prestolast
All as per Item No 147.00 here in above but of size 25mm
S&F MCB DB, SPN, 2 way with 200 Amps rated copper bus bar with mild steel sheet enclosure, vertical, double door type suitable for fixing MCBs including connecting etc., complete all as specified and as directed.
S&F MCB DB, SPN, 4 way with 200 Amps rated copper bus bar with mild steel sheet enclosure, vertical, double door type suitable for fixing MCBs including connecting etc., complete all as specified and as directed.
S&F MCB DB, SPN, 8 way with 200 Amps rated copper bus bar with mild steel sheet enclosure, vertical, double door type suitable for fixing MCBs including connecting etc., complete all as specified and as directed.
S&F MCB DB, TPN, 8 way with 200 Amps rated copper bus bar with mild steel sheet enclosure, vertical, double door type suitable for fixing MCBs including connecting etc., complete all as specified and as directed.
S&F MCB DB, TPN, 12 way with 200 Amps rated copper bus bar with mild steel sheet enclosure, vertical, double door type suitable for fixing MCBs including connecting etc., complete all as specified and as directed.
S&F MCB DB, TPN, 16 way with 200 Amps rated copper bus bar with mild steel sheet enclosure, vertical, double door type suitable for fixing MCBs including connecting etc., complete all as specified and as directed.
S&F MCB SP 6-32 Amps 230 volts 10 KA ISI marked of Make : Legrand/L&T/ Siemens / Standard.
All as per Item No 156.00 here in above but of capacity MCB SPN 40 Amps
All as per Item No 156.00 here in above but of capacity MCB SPN 63 Amps
All as per Item No 156.00 here in above but of capacity MCB DP 63 Amps
All as per Item No 156.00 here in above but of capacity MCB TPN 63 Amps
Disconnection and removing the u/s MCB plug and socket unit and S&F Single pole and neutral enclosure with a two pin earth plug and socket complete controlled by one single pole MCB 20 Amps 240 Volts, complete all as specified and as directed. Note for Item No 150 to 162 : Make : IndoAsian/Siemens/ Standard/Havells/Legrand
Disconnection and removing the u/s light fitting and S&F as in repair batten for LED tube light 1X18/20 watts LED, 230Volt energy saving,recess, industrial batton type, powder coated, CRC Sheet complete with all as accessories internally pre wired and including connecting up with twin core twisted flexible copper conductor cable with suitable size Complete all as specified and as directed by Engineer in Charge. MAKE: Philips/Wipro/C&S/Crompton/Havells
Supply and fixing in repair LED tube rod 18/20 watts (retrofit LED tube) energy saving, recess / surface mounted luminaire suitable for fix in the batten fitting 1x18W to 20W, complete all as specified and directed by Engineer in Charge. Make : Philips/Wipro/C&S/Crompton/Havells.
Disconnection and removing the u/s light fitting and S&F as in repair batten for LED tube light 1X9/12 watts LED, 230Volt energy saving,recess, industrial batton type, powder coated, CRC Sheet complete with all as accessories internally pre wired and including connecting up with twin core twisted flexible copper conductor cable with suitable size Complete all as specified and as directed by Engineer in Charge. MAKE: Philips/Wipro/C&S/Crompton/Havells
Supply and fixing in repair LED tube rod 1X10watts (retrofit LED tube) energy saving, recess / surface mounted luminaire suitable for fix in the batten fitting 1x10W, complete all as specified and directed by Engineer in Charge. MAKE: Philips/Wipro/C&S/Crompton/Havells
Disconnection and removing the u/s light fitting from the false ceiling carefully and S&F LED (2X2) indirect light fitting square shape 36 Watts 230 volts with internally pre-wired and including connecting up with three core twisted flexible copper conductor cable with suitable size compelte all as specified and directed. MAKE :- Philips/Wipro/C&S/Crompton
Disconnection and removing the u/s light fitting from the Surface mounted ceiling carefully and S&F LED (2X2) indirect light fitting square shape 36Watts, 230 volts with internally pre-wired and including connecting up with three core twisted flexible copper conductor cable with suitable size compelte all as specified and directed. MAKE :- Philips/Wipro/C&S/Crompton
Disconnection and removing the u/s light fitting from the Surface mountend carefully and S&F Surface mounted LED (1X4) Panel indirect light fitting 40Watts, 230 volts with internally pre-wired and including connecting up with three core twisted flexible copper conductor cable with suitable size compelte all as specified and directed. MAKE :- Philips/Wipro/C&S/Crompton
S&F Ceiling mounted Slim design LED recessed round Downlight with Superior light output and internal driver 18 Watts 230 volts with internally pre-wired and including connecting up with three core twisted flexible copper conductor cable with suitable size compelte all as specified and directed. MAKE :- Philips/Wipro/C&S/Crompton
S&F Ceiling mounted Slim design LED recessed Square Downlight with Superior light output and internal driver 18 Watts 230 volts with internally pre-wired and including connecting up with three core twisted flexible copper conductor cable with suitable size compelte all as specified and directed. MAKE :- Philips/Wipro/C&S/Crompton
S&F Flood Slim LED light output and internal driver 150 Watts, 230 volts with internally pre-wired and including connecting up with three core twisted flexible copper conductor cable with suitable size compelte all as specified and directed. MAKE :- Philips/Wipro/C&S/Crompton
Supply and Fixing lamp holder,batten/angular type, PVC/ polycarbonate with back plate of capacity 5 Amps 230 volts suitabel for general lighting system complete all as specified and as directed. Make : Anchor/Cona/Leader/Bajaj
Disconnection and removing the u/s LED lamp and S&F LED lamp 9 watts complete all as spfd and directed. MAKE : Philips/Wipro/Halonex/Crompton
S & F in relacement MCCB, four pole, 250 amps, 35 KA fixed thermal & adjustable magnetic setting complete all as specified and directed by Engr-in-charge. MAKE : Standard/Simens/Indoasian/L&T
All as per Item No 174.00 here in above but of capacity MCCB 200 Amp, 25KA MAKE : Standard/Simens/Indoasian/L&T
All as per Item No 174.00 here in above but of capacity MCCB 160 Amp, 35KA MAKE : Standard/Simens/Indoasian/L&T
S&F decorative Post top LED 40Watt for 360* indirect light with IP 65 protection 230 volts with internally pre-wired and including connecting up with two core twisted flexible copper conductor cable with suitable size complete all as specified and directed. MAKE :- Philips/Wipro/C&S/Crompton
Supply and Fixing two way swith universal 5 Amps 230 volts. Makes :- Anchor/Cona/Leader/SSK
GS Engineers
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .