A. SUPPLY OF MATERIALS FOR CONSTRUCTION OF NEW 11 KV LINES (3-PH)
GI ( Full Galvanised) Steel Tubular Pole SP-35(9.5M)
GI Channel 100x50x5 mm, 3.5 M Length weighing approx 9.60Kg/Mtr
GI Angle 65X65X6 mm, 1.5 M Length weighing approx 5.8 Kg/Mtr for 1 Pole (SP) Brackets
GI Angle 65X65X6 mm , 5 M Length weighing approx 5.8 Kg/Mtr for 2Pole (DP) Bracing
GI Angle 65X65X6 mm, 5M Length weighing approx 5.8 Kg/Mtr for Road Crossing
Pole Double Clamp of G.I flat 50x6 mm suitable for GI SP 35 ST Pole
dia - 90 mm (Top Section ) weighing 1.4 kg per pair
Pole Single Clamp of G.I flat 50x6 mm suitable for GI SP 35 ST Pole
dia - 90 mm (Top section) weighing 0.7 kg each for SP Brackets
dia - 115 mm (Middle section ) weighing 0.84 kg each for DP Bracing & Crossing
GI Nuts (heavy) & Bolts (full thread) of following sizes
16 mm dia x 250mm ((5/8"x10") each weighing 0.50 kg
16 mm dia x 150mm ((5/8"x6") each weighing 0.348 kg
16 mm dia x 75mm ((5/8"x3") each weighing 0.23 kg
GI Washers 3mm thick of 16mm (5/8") inner dia each weighing 0.011Kg, suitable for 16mm (5/8") thread bolt
HT stay set with GI Rod of 19mm dia and 1.6 Mtr Length, guy insulator complete set
GI Pipe 2", 3 mtr length for Pole Earthing
G.I Stay wire , 7/10 SWG, 14Mtr per stay set (weighing 0.460 kg per mtr)
G. I. wire , 8 SWG for Guarding weighing 0.131 Kg/Mtr
G. I. wire , 6 SWG for Pole earthing weighing 0.192 kg /mtr
11 kV Polymer Disc insulator B&S (70KN)
11kV Pin Polymer Insulator with GI Pin (24mm) with nuts and washers
H/W fittings for 11KV Polymer Disc Insulator (B&S) type 70KN tension type with DE Clamp (2 bolts)
ACSR Weasel Conductor
Tension Claim for ACSR Weasel
PG Claim for ACSR Weasel
11kV Danger plate
GI Barbed wire 12SWG for Anti Climbing device weighing 0.17kg/Mtr.
B. SUPPLY OF MATERIALS FOR CONSTRUCTION OF NEW 11 KV LINES (1-PH)
GI ( Full Galvanised) Steel Tubular Pole SP-35(9.5M)
GI Channel 100x50x5 mm, 3.5 M Length weighing approx 9.60Kg/Mtr
GI Angle 65X65X6 mm, 1.5 M Length weighing approx 5.8 Kg/Mtr for 1 Pole (SP) Brackets
GI Angle 65X65X6 mm , 5 M Length weighing approx 5.8 Kg/Mtr for 2Pole (DP) Bracing
GI Angle 65X65X6 mm, 5M Length weighing approx 5.8 Kg/Mtr for Road Crossing
Pole Double Clamp of G.I flat 50x6 mm suitable for GI SP 35 ST Pole
dia - 90 mm (Top Section ) weighing 1.4 kg per pair
Pole Single Clamp of G.I flat 50x6 mm suitable for GI SP 35 ST Pole
dia - 90 mm (Top section) weighing 0.7 kg each for SP Brackets
dia - 115 mm (Middle section ) weighing 0.84 kg each for DP Bracing & Crossing
GI Nuts (heavy) & Bolts (full thread) of following sizes
16 mm dia x 250mm ((5/8"x10") each weighing 0.50 kg
16 mm dia x 150mm ((5/8"x6") each weighing 0.348 kg
16 mm dia x 75mm ((5/8"x3") each weighing 0.23 kg
GI Washers 3mm thick of 16mm (5/8") inner dia each weighing 0.011Kg, suitable for 16mm (5/8") thread bolt
HT stay set with GI Rod of 19mm dia and 1.6 Mtr Length, guy insulator complete set
GI Pipe 2", 3 mtr length for Pole Earthing
G.I Stay wire , 7/10 SWG, 14Mtr per stay set (weighing 0.460 kg per mtr)
G. I. wire , 8 SWG for Guarding weighing 0.131 Kg/Mtr
G. I. wire , 6 SWG for Pole earthing weighing 0.192 kg /mtr
11 kV Polymer Disc insulator B&S (70KN)
11kV Pin Polymer Insulator with GI Pin (24mm) with nuts and washers
H/W fittings for 11KV Polymer Disc Insulator (B&S) type 70KN tension type with DE Clamp (2 bolts)
ACSR Rabbit Conductor
Tension Claim for ACSR Weasel
PG Claim for ACSR Weasel
11kV Danger plate
GI Barbed wire 12SWG for Anti Climbing device weighing 0.17kg/Mtr.
(C) SUPPLY OF MATERIALS FOR CONSTRUCTION OF 11/0.4 KV, 100KVA DISTRIBUTION TRANSFORMER (COPPER/ALUMINIUM WOUND) IS:1180 (PART I) 2014 AMENDMENT 4, CONFORMING TO BIS EFFICIENCY LEVEL-2, TABLE 3 TECHNICAL SPECIFICATIONS.
GI (Full Galvanised) Steel Tubular Pole SP-35(9.5M)
100 KVA, 11/0.4 KV 3-Ph Distribution Transformer (Copper/Aluminium Wound) IS:1180 (part I) 2014 Amendment 4, conforming to BIS efficiency Level-2
GI Channel 100x50x5 mm, 2.2 M Length weighing approx 9.60Kg/Mtr -7 nos
GI Angle 50X50X6 mm weighing, 2.2 Mtrs weighing approx 4.5 Kg/Mtr for LT hor Gap/Kit Kat/DTR Metering Box- 2 NOS
11 KV Lightning arrestor, (9KV, 5KA, 1Ph) Outdoor, Gapless Polymer Lightning/Surge Arrestor Distribution Type/Class complete with insulating base, terminal connectors.
11KV, 400A, 3-ph, Gang Switch (Rocking Type Air Break Isolator) along with support insulators operating mechanism, Base Channel, down GI Pipe, terminal connectors and other accessories complete.
11 KV Drop Out fuse of rated current 100 A/ 200A/400A, 3Ph complete with fuse carrier assembly, fuse base & tube and mounting arrangement as per IS:9385 (Part-I to III).
DT Earthing
Copper Plate 2ft x2 ft, 3mm thick (weighing 11Kg each) for DT Neutral and Body - 2 nos
Copper Plate 1'x1', 3 mm thick (weighing 3Kg each) for LA -1No
Copper wire 5 SWG for Neutral - 12 Mtrs (weighing 0.204Kg per mtr)
Copper wire 5 SWG for Body - 12 Mtrs (weighing 0.204Kg per mtr)
Copper wire 5 SWG for LA - 20 Mtrs (weighing 0.204Kg per mtr)
Charcoal - (20kg/bag)
salt - 50Kg
2" (25mm) GI Pipe 3 mtr (for water recharge/alternate electrode)
ACSR WEASEL Conductor 6/2.59mm + 1/2.59 mm.
11kV Pin Polymer Insulator with GI Pin (24mm) with nuts and washers
11 kV Polymer Disc insulator B&S (70KN)
H/W fittings for 11KV Polymer Disc Insulator (B&S) type 70KN tension type with DE Clamp (2 bolts)
Tension clamp for ACSR Weasel
PG Clamp for Weasel
LT XLPE Single Core Aluminium Conductor Armoured Power Cable (for DT terminal to LT Bus Bar and LT Bus bar to feeder Pole)
120 Sqmm (AL) for DTR LT Bushing to Bus Bar
95 Sqmm (AL) (for Bus to line 2 CKt)
70 Sqmm (AL) (for Neutral)
Copper Tubular Terminal ends/Lugs heavy duty (for DTs only)
Pole Double Clamp of G.I flat 50x6 mm suitable for GI SP 35 ST Pole
dia - 90 mm (Top Section ) weighing 1.4 kg per pair
Pole Single Clamp of G.I flat 50x6 mm suitable for GI SP 35 ST Pole
dia - 90 mm (Top section) weighing 0.7 kg each
dia - 115 mm (Middle section ) weighing 0.84 kg each
dia - 140 mm (Bottom Section) weighing 0.98 kg each
HT stay set with GI Rod of 19mm dia and 1.6 Mtr Length,Bow,Anchor Plate, guy insulator etc complete set
G.I Stay wire , 7/10 SWG, 14Mtr per stay set (weighing 0.460 kg per mtr) - 28Mtrs
GI Nuts (heavy) & Bolts (full thread) of following sizes
16 mm dia x 200mm ((5/8"x8") each weighing 0.43 kg - 12 nos
16 mm dia x 100mm ((5/8"x4") each weighing 0.269 kg - 48 nos
16 mm dia x 75mm ((5/8"x3") each weighing 0.23 kg - 16 nos
16 mm dia x 50mm ((5/8"x2") each weighing 0.19kg - 24 Nos
12 mm dia x 65mm ((1/2"x2 1/2") each weighing 0.115 kg
GI Washers 3mm thick of 18mm inner dia each weighing 0.011Kg, suitable for 16mm (5/8") threaded bolt - 200 nos
GI Washers 3mm thick of 14mm inner dia each weighing 0.0063Kg, suitable for 12 mm (1/2") threaded bolt - 6 nos
Danger plate 11KV
Aluminium Tape
DTR FENCING WITH welded Mesh Fencing made of GI Rod 6-Gauge vertical spacing 150mm horizontal spacing 100mm. The length of the roll shall be 15 Mtrs and height of the roll shall be 2.44 Mtrs.
G. I Pipe 50mm (2") 3 Mtrs (10') Length for Fencing Frame & Post
G. I Pipe 25mm (1") , 3 Mtr (10') Length for Fencing Gate Frame
(D) SUPPLY OF MATERIALS FOR CONSTRUCTION OF 11/0.4 KV, 25 KVA DISTRIBUTION TRANSFORMER (COPPER/ALUMINIUM WOUND) IS:1180 (PART I) 2014 AMENDMENT 4, CONFORMING TO BIS EFFICIENCY LEVEL-2, TABLE 3 TECHNICAL SPECIFICATIONS.
GI ( Full Galvanised) Steel Tubular Pole SP-35(9.5M)
25 KVA, 11/0.4 KV,3-Ph Distribution Transformer (Copper/Aluminium Wound) IS:1180 (part I) 2014 Amendment 4, conforming to BIS efficiency Level-2
GI Channel 100x50x5 mm, 2.2 M Length weighing approx 9.60Kg/Mtr -7 nos
GI Angle 50X50X6 mm weighing, 2.2 Mtrs weighing approx 4.5 Kg/Mtr for LT hor Gap/Kit Kat/DTR Metering Box
11 KV Lightning arrestor, (9KV, 5KA, 1Ph) Outdoor, Gapless Polymer Lightning/Surge Arrestor Distribution Type/Class complete with insulating base, terminal connectors.
11KV, 400A, 3-ph, Gang Switch (Rocking Type Air Break Isolator) along with support insulators operating mechanism, Base Channel, down GI Pipe, terminal connectors and other accessories complete.
11 KV Drop Out fuse of rated current 100 A/ 200A/400A, 3Ph complete with fuse carrier assembly, fuse base & tube and mounting arrangement as per IS:9385 (Part-I to III).
DT Earthing
Copper Plate 2ft x2 ft, 3mm thick (weighing 11Kg each) for DT Neutral and Body - 2 nos
Copper Plate 1'x1', 3 mm thick (weighing 3Kg each) for LA -1No
Copper wire 5 SWG for Neutral - 12 Mtrs (weighing 0.204Kg per mtr)
Copper wire 5 SWG for Body - 12 Mtrs (weighing 0.204Kg per mtr)
Copper wire 5 SWG for LA - 20 Mtrs (weighing 0.204Kg per mtr)
Charcoal - (20kg/bag)
salt - 50Kg
2" (25mm) GI Pipe 3 mtr (for water recharge/alternate electrode)
ACSR WEASEL Conductor 6/2.59mm + 1/2.59 mm.
11kV Pin Polymer Insulator with GI Pin (24mm) with nuts and washers
11 kV Polymer Disc insulator B&S (70KN)
H/W fittings for 11KV Polymer Disc Insulator (B&S) type 70KN tension type with DE Clamp (2 bolts)
Tension clamp for ACSR Weasel
PG Clamp for Weasel
LT XLPE Single Core Aluminium Conductor Armoured Power Cable (for DT terminal to LT Bus Bar and LT Bus bar to feeder Pole)
i). 70 Sqmm (AL) ( DT Terminal to LT Bus)
ii) 25 Sqmm (AL) (for Bus to line 1 CKt)
iii). 25 Sqmm (AL) (for Neutral)
Copper Tubular Terminal ends/Lugs heavy duty (for DTs only)
ii) 70 Sqmm
ii) 25 Sqmm
iii) 25 Sqmm
Pole Double Clamp of G.I flat 50x6 mm suitable for GI SP 35 ST Pole
dia - 90 mm (Top Section ) weighing 1.4 kg per pair
dia - 140 mm (Bottom Section) weighing 1.96 kg per pair
Pole Single Clamp of G.I flat 50x6 mm suitable for GI SP 35 ST Pole
dia - 90 mm (Top section) weighing 0.7 kg each
dia - 115 mm (Middle section ) weighing 0.84 kg each
dia - 140 mm (Bottom Section) weighing 0.98 kg each
HT stay set with GI Rod of 19mm dia and 1.6 Mtr Length,Bow,Anchor Plate, guy insulator etc complete set
G.I Stay wire , 7/10 SWG, 14Mtr per stay set (weighing 0.460 kg per mtr)
GI Nuts (heavy) & Bolts (full thread) of following sizes
16 mm dia x 200mm ((5/8"x8") each weighing 0.43 kg
16 mm dia x 100mm ((5/8"x4") each weighing 0.269 kg
16 mm dia x 75mm ((5/8"x3") each weighing 0.23 kg
16 mm dia x 50mm ((5/8"x2") each weighing 0.19kg
12 mm dia x 65mm ((1/2"x2 1/2") each weighing 0.115 kg
GI Washers 3mm thick of 18mm inner dia each weighing 0.011Kg, suitable for 16mm (5/8") threaded bolt
GI Washers 3mm thick of 14mm inner dia each weighing 0.0063Kg, suitable for 12 mm (1/2") threaded bolt
Danger plate 11KV
Aluminium Tape
DTR FENCING WITH welded Mesh Fencing made of GI Rod 6-Gauge vertical spacing 150mm horizontal spacing 100mm. The length of the roll shall be 15 Mtrs and height of the roll shall be 2.44 Mtrs.
G. I Pipe 50mm (2") 3 Mtrs (10') Length for Fencing Frame & Post
G. I Pipe 25mm (1") , 3 Mtr (10') Length for Fencing Gate Frame
(E) SUPPLY OF MATERIALS FOR CONSTRUCTION OF 6.35/0.234 KV, 25 KVA DISTRIBUTION TRANSFORMER (COPPER/ALUMINIUM WOUND) IS:1180 (PART I) 2014 AMENDMENT 4, CONFORMING TO BIS EFFICIENCY LEVEL-2, TABLE 3 TECHNICAL SPECIFICATIONS.
GI ( Full Galvanised) Steel Tubular Pole SP-35(9.5M)
25 KVA, 6.35/0.234 KV, 3-Ph Distribution Transformer (Copper/Aluminium Wound) IS:1180 (part I) 2014 Amendment 4, conforming to BIS efficiency Level-2
GI Channel 100x50x5 mm, 2.2 M Length weighing approx 9.60Kg/Mtr -7 nos
GI Angle 50X50X6 mm weighing, 2.2 Mtrs weighing approx 4.5 Kg/Mtr for LT hor Gap/Kit Kat/DTR Metering Box
11 KV Lightning arrestor, (9KV, 5KA, 1Ph) Outdoor, Gapless Polymer Lightning/Surge Arrestor Distribution Type/Class complete with insulating base, terminal connectors.
11KV, 400A, 1-ph, Gang Switch (Rocking Type Air Break Isolator) along with support insulators operating mechanism, Base Channel, down GI Pipe, terminal connectors and other accessories complete.
11 KV Drop Out fuse of rated current 100 A/ 200A/400A, 1Ph complete with fuse carrier assembly, fuse base & tube and mounting arrangement as per IS:9385 (Part-I to III).
DT Earthing
Copper Plate 2ft x2 ft, 3mm thick (weighing 11Kg each) for DT Neutral and Body - 2 nos
Copper Plate 1'x1', 3 mm thick (weighing 3Kg each) for LA -1No
Copper wire 5 SWG for Neutral - 12 Mtrs (weighing 0.204Kg per mtr)
Copper wire 5 SWG for Body - 12 Mtrs (weighing 0.204Kg per mtr)
Copper wire 5 SWG for LA - 20 Mtrs (weighing 0.204Kg per mtr)
Charcoal - (20kg/bag)
salt - 50Kg
2" (25mm) GI Pipe 3 mtr (for water recharge/alternate electrode)
ACSR WEASEL Conductor 6/2.59mm + 1/2.59 mm.
11kV Pin Polymer Insulator with GI Pin (24mm) with nuts and washers
11 kV Polymer Disc insulator B&S (70KN)
H/W fittings for 11KV Polymer Disc Insulator (B&S) type 70KN tension type with DE Clamp (2 bolts)
Tension clamp for ACSR Weasel
PG Clamp for Weasel
LT XLPE Single Core Aluminium Conductor Armoured Power Cable (for DT terminal to LT Bus Bar and LT Bus bar to feeder Pole)
i). 70 Sqmm (AL) ( DT Terminal to LT Bus)
iii). 25 Sqmm (AL) (for Neutral)
Copper Tubular Terminal ends/Lugs heavy duty (for DTs only)
ii) 70 Sqmm
ii) 25 Sqmm
Pole Double Clamp of G.I flat 50x6 mm suitable for GI SP 35 ST Pole
dia - 90 mm (Top Section ) weighing 1.4 kg per pair
dia - 140 mm (Bottom Section) weighing 1.96 kg per pair
Pole Single Clamp of G.I flat 50x6 mm suitable for GI SP 35 ST Pole
dia - 90 mm (Top section) weighing 0.7 kg each
dia - 115 mm (Middle section ) weighing 0.84 kg each
dia - 140 mm (Bottom Section) weighing 0.98 kg each
HT stay set with GI Rod of 19mm dia and 1.6 Mtr Length,Bow,Anchor Plate, guy insulator etc complete set
G.I Stay wire , 7/10 SWG, 14Mtr per stay set (weighing 0.460 kg per mtr)
GI Nuts (heavy) & Bolts (full thread) of following sizes
16 mm dia x 200mm ((5/8"x8") each weighing 0.43 kg
16 mm dia x 100mm ((5/8"x4") each weighing 0.269 kg
16 mm dia x 75mm ((5/8"x3") each weighing 0.23 kg
16 mm dia x 50mm ((5/8"x2") each weighing 0.19kg
12 mm dia x 65mm ((1/2"x2 1/2") each weighing 0.115 kg
GI Washers 3mm thick of 18mm inner dia each weighing 0.011Kg, suitable for 16mm (5/8") threaded bolt
GI Washers 3mm thick of 14mm inner dia each weighing 0.0063Kg, suitable for 12 mm (1/2") threaded bolt
Danger plate 11KV
Aluminium Tape
DTR FENCING WITH welded Mesh Fencing made of GI Rod 6-Gauge vertical spacing 150mm horizontal spacing 100mm. The length of the roll shall be 15 Mtrs and height of the roll shall be 2.44 Mtrs.
G. I Pipe 50mm (2") 3 Mtrs (10') Length for Fencing Frame & Post
G. I Pipe 25mm (1") , 3 Mtr (10') Length for Fencing Gate Frame
(F) SUPPLY OF MATERIALS FOR CONTRUCTION OF NEW LT LINES (3-PH)
GI ( Full Galvanised) Steel Tubular Pole SP-11
GI Angle 50X50X6 mm, 1 M weighing approx 4.5 Kg/Mtr for LT Cross Arms (2nos). The Cross Arm shall be provisioned with required holes of appropriate dia for fixing LT Shackle Straps, D Clamps and GI Pin
Pole Double Clamp 90mm dia (Top Section) made of G.I flat 50x6 mm, suitable for SP 11 GI ST Poles
Pole Single Clamp 90mm dia (Top Section) made of G.I flat 50x6 mm, suitable for SP 11 GI ST Poles
LT Pin Insulator (Porcelain) with G.I Pin, nuts and bolts
Shackle insulator 75x90mm
GI "D"CLAMP Made of GI Flat of size 75x90mm FOR SHACKLE INSULATOR with GI Nuts & bolts
GI Shackle Strap, (3½")
AAC ANT (50Sqmm) conductor
GI Nuts (heavy) & Bolts (full thread) of size 16 mm dia x 75mm ((5/8"x3") each weighing 0.23 kg - 12 nos
GI Nuts (heavy) & Bolts (full thread) of size 16 mm dia x 100mm ((5/8"x4") each weighing 0.269 kg - 6 nos
GI Washers 3mm thick of 16mm (5/8") inner dia each weighing 0.011Kg, suitable for 16mm (5/8") thread bolt
LT stay set with GI Rod of 16mm dia and 1.6 Mtr Length,Bow,Anchor Plate, guy insulator etc complete set
G.I Stay wire , 7/12 SWG, 10Mtr per stay set (weighing 0.300 kg per mtr)
(G) SUPPLY OF MATERIALS FOR CONSTRUCTION OF NEW LT LINES (1-PH)
GI ( Full Galvanised) Steel Tubular Pole SP-11
GI Angle 50X50X6 mm, 1 M weighing approx 4.5 Kg/Mtr each
Double pole Clamp 77 mm dia (Top Section) made of G.I flat 50x6 mm, suitable for SP 11 GI ST Poles weighing 0.86kg per pair
Shackle insulator 75x90mm
GI "D"CLAMP Made of GI Flat of size 75x90mm FOR SHACKLE INSULATOR with GI Nuts & bolts
GI Shackle Strap, (3½")
AAC ANT (50Sqmm) conductor
GI Nuts (heavy) & Bolts (full thread) of size 16 mm dia x 75mm ((5/8"x3") each weighing 0.23 kg - 12 nos
GI Nuts (heavy) & Bolts (full thread) of size 16 mm dia x 100mm ((5/8"x4") each weighing 0.269 kg - 6 nos
GI Washers 3mm thick of 16mm (5/8") inner dia each weighing 0.011Kg, suitable for 16mm (5/8") thread bolt
LT stay set with GI Rod of 16mm dia and 1.6 Mtr Length,Bow,Anchor Plate, guy insulator etc complete set
G.I Stay wire , 7/12 SWG, 10Mtr per stay set (weighing 0.300 kg per mtr)
(H) SUPPLY OF MATERIALS FOR CONSUMER CONNECTION
Cable PVC Wire BTC 6 Sq.mm (AL)
63 Ampere Kitkat Fuse Unit of 440-450 Volts Grade (High Quality)
Description of Work / Item(s)
Amount
(A) ERECTION, INSTALLATION & COMMISIONING OF MATERIALS FOR NEW 11 KV LINES (3-PH)
Detail Survey
Tree cutting along the line including trimmimg, looping, branching etc as required
Erection of poles including excavation of earth; fitting of channels, angles, Hardware fittings, insulators, GI earth pipes etc.
Stringing of conductors
Erection of stay wires
PCC 1:3:6 Grouting of Poles (1.5ftx1.5ftx4 ft) per pole - 0.25 Cum)
PCC 1:3:6 Grouting of Stay (1.5ftx1.5ftx4 ft) per pole - 0.25 Cum)
(B) ERECTION, INSTALLATION & COMMISIONING OF MATERIALS FOR NEW 11 KV LINES (1-PH)
Detail Survey
Tree cutting along the line including trimmimg, looping, branching etc as required
Erection of poles including excavation of earth; fitting of channels, angles, Hardware fittings, insulators, GI earth pipes etc.
Stringing of conductors
Erection of stay wires
PCC 1:3:6 Grouting of Poles (1.5ftx1.5ftx4 ft) per pole - 0.25 Cum)
PCC 1:3:6 Grouting of Stay (1.5ftx1.5ftx4 ft) per pole - 0.25 Cum)
(C) ERECTION, INSTALLATION & COMMISIONING OF OF 11/0.4 KV, 100KVA DISTRIBUTION TRANSFORMER (COPPER/ALUMINIUM WOUND) IS:1180 (PART I) 2014 AMENDMENT 4, CONFORMING TO BIS EFFICIENCY LEVEL-2, TABLE 3 TECHNICAL SPECIFICATIONS.
Erection of poles including excavation of earth; fitting of channels, angles, Hardware fittings, insulators, etc.
Erection, Installation, testing and commsissioning of 11/.4KV, 100 KVA Distribution Tranformers including Cables, LA, Gang Switch and DO Fuse alongwith all required accessories
Sub-Station Earthing; Earthing for DT and LA alongwith all required accessories
Erection of stay Set
Fencing of Sub-Station with welded Mesh Fencing including GI pipe as frame and post.
PCC 1:3:6 Grouting of Poles (1.5ftx1.5ftx4 ft) per pole - 0.25 Cum)
PCC 1:3:6 Grouting of Stay (1.5ftx1.5ftx4 ft) per pole - 0.25 Cum)
(E) ERECTION, INSTALLATION & COMMISIONING OF 11/0.4 KV, 25 KVA DISTRIBUTION TRANSFORMER (COPPER/ALUMINIUM WOUND) IS:1180 (PART I) 2014 AMENDMENT 4, CONFORMING TO BIS EFFICIENCY LEVEL-2, TABLE 3 TECHNICAL SPECIFICATIONS.
Erection of poles including excavation of earth; fitting of channels, angles, Hardware fittings, insulators, etc.
Erection, Installation, testing and commsissioning of 11/.4KV, 100 KVA Distribution Tranformers including Cables, LA, Gang Switch and DO Fuse alongwith all required accessories
Sub-Station Earthing; Earthing for DT and LA alongwith all required accessories
Erection of stay Set
Fencing of Sub-Station with welded Mesh Fencing including GI pipe as frame and post.
PCC 1:3:6 Grouting of Poles (1.5ftx1.5ftx4 ft) per pole - 0.25 Cum)
PCC 1:3:6 Grouting of Stay (1.5ftx1.5ftx4 ft) per pole - 0.25 Cum)
(F) ERECTION, INSTALLATION & COMMISIONING OF 6.35/0.234 KV, 25 KVA DISTRIBUTION TRANSFORMER (COPPER/ALUMINIUM WOUND) IS:1180 (PART I) 2014 AMENDMENT 4, CONFORMING TO BIS EFFICIENCY LEVEL-2, TABLE 3 TECHNICAL SPECIFICATIONS.
Erection of poles including excavation of earth; fitting of channels, angles, Hardware fittings, insulators, etc.
Erection, Installation, testing and commsissioning of 11/.4KV, 100 KVA Distribution Tranformers including Cables, LA, Gang Switch and DO Fuse alongwith all required accessories
Sub-Station Earthing; Earthing for DT and LA alongwith all required accessories
Erection of stay Set
Fencing of Sub-Station with welded Mesh Fencing including GI pipe as frame and post.
PCC 1:3:6 Grouting of Poles (1.5ftx1.5ftx4 ft) per pole - 0.25 Cum)
PCC 1:3:6 Grouting of Stay (1.5ftx1.5ftx4 ft) per pole - 0.25 Cum)
(G) ERECTION, INSTALLATION & COMMISIONING OF MATERIALS FOR CONTRUCTION OF NEW LT LINES (3-PH)
Detail Survey
Tree cutting along the line including trimmimg, looping, branching etc as required
Erection of poles including excavation of earth; fitting of channels, angles, Hardware fittings, insulators, GI earth pipes etc.
Stringing of conductors
Erection of stay wires
PCC 1:3:6 Grouting of Poles (1.5ftx1.5ftx4 ft) per pole - 0.25 Cum)
PCC 1:3:6 Grouting of Stay (1.5ftx1.5ftx4 ft) per pole - 0.25 Cum)
(H). ERECTION, INSTALLATION & COMMISIONING OF MATERIALS FOR CONSTRUCTION OF NEW LT LINES (1-PH)
Detail Survey
Tree cutting along the line including trimmimg, looping, branching etc as required
Erection of poles including excavation of earth; fitting of channels, angles, Hardware fittings, insulators, GI earth pipes etc.
Stringing of conductors
Erection of stay wires
PCC 1:3:6 Grouting of Poles (1.5ftx1.5ftx4 ft) per pole - 0.25 Cum)
PCC 1:3:6 Grouting of Stay (1.5ftx1.5ftx4 ft) per pole - 0.25 Cum)
(I). INSTALLATION OF MATERIALS FOR CONSUMER CONNECTION
Installation of Consumer Connection Accesories and Service cable
Description of Work / Item(s)
Amount
GSTon Supply (Sch-I)
GSTon Erection (Sch-II)
Description of Work / Item(s)
Amount
Total Amount for Supply of Materials (BoQ1)
Total Amount for Erection, Installation & Commissioning of Materials (BoQ2)
Total GSTon Supply & Erection of Materials (BoQ3)
ELMECHENT (BID ID -2868)
ELMECHENT (BID ID -2868)
ELMECHENT (BID ID -2868)
ELMECHENT (BID ID -2868)
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid