Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹21.3 LAccepted-Finance | L1 | Accepted-Finance Lowest Bidder | |
| 2 | L2₹21.4 L+₹13,431.42 (0.63%)Rejected-Finance | L2 | Rejected-Finance Higher Bidder | |
| 3 | L3₹21.7 L+₹44,771.42 (2.11%)Rejected-Finance | L3 | Rejected-Finance Higher Bidder | |
| 4 | Rejected-Technical BAKSI BAJAR KOTYALI PASCHIM MIDNAPUR PIN 721101 KOLKATA WEST BENGAL | KOLKATA | PASCHIM MIDNAPUR | WEST BENGAL | 721101 | - | Rejected-Technical Required shortfall documents not complied | |
| 5 | Rejected-Technical JHETA JAMBONI MOHOBONI WESTMEDINIPUR WESTBENGAL | HOOGHLY | WEST BENGAL | 712122 | - | Rejected-Technical Required shortfall documents not complied. |
Tender Value
₹22.4 L
EMD Value
₹44,771
Closing Date
16 Feb 2026, 1:00 pmClosed
Executive Engineer Paschim Med. Elecl. Div. PWDte.
Office of the Executive Engineer, Paschim Medinipur Electrical Division, P.W.Dte., Midnapore, Paschim Medinipur.
Renovation of Auditorium Hall of Midnapore Medical College, Paschim Medinipur- Electrical Installation.
2026_WBPWD_995780_1
WBPWD/EE/PMED/NIT-09/e-T /2025-2026
Open Tender
ELECTRICAL WORKS ORG
Percentage
30 days
Midnapore Medical College and Hospital.
Please refer Tender documents.
3 documents required · 3 mandatory
₹44,771
12 Mar 2026
29 Jan 2026
18 Feb 2026
29 Jan 2026
16 Feb 2026
29 Jan 2026
Part A: STAGE LIGHT:- S & D of 240V LED floodlight made up of pressure die cast aluminium housing with toughened glass and high power LEDs and secondary lenses with IP66 protection. System efficacy >110/120 LPW as per direction of EIC. (Make- Crompton-TFS-504-80-57-60D-HL2-GL-NSG or equivalant to Wipro / Philips / Bajaj) [NS]
S & fixing of 240V LED focus light with IP66 & IK08 protected recessed COB downlight, delivers uniform glare along with necessary connections as required. ( Wipro Model No. - LD07-381-026-57-WH/ Equivalent model of Philips/Crompton/ Bajaj co.) [NS]
Charges for installation of the above lighting system with suitable nuts, bolts washers etc as required as per direction of EIC. [NS]
S & F of a suitable angle iron frame structure for installation of the above lighting system a required & as per direction of EIC. [NS]
Supply & Fixing 240 V, 16 A, 3 pin Modular type plug socket (Make-Brand approved by EIC) with 16A Modular type switch, without plug top on 4 Module GI Modular type switch board with top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. [E18/9b]
Supply & Fixing 240 V, 6 A, 3 pin Modular type plug socket (Brand approved by EIC) with 6A Modular type switch, without plug top on 4 Module GI Modular type switch board with 3 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. [E18/9a]
Wiring with 1.1 KV grade single core PVC insulated stranded Copper wire in GI conduit and painting [E-1/1a&b]
(i) 2x1.5 sqmm wire in 19 mm conduit incl. S&F 1x14 SWG GI ECC
(ii) 2x2.5 sqmm wire in 19 mm conduit incl. S&F 1x14 SWG GI ECC
Part B: AUDIENCE AREA:- Wiring with 1.1 KV grade single core PVC insulated stranded Copper wire in GI conduit and painting (a)2x2.5 sqmm wire in 19 mm conduit incl. S&F 1x14 SWG GI ECC [E-1/1b] {for running loop wiring for group control through MS/GI conduit terminated at switch bank situated at stage / green room.} (for false ceiling light & Step light)
Supplying & Fixing GI Modular Switch Board of the following sizes complete with three no. suitable size Copper bar with holes (for Ph, N & E) fixed on bakelite/Hard Rubber insulator over the MS welded chairs incl. top cover flushed in wall for housing the board after cutting the brick wall incl. making earthing attachment, painting and mending good damages to building works [E17/1f] (a) 2 Row 18 Module
Supply & Fixing 240 V 16 A Modular type switch (Brand approved by EIC) on existing GI Modular type switch board having top cover plate and making necessary connections as required [E17/3b] [for group control of false ceiling lights]
Supply & fixing 250 V, recessed round Downlighters best quality light and aesthetic design. (Make : Crompton-LSCRM-18W-CDL or equivalent to Philips/Wipro/Bajaj) on false ceiling with all accessories & making necy. Connection as reqd & as per direction of the EIC. [NS]
Supply and Fixing of 240V, 2W LED Step light with suitable 4 module modular board (PHILIPS Model:30974 or equivalent to Wipro/ Crompton) [NS]
Supply and fixing of 240V LED signage with built in battery backup for 02 hours. (Make: BAJAJ, product code: 220210, Type: BESL 03 LED DSD WBB Green or equivalent to Wipro/Crompton/Philips) [NS]
Supply & Fixing 240 V, 16 A, 3 pin Modular type plug socket (Make-Brand approved by EIC) with 16A Modular type switch, without plug top on 4 Module GI Modular type switch board with top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. [E18/9b]
Supply & Fixing 240 V, 6 A, 3 pin Modular type plug socket (Brand approved by EIC) with 6A Modular type switch, without plug top on 4 Module GI Modular type switch board with 3 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. [E18/9a]
Wiring with 1.1 KV grade single core PVC insulated stranded Copper wire in GI conduit and painting [E-1/1a&b]
(i) 2x1.5 sqmm wire in 19 mm conduit incl. S&F 1x14 SWG GI ECC
(ii) 2x2.5 sqmm wire in 19 mm conduit incl. S&F 1x14 SWG GI ECC
Supplying & Fixing 240 V, INDUSTRIAL BELL -GOOD QUALITY, 225 mm gong size High Range, Very Loud Sound Heard for Auditorium on HW board incl. S&F HW board [NS]
Part C: OTHER AREA LIGHT:- Distribution wiring in 1.1 KV grade 2x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) partly in 20mm size PVC rigid conduit 'FR' (Precision make) [for ceiling portion only] and in 19mm bore, 3mm thick polythene pipe [for horizontal & vertical run embedded in wall], with 1x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, to light/fan/call bell points with Modular type switch (Brand approved by EIC) fixed on Modular GI switch board complete with 2 no. suitable size “Ph & N” copper bar with top cover plate making earthing attachment fixed on wall incl. mending good damages to original finish. [only PVC Rigid Conduit on ceiling and remaining portion concealed] (a) AVgG. RUN 8 mtr [E25/4c]
Do - do - do - to 6 amp. 3 pin Modular type plug socket with Modular type switch (Make-legrand myrius or Brand approved by EIC) - do - do - do. a) On Board [E24/3a]
Supply & Delivery 230 volt. 4 Ft. Long single LED tube fittings with one no LED tube complete with all accessories (Make- Crompton- Cat no IGP161LT8-16 1xT8 with 01 nos tube cat no.- LT8-20-865-(2) / Philips/Bajaj/ Wipro). [NS]
Supply & Delivery 230 volt. 4 Ft. Long Double LED tube fittings with two nos LED tube complete with all accessories (Make- Crompton- Cat no IGP162LT8-16 2xT8 with 02 nos tube cat no.- LT8-20-865-(2) / Philips/Bajaj/ Wipro). [NS]
Fixing only single/twin florescent light fitting complete with all accessories Directly on wall/ceiling with HW block and suitable size MS fastener, Ceiling plate, nipples etc. { or “L” type MS clamp whose one side fixed on ceiling with sutable size 4 nos. fastener and other side connected with the conduit with suitable size of bolts and nuts incl. S&F EI conduit, “L” type (125mmx125mm) 6mm thick and 25mm with MS clamp } as required [C2/14d]
Fixing only single/twin fluorescent light fitting suspended 25 cm bellow the ceiling with 2 No. 20 mm dia EI conduit (14 SWG) supports fixed with “L” type MS clamp whose one side fixed on ceiling with sutable size 4 nos. fastener and other side connected with the conduit with suitable size of bolts and nuts incl. S&F EI conduit, “L” type (125mmx125mm) 6mm thick and 25mm with MS clamps and connecting the length of PVC insulated wire and mending good damages to original finish and painting etc. by 2x24/0.20 mm (1.5sqmm.) flexible copper wire of 1.10 mt. length [C2/17]
Supply & Fixing angular batten holder (Anchor) on 75mm dia PVC round block / round bakelite on wall/ceiling. [D13/22]
Supply & fixing 250 V,9/10 watt LED Bulb (Philips make) for batten point.
Supply & Fixing 240V, Modular Socket (2 Module) type fan regulator (Step type) (Brand approved by EIC) on existing Modular GI switch board with top cover plate incl. Making necy. connections etc. [E18/10]
Supply & delivery of 240V, 50 Hz, 1200 mm sweep A.C. Ceiling Fan (Crompton-Standard Ceiling Fans-high speed / Aura or equivalent to Orient) with all accessories. [NS]
Fixing only ceiling fan complete with blades, canopy, fork, rubber bush etc. incl. S&F connecting wire for down rod upto 30 cm incl. painting the rod with approved paint and making necessary connection as required by 2x1.5 sqmm flexible copper wire. [C3/21a]
Supply & delivery of 18" Wall Bracket Fan [Make- Orient-450 mm or 18” Tornado Wall II all metal body] [NS]
Fixing only cabin fan on wall/ceiling by S&F rag bolts, nuts & washers (6 mm dia x 62 mm long) or as reqd. incl. S&F 24/0.20 PVC insulated flexible copper wire 0.5 mt. Length [C4/29]
Supply & delivery 30cm (12") 1420 r.p.m. sweep A.C. single phase heavy duty exhaust fan complete set ready to use x as per G.S. (E.P.C Electrical Pvt. Ltd.)
Supply & Fixing GI louver shutter on wall with necy. bolts & nuts (6 mm dia x 62 mm long) for 30 cm Exhaust fan (12") [D14/32b]
Fixing only exhaust fan after making hole in wall and making good damages and smooth cement finish etc. as practicable as possible and providing necy. length of PVC insulated wire and making connection for exhaust of 30 cm (12") diameter incl. fixing louver shuter as per G.S [C4/28b]
Supply & Fixing 240 V, 16 A, 3 pin Modular type plug socket (Make-Brand approved by EIC) with 16A Modular type switch, without plug top on 4 Module GI Modular type switch board with top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. [E18/9b]
Supply & Fixing 240 V, 6 A, 3 pin Modular type plug socket (Brand approved by EIC) with 6A Modular type switch, without plug top on 4 Module GI Modular type switch board with 3 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. [E18/9a]
Distribution wiring in 1.1 KV single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20mm size PVC rigid conduit 'FR' (Precision make) incl. necy. fittings as required. [E-14/1a]
(i) 2 x 22/0.3 (1.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) ECC
(ii) 2 x 36/0.3 (2.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) ECC
Part D: POWER DISTRIBUTION :- Supply, delivery and installation of fabricated cubical type compartmentalized dust and vermin proof L.T. distribution panel board of suitable size made of 2 mm thick M.S. sheet reinforced with (40x40x6 mm) angle iron frame work with individual hinged door with locking arrangement for all compartment and providing suitable ventilation arrangement. The complete panel board shall be painted by power coating paint, colour siemens white. The interconnection should be done with suitable size tinned copper strip between BBC to all main switches and other accessories including suitable stud connectors, socketing etc as required and earthing by nut, bolt in the body complete with base channel. The lower size of the base of panel board should rest on frame work (75x40x5 mm). The control panel will have suitable cable entry from bottom through data cable gland plate to access sufficient no. of cables as per direction of E.I.C. the panel comprising with following switches. (Make: L&T/Legrand/ABB/Siemens) [NS]
INCOMING: 415V, 250 Amp , TPN switches disconnector fuse with 3 no HRC fuse - 01Set BUSBAR: 415V, 315 Amp (4 x 40x5mm, 0.85 mtr long ) copper bus-bar with necessary nos of holes and different colour insulating tape on epoxy bus support.- 01 Set
OUTGOING: (i) 415V 160 Amp TPN switches disconnector fuse with 3 no HRC fuse- 02 Sets (ii) 415V 125 Amp TPN switches disconnector fuse with 3 no HRC fuse- 02 Sets (iii) 415V 63 Amp TPN switches disconnector fuse with 3 no HRC fuse- 02 Sets
Supplying and fixing 415V, 320A TPN on load front operated Changeover switch with Sheet Steel enclosure on angle iron frame on wall with nuts bolts etc. (at Sub station) [D-2]
Supplying and fixing 415V, 32-63A per way, 8 way double door Vertical TPN MCB Distribution board for MCCB incomer with IP-42/43 protection with 01 no 160A, Four Pole MCCB of Breaking capacity 25kA/35kA with fixed thermal and fixed magnetic / adjustable thermal and fixed magnetic settingas incomer and 08 nos 63A TP MCB ('C' Curve, 10kA), concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment. (Make: L&T/Legrand/Seimens/Schneider) [D-11/15, D-8/10, D-6/7]
Supplying and fixing 415V, 32-63A per way, 6 way double door Vertical TPN MCB Distribution board for MCCB incomer with IP-42/43 protection with 01 no 125A, Four Pole MCCB of Breaking capacity 25kA/35kA with fixed thermal and fixed magnetic / adjustable thermal and fixed magnetic settingas incomer and 06 nos 63A TP MCB ('C' Curve, 10kA), concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment. (Make: L&T/Legrand/Seimens/Schneider) [D-11/15, D-8/10, D-6/7]
Supplying and fixing 415V, 16-32A per way, 8 way double door Horizontal TPN MCB Distribution board with IP-42/43 protection with 01 no 63A FP Isolator as incomer and 24 nos 16-32A SPMCB ('C' Curve, 10kA) as outgoing, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment. (Make: L&T/Legrand/Seimens/Schneider) [D-9/13, D-5/6, D-6/7]
Supplying and fixing 250V, 6-16A per way, (2+14) way double-door SPN MCB Distribution Board with IP-42/43 protection with 01 no 40A DP Isolator as incomer and 14 nos 6-16A SPMCB ('C' Curve, 10kA) as outgoing , concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment. (Make: L&T/Legrand/Seimens/Schneider) [D-10/14, D-5/6, D-6/7]
Supply and delivery of following 1.1 KV grade XLPE/PVC armoured cables (Polycab/Mescab/Havells/Currency or PWD approved make as per direction of EIC ) [NS]
(i) 4 core 16 sqmm
(ii) 4 core 25 sqmm
(iii) 4 core 50 sqmm
(iv) 4 core 70 sqmm
(v) 4 core 120 sqmm
Laying of one No. 120 sqmm cable in underground trench 460mm wide x 760mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per Mtr. including filling the space between the bricks and cable and also the trenchwith shifted soil, leveling up and restoring surface duly rammed [F2/1b]
Laying of cable upto 3/4 core 25 sqmm on wall/surface incl. S & F MS saddles with earthing attachment in 10 SWG GI (Hot Dip) Wire, making holes etc. as necy. mending good damages and painting [F1/2b]
Laying of cable from 3/3½ core 35 sqmm to 50 sqmm on wall/surface incl. S & F MS saddles with earthing attachment in 2 x 10 SWG GI (Hot Dip) Wire, making holes etc. as necy., mending good damages and painting. [F1/2c]
Laying of cable above 3½ core 50 sqmm and upto 3½ core 90 sqmm on wall/surface including S & F MS clams with earthing attachment in 2 x 10 SWG GI (Hot Dip) Wire, making hole etc. as necy., mending good damages and painting [F1/2d]
Laying of cable above 3½ core 90 sqmm and upto 3½ core 150 sqmm on wall/surface including S & F MS clams with earthing attachment in 2 x 10 SWG GI (Hot Dip) Wire, making hole etc. as necy., mending good damages and painting [F1/2e]
Laying only Cable above 50 sqmm but not exceeding 400sqmm through existing RCC/ Hume/GI Pipe/open masonary trench for single, 2, 3, 3½ and 4 core
Laying 120 sqmm through existing RCC/ Hume/GI Pipe/open masonary trench for single, 2, 3, 3½ and 4 core [F1/3b]
Charges for cuttings of Pitch road & PCC road as per GS with Co. Own equipment for fixing of GI protection pipe for cable crossing and mending good damages to original finish as per direction of EIC. [NS]
Supplying & fixing medium gauge GI Pipe ( ISI-Medium) Protection with necessary fittings and jointing metarials as required (for 120 sqmm cable) [F-6/11]
(i) 80 mm dia
Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below : [F4/7c]
(i) 4 core 16 sqmm
(ii) 4 core 25 sqmm
(iii) 4 core 50 sqmm
(iv) 4 core 70 sqmm
(v) 4 core 120 sqmm
Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials : [F5/8b]
(i) 4 core 16 sqmm
(ii) 4 core 25 sqmm
(iii) 4 core 50 sqmm
(iv) 4 core 70 sqmm
(v) 4 core 120 sqmm
Supply and fixing 415V, 3ph 20Hp/15KW dol starter incl. electrical connection with socketing as pequired in angle iron frame on wall or take necessary housing arrangement for fixing the starter in place of existing one after dismantling as per direction of EIC. (L&T,MN 32 DOL, Cat no-SS94353) (for AC)
Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level by ISI-Medium GI pipe or TATA-Medium GI pipe
Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 25 mm x 6 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required [G2/4a]
Connecting the equipments to earth busbar including S & F No. 8 SWG GI (Hot Dip) wire of size as below on wall/floor with staples buried inside wall/floor as required and making connection to equipments with bolts, nuts, washers, cable lugs etc. as required and mending good damages [G2/5iii]
Part E: UPS system :- SIT & C of 6 KVA , 50 Hz, 230V, Single Phase input, Single phase output UPS system with required nos of of SMF Battery, Rack DC connecting cables and complies with following feature / specifications. (Make- AVO / APC / Numeric / GE / Emmerson) Technical Specification for 6 KVA Single phase input & Single phase out put on line UPS systems Topology, IGBT BASED DSP CONTROLED Input Voltage: 230 VAC, 160 - 270 VAC Input Frequency: 50 Hz, 47 to 53 Hz Input PF: > 0.99 Output Voltage: 220 VAC +/- 1% Output Frequency: 50 Hz +/- 0.1% in Free running & +/- 4% in Sync Isolation Transformer: Provided Inbuilt (No external transformer accepted) Power Factor: 0.8 Lag to Unity Crest Factor: 3:1 ; Waveform: Sinusoidal THD: < 3% on linear load & < 5% on non-linear load Overload: 110% for 10 minutes, 125% for 1 minutes, 150% for 30 minutes Transient Response : For 0 - 50% & 50% - 100% load change voltage remains within +/- 5% ; Ripple: < 2% ; Inverter Efficiency: > 93%
Battery : 12 V, Mono Block batteries. Battery Back UP: 30 minute back up minimum VAH required 6240 VAH Battery Make: Exide, Amar Raja Quanta Battery Cabin: With power coated MS angle with MS sheet suitable dimension and gauge, Protections: Input & Output Over / Under Voltage, Single Phasing DC - High / Under Voltage, Battery Charging Over Current, Output Overload / Short Circuit / Over Temp., UPS auto ON Mains recovery Audio Alarm, Mains Fail, Battery Low Pre-alarm, Inverter Trip Metering: Digital Seven segment - Voltage, Current & Frequency, Battery - Voltage & Current Indications: Mains - On / Fail / High / Low / Single Phasing DC - On / High, Battery - Low Pre-alarm / Low Trip Inverter - On / Trip / High / Low / Over Current Switchgear: MCB / MCCB for Input, Battery, Output & Manual Bypass Switch Termination: Input, Battery, Output & Bypass; Enclosure: IP 20 Operating Temp: 0 to 40 Deg C ; Humidity: Upto 95% Rh (non-condensing) Cooling: Forced Air ; Noise: < 55 dB
Charging Current: 5 to 10 Amps. (Site Settable) Cold Start : Provided Communication: RS 232 Static Switch: Provided with changeover < 5 msec in sync & < 20msec in non-sync Certification : ISO 9001: 2015, ISO 14001: 2015, ISO 18001, RoHS and OHSAS 18001 IEC/EN 62040-1-1,IEC/EN50091-1,IEC/EN 60950 (Safety) IEC/EN 50091-2, IEC/EN 62040-2(EMC Emmission),IEC/EN 62040-3(performance & Design)IEC/EN 61000-4(EMC Emmunity) & IEC/EN 60146 (Design & Manufacture) [NS]
Supplying & Fixing Industrial Plug & Socket board with 240 V, 20A, SPN & Earth Metal Industrial Plug socket & 20A Industrial top incl. S&F 20 A SP MCB breaking capcity 10kA (C- Curve) in SS enclosure fixed on wall and cecessary conection. [D12/17]
Add GST @ 18% on Item no 1 to 60
Add CESS @ 1% on Item no 1 to 61
Percentage BoQ
BoQ_Ver4.0
Name of the Bidder/ Bidding Firm / Company :
PRICE SCHEDULE (This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only )
NUMBER #
Part A: STAGE LIGHT:- S & D of 240V LED floodlight made up of pressure die cast aluminium housing with toughened glass and high power LEDs and secondary lenses with IP66 protection. System efficacy >110/120 LPW as per direction of EIC. (Make- Crompton-TFS-504-80-57-60D-HL2-GL-NSG or equivalant to Wipro / Philips / Bajaj) [NS]
S & fixing of 240V LED focus light with IP66 & IK08 protected recessed COB downlight, delivers uniform glare along with necessary connections as required. ( Wipro Model No. - LD07-381-026-57-WH/ Equivalent model of Philips/Crompton/ Bajaj co.) [NS]
Charges for installation of the above lighting system with suitable nuts, bolts washers etc as required as per direction of EIC. [NS]
S & F of a suitable angle iron frame structure for installation of the above lighting system a required & as per direction of EIC. [NS]
Supply & Fixing 240 V, 16 A, 3 pin Modular type plug socket (Make-Brand approved by EIC) with 16A Modular type switch, without plug top on 4 Module GI Modular type switch board with top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. [E18/9b]
Supply & Fixing 240 V, 6 A, 3 pin Modular type plug socket (Brand approved by EIC) with 6A Modular type switch, without plug top on 4 Module GI Modular type switch board with 3 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. [E18/9a]
Wiring with 1.1 KV grade single core PVC insulated stranded Copper wire in GI conduit and painting [E-1/1a&b]
(i) 2x1.5 sqmm wire in 19 mm conduit incl. S&F 1x14 SWG GI ECC
(ii) 2x2.5 sqmm wire in 19 mm conduit incl. S&F 1x14 SWG GI ECC
Part B: AUDIENCE AREA:- Wiring with 1.1 KV grade single core PVC insulated stranded Copper wire in GI conduit and painting (a)2x2.5 sqmm wire in 19 mm conduit incl. S&F 1x14 SWG GI ECC [E-1/1b] {for running loop wiring for group control through MS/GI conduit terminated at switch bank situated at stage / green room.} (for false ceiling light & Step light)
Supplying & Fixing GI Modular Switch Board of the following sizes complete with three no. suitable size Copper bar with holes (for Ph, N & E) fixed on bakelite/Hard Rubber insulator over the MS welded chairs incl. top cover flushed in wall for housing the board after cutting the brick wall incl. making earthing attachment, painting and mending good damages to building works [E17/1f] (a) 2 Row 18 Module
Supply & Fixing 240 V 16 A Modular type switch (Brand approved by EIC) on existing GI Modular type switch board having top cover plate and making necessary connections as required [E17/3b] [for group control of false ceiling lights]
Supply & fixing 250 V, recessed round Downlighters best quality light and aesthetic design. (Make : Crompton-LSCRM-18W-CDL or equivalent to Philips/Wipro/Bajaj) on false ceiling with all accessories & making necy. Connection as reqd & as per direction of the EIC. [NS]
Supply and Fixing of 240V, 2W LED Step light with suitable 4 module modular board (PHILIPS Model:30974 or equivalent to Wipro/ Crompton) [NS]
Supply and fixing of 240V LED signage with built in battery backup for 02 hours. (Make: BAJAJ, product code: 220210, Type: BESL 03 LED DSD WBB Green or equivalent to Wipro/Crompton/Philips) [NS]
Supply & Fixing 240 V, 16 A, 3 pin Modular type plug socket (Make-Brand approved by EIC) with 16A Modular type switch, without plug top on 4 Module GI Modular type switch board with top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. [E18/9b]
Supply & Fixing 240 V, 6 A, 3 pin Modular type plug socket (Brand approved by EIC) with 6A Modular type switch, without plug top on 4 Module GI Modular type switch board with 3 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. [E18/9a]
Wiring with 1.1 KV grade single core PVC insulated stranded Copper wire in GI conduit and painting [E-1/1a&b]
(i) 2x1.5 sqmm wire in 19 mm conduit incl. S&F 1x14 SWG GI ECC
(ii) 2x2.5 sqmm wire in 19 mm conduit incl. S&F 1x14 SWG GI ECC
Supplying & Fixing 240 V, INDUSTRIAL BELL -GOOD QUALITY, 225 mm gong size High Range, Very Loud Sound Heard for Auditorium on HW board incl. S&F HW board [NS]
Part C: OTHER AREA LIGHT:- Distribution wiring in 1.1 KV grade 2x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) partly in 20mm size PVC rigid conduit 'FR' (Precision make) [for ceiling portion only] and in 19mm bore, 3mm thick polythene pipe [for horizontal & vertical run embedded in wall], with 1x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, to light/fan/call bell points with Modular type switch (Brand approved by EIC) fixed on Modular GI switch board complete with 2 no. suitable size “Ph & N” copper bar with top cover plate making earthing attachment fixed on wall incl. mending good damages to original finish. [only PVC Rigid Conduit on ceiling and remaining portion concealed] (a) AVgG. RUN 8 mtr [E25/4c]
Do - do - do - to 6 amp. 3 pin Modular type plug socket with Modular type switch (Make-legrand myrius or Brand approved by EIC) - do - do - do. a) On Board [E24/3a]
Supply & Delivery 230 volt. 4 Ft. Long single LED tube fittings with one no LED tube complete with all accessories (Make- Crompton- Cat no IGP161LT8-16 1xT8 with 01 nos tube cat no.- LT8-20-865-(2) / Philips/Bajaj/ Wipro). [NS]
Supply & Delivery 230 volt. 4 Ft. Long Double LED tube fittings with two nos LED tube complete with all accessories (Make- Crompton- Cat no IGP162LT8-16 2xT8 with 02 nos tube cat no.- LT8-20-865-(2) / Philips/Bajaj/ Wipro). [NS]
Fixing only single/twin florescent light fitting complete with all accessories Directly on wall/ceiling with HW block and suitable size MS fastener, Ceiling plate, nipples etc. { or “L” type MS clamp whose one side fixed on ceiling with sutable size 4 nos. fastener and other side connected with the conduit with suitable size of bolts and nuts incl. S&F EI conduit, “L” type (125mmx125mm) 6mm thick and 25mm with MS clamp } as required [C2/14d]
Fixing only single/twin fluorescent light fitting suspended 25 cm bellow the ceiling with 2 No. 20 mm dia EI conduit (14 SWG) supports fixed with “L” type MS clamp whose one side fixed on ceiling with sutable size 4 nos. fastener and other side connected with the conduit with suitable size of bolts and nuts incl. S&F EI conduit, “L” type (125mmx125mm) 6mm thick and 25mm with MS clamps and connecting the length of PVC insulated wire and mending good damages to original finish and painting etc. by 2x24/0.20 mm (1.5sqmm.) flexible copper wire of 1.10 mt. length [C2/17]
Supply & fixing 250 V,9/10 watt LED Bulb (Philips make) for batten point.
Supply & Fixing 240V, Modular Socket (2 Module) type fan regulator (Step type) (Brand approved by EIC) on existing Modular GI switch board with top cover plate incl. Making necy. connections etc. [E18/10]
Supply & delivery of 240V, 50 Hz, 1200 mm sweep A.C. Ceiling Fan (Crompton-Standard Ceiling Fans-high speed / Aura or equivalent to Orient) with all accessories. [NS]
Supply & delivery of 18" Wall Bracket Fan [Make- Orient-450 mm or 18” Tornado Wall II all metal body] [NS]
Supply & delivery 30cm (12") 1420 r.p.m. sweep A.C. single phase heavy duty exhaust fan complete set ready to use x as per G.S. (E.P.C Electrical Pvt. Ltd.)
Supply & Fixing GI louver shutter on wall with necy. bolts & nuts (6 mm dia x 62 mm long) for 30 cm Exhaust fan (12") [D14/32b]
Fixing only exhaust fan after making hole in wall and making good damages and smooth cement finish etc. as practicable as possible and providing necy. length of PVC insulated wire and making connection for exhaust of 30 cm (12") diameter incl. fixing louver shuter as per G.S [C4/28b]
Supply & Fixing 240 V, 16 A, 3 pin Modular type plug socket (Make-Brand approved by EIC) with 16A Modular type switch, without plug top on 4 Module GI Modular type switch board with top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. [E18/9b]
Supply & Fixing 240 V, 6 A, 3 pin Modular type plug socket (Brand approved by EIC) with 6A Modular type switch, without plug top on 4 Module GI Modular type switch board with 3 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. [E18/9a]
Distribution wiring in 1.1 KV single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20mm size PVC rigid conduit 'FR' (Precision make) incl. necy. fittings as required. [E-14/1a]
(i) 2 x 22/0.3 (1.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) ECC
(ii) 2 x 36/0.3 (2.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) ECC
Part D: POWER DISTRIBUTION :- Supply, delivery and installation of fabricated cubical type compartmentalized dust and vermin proof L.T. distribution panel board of suitable size made of 2 mm thick M.S. sheet reinforced with (40x40x6 mm) angle iron frame work with individual hinged door with locking arrangement for all compartment and providing suitable ventilation arrangement. The complete panel board shall be painted by power coating paint, colour siemens white. The interconnection should be done with suitable size tinned copper strip between BBC to all main switches and other accessories including suitable stud connectors, socketing etc as required and earthing by nut, bolt in the body complete with base channel. The lower size of the base of panel board should rest on frame work (75x40x5 mm). The control panel will have suitable cable entry from bottom through data cable gland plate to access sufficient no. of cables as per direction of E.I.C. the panel comprising with following switches. (Make: L&T/Legrand/ABB/Siemens) [NS]
INCOMING: 415V, 250 Amp , TPN switches disconnector fuse with 3 no HRC fuse - 01Set BUSBAR: 415V, 315 Amp (4 x 40x5mm, 0.85 mtr long ) copper bus-bar with necessary nos of holes and different colour insulating tape on epoxy bus support.- 01 Set
OUTGOING: (i) 415V 160 Amp TPN switches disconnector fuse with 3 no HRC fuse- 02 Sets (ii) 415V 125 Amp TPN switches disconnector fuse with 3 no HRC fuse- 02 Sets (iii) 415V 63 Amp TPN switches disconnector fuse with 3 no HRC fuse- 02 Sets
Supplying and fixing 415V, 320A TPN on load front operated Changeover switch with Sheet Steel enclosure on angle iron frame on wall with nuts bolts etc. (at Sub station) [D-2]
Supplying and fixing 415V, 32-63A per way, 8 way double door Vertical TPN MCB Distribution board for MCCB incomer with IP-42/43 protection with 01 no 160A, Four Pole MCCB of Breaking capacity 25kA/35kA with fixed thermal and fixed magnetic / adjustable thermal and fixed magnetic settingas incomer and 08 nos 63A TP MCB ('C' Curve, 10kA), concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment. (Make: L&T/Legrand/Seimens/Schneider) [D-11/15, D-8/10, D-6/7]
Supplying and fixing 415V, 32-63A per way, 6 way double door Vertical TPN MCB Distribution board for MCCB incomer with IP-42/43 protection with 01 no 125A, Four Pole MCCB of Breaking capacity 25kA/35kA with fixed thermal and fixed magnetic / adjustable thermal and fixed magnetic settingas incomer and 06 nos 63A TP MCB ('C' Curve, 10kA), concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment. (Make: L&T/Legrand/Seimens/Schneider) [D-11/15, D-8/10, D-6/7]
Supplying and fixing 415V, 16-32A per way, 8 way double door Horizontal TPN MCB Distribution board with IP-42/43 protection with 01 no 63A FP Isolator as incomer and 24 nos 16-32A SPMCB ('C' Curve, 10kA) as outgoing, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment. (Make: L&T/Legrand/Seimens/Schneider) [D-9/13, D-5/6, D-6/7]
Supplying and fixing 250V, 6-16A per way, (2+14) way double-door SPN MCB Distribution Board with IP-42/43 protection with 01 no 40A DP Isolator as incomer and 14 nos 6-16A SPMCB ('C' Curve, 10kA) as outgoing , concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment. (Make: L&T/Legrand/Seimens/Schneider) [D-10/14, D-5/6, D-6/7]
Supply and delivery of following 1.1 KV grade XLPE/PVC armoured cables (Polycab/Mescab/Havells/Currency or PWD approved make as per direction of EIC ) [NS]
(i) 4 core 16 sqmm
(ii) 4 core 25 sqmm
(iii) 4 core 50 sqmm
(iv) 4 core 70 sqmm
(v) 4 core 120 sqmm
Laying of one No. 120 sqmm cable in underground trench 460mm wide x 760mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per Mtr. including filling the space between the bricks and cable and also the trenchwith shifted soil, leveling up and restoring surface duly rammed [F2/1b]
Laying of cable upto 3/4 core 25 sqmm on wall/surface incl. S & F MS saddles with earthing attachment in 10 SWG GI (Hot Dip) Wire, making holes etc. as necy. mending good damages and painting [F1/2b]
Charges for cuttings of Pitch road & PCC road as per GS with Co. Own equipment for fixing of GI protection pipe for cable crossing and mending good damages to original finish as per direction of EIC. [NS]
Supplying & fixing medium gauge GI Pipe ( ISI-Medium) Protection with necessary fittings and jointing metarials as required (for 120 sqmm cable) [F-6/11]
(i) 80 mm dia
Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below : [F4/7c]
(i) 4 core 16 sqmm
(ii) 4 core 25 sqmm
(iii) 4 core 50 sqmm
(iv) 4 core 70 sqmm
(v) 4 core 120 sqmm
Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials : [F5/8b]
(i) 4 core 16 sqmm
(ii) 4 core 25 sqmm
(iii) 4 core 50 sqmm
(iv) 4 core 70 sqmm
(v) 4 core 120 sqmm
Supply and fixing 415V, 3ph 20Hp/15KW dol starter incl. electrical connection with socketing as pequired in angle iron frame on wall or take necessary housing arrangement for fixing the starter in place of existing one after dismantling as per direction of EIC. (L&T,MN 32 DOL, Cat no-SS94353) (for AC)
Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level by ISI-Medium GI pipe or TATA-Medium GI pipe
Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 25 mm x 6 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required [G2/4a]
Connecting the equipments to earth busbar including S & F No. 8 SWG GI (Hot Dip) wire of size as below on wall/floor with staples buried inside wall/floor as required and making connection to equipments with bolts, nuts, washers, cable lugs etc. as required and mending good damages [G2/5iii]
Part E: UPS system :- SIT & C of 6 KVA , 50 Hz, 230V, Single Phase input, Single phase output UPS system with required nos of of SMF Battery, Rack DC connecting cables and complies with following feature / specifications. (Make- AVO / APC / Numeric / GE / Emmerson) Technical Specification for 6 KVA Single phase input & Single phase out put on line UPS systems Topology, IGBT BASED DSP CONTROLED Input Voltage: 230 VAC, 160 - 270 VAC Input Frequency: 50 Hz, 47 to 53 Hz Input PF: > 0.99 Output Voltage: 220 VAC +/- 1% Output Frequency: 50 Hz +/- 0.1% in Free running & +/- 4% in Sync Isolation Transformer: Provided Inbuilt (No external transformer accepted) Power Factor: 0.8 Lag to Unity Crest Factor: 3:1 ; Waveform: Sinusoidal THD: < 3% on linear load & < 5% on non-linear load Overload: 110% for 10 minutes, 125% for 1 minutes, 150% for 30 minutes Transient Response : For 0 - 50% & 50% - 100% load change voltage remains within +/- 5% ; Ripple: < 2% ; Inverter Efficiency: > 93%
Battery : 12 V, Mono Block batteries. Battery Back UP: 30 minute back up minimum VAH required 6240 VAH Battery Make: Exide, Amar Raja Quanta Battery Cabin: With power coated MS angle with MS sheet suitable dimension and gauge, Protections: Input & Output Over / Under Voltage, Single Phasing DC - High / Under Voltage, Battery Charging Over Current, Output Overload / Short Circuit / Over Temp., UPS auto ON Mains recovery Audio Alarm, Mains Fail, Battery Low Pre-alarm, Inverter Trip Metering: Digital Seven segment - Voltage, Current & Frequency, Battery - Voltage & Current Indications: Mains - On / Fail / High / Low / Single Phasing DC - On / High, Battery - Low Pre-alarm / Low Trip Inverter - On / Trip / High / Low / Over Current Switchgear: MCB / MCCB for Input, Battery, Output & Manual Bypass Switch Termination: Input, Battery, Output & Bypass; Enclosure: IP 20 Operating Temp: 0 to 40 Deg C ; Humidity: Upto 95% Rh (non-condensing) Cooling: Forced Air ; Noise: < 55 dB
Charging Current: 5 to 10 Amps. (Site Settable) Cold Start : Provided Communication: RS 232 Static Switch: Provided with changeover < 5 msec in sync & < 20msec in non-sync Certification : ISO 9001: 2015, ISO 14001: 2015, ISO 18001, RoHS and OHSAS 18001 IEC/EN 62040-1-1,IEC/EN50091-1,IEC/EN 60950 (Safety) IEC/EN 50091-2, IEC/EN 62040-2(EMC Emmission),IEC/EN 62040-3(performance & Design)IEC/EN 61000-4(EMC Emmunity) & IEC/EN 60146 (Design & Manufacture) [NS]
Supplying & Fixing Industrial Plug & Socket board with 240 V, 20A, SPN & Earth Metal Industrial Plug socket & 20A Industrial top incl. S&F 20 A SP MCB breaking capcity 10kA (C- Curve) in SS enclosure fixed on wall and cecessary conection. [D12/17]
Add GST @ 18% on Item no 1 to 60
Add CESS @ 1% on Item no 1 to 61
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.97 MB
BOQ_2436889.xls
BOQ • 0.38 MB
BOQ092526.xls
Tender Documents • 0.38 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .