| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹90.5 LAccepted-AOC 11TH FLOOR ECO CENTRE BUSINESS TOWER P NO 4 EM BLOCK SECTOR V KOLKATA 91 | KOLKATA | 24 PARAGANAS NORTH | WEST BENGAL | 700091 | ₹90.5 L | L1 | Accepted-AOC Lowest bid |
| 2 | L2₹90.7 L+₹22,738 (0.25%)Rejected-Finance ST 11 JEEWAN NAGAR CHOWK OPP PUDA NURSERY 101 AMI COMPLEX ST 11 JEEWAN NAGAR CHOWK FOCAL POINT FOCAL POINT | ₹90.7 L+₹22,738 (0.25%) | L2 | Rejected-Finance Higher bid |
| 3 | L3₹94.1 L+₹3.6 L (4.02%)Rejected-Finance | ₹94.1 L+₹3.6 L (4.02%) | L3 | Rejected-Finance Highest bid |
| 4 | Not Admitted-Finance 64 PHASE 3A MOHALI 160059 INDIA | S A S NAGAR | PUNJAB | 160059 | - | - | Not Admitted-Finance System rejected due to Highest value quoted |
Tender Value
Refer Docs
EMD Value
₹2.6 L
Closing Date
13 Jan 2025, 11:30 amClosed
DyCE,MM-1
DyCE,MM-1,GHTP,Lehra-Mohabbat
Renewals and replacement of existing centralized Air Conditioning system of UCB control rooms of 2x250 MW unit-3 and 4 Stage-II, GHTP, Lehra-Mohabbat
2024_POWER_131742_1
162/MM-I/MAMC-268/OM/GHTP/2024
Open Tender
Power/Energy Projects/Products
Tender cum Auction
60 days
DyCE, MM-1, GHTP, Lehra-Mohabbat
Please refer tender documents
3 documents required · 3 mandatory
₹2,360
₹2.6 L
4 Mar 2025
23 Dec 2024
15 Jan 2025
23 Dec 2024
13 Jan 2025
23 Dec 2024
Amount
Supply, installation, testing & commissioning (SITC) work of Water Cooled Screw Chiller units & connected accessories - As per AHRI/ EUROVENT certified standards:
WATER COOLED SCREW CHILLERS: SITC of Twin Screw type water cooled flooded Chiller with Star Delta Starter having a nominal capacity 120 TR (Variation ± 5 TR), latest model at below mentioned parameters suitable for operation on Eco friendly refrigerant for Screw type Machine each comprising of the following complete as per specifications and as required. Twin Screw Single Compressor hermetic complete with automatic capacity control safety switches, forced feed lubrication system, 100% to 25% stem less control, shell & tube flooded evaporator having, electronic expansion valve, motor, factory insulated chiller, vibration isolator, integrated refrigerant piping, fittings & valves and wiring, first charge of refrigerant (CFC free R-134 a) and lubricant, Star - Delta Starter, accessories as required and called for, automatic and safety controls and all mounted on a steel frame as per specifications. Motor shall be suitable for 415 ± 10% Volt, 50Hz, 3ph AC supply as per specification and drawings. Microprocessor based control panel complete with accessories as per specifications and BMS compatible (Details as per tender specifcations)
COOLING TOWER: SITC of FRP induced draft counter flow 150 TR Rectangular cooling tower each guaranteed to cool 600 USGPM of water from 97.5°F to 90°F at a design wet bulb temperature of 83°F with FRP water basin, PVC fills with integral louvers and drift elimination, hot water distribution by gravity complete with statically and dynamically balanced axial flow, direct driven fans with TEFC induction motor suitable for operation on 415 ± 10% Volt, 50 Hz. AC supply, suction screen, make up with float valve and quick fill arrangement, overflow and drain connections, with necessary valves, suitable inspection ladders, access arrangement for cooling tower interior, steel supporting structure, anti-vibrating mountings, painting etc. complete as per specification. Make: Paharpur / Sona Cooling Tower / Baltimore / Mihir or any other standard make. (Details as per tender specifcations)
CHILLED WATER PUMP: SITC of End Suction Top Discharge Flexible Coupled type Pumps with electric motor for re-circulation of water for the central air conditioning system with CI casing. Bronze / SS (CF8) impeller, high strength steel shaft. The pump motor shall be suitable for 415 +10% volts, 50 Hz, 3-phase AC power supply of minimum IE2 efficiency class. Pumps shall have outside type mechanical seal and CI casing. Pump and motor shall be factory assembled for unit responsibility all the items shall be sourced from single supplier. Pumps shall be complete as per specifications and shall have operating parameters as given below. The internal components of pumps including mechanical seal shall be suitable to sustain a temperature of 122°F. Make: Xylem / Groundfoss / Armstrong / Wilo Mather & Platt or any other standard make ( Details as per tender specifcations)
CONDENSER WATER PUMP: SITC of End Suction top Discharge Flexible Coupled type pumps with electric motor for re-circulation of water for the central air conditioning system with CI casing. Bronze / SS (CF8) impeller, high strength steel shaft. The pump motor shall be suitable for 415 +10% volts, 50 Hz, 3-phase AC power supply of minimum IE2 efficiency class. Pumps shall have outside type mechanical seal and CI casing. Pump and motor shall be factory assembled for unit responsibility all the items shall be sourced from single supplier. Pumps shall be complete as per specifications and shall have operating parameters as given below. The internal components of pumps including mechanical seal shall be suitable to sustain a temperature of 122 °F. Make: Xylem / Groundfoss / Armstrong / Wilo Mather & Platt or any other standard make (Details as per tender specifcations)
Hydraulic balancing of water flow of chillers, pumps, cooling towers and Chilled & Condenser water line.
Dismantlement work:
Dismantling of existing AC chiller units of capacity 90 TR.
Dismantlement of existing cooling tower units etc.
Dismantlement work of existing condenser & chiller pumps.
Bidder Name
Amount in Words
QUVIX INDIA PRIVATE LIMITED (BID ID -606881)
SMD Solutions (BID ID -606818)
Blue Star Limited (BID ID -608855)
Blue Star Limited (BID ID -608855)
SMD Solutions (BID ID -606818)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .