Loading…
Loading…
Tender Value
₹1.5 Cr
EMD Value
₹2 L
Closing Date
21 Apr 2026, 10:00 pmClosed
Hubli Electricity Supply Company Limited
NAGAPPA C BELAKERI
Providing additional 3rd 5 MVA, 33/11KV power transformer at 33/11KV sub-station Khanapur in Khanapur Taluk, Belagavi District in 33KV S&L Division, Belagavi on PTK basis (5 MVA Power Transformer will be supplied by departmentally)
HESCOM/2025-26/EL/WORK_INDENT1104
HESCOM/2025-26/EL/WORK_INDENT1104
Open
Electrical
Two Tender Document System(Two Cover)
HESCOM Superintending Engineer (PMC)Corporate Office Hubli
19 documents required · 19 mandatory
The bidder should have executed work of installation and commissioning of minimum of One No. 5MVA and above higher capacity power transformers of 33/11KV and above voltage class with associated switchgears and ODS on Total Turnkey or Partial turnkey or labour Contract basis in any one of the in the last Five Financial Years. (i.e.,2019-20, 2020-21,2021-22,2022-23 and 2023-24) on Total Turnkey/Partial Turnkey Basis/ Labour contract basis /self-execution basis in any State/ Central Govt. Distribution Companies / PSUs.Such works shall be in successful operation for a period of at least 1(One) year as on date of submission of bid.As a proof of documentary evidence Award copies and work completion certificates duly mentioning date of work completion and Executed cost issued by the competent authority not below the rank of Executive Engineer (Ele) of any State/Central Govt. Distribution Companies / PSUs shall be uploaded. The Experience certificate shall be submitted as per Annexure-IV
The Bidder should have achieved in at least Two financial year, a minimum financial turnover of not less than Two Times the amount put to tender in the last five financial years (i.e., ,2020-21 2021-22, 2022-23, 2023-24 & 2024-25).The bidder shall upload the downloaded Form GSTR-9/9C, 3CA/3CB & 3CD from the portal along with Copies of Annual turnover certificate and audited balance sheet of profit and loss account duly mentioning the UDIN No duly certified by Chartered Accountant as applicable.Documents without UDIN No, GSTR-9/9C, 3CA/3CB & 3CD downloaded from portal are liable for rejection.Note: Updated to the FY in which the tenders are invited. Financial turnover of previous years shall be given a weight of 10% (say) per year to bring them to the price level of the FY in which the tenders are invited.
The cash at bank, term deposits and availability of fund based credit facilities shall not be less than 30% of the amount put to tender (Rs. 38.02Lakhs)shall be supported by a certificate issued by Nationalized/ scheduled Bank as per the Annexure format attached shall be uploaded.If the Tenderer has banking with more than one Bank, then the available liquid assets mentioned above on a particular date i.e., as on date of bid submission or at a later date before the last date for bid submission of tender shall be the same date for all the banks.The said Credit Facility Certificate should possess the name of the Firm and tender Indent number and the credit facility to be issued in the name of Superintending Engineer (Ele),PMC, Corporate Office,HESCOM, Navanagar, Hubli. The credit facility certificate should be in the Format Annexed to this bid.ANNEXURE.The conditional credit certificates are liable for rejection.
The bidder should have Satisfactorily completed (at least 90% of the contract value), as prime a contractor, at least one contract involving work of installation and commissioning of 5MVA and above higher capacity power transformers 33/11KV and above voltage class of value not less than 50% of the amount put to Tender of Rs. 63.37Lakhs in any State/Central Govt./ Distribution Companies/PSUs in the last Five Financial Years (i.e.,2019-20, 2020-21,2021-22,2022-23 and 2023-24)As a proof of documentary evidence Award copies and work completion certificates duly mentioning date of work completion and Executed cost issued by the competent authority not below the rank of Executive Engineer (Ele) of any State/Central Govt. Distribution Companies / PSUs shall be uploaded. The Experience certificate shall be submitted as per Annexure-IV.Note- Updated to the FY in which the tenders are invited. The value of the completed works shall be given a weight of 10% per year to bring them to the price level of the FY in which the tenders are invited
The bidder shall be a sole proprietorship firm or a partnership firm or a company incorporated under companies Act 1956/2013. Copy of the Certificate of Incorporation in case of Registered Company/ Partnership deed in case of Partnership Firm/GST or PAN registration in case proprietor ship firm is to be uploaded.
The bidder should possess valid Class-I / Super grade Electrical Contractor license issued by the Electrical Inspectorate, Govt. of Karnataka. The validity of the license should be in force at the time of submission of Bids. The bidder should possess valid Class-I / Super grade Electrical Contractor license issued by the Electrical Inspectorate, Govt. of Karnataka. The validity of the license should be in force at the time of submission of Bids.(Note: Firm name in the license as well as all the statutory documents should be same otherwise bid is liable for rejection).Scanned original copy of the Class-1 / Super grade Electrical Contractors License issued by Electrical Inspectorate, Government of Karnataka is to be uploaded by the bidder.
The bidder should upload original scanned copy of ESI issued by the respective competent authorities of the concerned department.
The bidder should upload original scanned copy of EPF Reg. No issued by the respective competent authorities of the concerned department
The bidder should upload original scanned copy of Pan No issued by the respective competent authorities of the concerned department.
The bidder should upload original scanned copy of GST No. issued by the respective competent authorities of the concerned department.
The bidder should possess valid original scanned copy of Registration Certificate of Establishment FORM C (Labour Reg.) issued by Department of Labour, Government of Karnataka. The bidder should upload original scanned copy of Registration Certificate of Establishment FORM C (Labour Reg.) issued by Department of Labour, Government of Karnataka
The bidder should not have been Black-Listed by ESCOMs/ KPTCL/ any other Government Distribution/ Transmission utilities including PSUs as on date of bid submission. Self-declaration for the same shall be uploaded (Annexure-I).
The bidder should not have been defaulted & Terminated due to non-performance in execution of works against the order placed by ESCOMs/KPTCL/any other Government Distribution/Transmission utilities including PSUs as on date of bid submission. Self-declaration for the same shall be uploaded (Annexure-II)
The bidder should provide detailed information on any litigation or arbitration arising out of contracts completed or under execution by it over the last five years with /KPTCL/ESCOMS. A history of awards involving litigations against the bidder or any part may result in rejection of bid. Self-declaration for the same shall be uploaded (Annexure-III)
Tender Capacity: The bidder should upload available tender capacity calculated in the prescribed format through e-procurement portal within due date of submission of bids. The available tender capacity shall be more than the total tender value.
Pre Survey: The bidder at his own responsibility must visit and examine the site of works & its surroundings and obtain all information that may be necessary for participating in the tender. The cost of the visiting/survey of the proposed works shall be at the bidders own expenses.The site inspection survey certificate of the proposed works issued by the concerned Executive Engineer (Ele).33KV S&L Division, HESCOM should be obtained by the bidder and shall be uploaded
The bidder from Nations sharing Border with India should upload the certificate issued by GOI.OR Self-declaration for not from Nations sharing Border with India.Registration certificate issued by the competent authority shall be uploaded. OR If not Self-declaration in the prescribed format as per Annexure-VII shall be uploaded.The self-declaration shall clearly indicate the tender enquiry number & date on which declaration is done.
₹3,740
₹2 L
5 Apr 2026
5 Apr 2026
22 Apr 2026
9 Apr 2026
10 Apr 2026
Tender Capacity Format
Details of work Executed during last 05 years ( To asses the value of A)
Sl No Year Work Executed Other related Electrical Works if any Cost of executed work in Rs Lakhs
New substations / Augmentation in Nos HT line in Rkms(11KV & above) DTC in Nos
Details of existing commitments and on-going works to be completed during next '6 months ( To asses the value of B) Attached in the next sheet
SL No Details of On Going works Award amount Rs in Lakhs Amount of work to be completed during next "6 months" Rs in Lakhs Completion period as per award Completion period remaining
Tender Capacity Formula= A*N*1.5-B
Where 'N'= 01=6months of completion period for above subject work
Seal and signature of the Bidder
A= Maximum value of Distribution network work executed in any one year during the last 5 years i.e 2018-19 ,2019-20,2020-21,2021-22 &2022-23 ( UP dated to __________________ price level) taking into account the completed as well as works in progress
N= Number of years/months prescribed for completion of the works for which Tenders are invited
B= Value,at________price level, of existing commitments and on-going works to be completed during the 'N'
Note: 1) The available tender capacity shall be more than the total tender value 2) Documentary Proof in support of value ‘A’, the Total value of works executed and payments received annually in the last 5 years shall be uploaded in the form of certificates issued by Chartered Accountant. In case if the same is not uploaded, then the maximum value of annual payments received towards the works executed which is indicated in the audited balance sheet in any one year during the last five years will be considered.
Tender Capacity Format
Details of existing commitments and on-going works to be completed during next "6 months ( To asses the value of B)
SL No Details of On Going works Award amount Rs in Lakhs Amount of work to be completed during next "6 months" Rs in Lakhs Completion period as per award Completion period remaining
Where 'N'= 1=4 months of completion period for above subject work
Note: The statement showing the value of existing commitments and ongoing works as well as the stipulated period of completion remaining for each of the works listed shall be countersigned by the Employer in charge, not below the rank of Executive Engineer or equivalent.( Note: L-1 in any of the recently called tender amount is also be considered as value of B along with the above)
Seal and signature of the Executive Engineer(Ele)
HUBLI ELECTRICITY SUPPLY COMPANY LIMITED
Estimate for Providing additional 3rd 5 MVA, 33/11KV power transformer at 33/11KV sub-station Khanapur in Khanapur Taluk, Belagavi District in 33KV S&L Division, Belagavi on PTK basis (5 MVA Power Transformer will be supplied by departmentally)
Sl. No Particulars Material Labour Civil Total
1 Materials cost (Exclusive of GST) 10222917.55 10222917.55
2 Labour charges+ Decommissioning (Exclusive of GST) 321280.36 321280.36
3 Civil Engineering Charges (Exclusive of GST) 2128830.85 2128830.85
5 Area Specific Loading @ 3% on SI No 4 0 0 0 0.00
6 GST @ 18% on Si no 4 & 5
7 Cost of the Estimate /APT (Without GST) 10222917.55 321280.36 2128830.85 12673028.76
% age of tender compenents included
Executive Engineer (EL), Superintending Enginner (El),
Projects - 1 , HESCOM, Hubli PMC, HESCOM, Hubli
HUBLI ELECTRICITY SUPPLY COMPANY LIMITED
Estimate for Providing additional 3rd 5 MVA, 33/11KV power transformer at 33/11KV sub-station Khanapur in Khanapur Taluk, Belagavi District in 33KV S&L Division, Belagavi on PTK basis (5 MVA Power Transformer will be supplied by departmentally)
PART-A (Material portion)
Sl. No. Particulars Unit Qty Rate Amout in Rs. Remarks
A.1 Power Transformers:
a) 33/11KV, 5 MVA, DELTA/STAR, DY 11, 3Ph, 50Hz,Core type winding with OLTC, RTCC panel etc., complete filled with Transil Oil and 10 % spare Oil in Non Returnable Drums (Power Transformer shall be supplied by departmentaly) (As per ESCOM's CSR- 2023-24 33KV Material. page No- 69 of 81 SL.No-1, Item No-1.01 ,Material Code-1.01) Nos 0 8381013.60 0
De-Loading the departmentally supplied material by 21%.Rs.6284178/1.21=Rs.5193535.54
A.2 11kV Switch Gear (MCVCB)
a) 11 kV MCVCB, 350 MVA, 25 kA, 1250 A incomer, (SCADA compatible) comprising of INCOMER ( MEI MAKE ), (As per KPTCL CSR 2023-24 Page No. 12, Sl.No.2377 ) No 1 987039 987039
b) 11 kV MCVCB, 350 MVA, 25 kA, Feeder 800 A feeder (SCADA compatible) comprising of Feeder( MEI MAKE ), (As per KPTCL CSR 2023-24 Page No. 12, Sl.No.2377) No 3 878202 2634606
A.3 33KV SF-6/ VCB Breakers: 0
a) 66 kV, 40 kA class, SF-6 Circuit Breaker with terminal connector suitable for Al. tube/conductor with spring/semi-pneumatic/pneumatic type operating mechanism and mounting structure etc., as per technical specification. (As per KPTCL SR- 2025-26, Page No- 14, SL.No-278 Nos 1 730000 730000
A.4 Control and relay panels Simplex type as per technical specifications (Control Voltage 110V DC) 0
a) 5MVA, 33/11KV Transformer Panel (KPTCL SR-2023-24, Page No:41, Sl. No-16 Item No:16.2.7,HSN Code,8537 Rs:631620 (66KV Panel rate rate is considered due to non availability for 33 KV Panel in the CSR 2023-24) panel 1 631620.00 631620 Not updated in new SR
A.5 33KV Current Transformers 0
a) 36KV, 20KA CT of ratio 200-100/1-1-1A with rigid terminal connector suitable for Coyote ACSR conductor with marshallling Box for power transformer. (As per KPTCL SR- 2023-24, No- 7, SL.No-136 Nos 3 45000 135000
b) 11kV NCTs 600-300/1-1-1A (for PCVCBs upto 10 MVA Transformer),(As per KPTCL SR- 2023-24, No- 7, SL.No-140 No's 1 50000 50000
33KV Potential Transformers 0
a) 33 KV, Potential transformer with ratio of 33kV Voltage Transformer 33kV √3 110√3- 110√3 (As per KPTCL SR- 2023-24, No- 9, SL.No-161 Nos 3 48000 144000
A.6 Surge Arrestors, Metal Oxide, as per Technical Specification. 0
a) 30KV, 10KA normal duty Polymeric with terminal connectors suitable for Coyote Conductor (As per KPTCL SR- 2023-24, Page No.34 SL.No.8, Item No.8.7,HSN Code-8535 Rs.4840/-) No's 3 11918 35754 Not updated in new SR
b) 10 kV, 5 kA Lightning Arrester Polymeric type with GROUND DISCONNECTOR),(As per ESCOM's SR-2025-26 Page No.8 of 5 SL.No.174 Set (3 Nos) 4 1786 7142 Not updated in new SR
A.7 33 KV Isolators : 0
1) 33KV, 800A, 25 KA Class Double Break manually operated isolators with Pad connectors suitable for Coyote ACSR Conductor, as per technical specification with Solid Core, cylindrical post insulators 0
a) a) 33 kV, 800 A, 25 kA Upright without Earth Switch (Live Point Height 3750 mm) (As per KPTCL SR- 2023-24 Page No.34 SL.No-9, Item No-9.14.2 HSN Code-8535, RS-70180/-) Nos 2 84700.00 169400 Not updated in new SR
2) 11 KV Isolators 400A with manually operated isolators with Pad connectors suitable for Lynx ACSR Conductor, as per technical specification with cylindrical post insulators 0
a) 11KV 400A Special Roaster switch with H frame for mounting Structure(As per ESCOMsSR- 2023-24, Page No- 10 of 50, SL.No-210) Set 3 15005 45014 Not updated in new SR
b 11KV 400 A Double break GOS for capacitor bank(As per ESCOMs SR- 2023-24, Page No- 10 of 50, SL.No-205) Set 1 23135 23135 Not updated in new SR
b) Annunciator Panel for the following combinations (for both MCVCB & PCVCB), 1IC+4F+1CB (As per KPTCL SR-2023-24, (As per KPTCL SR-2023-24, (As per KPTCL SR- 2023-24, No- 13, SL.No-251) No 1 172118 172118
A.8 CAPACITOR BANK with 0.2% Series Reactor & NCT 0
a) Design, engineering, supply, erection of Capacitor Bank with internal fuses, terminal connector, Neutral CTs & 0.2% series reactors on neutral side with elevating/mounting structure and with 10% spare capacitors complete, 12.1 kV, 2.9 MVAr Star connected Capacitor Bank (This does not include breaker, panel, civil works like excavation and foundation concreting works),(As per KPTCL SR 2023-24,Volume-6,Page No.39,Sl.No.12,Item No.12.1.7) Set 1 538450.00 538450 Not updated in new SR
b) 11 kV MCVCB, 500 MVA, 25 kA, 1250 A feeder (SCADA compatible) Feeder Panel for Capacitor Bank(As per KPTCL SR- 2023-24, No- 12, SL.No-220) No. 1 997047 997047 Not updated in new SR
A.9 MOUNTING STRUCTURES: 0
a) Mounting Structure: 33KV, 800A, 25 KA Class Double Break manually operated ISOLATOR Live point height 3750 mm - 2Nos. (As per KPTCL SR- 2023-24, No- 02, SL.No-16) ii) (The weight of structure is 0.240t X2 Nos=480t) T 0.48 124000 59520
b) Mounting Structures:33KV Current Trasformers- 0.142x 3Nos =0.426 t As per KPTCL SR- 2023-24, No- 02, SL.No-16) T 0.426 124000 52824
b) Mounting Structures:33KV Potential Trasformers -0.142x 3Nos =0.426 t (As per KPTCL SR 2023-24, Page No-245 Sl.NO:I,Item.No:E (3)(d), As per KPTCL SR- 2025-26, No- 02, SL.No-16) T 0.426 124000 52824
c) Mounting Structures: P.I. Support (33kv side): 0.082x 9 Nos =0.738 t As per KPTCL SR- 2023-24 No- 02, SL.No-16) T 0.492 124000 61008
d) Mounting Structures:33KV Lightning Arrestors - 0.082 x 3 Nos =0.0.246 tAs per KPTCL SR- 2023-24, No- 02, SL.No-16) t 0.246 124000 30504
e) Mounting Structures:11KV NCT 1 No. 0.146x 1 No =0.146 t As per KPTCL SR- 2023-24, No- 02, SL.No-16) t 0.146 124000 18104
f) Mounting Structures:High P.I. Support (11kv side),2 Nos Harizontal cross arm for support of 11 KV 3CX400 Sq.mm XLPE U.G cable 0.22x 2 Nos =0.44 t As per KPTCL SR- 2023-24, No- 02, SL.No-16) t 0.22 124000 27280
g) Bolts & Nuts for all Station Mounting Structures, such as, A)3T1- (0.017t), 3B1 (0.010t), As per KPTCL SR 2023-24, Page No. 244, Sl. No. I; Item No. (D)(i.ii). B)33KV PT (0.010t X 3 =0.030t)Asper KPTCL SR 2023-24, Page No. 245,Sl. No. I; Item No.(E)3 (d). C) 33KV CT (0.010t X 3 =0.030t) Asper KPTCL SR 2023-24, Page No.245,Sl. No.I; Item No.(E)2 (d). D) 33KV LAs( 0.005X3=0.015) Asper KPTCL SR 2023-24, Page No.245,Sl. No.I; Item No. E) 4(d). E) 33KV PI (0.005x 9 =0.003 t) ( Asper KPTCL SR 2023-24,Page No-247 Sl.NO:II, Item.No:E (iv), F)11KV NCT(0.011x 4 No =0.044t) (Asper KPTCL SR 2023-24, Page No-247 Sl.NO:II, Item.No:D(viii), G)11KV High P.I(0.011x 1 No =0.011t). (Asper KPTCL SR 2023-24, Page No-247 Sl.NO:II, Item.No:E(viii), (Bolts & Nuts Rate, As per KPTCL SR 2023-24; Page No-43;Sl.No.18 Item No.18.3) Rs 142780.00t t 0.124 142780.00 17705
A.10 a) S.M. Rail angle for Transformer plinth ( 2 nos. of 3m long) SM rail. (As Per KPTCL SR-2023-24, Page No:116, Sl.No.10, Set Rs=1626.00) and .M.S angle 75 x 75 x 6 mm angle iron 8 mtr long 0.2 MT each.(As Per PWD Electrical SR-2023-24, Page No:19, Sl.No.5.40, Item No:5.41.3, Per Mtr Rs:555 X 8 = Rs.4440.00) ,(1626+4440=6066.00) Set 1.000 6066.00 6066 Not updated in new SR
A.11 Conductors 0
a) Lynx ACSR (30/2.79 mm Al + 7/2.79 mm St), Std Wt: 842 Kg/KM As per KPTCL SR- 2023-24, No- 02, SL.No-23) Kms. 0.000 213000 0
b) Coyote ACSR (26/2.54 mm Al + 7/1.90 mm St), Std Wt: 521 Kg/KM As per KPTCL SR-2023-24, No- 02, SL.No-24) Km 0.100 155000 15500
A.12 11KV ODS: 0
a) 9 Mtr. Long, 145kg RCC pole for 11KV ODS.( As per KPTCL SR- 2025-26, No- 02 of 50, SL.No-01) Nos 0 7531 0 Not updated in new SR
b) RCC Pole - 8 Mtr Long, 115 Kg WL for LED Light ( As per ESCOMs SR- 2025-26, No- 02 of 50, SL.No-03) Nos 2 5647 11294 Not updated in new SR
A.13 33 kV side Station Structure 0
a) Station structures Tower - 3T1 with peak and Fabrication, galvanising and supply of Mild Steel tower materials As per KPTCL SR- 2023-24, No- 02, SL.No-16) t 0.696 124000 86304 0
b) Station structures Beam - 3B1 (6M Width), As per KPTCL SR-2023-24, No- 02, SL.No-16) t 0.184 124000 22816
A.14 11 KV D.P.Structures: 0
a) D.P. Structures with hardware consisting of double power X-arms, horizonontal cross brace, cross braces, back cleat, strain plate, bolt & nuts, painted with two coats of metal primer and aluminium paint, etc as per drawing. (As per ESCOM SR-2023-24, Page No:442, Sl.No.178, Item No:26.01,material code-279100 Rs:6401.00 *3=19203.00 ) . Set 4 6164 24658 Not updated in new SR
A.15 Control Cable with Accessories: (With glands/lugs/ferruels) 0
a) 19 Core 2.5 Sq.mm (As per KPTCL SR-2023-24,As per KPTCL SR- 2025-26, No- 10, SL.No-181) . Kms. 0.200 585000 117000
b) 4 Core 6 Sq.mm (As per KPTCL SR-2023-24, Page No:40 Sl No-13, Item No:13.8, HSN Code:8544, Rs:247*1000=.247000 Total Rs =247000) Kms. 0.250 247000.00 61750 Not updated in new SR
c) 4 core 2.5 Sq.mm As per KPTCL SR- 2023-24 No- 10, SL.No-176) Kms. 0.150 153000 22950
d) 2 core 2.5 Sq.mmAs per KPTCL SR- 2023-24, No- 10, SL.No-175) Kms. 0.250 99000 24750
e) 10 Core 2.5 Sq.mm As per KPTCL SR- 2023-24, No- 10, SL.No-179) Kms. 0.075 344000 25800
A.16 Insulators & Hardware materials: 0
a) Pad clamp for Coyote ACSR As per KPTCL SR- 2023-24, No- 3, SL.No-45) Nos 12 848 10176
b) Pad clamp for Lynx ACSR As per KPTCL SR- 2023-24, No- 3, SL.No-45) Nos 18 849 15282
c) T clamp for Coyote ACSR As per KPTCL SR- 2023-24, No- 5, SL.No-90) Nos 12 576 6912
d) T clamp for Lynx ACSR As per KPTCL SR- 2023-24, No- 5, SL.No-87) Nos 18 606 10908
e) 33KV CT bimetalic clamps for Lynx ACSR (As per present market rate) Nos 6 1000 6000
f) NCT Pad Clamp As per KPTCL SR- 2023-24, No- 16, SL.No-327) Nos 2 977 1954
g) Post Insulator Clamps As per KPTCL SR-2023-24, No- 5, SL.No-74) Nos 6 991 5946
h) Terminal Connector Clamps Suitable for 36 kV class bushing to suit Coyote / Lynx conductor for HV Bushings of Power Transformers (Asper KPTCL SR-2023-24, Page No 135, Sl.No-E Item No-viii HSN Code:8536 Total Rs =512) Nos 3 512.00 1536 Not updated in new SR
i) Terminal Connector Clamps Suitable for 12.1 kV class bushing to suit Drake conductor for Bushings of Power Transformers (As per KPTCL SR-2023-24, Page No 135, Sl.No.2E Item No-ix HSN Code:8536 Total Rs.1113/-) Nos 4 1113.00 4452 Not updated in new SR
j) Strain Clamp for Lynx ACSR, (As per ESCOMs SR-2023-24, Page No- 3 of 50 SL.No-46) Nos 6 707 4242 Not updated in new SR
k) Solid Core Bus Post Insulator 33 kV As per KPTCL SR- 2023-24, No- 11, SL.No-186) Nos 6 3663 21978
l) 70 KN Disc Insulators Ball and socket type As per KPTCL SR- 2023-24, No- 11, SL.No-190) Nos 9 519 4671
m) I bolts (As per present market rate) Nos 6 55 330
A.17 11kV, 3X400 Sqmm Core, XLPE HTUG Cable (ROUND Armoured Cable) 0
a) 11 kV, 3x400Sqmm Core, XPLE HTUG Cable with pressure extruded inner sheeth, ROUND WIRE ARMOURED as per IS-7098 (Part-2) Armouring wires dia and Resistivity as per IS-3975 As per ESCOMs SR- 2023-24, No- 15 of 50, SL.No-323) Kms. 0.200 2990892 598178 Not updated in new SR
b) 11 kV, 3x240Sqmm Core, XPLE HTUG Cable with pressure extruded inner sheeth, ROUND WIRE ARMOURED as per IS-7098 (Part-2) Armouring wires dia and Resistivity as per IS-3975 As per ESCOMs SR- 2023-24, No- 15 of 50, SL.No-321) Kms. 0.270 2050618 553667 Not updated in new SR 1,708,848
c) Cable Covering Tiles 250x125x40 mm or 125x125x40mm. As per KPTCL SR- 2023-24, No- 31 of 50, SL.No-675 & 676) Nos 0 11 0 Not updated in new SR
Nos 0 5 0 Not updated in new SR
d) Artificial/Manufacture Sand (Extracted from Vol-1, PWD SR Sl No. 62),(As per BESCOM's SR-2023 CDS-24,Sl.No.257,CDS-21,Item No.6) Cmt 0 1771 0 Not updated in new SR
e) GI Pipe, 150 mm Dia for drain crossing, cable raising etc., (As per BESCOM's Cost data sheet-23, Sl No-9 (Extracted from Vol-5, BWSSB SR Item No. 177) Mtr 60 1854.00 111240 Not updated in new SR
f) Route and Joint indicating stones KPTCL SR- 2023-24, No- 31 of 50, SL.No-677 & 676) No's 0 140 0 Not updated in new SR
g) 11kV Jointing and Cable Termination Kits 0 Not updated in new SR
h) Heat Shrinkable Outdoor Type Cable Termination Kit for XLPE Cable3x400 Sqmm(As per As per ESCOMs SR- 2023-24, No- 20 of 50, SL.No-419) Set 2 5633 11266 Not updated in new SR
i) Heat Shrinkable Indoor Type Cable Termination Kit for XLPE Cable 3x400 Sqmm (As per As per ESCOMs SR- 2023-24 No- 20 of 50, SL.No-416) . Set 2 5062 10123 Not updated in new SR
j) Heat Shrinkable Outdoor Type Cable Termination Kit for XLPE Cable 3X240 Sqmm (As per As per ESCOMs SR- 2023-24, No- 20 of 50, SL.No-418) Set 5 5591 27954 Not updated in new SR
k) Heat Shrinkable Indoor Type Cable Termination Kit for XLPE Cable 3X240 Sqmm (As per (As per As per ESCOMs SR- 2023-24, No- 20 of 50, SL.No-415) . . Set 5 4932 24660 Not updated in new SR 4,110
A.18 Ground Mat & Earthing : 0
a) Grounding of equipment by providing Cast iron pipe of 100 mm ID 13 mm thickness, 2.75 metre long with 2 part clamp out of G.I. Flat 50 X 6 mm continuously welded alround the pipe using cast iron welding electrodes as per drawing including the cost of excavation (All materials to be supplied by the contractor) (As per KPTCL SR-2023-24, Page No:115, Sl.No-6 Item No:c Material Rs-12792+3491 Labour Set 30 16283.00 488490 Not updated in new SR
b) Supplying & providing 450 mm dia 450 mm height 1.5" to 2" thick hume pipe collar (non pressure type) for earth pits including all lead and lifts etc.,.(As per KPTCL SR-2023-24, Page No:124, Sl.No-26 Item No:i Material Rs-1499.00 Each 30 1499.00 44970 Not updated in new SR
c) Grounding of equipment with 50X6 mm GI flat & connecting equipment to the earth mat / ground pit. Each point of Earthing with all formation works like bending, twisting, drilling of holes & conncting by welding (inclusive of all T & P consumables) to the earth mat/ ground pit/point of earth connection, all the materails supplied by the contractor (As per KPTCL SR-2023-24, Page No:123, Sl.No-26 Item No:i Material Rs-335.00 Rmt 225 335.00 75375 Not updated in new SR
d) Supplying and laying of MS Flats of various sizes, welding and applying ACB paint to welded portion and covering with sodium bentonite clay as per the drawing/standard specification and consolidation (MS Flat of size 50x6 ) (As per KPTCL SR-2023-24, Page No:123, Sl.No-26 Item No:f Material Rs-404.00 m 210 404.00 84840 Not updated in new SR
A.19 Miscellaneous items 0
a) Caution/Danger Board (As per ESCOM SR 2023-24, Page No.32 of 81, Sl. No.593 , Item No.68.17, Rs. 150/- Nos 5 157 786 Not updated in new SR
b) Phase plates (As per KPTCL SR 2023-24, Page No.43, Sl. No.19, Item No,19.1, Rs.528/- Set (3 Nos) 1 528.00 528 Not updated in new SR
c) Name Plates for equipment/Earth Pit (As per present market rate due to non availability of rates in the current SR) Nos 20 250.00 5000
d) Name plate for feeders and banks (As per present market rate due to non availability of rates in the current SR) Nos 7 250.00 1750
A.20 a) Station yard LED outdoor light fitting Higher end Philips / Havells / Equivalent complete fitting set.
Supply of 90W LED yardlight with pressure die cast aluminium housing body with optimal heat sink for better thermal dissipation. Lamp compartment comprising of anti glare clear diffuser with Injection moulded polycarbonate material, delivering superior light output. Rated life Burning Hrs 50000 hr & Lumen Mainanance of 70%, maximum light intensity should be between 60 degrees to 70 degrees. CCT > 5500K, IP 66 optiical and electrical compartment & impact resistance of complete luminare > IK08. Power Factor > 0.9 with mains Surge Protection - Min 5KV along with over Voltage / Overload, short circuit / miswiring protection. Compatible for pole mounting with outer dia of 40mm to 50mm. Universal Voltage driver to operate wide voltage range from 100V to 270V 50/60 Hz application. Overload & Short circuit protection ensures reliable operation in spite of problem in output side. Compliance to IS 10322/IEC 60598, LM 79 & LM 80 Adherence with RoHS. UL approved MCPCB. Top access street light with single screw to ensure ease of maintanance at the sight location with minimized minimal tools. LED light fixture with ...90 W System Power Consumption. LED Efficiency>130lm/w nominal CRI. 75. LImunaire manufacturer should have in-house facilitty accredited by NABL/CPRI & any Government certified agency & Design & Development facility certified by ISO 9001:2008. Housing with supplier word mark /name shall be Engraved / Embossing on the die cast housing / Body part. warranty of 2 Years against any manufacturing defect working under standard electrical conditions as mentioned above should be given by LED manufacture & Cree/Nichia/Lumileds/Osram make LED Source. Elec. KPWD Ele SR 23-24 (Pg No.45 of 105, item No 11.8.4) Nos 2 8860.00 17720 Not updated in new SR
b) 2 Core , 6 Sq. mm, 1.1KV class armoured Al. Cable including PVC pipes for Yard Lighting complete. ,Material Page No: 4 of 28, Sl No.1,item no.1.12.2,Material Rate Rs.120.32 Mtrs 100 155 15471 Not updated in new SR
c) 32 Amps, DP Switch for Yard Lighting complete.(As per PWD SR 2023-24 Pg no.9 of 105,Sl.no.3.6,item no.3.6.9)Supplying and fixing. Rs-326 Nos. 2 326.00 652 Not updated in new SR
d) MCB 6-32 A DP (Supplying & fixing miniature circuit breakers on existing MCB distribution boards using necessary fixing materials and 'C' Type curve, indicator ON/OFF, energy cross-3 with Short circuit breaking capacity of 10K and complete wiring as required confirming to IEC 60898 ) (As per PWD SR 2023-24 Pg no.17 of 105,Sl.no.5.18,item no.518.4). Rs-739.00 Nos. 2 739.00 1478 Not updated in new SR
A.21 Station Service Equipments: 0
a) Single line diagram Photo sheet paper (Size 20x20 inch) (As per present market rate) Nos 2 2000.00 4000 Not updated in new SR
b) Supplying and installation of Rubber mat 1mtr x 1mtr -1Omm thick.complete including cost of materials, labour, usage charges of machinery complete as per specifications. (As per PWD SR 2023-24, Page No.93 of 105 Sl.No.15, Item No,15.117, Rs 1900/-) Nos 6 1900.00 11400 Not updated in new SR
Total Material cost 10222917.55
HUBLI ELECTRICITY SUPPLY COMPANY LIMITED
Estimate for Providing additional 3rd 5 MVA, 33/11KV power transformer at 33/11KV sub-station Khanapur in Khanapur Taluk, Belagavi District in 33KV S&L Division, Belagavi on PTK basis (5 MVA Power Transformer will be supplied by departmentally)
PART-B (Electricals Erection Works)
Sl. No. Particulars Unit Qty Rate Amout in Rs.
B.1 a) Power Transformers: Moving the Transformer to the plinth. (15 MT for 20 mtrs) on ramp.15*20=300 Ton Mtrs (As per KPTCL SR-2023-24 Page No-116, Sl.No-9, Item No-(a)) Rs-80/- per MT/ mtr 300 80.00 24000
b) Assembly of Transformer parts like bushings, radiators, filling oil into Transformer etc., for the total weight of the Transformer. (As per KPTCL SR-2023-24 Page No-116, Sl.No-9, Item No-(b)) 1134.00 MT 15 1134.00 17010
c) Filtration of oil using filter set of the contractor, to bring the insulation value to I.E. Specifications.(As per KPTCL SR-2023-24 Page No-116, Sl.No-9, Item No-(d)) Rs-7.00 ltrs 3500 7.00 24500
d) 5 MVA to 6.3/8 MVA Tr Wiring: Identification of wires,Wiring of Transformer marshalling box, bucholtz relay, OLTC upto control panel Ferruling crimping and termination of wires. Wiring of Protective Devices, OLTC, RTCC , fixing Thermometer, etc.,including assisting in Testing & Commissioning: (As per KPTCL SR-2023-24 Labour,Page No-116, Sl.No-9, Item No-(f&i)) 6708 per transfor mer 1 6708.00 6708
e) Fabrication of Transformer railing & embedding in Transformer plinth. (As per KPTCL SR-2023-24 Labour, Page No-116, Sl.No-10,Rs-1626 Set 1 1626.00 1626
B.2 a) 33KV SF-6/ VCB Breakers: Breaker Erection, assembly, alignment & wiring of breakers with its connected equipments including movement from the point of unloading to the point of erection. (As per KPTCL SR-2023-24 Labour,Page No-117, Sl.No-13, Item No-(a) Rs-5934 Per Set 1 5934.00 5934
b) Assisting in Testing & Commissioning: (As per KPTCL SR-2023-24 Labour, Page No-117, Sl.No-13, Item No-(b) Rs-1938.00 Set 1 1938.00 1938
c) Wiring : Identification, Ferruling crimping and termination of wires in Breaker & Wiring up to control panel/Relay panels. (As per KPTCL SR-2023-24 Labour,Page No-117, Sl.No-13, Item No-(c) Rs-8487 Set 1 8487.00 8487
B.3 a) Control Panels : Erection of control panel, auxilary panel, carrier cabinet etc., alignment and fixing properly to foundation base including movement from the point of unloading to the point of erection.(As per KPTCL SR-2023-24 Labour,Page No-120, Sl.No-23, Item No-(a) Rs-4191 No 1 4191.00 4191
b) Wiring & Assisting in Testing & Commissioning: (As per KPTCL SR-2023-24 Labour,Page No-120, Sl.No-23, Item No-(b) Rs-7612.00 No 1 7612.00 7612
B.4 a) Erection of CTs and wiring including movement from the point of unloading to the point of erection. (As per KPTCL CSR 23-24, Labour, Page No: 118, Sl No.: 14 a) Rs-2199 Set (3 Nos) 1 2199.00 2199
b) Assisting in Testing & Commissioning: (As per KPTCL CSR 23-24, Labour, Page No: 118, Sl No.: 14 (b) Rs-768.00 Set (3 Nos) 1 768.00 768
B.5 a) Erection of NCTs including movement from the point of unloading to the point of erection with grounding connections (As perKPTCL CSR 2023-24, Labour, Page No: 118, Sl No.:15(a) Rs-733.00 Set 1 733.00 733
b) Assisting in Testing & Commissioning:(As per KPTCL CSR 2023-24, Labour, Page No: 118, Sl No.:15(c) Rs-99.00 Set 1 99.00 99
Erection of 33KV Potential Transformers 0
a) 33 KV, Potential transformer with ratio of 33kV Voltage Transformer 33kV √3 110√3- 110√3 (As per KPTCL SR- 2023-24 page No- 33 SL.No-07, Item No-7.4 ,HSN Code-8504, RS-45980/-) Nos 3 1979.10 5937 need to check the rates
B.6 a) Erection of Lightning arrestors and wiring including movement from the point of unloading to the point of erection (33 KV) (As per KPTCL CSR 23-24, Labour, page No119, Sl.No:18 )Rs.333/- Set 1 333.00 333
b) 9 KV, 5 KA class (Station type) (11kv) (As per ESCOMS SR 23-24, Labour, page No: 48 of 81, Sl.No:101, item no: 13.06) Rs-119.00 Set (3 Nos) 4 119.00 476
B.7 1) 33 KV Isolators : 0
a) Erection of Isolators (33 KV) Assembly, Errection alignment and wiring including movement from the point of unloading to the point of erection.(Upright type),( As per KPTCL CSR 23-24, Labour, Pg No: 119, Sl No.: 17 A(i) ,) Rs-1319.00 ) Set 2 1319.00 2638
b) Assisting in Testing and Commissioning ( KPTCL CSR 23-24, Labour, Pg No:119 , Sl No.: 17 E(i) ,) Rs-191/- Nos 2 191.00 382
2) 11KV Isolators: 0
a) Erection of 400A, special roster switch with H-frame & clamps to be mounted on DP (As per ESCOM SR- 23-24, Labour, Pg No:48 of 81 Sl No.: 98 ,itme no:13.03 ) Rs-1214 Nos 3 1298.40 3895
b) Erection of 11 kV, 400 Amps Double Break GOS (As per ESCOM SR- 23-24, Labour, Pg No:48 of 81 Sl No.: 98 ,itme no:13.03 ) Rs-1214/- Nos 1 1298.40 1298
B.8 a) 11 KV Switchgear : Erection, alignment and fixing to the foundation, indoor/outdoor 11KV switchgear Panel/unit including movement from the point of unloading to the point of erection. (1Bank+3 feeders+ 1 CB) (As per KPTCL SR 23-24, Labour, page No: 121, Sl.No:24 a (i) ) Rs-2081/-) Per Panel 5 2081.00 10405
b) Wiring and assisting in Testing & Commissioning: (As per KPTCL SR 23-24, Labour, page No: 122, Sl.No:24 b (i) ) Rs-941.00 Per Panel. 5 941.00 4705
B.9 a) 33KV Station structures: 0
Erection, alignment & assembly of fabricated steel lattice structure, pedestal structures & Mounting structures, for G.O.S., CTs, PTs LAs etc. (As per KPTCL SR 2023-24, Labour, Page No: 116, Sl No.: 8, (b) , Rs-5723.00) MT 2.66 5723.00 15200
B.10 a) Bus Formation 0
Formation of cross bus in each individual bay using Lynx/Coyote -Single/Double conductor with fixing of insulators, spacers, levelling the strung conductors to the required height above the equipment including providing jumps to inter-connect different segments of the main bus. ( As per KPTCL SR 23-24, Labour, Page No: 122, Sl No.: 25) Rs-7364.00 (Incuding 33KV Bus Formation) Per bay 1 7364.00 7364
B.11 a) 11KV ODS: 0
1) Digging of Pit 1.8 Mtr depth (Hard Soil) for errection of 9Mtr 11KV ODS pole- ESCOMs Labour SR-23-24 Page No- 43 of 81 Sl.No-2 Item No-1.1.2 RS- 11322) Errection of 9 Mtr. Long, 145kg RCC pole for 11KV ODS.As per ESCOMs Labour SR-23-24 Page No- 44 of 81 Sl.No-29 Item No-2.01 RS-922 Total Rs-2054 Nos 0 2054.00 0
b) 1) Digging of Pit 1.6 Mtr depth (Hard Soil) for erection of 7.5/8 Mtr Long Steel/RCC pole for LED Light ( As per ESCOMs Labour SR-23-24 Page No- 43 of 81 Sl.No-6 Item No-1.2.2 RS-1006 ) 2) Errection of RCC Pole - 8 Mtr Long, 115 Kg WL. (As per ESCOMs Labour SR-23-24 Page No- 44 of 81 Sl.No-29 Item No-2.01 RS-922 Total Rs-1928 Nos 2 1928.00 3856
c) Supplying and fixing angle iron frame work fabricated out of M.S. angle iron.. and M.S. Flat......with bolts, washers etc., and painted with 2 coats of red oxide and then two coats of approved paint for 11 KV ODS mounting structure using 75 x 150 x 75 x 6 mm C channel MS, each 6.0 mtr long , (As per PWD Electrical Page 20, Sl.No- 5.41.5 Rs-Per Mtr- 926.00, 4NosX6Mtr=24 Mtr) Mtr 24 2400 57600 112
B.12 a) Erection of station structure 3T1 Tower and 3B1 Beams Asper KPTCL Labour SR-2023 -24 Page No-113, Sl.no-1, item No 1.1© Rs-5723.00,(3T1 Tower T-0.730+3B1-0.194=0.924) t 0.696 2266 1577
B.13 b) Erection of 2 Pole DP Structure using RCC/PSCC Pole 9 to 10 Mtr long As Per Escoms SR-2023-24 Page No-44 of 81, Sl.No-34, Item No-2.06 Rs-4134 Per Structure 4 4418 17674 1403 only dp 1341
B.14 Laying of Power cables from Power Transformer to 11 KV switchgears and from switchgears to DP of 11 kV cables in existing trench/G.I. pipe/stoneware pipe/RCC hume pipe using wooden/aluminium rollers as directed by KPTCL staff. 4418 0
a) Cables of sizes 3C x 185 to 3C x 240 Sq mm (As per ESCOM's SR 2023-24, Labour, page No:52 of 81,Sl.No.171,Item No.21.02) Km 0.270 64153.00 17321
b) Cables of sizes 3C x 300 to 3C x 400 Sq mm (As per ESCOM's SR 2023-24, Labour, page No:52 of 81,Sl.No.172,Item No.21.03) Km 0.160 66040.00 10566
c) Making and Fixing of Pothead of 3C X 185 to 3C X 240 Sq mm (Indoor and Outdoor) page No. 52 of 81, Sl.No. 183, item No. 22.05 Set 4 2658.00 10632
d) Making and Fixing of Pothead of 3C X 300 to 3C X400 Sq mm (Indoor and Outdoor) page No. 52 of 81, Sl.No. 184, item No. 22.06 Set 10 2658.00 26580
B.15 Laying of copper control cables from equipments to control panels. 0
a) 19 Core 2.5 Sq.mm (As per KPTCL SR 23-24, Labour, page No: 120, Sl.No:22, (b) Rs- Per Mtr-15.00 Rmtr 200 15.00 3000
b) 4 Core 6 Sq.mm (As per KPTCL SR 23-24, Labour, page No: 120, Sl.No:22, (b) Rs- Per Mtr-15.00 Rmtr 250 15.00 3750
c) 4 core 2.5 Sq.mm (As per KPTCL SR 23-24, Labour, page No: 120, Sl.No:22, (b) Rs- Per Mtr-15.00 Rmtr 150 15.00 2250
d) 2 core 2.5 Sq.mm (As per KPTCL SR 23-24, Labour, page No: 120, Sl.No:22, (b) Rs- Per Mtr-15.00 Rmtr 250 15.00 3750
e) 10 core 2.5 Sq.mm (As per KPTCL SR 23-24, Labour, page No: 120, Sl.No:22, (b) Rs- Per Mtr-15.00 Rmtr 75 15.00 1125
A.16 Miscellaneous items 0 0
a) Fixing Caution/Danger Boards (As per KPTCL SR- 2025-26, Page No- 34 of 50, SL.No-2, 35 of 50, SL.No-30) Nos 5 85 426
b) Fixing Phase Plates As per KPTCL Labour SR 23-24,Pg No.113 ,Sl No.3(c) Rs-238 Set (3Nos) 4 238.00 952 71.5986
c) Fixing Name Plates for equipment/Earth Pit ,KPTCL SR 21-22, page No-09 of 27 Sl No-7 Item No:- (d), Labour Charge Rs.54 Nos 20 54.00 1080
d) Name plate for feeders and banks KPTCL SR 21-22 , Labour Charge No-09 of 27 Sl No-7, Item No:- (d),Rate Rs.54 Nos 7 54.00 378
A-17 a) Fixing halogen/metal halide /SVL/IL/LED floodlight fitting over existing pole / wall ceiling including clamps, bolts, nuts and wiring using suitable capacity wires. (As per PWD Ele SR 2-2023-24 Page No-56 Of 105,Item No:13.5) Each 2 162 324
Total Lobour ost 321280.36
HUBLI ELECTRICITY SUPPLY COMPANY LIMITED
Estimate for Providing additional 3rd 5 MVA, 33/11KV power transformer at 33/11KV sub-station Khanapur in Khanapur Taluk, Belagavi District in 33KV S&L Division, Belagavi on PTK basis (5 MVA Power Transformer will be supplied by departmentally)
PART-C-(CIVIL WORKS)
Sl No. Item Description Unit Qty Unit Price (Rs) Total Price (Rs)
C SCHEDULE OF ITEMS FOR ASSOCIATED CIVIL WORKS AND STRUCTURES:
C.1 Cable Trenches including road crossing :
a) RCC Cable duct for laying of control cables with cable tray.(Duct size:1 mtr WidthX 1 mtr DepthX 120 Mtr Length including 33 KV and 11 KV side) Mtrs 120.00 7665.00 919800.00 Road crossing 40
b) b) Providing and Laying RCC Hume pipe sub ducts using NP 2 class 300mm dia Hume pipe including cost of Excavation, laying charges and back filling wherever required as per technical specification and enclosed drawings including cost of all materials, labour, etc., complete. Rmtrs 0.00 853.00 0.00 ?
c) Cable duct covers RCC made with suitable size to cover the duct length of 35 Mtrs ( of Size 1m x 1m x 0.15m) Nos 120.00 1694.00 203280.00
C.2 SITE SURFACING: Jelly Spreading (20-25 mm) : Supplying and providing jelly in the station yard of uniform thickness of 100 mm including the cost of materials, labour charges, required tools and plants etc., complete. Work shall be carried out as per the instructions of Engineer- in-charge of works as per the standard procedure(As per KPTCL SR 2023-24,Page No.158,Sl.No.1) Cmt 25.65 1773.00 45477.45
C.3 Foundations: Engineering, supply of all labour,material and construction of RCC footing including the cost of excavation, cement concreting, reinforcement, backfilling, waterproof cement painting, for all works, grouting underpinning etc ,for the following works 0.00
a) 9 mtrs long RCC poles for ODS (As per ESCOM's SR 2023-24,Base concreting Rs.312+Pole concreting Rs.3434,Coping Rs.312) No's 0 4058.00 0.00
b) 8 mtrs long RCC poles for station Yard lights (As per ESCOM's SR 2023-24,Base concreting Rs.312+Pole concreting Rs.1498+Coping Rs.312) No's 2 2112.00 4224.00
c) 33KV CT support structure (0.95 mtrX0.55 mtr X 1mtr Depth) Nos 3 5650.00 16950.00
c) 33KV PT support structure (0.95 mtrX0.55 mtr X 1mtr Depth) Nos 3 5650.00 16950.00
d) 33KV Surge arrestor support structure (0.95 mtrX0.55 mtr X 1mtr Depth) Nos 3 5650.00 16950.00
e) PI support structure (0.95 mtrX0.55 mtr X 1mtr Depth) Nos 0 5650.00 0.00
f) 11 KV NCT mounting structure (1.1 mtrX0.55 mtr X 1mtr Depth) Nos 1 5941.00 5941.00
g) 33KV Isolators support structure(0.95 mtr X 0.45 mtr X 1mtr) Set 1 5674.00 5674.00
h) 3T Tower Foundation (1.5 m X .9 m x 2.5 m ) Nos 2 35950.00 71900.00
C.4 Transformer foundation and associated rail track: 0.00
Design, Engineering,supply of material / equuipment, labour and construction of Tr. Foundation by providing all associated works, rail tracks jacking pads, anchor block RCC, PCC misscellanellaneous structural steel including MS, grouting gravel filling pylon support system and other items not mentioned herein, but required for the completion of the work as per the technical spcfication and drawings 0.00
a) 5 MVA, 33/11 KV Power Transformer (3.0 mtr Width X 3.0 mtr Length X 3.0 mtr Depth) Nos 1 307207.00 307207.00
C.5 a) SF-6 Breaker foundation, 33KV SF-6 Breaker foundation as per approved design and drawing including supply of material and labour Nos 1 26247.00 26247.00
C.6 Providing PVC ringtite pipes conforming to IS 4985:2000 with latest amendments and conveying to worksite, rolling and lowering into trenches, laying true to line and level and perfect linking at joints, testing and commissioning, including loading unloading at both destinations and cuts of pipes wherever necessary including jointing of PVC pipes and specials (excluding cost of specials) with jointing of approved type, with all labour with all lead & lift including encasing the pipe alround to a depth of not less than 15 cms. with soft gravel or selected earth available from the excavation etc. complete and giving necessary hydraulic test to the required pressure as per ISS (Contractor will make his own arrangements for procuring water for testing) etc. complete For: 0.00
a) PVC pipes 63mm dia., 6 kg/sqcm & class 3 Mtrs 50 161.00 8050.00
b) PVC pipes 75mm dia., 6 kg/sqcm & class 3 Mtrs 30 220.00 6600.00
C.7 a) Earth mat formation : 0.00
Excavation, formation, refilling. (63L X 0.9X1Mtr W= 56.7 CMT) CMT 56.7 202.00 11453.40
C.8 a) Design, Engineering,supply of material / equuipment, labour and construction of 11 KV Indoor MCVCB Plat form foundation by providing all associated works as per standard and approved specification. No's 1 435507.00 435507.00
b) Design, Engineering,supply of material / equuipment, labour and construction of 11 KV out door Capacitor Bank cells foundation by providing all associated works as per standard and approved specification. Set 1 26620.00 26620.00
Total cost 2128830.85
HUBLI ELECTRICITY SUPPLY COMPANY LIMITED
Estimate for Providing additional 3rd 5 MVA, 33/11KV power transformer at 33/11KV sub-station Khanapur in Belagavi Taluk, Belagavi District in 33KV S&L Division, Belagavi on PTK Basis (5 MVA Power Transformer will be supplied by departmentally)
PART-C-(CIVIL WORKS)
Sl No. Item Description Unit Qty Unit Price (Rs) Total Price (Rs)
C SCHEDULE OF ITEMS FOR ASSOCIATED CIVIL WORKS AND STRUCTURES:
C.1 Cable Trenches including road crossing :
a) RCC Cable duct for laying of control cables with cable tray.(Duct size:1 mtr WidthX 1 mtr DepthX 120 Mtr Length including 33 KV and 11 KV side) Mtrs 120.00 7770.00 932400.00 Road crossing 40
b) b) Providing and Laying RCC Hume pipe sub ducts using NP 2 class 300mm dia Hume pipe including cost of Excavation, laying charges and back filling wherever required as per technical specification and enclosed drawings including cost of all materials, labour, etc., complete. Rmtrs 0.00 853.00 0.00 ?
c) Cable duct covers RCC made with suitable size to cover the duct length of 35 Mtrs ( of Size 1m x 1m x 0.15m) Nos 120.00 1727.00 207240.00
C.2 SITE SURFACING: Jelly Spreading (20-25 mm) : Supplying and providing jelly in the station yard of uniform thickness of 100 mm including the cost of materials, labour charges, required tools and plants etc., complete. Work shall be carried out as per the instructions of Engineer- in-charge of works as per the standard procedure(As per KPTCL SR 2023-24,Page No.158,Sl.No.1) Cmt 25.65 1773.00 45477.45
C.3 Foundations: Engineering, supply of all labour,material and construction of RCC footing including the cost of excavation, cement concreting, reinforcement, backfilling, waterproof cement painting, for all works, grouting underpinning etc ,for the following works 0.00
a) 9 mtrs long RCC poles for ODS (As per ESCOM's SR 2023-24,Base concreting Rs.312+Pole concreting Rs.3434,Coping Rs.312) No's 0 4058.00 0.00
b) 8 mtrs long RCC poles for station Yard lights (As per ESCOM's SR 2023-24,Base concreting Rs.312+Pole concreting Rs.1498+Coping Rs.312) No's 2 2112.00 4224.00
c) 33KV CT support structure (0.95 mtrX0.55 mtr X 1mtr Depth) Nos 3 5695.00 17085.00
c) 33KV PT support structure (0.95 mtrX0.55 mtr X 1mtr Depth) Nos 3 5695.00 17085.00
d) 33KV Surge arrestor support structure (0.95 mtrX0.55 mtr X 1mtr Depth) Nos 3 5695.00 17085.00
e) PI support structure (0.95 mtrX0.55 mtr X 1mtr Depth) Nos 0 5695.00 0.00
f) 11 KV NCT mounting structure (1.1 mtrX0.55 mtr X 1mtr Depth) Nos 1 5927.00 5927.00
g) 33KV Isolators support structure(0.95 mtr X 0.45 mtr X 1mtr) Set 1 5695.00 5695.00
h) 3T Tower Foundation (1.5 m X .9 m x 2.5 m ) Nos 2 7033.00 14066.00
C.4 Transformer foundation and associated rail track: 0.00
Design, Engineering,supply of material / equuipment, labour and construction of Tr. Foundation by providing all associated works, rail tracks jacking pads, anchor block RCC, PCC misscellanellaneous structural steel including MS, grouting gravel filling pylon support system and other items not mentioned herein, but required for the completion of the work as per the technical spcfication and drawings 0.00
a) 5 MVA, 33/11 KV Power Transformer (3.0 mtr Width X 3.0 mtr Length X 3.0 mtr Depth) Nos 1 169749.00 169749.00
C.5 a) SF-6 Breaker foundation, 33KV SF-6 Breaker foundation as per approved design and drawing including supply of material and labour Nos 1 26800.00 26800.00
C.6 Providing PVC ringtite pipes conforming to IS 4985:2000 with latest amendments and conveying to worksite, rolling and lowering into trenches, laying true to line and level and perfect linking at joints, testing and commissioning, including loading unloading at both destinations and cuts of pipes wherever necessary including jointing of PVC pipes and specials (excluding cost of specials) with jointing of approved type, with all labour with all lead & lift including encasing the pipe alround to a depth of not less than 15 cms. with soft gravel or selected earth available from the excavation etc. complete and giving necessary hydraulic test to the required pressure as per ISS (Contractor will make his own arrangements for procuring water for testing) etc. complete For: 0.00
a) PVC pipes 63mm dia., 6 kg/sqcm & class 3 Mtrs 50 161.00 8050.00
b) PVC pipes 75mm dia., 6 kg/sqcm & class 3 Mtrs 30 220.00 6600.00
C.7 a) Earth mat formation : 0.00
Excavation, formation, refilling. (63L X 0.9X1Mtr W= 56.7 CMT) CMT 56.7 202.00 11453.40
C.8 a) Design, Engineering,supply of material / equuipment, labour and construction of 11 KV Indoor MCVCB Plat form foundation by providing all associated works as per standard and approved specification. No's 1 693706.46 693706.46
b) Design, Engineering,supply of material / equuipment, labour and construction of 11 KV out door Capacitor Bank cells foundation by providing all associated works as per standard and approved specification. Set 1 23573.00 23573.00
Total cost 2206216.31
HUBLI ELECTRICITY SUPPLY COMPANY LIMITED
Name of the work: Construction of MCVCB Platform at 33/11 KV S/S Khanapur
Sl.No Description Unit Qty Rate Amount
1.000 Earth work excavation by manual means for drains,canals and similar works in all kinds of soils, as per drawing and technical specifications, including setting out, shoring, strutting, barricading, caution lights, removal of stumps and other deleterious matter, excavated surface leveled and sides neatly dressed disposing off the excavated stuff or sorting & stacking the selected stuff for reuse in a radius of 50 m and lift upto 1.5 m including cost of labour, tools & other appurtenaces required to complete the work In all kinds of soils Depth upto 1.5 m (SR 2023-24,I.no 1.4.1, volume-I). Cum 42.00 242.00 10164.00 234.951
Along - Breadth 2 3.57 1.20 1.50 12.85
2.000 Providing crushed stone aggregate, depositing on a prepared surface by hauling vehicles, spreading and mixing with a motor grader, watering and compacting with a vibratory roller to clause 407 to form a layer of sub-base/Base. By Mix in Place Method. ii) For 37.5 mm maximum size (Table 400-14)(SR 2023-24,I.no 4.23.A.ii, volume-III). Cum 8.50 2419.00 20561.50 2348.544
Along - Length 2 7.97 1.20 0.30 5.74
Along - Breadth 2 3.57 1.20 0.30 2.57
3.000 Providing and laying in position plain cement concrete Mix 1:4:8(M5) Using 40 mm and down size graded crushed coarse aggregates for levelling course for all works in foundation. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed, laid in layers not exceeding 150 mm thickness, well compacted using plate vibrators, including all lead & lifts, cost of all materials of quality, labour, Usage charges of machineries, curing, and all the other appurtenances required to complete the work as per technical specifications.(The cost of steel reinforcement & formwork shall be paid separately) (SR 2023-24,I.no 2.1.2, volume-I) Cum 9.50 5664.00 53808.00 5499.029
Along - Length 2 7.97 1.20 0.15 2.87
Along - Breadth 2 3.57 1.20 0.15 1.29
4.000 Construction of Embankment by excavating the available approved Gravel/Murrum deposited at a place or borrow pits during or prior excavation with all lifts and lead, transportation to site, spreading, grading to required slope and compacting to meet the requirement complete as per specifications, including cost of labour,rolling,water,all materials,usage& all other appurtenaces required to complete the work.(SR 2023-24,I.no 1.8, volume-I). Cum 55.00 474.00 26070.00 460.194
Along - Length 2 7.97 1.20 0.15 2.87
Along - Breadth 2 3.57 1.20 0.15 1.29
backfilling 1 7.54 5.54 1.20 50.13
5.000 Providing and laying in position Reinforced cement concrete for all Foundation works. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticizers laid in finished layers, well compacted using needle vibrators, including all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing and all the other appurtenances required to complete the work as per technical specifications. 3% formwork is included (The cost of steel reinforcement to be paid separately)M20 Design Mix Using 20 mm nominal size graded crushed coarse aggregates(SR 2023-24, I.No - 2.2.1, Volume 1) Cum 5.50 6475.61 35615.86 #REF!
raft along length 2.00 7.97 1.00 0.23 3.67
raft along breath 2.00 3.77 1.00 0.23 1.73
6.000 Providing and laying in position Reinforced cement concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/ trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing and all other appurtenances required to complete the work as per technical specifications. 5% formwork is included (The cost of steel reinforcement, dowel bars to be paid separately) M20 Design Mix Using 20 mm nominal size graded crushed coarse aggregates (KPWD SR 2023-24,Vol-1, It.No.2.5.1) Cum 15.00 7293.00 109395.00
retaining wall -L 2.00 7.00 0.23 1.20 3.86
Retaining wall - B 2.00 4.54 0.23 1.20 2.51
7.000 Supplying, fitting and placing TMT FE 550 /550D Steel Reinforcement including cost of all materials, machinery, labour, cleaning, straightening, cutting, bending, hooking, laping/welding joints, tying with binding wire / soft annealed steel wire and other ancilary operations complete as per drawing and technical specification.-All other type of structures (SR 2023-24, I.no 2.11(h) volume-I) T 1.10 79011.00 86912.10 76709.709
8.000 Providing 12 mm cement plaster with cement mortar 1:6 (1 cement:6 fine sand) including rounding off corners wherever required smooth rendering, providing and removing scaffolding, including cost of materials, labour, curing complete as per specifications and as per directions of Engineer-in-charge.(SR-2023-24, I no - 8.1.2, Volume 2) Sqm 55.00 241.00 13255.00
9.000 Providing and fixing Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required. In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works including cost of materials, labour, usage charges of machinery complete as per specifications and as per directions of the Engineer-in-Charge. (SR 2023-24, I.No. 11.25.2, Volume -2) Kg 2000.00 136.00 272000.00 111.240
10.000 Providing & fixing corrugated G.S. sheet roofing including vertical/curved surface fixed with polymer coated J or L hooks, bolts and nuts 8 mm diameter with bitumen and G.I. limpet washers or with G.I. limpet washers filled with white lead, including a coat of approved steel primer and two coats of approved paint on overlapping of sheets complete as per design drawings (up to any pitch in horizontal/ vertical or curved surfaces), excluding the cost of purlins, rafters and trusses and including cutting to size and shape wherever required as per the direction of Engineer in charge. Sqm 75.00 879.00 65925.00 3.810
Subtotal B 693706.46
HUBLI ELECTRICITY SUPPLY COMPANY LIMITED.
HTVR & Annual energy loss calculation of existing 33 KV Khanapur feeder eminating from 110\33\11 KV MUSS Dukkarwadi . before providing 3rd 5MVA Power transformer at 33/11 KV MUSS Khanapur.
Node No KVA at node CUM KVA Distance KM KVA-KM Conductor constant ohm/kms KVA-KM Conductor constant Hulkund 33 KV feeder monthwise consumption
1. Total connected load P= 10000 4 Apr-24 2854680 2854680
2. Total length in Km. L= 5.15 5 May-24 2211840 2211840
3. Sum of moments= KVA*KM= 51500 6 Jun-24 1470480 1470480
5. Annual energy sent out of the feeder 24868380 8 Aug-24 1402140 1402140
7. Diversity factor= Total connected load in KVA/1.73*33*Peak load 1.06 10 Oct-24 1379280 1379280
8. Load factor = Annual energy sent out on the feeder/ Energy computed on the basis of the peak load= Annual energy sent out/ 1.73*33*0.8*8760*peak load 0.37 11 Nov-24 1214600 1214600
9. Loss load factor(LLF) =0.30*LF+.70*LF*LF) 0.21
10.Load density factor= 1
11. Annual energy losses= 0.105*P*P*L*R*LLF/2*LDF*DF*DF 3250621.19
Resistance of the conductor in Ohms per KM= 0.636
12. Add 10% spur line loss= Annual energy loss*0.1= 0.00
13. Total loss = 3250621.19
14. HTVR calculation
Asst. Executive Engineer(El), Junior Engineer(El)
33 KV S & L Sub-Division, HESCOM, Belagavi 33/11 KV MUSS Khanapur
Executive Engineer(El),
33 KV S & L Division, HESCOM, Belagavi
HUBLI ELECTRICITY SUPPLY COMPANY LIMITED.
HTVR & Annual energy loss calculation of existing 33 KV Khanapur feeder eminating from 110\33\11 KV MUSS Dukkarwadi after providing 3rd 5 MVA Power transformer at 33/11 KV MUSS Khanapur
Node No KVA at node CUM KVA Distance KM KVA-KM Conductor constant ohm/kms KVA-KM Conductor constant
1. Total connected load P= 15000
2. Total length in Km. L= 5.15
3. Sum of moments= KVA*KM= 77250.00
4. LDF= P*L/ KVA*KM 1.00
5. Annual energy sent out of the feeder 31085475
6. Peak load= 148.00 148
7. Diversity factor= Total connected load in KVA/1.73*33*Peak load 1.78
8. Load factor = Annual energy sent out on the feeder/ Energy computed on the basis of the peak load= Annual energy sent out/ 1.73*11*0.8*8760*peak load 0.52
9. Loss load factor(LLF) =0.30*LF+.70*LF*LF) 0.35 13.9
10.Load density factor= 1
11. Annual energy losses= 0.105*P*P*L*R*LLF/2*LDF*DF*DF 23064.69
Resistance of the conductor in Ohms per KM= 0.00341
12. Add 10% spur line loss= Annual energy loss*0.1= 0.00
13. Total loss = 23064.69
14. HTVR calculation
Total Energy savings 3227556.50
Asst. Executive Engineer(El), Junior Engineer(El)
33 KV S & L Sub-Division, HESCOM, Belagavi 33/11 KV MUSS Khanapur
Executive Engineer(El),
33 KV S & L Division, HESCOM, Belagavi
HUBLI ELECTRICITY SUPPLY COMPANY LIMITED
Estimate for providing additional 3rd 5MVA, 33/11 KV Power Transformer at existing 2X5 MVA,33/11 KV Substation Khanapur in O&M Rural Division, HESCOM, Belagavi Under Partial Turnkey basis.
1 Estimated cost Rs. #REF!
2 Annual O&M Charges/expenses @ 1% of item no.1 (Estimated cost) Rs. #REF!
3 Present value of annual O&M expenses over project period of 30 years (item no.2X8.055) Rs. #REF!
4 Total investment + Present value of O&M (item no.1 + item no.3) Rs. #REF!
5 Annual energy savings Units 3227556.50
6 Cost of energy per unit Rs. 8.31
7 Proposed additional of the capacity MVA 5.00
8 Cost of annual energy savings (Item no. 5 X Item no. 6) Rs. 26820994.50
9 Benefit cost ratio = Item no.8 X0.85 / Item no. 4 #REF!
Asst. Executive Engineer (Ele) S&L Sub-Division,HESCOM, Belagavi Junior Engineer (Ele), 33/11KV MUSS, Khanapur
Sl.No Description of Item No L B H Qty
1 RCC Cable Duct
C4 a 5MVA Transformer
Refilling 0.30 204 61.2
C5 a SF6 Breaker
C3 CT Support/PI/LA
Structural Steel 1 2.70 3.50 9.45 106 1001.7
Chain Link Fencing 1 1.00 1.80 1.80 841 1513.8
C8 Capacitor Bank Foundation
33 KV SIDE 11 KV SIDE CI PIPE DETAILS 33 KV SIDE G.I.FLAT 33 KV SIDE Equipment Name Boards PVC PIPES 33 KV SIDE
LYNX 150 600 TFR 2 TFR 15 TFR 1 10
33 KV BKR 1 33 KV BKR 5 33 KV BKR 1 5
CT 3 CT 15 CT 3 15
PT 3 PT 0 PT 3 15
LA 3 LA 15 LA 3 0
STRUCTURE 2 STRUCTURE 5 STRUCTURE 0 0
NCT 2 NCT 15 NCT 1 10
C&R PANEL 1 C&R PANEL 15 C&R PANEL 1 0
GOS 1 GOS 12 GOS 1 0
FENCING 0 FENCING 0 EARTHINGS 21 0
TOTAL: 18 TOTAL: 97 TOTAL: 35 55
CI PIPE DETAILS 11 KV SIDE G.I.FLAT 11 KV SIDE G.I.FLAT 11 KV SIDE PVC PIPES 11 KV SIDE 23
11 KV BKR 2 11 KV BKR 25 11 KV BKR 5 25 41
CT 0 CT 0 CT 1 15 64
GOS 10 GOS 100 GOS 3 0 10
ANNUNCIATOR 0 ANNUNCIATOR 1 ANNUNCIATOR 1 0
FENCING 0 FENCING 0 EARTHINGS 24 0
TOTAL: 12 TOTAL: 126 TOTAL: 34 40
GRAND TOTAL: 30 GRAND TOTAL: 223 GRAND TOTAL: 69 95
Jelly spreading Mtrs Earth mat Dimensions MS Flat
Length 41 Length 13 3 Lines 39 81
Width 18 Width 8 3 Lines 24 57
Thickness 0.1 Total cubic 104 63 138
HUBLI ELECTRICITY SUPPLY COMPANY LIMITED
SINGLE LINE DIAGRAM FOR 33/11KV MUSS Khanapur
FROM 110KV MUSS Dukkarwadi(Khanapur) Incomer GOS
Prop GOS GOS GOS
Prop 5MVA 5MVA TRF-II 5MVA TRF-I
Prop 11KV Bank-III 11KV Bank-II 11KV Bank-I
GOS GOS GOS GOS GOS GOS
11KV Breaker 11KV Breaker 11KV Breaker 11KV Breaker 11KV Breaker 11KV Breaker 11KV Breaker 11KV Breaker 11KV Breaker
GOS GOS GOS GOS GOS GOS GOS GOS GOS
F-1 KAHANPUR F-2 NANDGAD EIP F-3 OTHOLLI CNJY F-4 LONDA CNJY F-5 OLD JAMBOTI CNJY F-6 ASOGA CNJY
ProposedFeeder Proposed feeder Proposed feeder
Asst. Executive Engineer(El), Junior Engineer(El)
33 KV S & L Sub-Division, HESCOM, Belagavi 33/11 KV MUSS Khanapur
Executive Engineer(El), Superintending Engineer (El)
33 KV S&L Division, HESCOM, Belagavi O&M Circle, HESCOM, Belagavi
HUBLI ELECTRICITY SUPPLY COMPANY LIMITED
Name of the work: Construction of MCVCB Platform at 33/11 KV S/S Khanapur
Sl.No Description Unit Qty Rate Amount
1.000 Earth work excavation by manual means for drains,canals and similar works in all kinds of soils, as per drawing and technical specifications, including setting out, shoring, strutting, barricading, caution lights, removal of stumps and other deleterious matter, excavated surface leveled and sides neatly dressed disposing off the excavated stuff or sorting & stacking the selected stuff for reuse in a radius of 50 m and lift upto 1.5 m including cost of labour, tools & other appurtenaces required to complete the work In all kinds of soils Depth upto 1.5 m (SR 2023-24,I.no 1.4.1, volume-I). Cum 42.00 242.00 10164.00 234.951
Along - Breadth 2 3.57 1.20 1.50 12.85
2.000 Providing crushed stone aggregate, depositing on a prepared surface by hauling vehicles, spreading and mixing with a motor grader, watering and compacting with a vibratory roller to clause 407 to form a layer of sub-base/Base. By Mix in Place Method. ii) For 37.5 mm maximum size (Table 400-14)(SR 2023-24,I.no 4.23.A.ii, volume-III). Cum 8.50 2419.00 20561.50 2348.544
Along - Length 2 7.97 1.20 0.30 5.74
Along - Breadth 2 3.57 1.20 0.30 2.57
3.000 Providing and laying in position plain cement concrete Mix 1:4:8(M5) Using 40 mm and down size graded crushed coarse aggregates for levelling course for all works in foundation. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed, laid in layers not exceeding 150 mm thickness, well compacted using plate vibrators, including all lead & lifts, cost of all materials of quality, labour, Usage charges of machineries, curing, and all the other appurtenances required to complete the work as per technical specifications.(The cost of steel reinforcement & formwork shall be paid separately) (SR 2023-24,I.no 2.1.2, volume-I) Cum 9.50 5664.00 53808.00 5499.029
Along - Length 2 7.97 1.20 0.15 2.87
Along - Breadth 2 3.57 1.20 0.15 1.29
4.000 Construction of Embankment by excavating the available approved Gravel/Murrum deposited at a place or borrow pits during or prior excavation with all lifts and lead, transportation to site, spreading, grading to required slope and compacting to meet the requirement complete as per specifications, including cost of labour,rolling,water,all materials,usage& all other appurtenaces required to complete the work.(SR 2023-24,I.no 1.8, volume-I). Cum 55.00 474.00 26070.00 460.194
Along - Length 2 7.97 1.20 0.15 2.87
Along - Breadth 2 3.57 1.20 0.15 1.29
backfilling 1 7.54 5.54 1.20 50.13
5.000 Providing and laying in position Reinforced cement concrete for all Foundation works. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticizers laid in finished layers, well compacted using needle vibrators, including all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing and all the other appurtenances required to complete the work as per technical specifications. 3% formwork is included (The cost of steel reinforcement to be paid separately)M20 Design Mix Using 20 mm nominal size graded crushed coarse aggregates(SR 2023-24, I.No - 2.2.1, Volume 1) Cum 5.50 6475.61 35615.86 #REF!
raft along length 2.00 7.97 1.00 0.23 3.67
raft along breath 2.00 3.77 1.00 0.23 1.73
6.000 Providing and laying in position Reinforced cement concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/ trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing and all other appurtenances required to complete the work as per technical specifications. 5% formwork is included (The cost of steel reinforcement, dowel bars to be paid separately) M20 Design Mix Using 20 mm nominal size graded crushed coarse aggregates (KPWD SR 2023-24,Vol-1, It.No.2.5.1) Cum 15.00 7293.00 109395.00
retaining wall -L 2.00 7.00 0.23 1.20 3.86
Retaining wall - B 2.00 4.54 0.23 1.20 2.51
7.000 Supplying, fitting and placing TMT FE 550 /550D Steel Reinforcement including cost of all materials, machinery, labour, cleaning, straightening, cutting, bending, hooking, laping/welding joints, tying with binding wire / soft annealed steel wire and other ancilary operations complete as per drawing and technical specification.-All other type of structures (SR 2023-24, I.no 2.11(h) volume-I) T 1.10 79011.00 86912.10 76709.709
8.000 Providing 12 mm cement plaster with cement mortar 1:6 (1 cement:6 fine sand) including rounding off corners wherever required smooth rendering, providing and removing scaffolding, including cost of materials, labour, curing complete as per specifications and as per directions of Engineer-in-charge.(SR-2023-24, I no - 8.1.2, Volume 2) Sqm 55.00 241.00 13255.00
9.000 Providing and fixing Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required. In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works including cost of materials, labour, usage charges of machinery complete as per specifications and as per directions of the Engineer-in-Charge. (SR 2023-24, I.No. 11.25.2, Volume -2) Kg 2000.00 136.00 272000.00 111.240
10.000 Providing & fixing corrugated G.S. sheet roofing including vertical/curved surface fixed with polymer coated J or L hooks, bolts and nuts 8 mm diameter with bitumen and G.I. limpet washers or with G.I. limpet washers filled with white lead, including a coat of approved steel primer and two coats of approved paint on overlapping of sheets complete as per design drawings (up to any pitch in horizontal/ vertical or curved surfaces), excluding the cost of purlins, rafters and trusses and including cutting to size and shape wherever required as per the direction of Engineer in charge. Sqm 75.00 879.00 65925.00 3.810
Subtotal A 693706.46
HUBLI ELECTRIC SUPPLY COMPANY LIMITED
Block Diagram of 110 KV Dukkarwadi to 33KV Line Khanapur
110KV MUSS Dukkarwadi
S/C Line COYOTE 33KV MUSS KHANAPUR 2X5MVA 33/11KV
33KV MUSS LONDA
2X5MVA -33/11KV
JUNIOR Engineer (E) Assistant Executive Engineer (E) Executive Engineer (E)
33KV MUSS Khanapur 33KV S&L Nodal Sub division 33KV S&L Nodal Division
HESCOM Belagavi HESCOM Belagavi
HUBLI ELECTRICITY SUPPLY COMPANY LIMITED
Self-Declaration statement of Bidder/Contractor for works Done…as on date of Bid submission.
Note: Please fill all required data and upload the signed copy in e-procurrement portal.
Bid Indent No: HESCOM/2025-26/EL/WORK_INDENT1104 Format-I
Work done certificate details as per QR.
Sl.No. Year of Completion Name of the Department Work Done Certificate No.& Date. Work Done Certificate issued by (Executive Engineer, Superintending Engineer .,.etc.,) Station voltage Class (220kV, 110kV, 66kV, 33kV) Station Capacity (MVA) 33 KV Line in R.Kms 33KV ROC in R.Kms 11 KV & above in R.Kms Others Cost of the work/project Rs.in Lakhs
Note:Works completed during the period from(i.e.,2019-20, 2020-21,2021-22,2022-23 and 2023-24) shall only be furnished, others will not be accepted.
I/We hereby declare that I/We had carried out above works and completed in all respects and are in successful operation for the last 1 (One) year i.e.,as on date of Bid submission. Further notice for defects in executed works is not received from concerned Department/recieved and same have been attended within the time. Any information, if found to be incorrect, wrong, misleading or misrepresenting , I/We am/are aware that I/We may be held liable for it.
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
6 section v SCC INDENT 1104.doc
Others - SCC • 0.11 MB
2 section 1 IFB 1104.doc
Others - IFB • 1.41 MB
8 technical specification 1104.doc
Others - technical specification • 0.58 MB
15 KPTCL Cicrcular insurance surety bond.pdf
Others - KPTCL Cicrcular insurance surety bo • 1.59 MB
9 tender capacity.xlsx
Others - tender capacity • 0.02 MB
3 section ii ITB 1104.doc
Others - ITB • 0.11 MB
13 FD417EXP Circular.pdf
Others - FD417EXP Circular • 0.12 MB
11 Khanapur 3rd 5MVA Final 1104.xlsx
Others - ESTIMATE • 0.78 MB
14 Stamp Duty Circular.pdf
Others - Stamp Duty Circular • 0.09 MB
4 section iii GCC INDENT 1104.doc
Others - GCC • 0.14 MB
5 section iv ECC INDENT 1104.doc
Others - ECC • 0.09 MB
1 NIT INDENT 1104.doc
Others - 1 NIT INDENT 1104 • 0.14 MB
10 work done.xls
Others - work done • 0.03 MB
12 Advisory NOte.pdf
Others - Advisory NOte • 0.67 MB
7 Annexures 1104.doc
Others - Annexures • 0.16 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .