Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹51.9 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹54.2 L+₹2.3 L (4.39%)Rejected-AOC 1 SHAKTI NAGAR JAMMU JAMMU KASHMIR 180001 | JAMMU | JAMMU AND KASHMIR | 180001 | L2 | Rejected-AOC L2 | |
| 3 | L3₹54.4 L+₹2.5 L (4.78%)Rejected-AOC | L3 | Rejected-AOC L3 | |
| 4 | L4₹54.9 L+₹3.0 L (5.75%)Rejected-AOC | L4 | Rejected-AOC L4 | |
| 5 | L5₹55.0 L+₹3.1 L (5.88%)Rejected-AOC | L5 | Rejected-AOC L5 |
Tender Value
₹72.0 L
EMD Value
₹1.4 L
Closing Date
30 Jan 2020, 4:00 pmClosed
XEN
XEN MHCH DIVISION GMCH JAMMU
DESIGN, SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF FIRE FIGHTING SYSTEM AND 01 YEAR AMC FOR GOVT. CHEST DISEASES HOSPITAL, JAMMU
2020_PWDJK_89673_1
MHDJ/e-NIT 86 of 2019-20
Open Tender
Machineries/ Mechanical Engg Items
Turn-key
90 days
CHEST DISESASE HOSPITAL JAMMU
AS PER E NIT
2 documents required · 2 mandatory
₹2,000
XEN MHCH DIVISION GMCH JAMMU
₹1.4 L
XEN MHCH DIVISION GMCH JAMMU
5 Sept 2020
3 Jan 2020
31 Jan 2020
3 Jan 2020
30 Jan 2020
20 Jan 2020
3 Jan 2020 - 14 Jan 2020
9 Jan 2020
Amount
Providing and laying of underground M S Pipe (Class-B)conforming to IS:1239, ISI marked, capable of withstanding 150 per cent of the working pressure including water hammer effects and test pressure upto 12.0 kg/cm². including cutting, screwing, welding etc and providing and fitting of all fittings including flanges, bends, tees, elbows, reducers, clamps, hinges etc along with all the earth works. These underground pipes shall be wrapped and coated by providing twin coatings of bitumen, wrapping with first coating then wrapping with bitumen Hessian cloth, of following sizes: 150 mm dia. (Payment to be made as per actual measurements.)
Providing and laying of underground M S Pipe (Class-B)conforming to IS:1239, ISI marked, capable of withstanding 150 per cent of the working pressure including water hammer effects and test pressure upto 12.0 kg/cm². including cutting, screwing, welding etc and providing and fitting of all fittings including flanges, bends, tees, elbows, reducers, clamps, hinges etc along with all the earth works. These underground pipes shall be wrapped and coated by providing twin coatings of bitumen, wrapping with first coating then wrapping with bitumen Hessian cloth, of following sizes: 100 mm dia (Payment to be made as per actual measurements.)
Providing and laying of underground M S Pipe (Class-B)conforming to IS:1239, ISI marked, capable of withstanding 150 per cent of the working pressure including water hammer effects and test pressure upto 12.0 kg/cm². including cutting, screwing, welding etc and providing and fitting of all fittings including flanges, bends, tees, elbows, reducers, clamps, hinges etc along with all the earth works. These underground pipes shall be wrapped and coated by providing twin coatings of bitumen, wrapping with first coating then wrapping with bitumen Hessian cloth, of following sizes: 80 mm dia. (Payment to be made as per actual measurements.)
Providing and laying of overground M S Pipe (Class-B) including cutting holes and chasis in bricks or RCC walls/slabs. The job then includes painting with one coat of primer and two coats of synthetic enamel of approved shades of following sizes: 200 mm dia. (Payment to be made as per actual measurements.)
Providing and laying of overground M S Pipe (Class-B) including cutting holes and chasis in bricks or RCC walls/slabs. The job then includes painting with one coat of primer and two coats of synthetic enamel of approved shades of following sizes: 150 mm dia (Payment to be made as per actual measurements.)
Providing and laying of overground M S Pipe (Class-B) including cutting holes and chasis in bricks or RCC walls/slabs. The job then includes painting with one coat of primer and two coats of synthetic enamel of approved shades of following sizes: 100 mm dia Payment to be made as per actual measurements.)
Providing and laying of overground M S Pipe (Class-B) including cutting holes and chasis in bricks or RCC walls/slabs. The job then includes painting with one coat of primer and two coats of synthetic enamel of approved shades of following sizes: 80 mm dia (Payment to be made as per actual measurements.)
Providing and laying of overground M S Pipe (Class-B) including cutting holes and chasis in bricks or RCC walls/slabs. The job then includes painting with one coat of primer and two coats of synthetic enamel of approved shades of following sizes: 25 mm dia (Payment to be made as per actual measurements.)
SITC of single headed oblique pattern hydrant landing valve with 80 mm dia flanged inlet and 63 mm dia instantaneous type female outlet with orifice plate for controlling the system pressure at every point. Complete with cap and all accessories (ISI marked)
Supply of non – percolated flexible hose RRL 63 mm dia x 15 mtr long complete with instantaneous type 63 mm dia male and female ISI market coupling and riveted to hose pipe with rivets and copper wire and ISI marked.
Supply and Installation of gunmetal 63 mm dia short branch Pipe with 20 mm dia nozzle.
SITC of first aid hose reel wall mounting swinging type complete with drum and brackets, 25 mm dia ball valve and 20 mm dia 30 mtr long hose pressure pad hose with shut off nozzle complete as required.
SITC of cast iron double flanged ISI marked butterfly valve complete with rubber insertion, nuts, bolts, washers and tested to to minimum of 20 kg / sq cm pressure, of the following sizes: 150 mm dia The Valve shall be fitted between two flanges on either side of pipe flanges and shall be supplied with manual gear operated opening / closing system by lever as required.
SITC of cast iron double flanged ISI marked butterfly valve complete with rubber insertion, nuts, bolts, washers and tested to to minimum of 20 kg / sq cm pressure, of the following sizes: 100 mm dia The Valve shall be fitted between two flanges on either side of pipe flanges and shall be supplied with manual gear operated opening / closing system by lever as required.
SITC of cast iron double flanged ISI marked butterfly valve complete with rubber insertion, nuts, bolts, washers and tested to to minimum of 20 kg / sq cm pressure, of the following sizes: 80 mm dia The Valve shall be fitted between two flanges on either side of pipe flanges and shall be supplied with manual gear operated opening / closing system by lever as required.
Supply, installation, testing and commissioning of the following accessories: 25 mm dia spring loaded air release valve with isolation cork.
Supply, installation, testing and commissioning of the following accessories: Pressure gauge
Supply, installation, testing and commissioning of the following accessories: Pressure switch
Supply, installation, testing and commissioning of the following accessories: 25 mm dia gate valve. .
SITC of cast iron double flanged ISI marked NRV complete with rubber insertion, nuts, bolts, washers etc of the following sizes: 150 mm dia
SITC of cast iron double flanged ISI marked NRV complete with rubber insertion, nuts, bolts, washers etc of the following sizes: 100 mm dia
SITC of gunmetal fire brigade connection with collecting head 63 mm, 4 way instantaneous type male couplings with flanged outlet. Complete with blank caps, nuts, bolts and runner insertions confirming IS 904-1983.
SITC of automatic control panel fabricated with 16 SWG for Doors and Covers and 14 SWG for frame and of CRCA M.S. Sheet Construction with Red Oxide Primer and finally with approved colour paint to be stove enamalled. The busbar shall be of aluminum with PVC sleeving of appropriate colour code, have a minimum current carrying capacity to run Hydrant pump and Jockey pump as designed and shall be powder coated including P/F of DoL Starter, Star Delta Starter, Automization Circuit, Battery Charger, MCCB’s, Water Line controller, Single Phase Preventer and internal wiring. The Panel should be cubical compartmentalized type with separate cable chamber & Bus bar Chamber. The Control terminals & Power terminals should be separated and necessary ferrule markings. Necessary M.S. channel for the foundation shall be provided. The ammeter & voltmeter shall be provided with HRC fuses. The Bus bar calculation shall be made for 1 Amp / mm² for Aluminum. The apparatus and circuits in the panels shall be so arranged as to facilitate their operation and maintenance and at the same time to ensure the necessary degree of safety. Provision shall be made in the panel for terminating the incoming cables as required in the single line diagram. Only Top entries shall be permitted and all cables shall be provided with cable terminations. Provision shall also be made for permanently earthing the frames and other metal parts.
Supply and laying of 3½ core 10 sq. mm aluminum cable from motor to electric panel for automation of the jockey pump.
Supply and laying of 3½ core 50 sq. mm aluminum cable from motor to electric panel for automation of the main motor.
SITC of pump with bronze impeller of capacity 2280 LPM with 90 mtr head with diesel engine 85.90 bhp,12 volt, water cooled with 125 mm suction and 100mm delivery, with base frame, coupling, battery, fuel tank, AVM pads etc. The pump shall be provided with mechanical seal complete as required.
SITC of horizontally centrifugal suction Hydrant pump complete for delivery of 2280 LPM against a total head of 90 mtrs, 73.76 HP with 3 phase motor with bronze impellers and coupling, base frame and AVM pads. The pump shall be provided with mechanical seal. The motor shall have a 15% margin of power rating over the rated pump input power. The motor shall be designed not to draw starting current more than 3 times normal running current. It shall be designed for continuous full load duty. The motor shall be full load duty & shall be capable of handling the required starting torque of the pumps.
SITC of horizontally mounted centrifugal Jockey pump complete for delivery 180 LPM against a total head of 90 mtr/14.75 HP, 3 phase motor with a speed of 2900 rpm with bronze impellers and coupling, base frame and AVM pads. Compete as required. The pump shall be provided with mechanical seal.
Earth work, excavation in trenches including back filling and leveling the top after laying of MS pipes of different sizes.
Supply and installation of weather proof external hose cabinets fabricated from 18 gauge MS sheet / suction with full front glass door and suitable to accommodate 2 no’s, 15 mtr long hoses and 1 no. branch pipes as required.
SITC of air vessel 250 mm dia and 1.5 mtr high with dished top, made out of 6mm thick MS pipe complete with provision for 25 NB dia gunmetal air release valve, 20 mm dia stop valve, 25 NB gunmetal pressure release valve, 49 NB drain valve, pressure gauge and painting as required.
Chemical earthing of fire fighting machines by excavation of pit of proper size for main body and neutral for providing and laying of copper rod in hard and soft soil suitable for 12 ft long copper electrode followed by filling of required quantity of earthing chemical, Providing and fitting of suitable size copper strip from copper electrode up to the machines. Job includes filling of pit with excavated soil after fitment of copper electrode.
SITC of gunmetal suction coupling for fire brigade drawl of water from fire tank of 100 mm dia
Supply and installation of 3 ½ x 1.5 sq. mm dia. PVC insulated copper conductor armored cable directly on the surface for pressure switch. Complete as required.
Providing and fitting of 5 Kg. Ceiling mounted modular type automatic fire extinguishers with pressure gauge filled with ABC powder for auto activation for Medical Store, Electric Panel Room & Machine Rooms etc
Providing and Installation of New 4 kg ISI marked (IS:940) ABC type Fire Extinguisher with gun metal cap and nozzle and complete in all respects including initial fill and wall suspension brackets as required as per specifications of NFPA 10, standards.
Providing and Installation of New 4.5 Kg. CO2 type fire extinguishers, Flat base including valve, discharge hose of not less than 10 mm dia, 1M long and complete in all respects including initial fill with CO2 gas conforming to IS:307-1966 and walll suspension braket as required as per specifications
Providing and fitting of 50 Ltrs. Mechanical Aqueous film forming foam (AFFF) type trolley mounted fire extinguishers.
Fabrication of fire point stands of MS angle and sheet fixed with fire buckets-06 no. filled with sand along with fire beater 06 no. and 06 no. shovels each fire point
Providing and laying of GI pipe of 1¼” dia (4 lengths) for water connection to the water storage tank from the main supply line including cost of sockets and fittings. Complete job.
Fabrication of signage board made out of flex board of dimension 3ft x 5ft for providing information regarding important telephone no.s of nearest fire station and other allied agency to be displayed in every block as well as on main entrance gate.
Providing and fixing of Fire Auto glow Signage with printed “IN CASE OF FIRE, USE STAIRS UNLESS INSTRUCTED OTHERWISE" in sticker/acrylic sheet form on boards made out of 3mm thick PVC foam board of 1.5 cm height letters in red with white back ground for Old Building Block and New Building Block. The size of the board shall be 25cm x 30 cm and shall be fixed at the height of 2 mtrs. from finished floor near Manual call points
Providing and fixing of Fire Notice, Fire order, Exit sign, Floor Nos. to be displayed at conspicuous places as per requirements of NBC Part IV
Design of Automatic addressable Fire detection and alarm system conforming to EN 54 by Supply, Testing & Commissioning, fixing of Microprocessor based Networkable analogue addressable type fire alarm control panel with LCD display and 24 volts sealed lead acid batteries sufficient for 24 hours normal working and then capable of operating the system for 2 hours during an emergency conditions as required. Job includes P/F of one loop panel, 12 No. (Approximate) Addressable Manual Pull Stations complete as required, 12 No. Addressable Wall mounted Hooter cum speaker,12 No. I/O modulus complete as required as per specifications. Providing and drawing of approximately 1200 mtrs of 3 ½ x1.5sqmm copper armored cables.
Annual Maintenance Contract for one years. Note:- i) AMC includes checking, inspection, maintenance and testing of the system on quarterly basis. ii) The contractor shall impart training to the security personals in handling/operation and Procedure for Fighting the Fire of all the fire fighting system.
ZOON ENGINEERING TRADERS
Bee Kay Protection Systems
FIRE TECHNOS
Skylight Innovations
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .