Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹12.0 LAccepted-AOC 24 25 MANGAL ARCADE TELCO ROAD OPP HOTEL DOUBLE TREE MOHAN NAGAR CHINCHWAD PUNE 411019 | PUNE | MAHARASHTRA | 411019 | L1 | Accepted-AOC BEING L1 | |
| 2 | L2₹13.8 L+₹1.8 L (15.4%)Rejected-Finance | L2 | Rejected-Finance BEING NOT L1 | |
| 3 | L3₹14.3 L+₹2.3 L (19.5%)Rejected-Finance | L3 | Rejected-Finance BEING NOT L1 |
| Sl No | Description | Qty | Unit | M/s.NIKI ENTERPRISES L2 | SHRI SULAI ELECTRICALS L3 | metro electrical services L1 |
|---|---|---|---|---|---|---|
| 1.00 | Supply, installation, testing and commissioning of silent diesel engine driven ,factory assembled, floor mounted generating set with suitable Automatic on Mains failure control panel (AMF) suitable for out put, 15KVA, 415 volts, 3 phase, 4 wire, 50 HZ,1500 RPM Liquid Cooled complete with safety control and metering equipment mounted on & including common base frame on new PCC foundation as recommended by manufacturer all as specified and comprising of the following :-
Prime Mover: Directly coupled diesel engine with blower fan, suitably matching under NTP condition of BS:5514 for driving 15 KVA capacity, alternator electric start, four stroke confirming to latest IS-10001/10002 Part -II 19801 for continuous running and capable for taking 10% over load for 1 hours in every 12 hours complete with following accessories :-
(i) Engine
(ii) Fly wheel to suitable coupling with guard
(iii) Air cleaner with filters (Dry type, Replaceable paper element air cleaner with restriction indicator,
(iv) Spin on filters-fuel, lube oil filter ,
(v) Lubricating oil gauge.
(vi) Anti- vibration pad as recommended by manufacturers
(vii) PT pump with governor of suitable capacity & flywheel housing and flywheel to suit single bearing alternator
(viii) Electric starters-self starter 12 Volt DC | 1 | Each Job | 5,75,000 ₹5,75,000 | 5,81,000 ₹5,81,000 | 5,05,000 ₹5,05,000 Lowest |
| 1.10(ix) 12 volts, dry maintenance free b+B12 battery supplied along with the in charged condition along with flexible copper battery lead and connector & Battery charging alternator (x) Standard safety devices. (xi) Daily services fuel tank ( Tank complete with level indicator, fuel inlet and outlet, air vent , drain plug including arrangement for direct filling ) for full running capacity of DG set for min 08 hours enclosed within the canopy all as per CPCB with level indicator, fuel outlet drain pug, air vent and locking arrangements etc including fuel pipe connections with connected GI pipe medium grade from fuel tank to DG set and over flow from the DG set to fuel tank complete with gate valve. (xii) Exhaust system shall be provided with thermal insulation by using fire retardant / non igniting foam to prevent excess heat radiation on the engine and sage for operator, Critical grade silencer suitable optimized to meet stringent sound emission Control standards laid down by MOEF/CPCB, Stainless steel exhaust flexible bellows to meet emission norms & Exhaust system shall not be based on (Exhaust Gas regeneration) i.e. EGR (a) Integrated DG set controller (DG set should have a microprocessor based controller with LCD display for engine and alternator parameter) Integrated Electronic Control Panel (displaying the following Engine parameters): (1) Engine Metering: Oil pressure, Engine temperature, starting battery voltage, Engine running hours. (2) AC Alternator Metering : L-L Voltage and L-N Voltage, (3) Current (phase and total), KVA (phase and total), Frequency, (4) Engine Protection : Low lube oil pressure, Battery Over/under/Weak Volts, Fail to Crank/Start, Sensor failure, cranking lockout MODBUS interface (RS 485 RTU) (5) AC Alternator Protection : Over/Under Voltage, Over/Under Frequency, Loss of AC sensing. (6) Safety Control (Trip & Indication) | ||||||
| 1.20(7) High water temperature (hwt) (8) low lube oil pressure (llop) (9) Battery Over/Under/Weak Volts. (10) Failed to start, over crank lockout stop pressed. (b) Alternator: 15 KVA / 25KW at 0.8 power factor, self regulated 3 phase with neutral 415 volts 50 Hz 1500 RPM with brushless excitation, Band of Voltage regulation + 1% of rated voltage, from no load to full load, Insulation Class "H" The alternator generally confirms to BS EN : 60034-1 / IS:4722. (C) Repair/Maint tools to be supplied with DG set are as under :- (i) standard packing set suitable for DG set working (d) ACOUSTIC ENCLOSURE : Floor Mounted Acoustic Enclosure suitable for 30 KVA DG Set as per atest CPCB IV Norms of Make: Cummins (powerica limited) or Kirloskar KOEL or Equivalent in Greaves The DG set shall be guaranteed against faulty workmanship/poor material quality and against failures due to the same, for minimum of two years or 5000 Hrs of operation whichever is earliest, from the date of commissioning complete all as specified and directed. Make: Kirloskar / KOEL Green or equivalent in Cummins/ Crompton Greaves, Polycab, Gloster and Havells or equaling Note: PCC concrete Type B1 1:2:4 using 20 mm graded stone aggregate cement concrete foundation included quoted rate will be measured and paid separately under respective item of schedule. | ||||||
| 2.00 | Supply and lay in trenches/floor/on wall/ on surface with necessary fixing accesseries LT XLPE insulated screened PVC beded galvanised steel strip or wire armoured electric power cable (heavy duty)1100 volts grade with multi-stranded aluminium conductor of size 35 Sqmm 3.5 Core including necessary connection with provision of lugs & cable gland fixing arrangements all as specified and directed. | 140 | RM | 290 ₹40,600 | 315 ₹44,100 | 282 ₹39,480 Lowest |
| 3.00 | Supply,install,testing & commissioning Max 120 W LED Flood Light for Epoxy powder coated die-cast aluminium housing (ADC 12) with aesthetically designed heat sink for efficient thermal management, sturdiness & excellent corrosion resistant. M16 size gland is used for cable entry and provision for loopin-loopout, System wattage consist of 120 W with composite Wide Beam PC Lens cover to ensure better uniformity Powered by an Isolated integral IP 66 Potted electronic driver with 4 KV Surge Protection (SMPS based constant current supply) with lower THD, Output Short Circuit, Over Voltage, Surge Protection. cool white/warm white coloure temperature with minimum 5700K/3K , CRI >70, THD < 10%, PF >.95, IP65, IK07 .Life class of 50,000 hrs @ L70, Operating Temperature :-10 TO + 45 DEG.C TEST REPORT TO BE SUBMITTED; Test Report LM 79 FOR Complete LED Luminaries and LM 80 for LED Chip as well as PHOTO BIOLOGICAL SAFETY for LD chip. LED fixture with BIS R mark and R Registration no. must for each Fixture. As per CROMPTON Cat Ref :TFS-504-120-57-60D-HL2-GL-NSG (120 lm/w 10KV SPD ) with 5 Year warranty or equivalent in Havells/Philips | 20 | Each | 5,450 ₹1,09,000 | 6,000 ₹1,20,000 | 5,100 ₹1,02,000 Lowest |
| 4.00 | Supply,install,testing & commissioning of LED street light fittings 70 watt with minimum110 lumen/ watt system lumen output .The luminaire should have cool white coloure temperature with minimum 5700 K. The luminaire housing should be made of pressure die cast aluminium Epoxy power coated with wether proof gasket for LEDs and control gear compartments, heat resistance toughened clear glass fixed with SS screw with IP 66 protection, lumen efficiency of 120 lumen /W, isolated electronic LED driver ( SMPS based constant current supply), IK-07, life class of 50,000 hrs @ L 70 5 yrs written warranty in r/o of fittings shall be submittted from manufacturer, surge voltage protection not less than 10 KV . Make Crompton CAT No CRP-409-70-57-SL-GL-NSG or equivalent in Havells/ Phillips.complete all as specified and directed by Engineer- in-charge.. | 50 | Each | 3,500 ₹1,75,000 | 3,800 ₹1,90,000 | 3,200 ₹1,60,000 Lowest |
| 5.00 | Supply and fix street light bracket 32/40 mm bore GI pipe/tubing light grade not less than 1.2 Mtr long bend by putting sand inside it to 45 degree angle shape with 2 nos MS clamps flat iron 50 x 5 mm for nuts, bolts and washers suitable for Steel/PCC Pole etc and applying two coats of aluminium paint over a coat of red oxide primer complete all as specified and directed. Make- Prakesh surya/Swastik/Jindal,complete all as specified & as directed by Eng-In-Charge. | 50 | Each | 600 ₹30,000 | 500 ₹25,000 | 400 ₹20,000 Lowest |
| 6.00 | M&L & fixing of DWC pipes it should be flexible & should allow deformation in diameter as well as In joints under external load & soil natural movement, socket & spigot joint with electrometric sealing ring , it should be highly corrosive resistant & it should be impact resistant, chemiacal resistant, flexible & light weight of size 50 mm ID & 63 mm outer dia complete with coupler, elbows, joints,& necessary space parts complete all as specified.
Make: Dura line/ Astrel/Prince or equaling | 100 | RM | 110 ₹11,000 | 110 ₹11,000 | 60 ₹6,000 Lowest |
| 7.00 | Excavation in trenches n. exc 1.5 Mtr wide and n. exc 1.5 mtr in depth and getting out in hard soil. | 22 | Cum | 180 ₹3,960 | 150 ₹3,300 | 130 ₹2,860 Lowest |
| 8.00 | Returning Filling in including spreading, leveling, watering & well ramming in layers n. exc 25 Cm. | 20 | Cum | 60 ₹1,200 | 50 ₹1,000 | 30 ₹600 Lowest |
Tender Value
₹13 L
EMD Value
₹26,000
Closing Date
19 May 2025, 6:00 pmClosed
GE AF OJHAR
GE AF OJHAR
PROVN OF STANDBY POWER SUPPLY FLAME PROOF LIGHT, FAN, EXHAUST FAN AND ALLIED WORKS AT BCR AT 25ED DEOLALI
2025_MES_704455_2
8290/E8
Open Tender
Civil Works
Item Rate
180 days
DEOLALI
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE AF OJHAR
₹26,000
14 Oct 2025
3 May 2025
21 May 2025
4 May 2025
19 May 2025
6 May 2025
Amount
Supply, installation, testing and commissioning of silent diesel engine driven ,factory assembled, floor mounted generating set with suitable Automatic on Mains failure control panel (AMF) suitable for out put, 15KVA, 415 volts, 3 phase, 4 wire, 50 HZ,1500 RPM Liquid Cooled complete with safety control and metering equipment mounted on & including common base frame on new PCC foundation as recommended by manufacturer all as specified and comprising of the following :- Prime Mover: Directly coupled diesel engine with blower fan, suitably matching under NTP condition of BS:5514 for driving 15 KVA capacity, alternator electric start, four stroke confirming to latest IS-10001/10002 Part -II 19801 for continuous running and capable for taking 10% over load for 1 hours in every 12 hours complete with following accessories :- (i) Engine (ii) Fly wheel to suitable coupling with guard (iii) Air cleaner with filters (Dry type, Replaceable paper element air cleaner with restriction indicator, (iv) Spin on filters-fuel, lube oil filter , (v) Lubricating oil gauge. (vi) Anti- vibration pad as recommended by manufacturers (vii) PT pump with governor of suitable capacity & flywheel housing and flywheel to suit single bearing alternator (viii) Electric starters-self starter 12 Volt DC
(ix) 12 volts, dry maintenance free b+B12 battery supplied along with the in charged condition along with flexible copper battery lead and connector & Battery charging alternator (x) Standard safety devices. (xi) Daily services fuel tank ( Tank complete with level indicator, fuel inlet and outlet, air vent , drain plug including arrangement for direct filling ) for full running capacity of DG set for min 08 hours enclosed within the canopy all as per CPCB with level indicator, fuel outlet drain pug, air vent and locking arrangements etc including fuel pipe connections with connected GI pipe medium grade from fuel tank to DG set and over flow from the DG set to fuel tank complete with gate valve. (xii) Exhaust system shall be provided with thermal insulation by using fire retardant / non igniting foam to prevent excess heat radiation on the engine and sage for operator, Critical grade silencer suitable optimized to meet stringent sound emission Control standards laid down by MOEF/CPCB, Stainless steel exhaust flexible bellows to meet emission norms & Exhaust system shall not be based on (Exhaust Gas regeneration) i.e. EGR (a) Integrated DG set controller (DG set should have a microprocessor based controller with LCD display for engine and alternator parameter) Integrated Electronic Control Panel (displaying the following Engine parameters): (1) Engine Metering: Oil pressure, Engine temperature, starting battery voltage, Engine running hours. (2) AC Alternator Metering : L-L Voltage and L-N Voltage, (3) Current (phase and total), KVA (phase and total), Frequency, (4) Engine Protection : Low lube oil pressure, Battery Over/under/Weak Volts, Fail to Crank/Start, Sensor failure, cranking lockout MODBUS interface (RS 485 RTU) (5) AC Alternator Protection : Over/Under Voltage, Over/Under Frequency, Loss of AC sensing. (6) Safety Control (Trip & Indication)
(7) High water temperature (hwt) (8) low lube oil pressure (llop) (9) Battery Over/Under/Weak Volts. (10) Failed to start, over crank lockout stop pressed. (b) Alternator: 15 KVA / 25KW at 0.8 power factor, self regulated 3 phase with neutral 415 volts 50 Hz 1500 RPM with brushless excitation, Band of Voltage regulation + 1% of rated voltage, from no load to full load, Insulation Class "H" The alternator generally confirms to BS EN : 60034-1 / IS:4722. (C) Repair/Maint tools to be supplied with DG set are as under :- (i) standard packing set suitable for DG set working (d) ACOUSTIC ENCLOSURE : Floor Mounted Acoustic Enclosure suitable for 30 KVA DG Set as per atest CPCB IV Norms of Make: Cummins (powerica limited) or Kirloskar KOEL or Equivalent in Greaves The DG set shall be guaranteed against faulty workmanship/poor material quality and against failures due to the same, for minimum of two years or 5000 Hrs of operation whichever is earliest, from the date of commissioning complete all as specified and directed. Make: Kirloskar / KOEL Green or equivalent in Cummins/ Crompton Greaves, Polycab, Gloster and Havells or equaling Note: PCC concrete Type B1 1:2:4 using 20 mm graded stone aggregate cement concrete foundation included quoted rate will be measured and paid separately under respective item of schedule.
Supply and lay in trenches/floor/on wall/ on surface with necessary fixing accesseries LT XLPE insulated screened PVC beded galvanised steel strip or wire armoured electric power cable (heavy duty)1100 volts grade with multi-stranded aluminium conductor of size 35 Sqmm 3.5 Core including necessary connection with provision of lugs & cable gland fixing arrangements all as specified and directed.
Supply,install,testing & commissioning Max 120 W LED Flood Light for Epoxy powder coated die-cast aluminium housing (ADC 12) with aesthetically designed heat sink for efficient thermal management, sturdiness & excellent corrosion resistant. M16 size gland is used for cable entry and provision for loopin-loopout, System wattage consist of 120 W with composite Wide Beam PC Lens cover to ensure better uniformity Powered by an Isolated integral IP 66 Potted electronic driver with 4 KV Surge Protection (SMPS based constant current supply) with lower THD, Output Short Circuit, Over Voltage, Surge Protection. cool white/warm white coloure temperature with minimum 5700K/3K , CRI >70, THD < 10%, PF >.95, IP65, IK07 .Life class of 50,000 hrs @ L70, Operating Temperature :-10 TO + 45 DEG.C TEST REPORT TO BE SUBMITTED; Test Report LM 79 FOR Complete LED Luminaries and LM 80 for LED Chip as well as PHOTO BIOLOGICAL SAFETY for LD chip. LED fixture with BIS R mark and R Registration no. must for each Fixture. As per CROMPTON Cat Ref :TFS-504-120-57-60D-HL2-GL-NSG (120 lm/w 10KV SPD ) with 5 Year warranty or equivalent in Havells/Philips
Supply,install,testing & commissioning of LED street light fittings 70 watt with minimum110 lumen/ watt system lumen output .The luminaire should have cool white coloure temperature with minimum 5700 K. The luminaire housing should be made of pressure die cast aluminium Epoxy power coated with wether proof gasket for LEDs and control gear compartments, heat resistance toughened clear glass fixed with SS screw with IP 66 protection, lumen efficiency of 120 lumen /W, isolated electronic LED driver ( SMPS based constant current supply), IK-07, life class of 50,000 hrs @ L 70 5 yrs written warranty in r/o of fittings shall be submittted from manufacturer, surge voltage protection not less than 10 KV . Make Crompton CAT No CRP-409-70-57-SL-GL-NSG or equivalent in Havells/ Phillips.complete all as specified and directed by Engineer- in-charge..
Supply and fix street light bracket 32/40 mm bore GI pipe/tubing light grade not less than 1.2 Mtr long bend by putting sand inside it to 45 degree angle shape with 2 nos MS clamps flat iron 50 x 5 mm for nuts, bolts and washers suitable for Steel/PCC Pole etc and applying two coats of aluminium paint over a coat of red oxide primer complete all as specified and directed. Make- Prakesh surya/Swastik/Jindal,complete all as specified & as directed by Eng-In-Charge.
M&L & fixing of DWC pipes it should be flexible & should allow deformation in diameter as well as In joints under external load & soil natural movement, socket & spigot joint with electrometric sealing ring , it should be highly corrosive resistant & it should be impact resistant, chemiacal resistant, flexible & light weight of size 50 mm ID & 63 mm outer dia complete with coupler, elbows, joints,& necessary space parts complete all as specified. Make: Dura line/ Astrel/Prince or equaling
Excavation in trenches n. exc 1.5 Mtr wide and n. exc 1.5 mtr in depth and getting out in hard soil.
Returning Filling in including spreading, leveling, watering & well ramming in layers n. exc 25 Cm.
Removing excavated/Surplus soil n exc 50 Mtr & depositing where directed at a level n. exc 1.5 Mtr above the starting point.
S & F Sheet Metal enclosure double door for mounting MCBs with 200 A rated bus bar 4 way AC 240 Volt with IP-43 protection including cutting chases to wall for fixing DB and making good the disturbed wall surface all as required at site or directed by Engr-in-Charge . Make Indoasian/L&T/HPL
Supply and fixing amp rating 240V, 10KA 'C' curve miniature circuit breaker (MCB) of following poles and current carrying capacity in the MCB DB complete with connection testing and commissioning. MCB SP 5-32 Amp. Make : Indoasian/L&T/HPL
S&F in MCB TPN 63Amp. Make : Indoasian/L&T/HPL
Material and labour for earthing complete with Cooper earth plate electrode of size 60cm x 60 cm x 3.15 mm thick buried directly in ground ( earth pit not less than 2.25 mtr deep below ground level) with top edge of earth plate not less than 1.5 mtr below ground level connected to copper strip 20x3 mm by means of of galvanized iron nuts & bolts or as directed at site by Engineer -in-Charge protected by GI Pipe 40 mm dia light grade and connected to test point and further connected to equipment, mcachinery, electrical panel or any other as directed by Engineer-in-Charge, which to be earthed, all as shown in electrical plate No 3 of SSR Part I including providion of concrete earth pit constructed in PCC 1:3:6 type C-1 as earth pit and PCC 1:2:4 type B-1 for cover slab with necessary reinforcement with handle for lifting also including provision of funnel with wiremesh with 20 mm GI pipe medium grade for watering, charcoal and salt in alternative layers of 15 cm thick all around the electrode , including necessary excavation and earth work , testing and commissioning complete all as directed at site.
Earth continuity conductor or main earthing strip fixed to wall on batten or recess or chases or buried in ground fixed with proper clamping or saddling duly supported on porecelene/polycarbonate/wooden block with suitable fixing arrangement of nuts & bolts or psses through wall by making hole or any other indicated situation of size 20x3 mm copper earthing Srtip complete all as specified and directed.
M&L for point wiring complete with two single core, PVC insulated, unsheathed, multi stranded bright annealed copper conductor cable, 1.5 Sq.mm 1100 Volts, FRLSH grade drawn through and including heavy duty Instove enameled steel conduit not less than 25 mm width and accessories surface mounted on walls, ceilings etc. on & including suitable board for flame proof with earth dolly arrangement with surface plate for mounting switches, sockets, regulators etc and one run of 1.5 Sq.mm PVC insulated, unsheathed, multistranded, copper conductor cable FRLS grade as earth wire and connected to common earth dully complete for the following :- (a) One light/fan point controlled by one switch.
Ditto- all as per Sl item No 01 above but with two runs of 2.5 Sq.mm cable and one run of 2.5 Sq.mm cable as earth wire for one 3 pin socket outlet/power point 15 Amps controlled by one switch.
Supply & fix switch flame proof rotary type with termination box in LM6, 16A, single pole 250V Make : Shyam/Sudhir/Crompton Greves
Supply & fix socket 16 Amp flame proof rotary type with termination box in LM6, 16A, single pole 250V Make : Shyam/Sudhir/Crompton Greves
Supply and fixing LED light fitting 1x 20 Watt flameproof, CMRI certified recommended for gas/ vaporgroup of IIA & IIIB, Zone 1 & 2 and IP 65 protection with die cast aluminum hosing with heat resistanttoug hened glass with LED tube light fixtures driver,holders, connector etc.Complete with all accessories prewired and including connecting up with three core flexible copper conductor cable with suitable size. Make : Shyam/Sudhir/Crompton Greves
S&F Flame proof Ceiling Fan 1200 mm sweep with concrete drilling to ceiling and as directed place fixing with concrete hold fast for hanging of flame proof ceiling fan complete all as directed by Engr-in-Charge. Make : Shyam/Sudhir/Crompton Greves
S&F Flame proof Exhaust 18'' mm sweep with external louvers on wall or window Cutting the wall to sweep size fitting complete with iron frame nut bolt and hold fast and making good of disturbed surfaces & paiting to match with existing touch up for all as directed by Engr-in-Charge. Make : Shyam/Sudhir/Crompton Greves
S&F sheet metal enclosure 8 way MCB SPN distribution board flame proof type 240/415 volt, double door with DIN rail bus bar, neutral link, earth terminal etc IP-43, IK 09 protection including MCB SP and SPN for suitable sze all as specified and directed by Engr-in-Charge. Make : Shyam/Sudhir/Crompton Greves
Supply & Fix 20 Watt LED recessed panel, STAR LORD, with IN-BUILT surge protection of upto 3KV, extra bright iumen efficacy OF 100 Lumen/Watt CAT REF : LSDRLORD-20W-CDL CROMPTON or equivalent in Philips/Havells
Supply & fix 06 WATT LED surface panel, STAR STULUS, with IN-BUILT surge protection of upto 2.5KV, easy to fit with twist and lock method CAT REF : LSDRSTYL-6W-CDL MAKE : CROMPTON or equivalent in Philips / Havells
Supply & fix 36 Watt Decorative suspended ROUND fittiing LUNAR,Timeless classic design CAT REF : LCSUR4-36 MAKE : CROMTON or equivalent in Philips/Havells
Supply & fix /replacement of decorative LIARA LED Bollard IP65 rated Inverted Pyramid Tripod type LED Bollard with soft 360º light distribution Crompton Cat pt LBLSN-10-CDL or as require at site ,complete all as specified & as directed by Eng-In-Charge.
Supplying and fixing 1100 volts grade heavy duty cable PVC insulated Copper conductor, served with inner sheathing of PVC tape and overall PVC sheathed , 6 sq mm multi-stranded three core cable flat cable all as specified and directed.
S & F PVC Insulated and weather proof three core multistrand conductor cable 3 core x1.5 sqmm, size as required length for replacing US cable for street light where ever founf US from junction box to street light Make Havells, polycab, Gloster and KEI,complete all as specified & as directed by Eng-In-Charge.
M&L for earthing complete with galvanised steel earth plate electrode 600x600x6 mm thick, burried directly in ground (earth pit not less than 2.25 mtr deep below ground level) with top edge of the plate not less than 1.5 mtr below normal ground level, connected to GI strip 25x4 mm through GI pipe of suitable dia light grade by means of bolts,nuts, check nuts and washers of galvanised iron or steel,with adequate quantity of charcoal and salt, proper watering arrangements including 20 mm dia medium grade GI tubing.PCC chamber,Chamber Cover all as shown in electrical plate no 3 of SSR part I 2009 connected to earthing test point all as specified or indicated and testing on completion. The end point connection of eatrhing will be carried out with the help of GI bolt grouted and washer and nut.
M/s.NIKI ENTERPRISES (BID ID -3294778)
SHRI SULAI ELECTRICALS (BID ID -3295245)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .