| 1 | L1₹54.1 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹56.3 L+₹2.2 L (4.14%)Rejected-AOC C 8 78A KESHAV PURAM DELHI 110035 | DELHI | NORTH WEST DELHI | DELHI | 110035 | L2 | Rejected-AOC L2 | |
| 3 | L3₹60.7 L+₹6.6 L (12.1%)Rejected-AOC | L3 | Rejected-AOC L3 | |
| 4 | L4₹61.0 L+₹6.9 L (12.7%)Rejected-AOC | L4 | Rejected-AOC L4 | |
| 5 | L5₹63.6 L+₹9.5 L (17.6%)Rejected-AOC | L5 | Rejected-AOC L5 |
Tender Value
₹54.1 L
EMD Value
₹1.1 L
Closing Date
9 May 2024, 3:00 pmClosed
Chief Engineer, CEG, GSO
Room No. 306, GSO, Annex Building, Kalpakkam
Providing of LT Panel
2024_GSO_804133_1
GSO/CTC/ESD/07/2024
Open Tender
Electrical Works
Item Rate
270 days
Anupuram Township
As stipulated in NIT/tender
8 documents required · 8 mandatory
₹0
₹1.1 L
16 May 2025
17 Apr 2024
10 May 2024
17 Apr 2024
9 May 2024
3 May 2024
18 Apr 2024 - 1 May 2024
Amount
Design, manufacturing, testing at manufacturer's works, packing, transportation, delivery, unloading and storage at site, installation, site testing and commissioning of the 415 Volts Switch Boards as per single line diagram and the detailed specification and as directed by Engineer in Charge.
Load Distribution Panel consisting of : (a). 630 Amps 4 Pole ACB with Numeric relay, MFM, R,Y,B & Breaker functional indication Lamps, Castel interlock, Auto/Manual closing facility - 2 Sets. (b). 250 Amps 4 Pole MCCB with Thermal magnetic based tripping facility - 3 sets (c). 63 Amps 4 Pole MCCB with Thermal magnetic based tripping facility - 15 Sets
Supply, Loading, Transportation, Unloading at site, Laying, Testing and Commissioning of one number XLPE insulated and PVC sheathed power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering with chamber burnt/cement bricks on sides & top, refilling the trench and providing RCC route indicator etc as required.(Refer Sec VI, Clause No.3)
3.5 CORE X 400 Sq.mm, 1.1kV grade A2XYWY CABLE
Supply, Loading, Transportation, Unloading at site, installation, Testing and Commissioning of 1100 Volts Grade XLPE insulated, Stranded Aluminium conductor cables of following sizes in built-in trenches, on walls, poles and through embedded pipes including supply of GI spacer, clamps etc and as per the detailed specification.(Refer Sec VI, Clause No.3)
3.5 CORE X 400 Sq.mm, 1.1kV grade A2XYWY CABLE
Loading, Transportation, Unloading at site, installation, Testing and Commissioning of 1100 Volts Grade PVC/HRPVC/XLPE insulated, Stranded Aluminium/copper conductor cables of following sizes in built-in trenches, on walls, poles and through embedded pipes including supply of GI spacer, clamps etc and as per the detailed specification (Note: Cable will be issued free of cost by the department).(Refer Sec VI, Clause No.3)
3/3.5/4 Core Above 25sqmm & upto120 sq.mm
3/3.5/4Core X above 120 & up to 240 sq.mm
Retrieval of the already laid one number 1100 Volts Grade XLPE/HRPVC insulated, Stranded Aluminium conductor cables of following sizes in built-in trenches, on walls, poles and from embedded pipes including removal of GI spacer, clamps etc and Relaying the same cable in built-in trenches, on walls, poles and through embedded pipes using the retrieved spacer & clamp & supplying the shortage spacer & clamp if any as per the detailed specification. (Refer Sec VI, Clause No.7)
3/3.5/4 C X 25 Sq.mm
3/3.5/4 Core Above 25 & Upto 120 Sq.mm
3/3.5/4 Core Above 240 & Up to 400 Sqmm
Retrieval of the existing one number PVC/HRPVC/XLPE insulated and PVC sheathed power cable of 1.1 KV grade of following sizes laid direct in ground including Removal of end termination, excavation of trenches, retrieving of bricks and back filling as per the detailed specification.(Refer Sec VI, Clause No.5)
3/3.5/4 Core Above 240sqmm & up to 400 sq.mm
Retrieval of the already laid one number 1100 Volts Grade XLPE/HRPVC insulated, Stranded Aluminium conductor cables of following sizes in built-in trenches, on walls, poles and from embedded pipes including removal of end termination GI spacer, clamps etc as per the detailed specification. (Refer Sec VI, Clause No.5)
3/3.5/4 Core Above 120 & Up to 240 Sq.mm
End Termination of the following sizes of Aluminium Conductor PVC Insulated and sheathed armoured UG Cable using Single Compression, Heavy Duty, Gland connecting the cable to the equipment such as Switches/Panel Boards etc. using Comet or equivalent make Aluminium crimping lugs as directed by Engineer-in-Charge. The rate shall include the cost of supply of Cable Gland and Lugs. The Contractor shall arrange for making holes wherever necessary for fixing cable gland. (Refer Sec VI, Clause No.10.1).
4 Core X10sq.mm
4 Core X 16 Sq.mm
3.5/4 C x 35 sq.mm
3.5 x 185 sq.mm
3.5 x 400 sq.mm
Supply installation, testing and commissioning of following Raychem make Heat Shrinkable Cable Straight Through Jointing Kits (Crimping type) for 3.5 Core Aluminium Conductor, 1.1 KV (E), PVC/XLPE insulated cables of following sizes including excavation of soil, backfilling etc as per the detailed specification.
Straight Through Joint (Crimping type) for 3.5 Core x 400 Sq. mm
Straight Through Joint (Crimping type) for 3.5 Core, 25- 50 Sq. mm
Supply, Installation, testing and commissioning of Tempra combined units with interlocked switched socket IP66 of Legrand make as per Cat No:0572 99 and Tempra Plug as per Cat No:55509
Supply, open installation testing and commissioning of the following sizes of VTPN DBs on MS frame work (MS frame will be measured separately) as per the scope of work.
DB VTPN 4 Way (8 Plus 12) IP 43 - IK 09 Cat No:507725 or equivalent , 2 Nos Cable end box, 1 No.100A FP MCB and 4Nos 32A 3P MCB.
Supply, installation testing and commissioning of 100 Amps 4 Pole Change Over Switch with Sheet steel Enclosure as per Cat No: CO11000OSOO and Type CO1-100 Amps
Supply and Installation of following sizes of PVC trunking (casing & capping) on walls/Ceiling for routing of Power, Lighting and Telephone wires including all the required accessories like JBs, Coupling, External & Internal Bends, Elbows and end cap as per the detailed specification.(Refer Sec VI, Clause No.29)
32 X 12mm size of PVC Mini trunking
Wiring for lights / fans /sensors/ Power point with 1100V grade FRLS insulated copper conductor wires in existing concealed/ Exposed PVC / ERW / Flo-coated Metal conduits as per the detailed scope of work, including supply of Wires, termination of copper wires at either end by crimping including supply of PVC Sleeves/Ferrules, Copper Crimping Lugs and connecting the wires to various switches, sockets, etc. including testing and commissioning as per the detailed specification.(Refer Sec VI, Clause No.18)
Wiring with 1 Run of 6 Sq.mm Copper wire
Wiring with 1 Run of 2.5 Sq.mm Copper wire
Supply, fabrication and installation of the following size of Hot dip Galvanised GI Flats in Built in trenches on walls, poles, RCC Concrete and through embedded pipes as per the detailed specification. No cutting or drilling permitted after galvanisation. (Refer Sec VI, Clause No.12.9).
50 X 6 mm GI flat
Supply and Installation of MS Brackets, Supports, Frame work, Clamps, Base Channels, etc. fabricated out of angle / Channel / Rods etc. The rate quoted shall include the cost of fabrication / welding, cleaning and painting/ galvanising as follows including supply of required, fasteners, nuts, washers, etc.(Refer Sec VI, Clause No.11).
MS fabrication 1 coat primer & 2 coats synthetic enamel paint
Supply and installation of 300mm(W) x 50mm(H) x 2mm thick Hot dip Galvanised Perforated type Cable Tray with 2 Nos. Coupler Plates as per the detailed specification.
Supply, cleaning the floor, proper pasting and installation of following insulating mat as per specification. (Refer Sec VI, Clause No.25).
2.0 mm thickness, Max useable voltage 3.3kV, AC Proof voltage 10kV for 3 minutes, AC dielectric strength 30kV RMS Insulating Mat confirming to IS:15652
Supply and Installation of 1100V grade, 3 Core x 1.5 Sq.mm, FR-PVC insulated, unsheathed, multi stranded copper conductor flexible cable in existing conduits / through HDPE pipe, including termination of wires on both sides and all required accessories.
Assembling, installation, testing and commissioning of MCB DB enclosure already embedded in the wall including supply of Engraved Circuit Identification Plate and Danger Board as per the detailed specification for the following size of MCB DBs. (Refer Sec VI, Clause No.15.3).
SPN, 4/6/8 Way Distribution Board
Installation testing and commissioning of the following RCCBs on Distribution Boards as per the detailed specification. (Refer Sec VI, Clause No.14.2). Note : RCCB will be issued by the Depatment as a free issue item.
RCCB DP 25A sensitivity 30mA, TYPE Hpi / AC
Installation testing and commissioning of the following MCB on Distribution Boards as per the detailed specification. (Refer Sec VI, Clause No.14.2). Note : MCB will be issued by the Depatment as a free issue item.
6-32 Amps SP MCB (Type-C)
Supply, installation, testing and commissioning of following sizes of Wall Mounting Exhaust Fans including supply of Aluminium grill bracket with Stainless Steel Bolts for mounting of Exhaust Fan & Aluminium grill bracket and 3 Core, 1.5 Sq.mm (14/0.3) PVC insulated & FRLS sheathed copper flexible cable of required length as per the detailed specification. (Refer Sec VI, Clause No.17.2).
300 mm Dia Turbo Heavy Duty Exhaust Fan
Supply, installation, testing, commissioning of 71Watts, 7900 Lumens, LED High bay luminiaries including removal of existing highbay luminiaries at the same location and all required accessories as per the detailed specification.
RR ENTERPRISES
EC Enterprises
A K Engineering Services
SRIRAM ELECTRICALS
Bidder Name
A K Engineering Services
SAS ENTERPRISES
RR ENTERPRISES
EC Enterprises
SRIRAM ELECTRICALS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .