SE/ES/TTPS
Superintending Engineer-Electrical Systems- Tuticorin Thermal Power Station-Tuticorin
EM II Major overhauling of 5 Nos fan motors and 4 Nos Mill motors and Annual preventive maintenance of 1 No fan motor and 1 No Mill motor during unit III capital overhauling period of 2023 2024
2023_EB_316656_1
SE/ES /TTPS /No.80/2023-24
Open Tender
Electrical Works
Item Rate
45 days
TTPS
As per BQR conditions in NIT
7 documents required · 7 mandatory
₹0
₹21,000
Yes
24 Jul 2023
18 May 2023
5 Jun 2023
18 May 2023
3 Jun 2023
18 May 2023
Charges for the complete overhauling of ID-3A fan motor as follows: Charges for the complete overhauling of ID fan motor 6.6 Kv, 1700 KW, 990 RPM as follows. Disconnection of power and control cable and measuring IR value of motor winding, Dismantling of the motor from the bed, transporting the motor to repair bay, opening the end covers and threading out the rotor, cleaning the stator and rotor with compressed air, kada cloth and petrol, Checking and tightening of all loose wedges in the stator winding by adding additional glass texolite liners and replacing all damaged wedges with new glass texolite wedges, pre heating the stator improve the IR value and make ready for high voltage test to ascertain the insulation deterioration value of stator winding, Varnishing the rotor and stator with Dr.Beck insulation varnish, Threading in the rotor and assembly, erect the motor on bed, alignment of motor, inspection and blue matching the bearing if necessary, cleaning and overhauling the cooler and renewing of all bolts and gaskets, Replacing the wire mesh of the motor wherever necessary, checking PI value of the motor, conducting trail run of the motor, magnetic centre adjustment if necessary for the required coupling gap, painting the motor with two coats of deep Orange enamel of Asian / British paint including cost of paint & consumables and hire charges and T&P etc.
Charges for the complete overhauling of FD Fan motor 6.6 Kv, 1100 KW, 1490 rpm as follows. Disconnection of power and control cable and measuring IR value of motor winding, Dismantling of the motor from the bed, transporting the motor to repair bay, opening the end covers and threading out the rotor, cleaning the stator and rotor with compressed air, kada cloth and petrol, Checking and tightening of all loose wedges in the stator winding by adding additional glass texolite liners and replacing all damaged wedges with new glass texolite wedges, pre heating the stator improve the IR value and make ready for high voltage test to ascertain the insulation deterioration value of stator winding, Varnishing the rotor and stator with Dr.Beck insulation varnish, Threading in the rotor and assembly, erect the motor on bed, alignment of motor, inspection and blue matching the bearing if necessary, cleaning and overhauling the cooler and renewing of all bolts and gaskets, Replacing the wire mesh of the motor wherever necessary, checking PI value of the motor, conducting trail run of the motor, magnetic centre adjustment if necessary for the required coupling gap, painting the motor with two coats of deep Orange enamel of Asian / British paint including cost of paint & consumables and hire charges and T&P etc.
Charges for the complete overhauling of PA Fan motor 6.6 Kv, 900 KW, 1490 rpm as follows. Disconnection of power and control cable and measuring IR value of motor winding, Dismantling of the motor from the bed, transporting the motor to repair bay, opening the end covers and threading out the rotor, cleaning the stator and rotor with compressed air, kada cloth and petrol, Checking and tightening of all loose wedges in the stator winding by adding additional glass texolite liners and replacing all damaged wedges with new glass texolite wedges, pre heating the stator improve the IR value and make ready for high voltage test to ascertain the insulation deterioration value of stator winding, Varnishing the rotor and stator with Dr.Beck insulation varnish, Threading in the rotor and assembly, erect the motor on bed, alignment of motor, inspection and blue matching the bearing if necessary, cleaning and overhauling the cooler and renewing of all bolts and gaskets, Replacing the wire mesh of the motor wherever necessary, checking PI value of the motor, conducting trail run of the motor, magnetic centre adjustment if necessary for the required coupling gap, painting the motor with two coats of deep Orange enamel of Asian / British paint including cost of paint & consumables and hire charges and T&P etc.
Charges for the complete major overhauling of mill motor:Charges for the complete overhauling of 6.6 KV, 320 KW, 990 RPM mill motor with the description of work as follows. Removal of electrical connection and measuring the IR value of motor winding, dismantling the end covers, cooler fans and cooler, threading out the rotor, checking the bearing and changing if necessary, cleaning the rotor and stator with compressed air, gada cloth and petrol. Checking and tightening of all loose wedges, in the stator by adding additional glass textolite wedges, drying of stator by preheating and make ready for tan delta test to ascertain the reinsulation deterioration of stator winding inspection of rotor bars and end rings, varnishing the stator winding and rotor with Dr. Beck or equivalent insulation varnish, checking the IR values and resistance of stator winding, assembling the bearings with proper greasing, threading in the rotor, assembling of cooler and end covers etc., renewing of broken bolts and gaskets replacing the wire mesh of the end cover of the motor. Wherever necessary spray painting the motor with two coats of deep orange enamel paint.(Asian British paint).Erection and fixing up of motor to the required alignment and coupling gap. Taking IR value, PI value and trial running of the motor, observing the vibration ,temperature measurement etc. including cost of paint & consumables and hire charges and T&P etc.
Annual Preventive maintenance of ID- 3B fan motor: Charges for dismantling the end cover, checking and cleaning the end winding, cleaning the motor internally by compressed air, both the bearing cleaning and checking, blue match the bearing, Oil clearance measurement and changing the gaskets if necessary and make ready the motor for trial run during AOH period for ID fan motor Including cost of consumable T&P hire charges.
Charges for dismantling the ID fan motor water cooler, rack out the cooler from the chamber, cleaning the cooler internally with wire brush and water, painting the cooler internally and externally, assembling the cooler conducting required hydraulic pressure test, fixing the cooler with the motor, painting both side wall cover during AOH period for ID Fan Motors. Including cost of consumable T&P hire charges.
Charges for dismantling the power cable from the motor, checking the misalignment, align the motor with fan within the limit, checking the stator-rotor air gap and keeping the air gap within the limit and make ready the motor with required coupling gap for trial run during AOH period for ID Fan Motor. Including cost of consumable T&P hire charges.
Preventive maintenance of Mill motor3B: Charges for releasing of M.S Grill and Mill motor roof cover from frame and lowering to ground for removal of motor NDE cover and assembling of motor roof cover and M.S Grill after completing the motor cleaning works during AOH period of 320 KW Mill motor. Including cost of consumable T&P hire charges.
Charges for dismantling the cooler cover, cleaning the cooler, cleaning the cooler tubes internally with compressed air and then with wire brush and pull through, assembling the cooler cover after inside painting and changing the gaskets during AOH period of 320 KW Mill motor. Including cost of consumable T&P hire charges.
BLUE MOUNTAIN
stage.html
html • 0.04 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .