Executive Engineer
Executive Engineer, TLMD-II JKPTCL Gladni
Capacity addition of 50 MVA at 132 33 kV level augmenting it from 170 MVA to 200 MVA along with associated works such as uprating of 220 132 33KV busbars construction of 2 no 132kV line bays 2 no 33kV feeder bays
2021_PDD_119417_1
TLMD-II/J/17 of 2020-21 dated 05-03-2021
Open Tender
Electrical Works
270 days
Gladni
As per NIT and SBD
3 documents required · 3 mandatory
₹8,000
Executive Engineer, TLMD-II JKPTCL Gladni
₹25 L
24 Apr 2021
5 Mar 2021
9 Apr 2021
8 Mar 2021
6 Apr 2021
25 Mar 2021
10 Mar 2021 - 15 Mar 2021
Amount
(A)Design, Engineering, Manufacture, testing at manufacture’s work, packing and forwarding, insurance, transportation to project site as per approved design/drawings and in conformity to the relevant and applicable BIS/ IEC and CEA standards
MAIN EQUIPMENTS
POWER TRANSFORMER
50 MVA 132/33 KV three phase power Xmer with OLTC ,SCADA compatible ,Digital RTCC,NIFPS,Common Marshalling Box, HV& LV connectors and other required accessories including mandatory spares .
CIRCUIT BREAKERS
3 pole, SF6 Gas filled, out door circuit breakers with operating mechanism, all accessories, auxiliaries and marshalling boxes / kiosks, SF6 Gas (first filling plus 10 Kg. cylinder additional) alongwith supporting structures etc. complete in all respects as specified in the technical specification and its erection including its testing and commissioning.
145 kV, 1600 Amps of 3 Phase,50C/s,and 31.5 kA(rms) for 1sec
3 Pole , Vaccum Circuit Breaker (outdoor) 2500 Amp with offered operating mechanism all accessories auxillaries and marshalling boxes/ kiosks, etc complete in all respects with spare Vaccum bottle as specified in the technical specification. and its erection including its testing and commissioning.
36KV ,2500 Amps of 3 phase ,50 C/s and 25 KA(rms) for I sec
ISOLATORS (including bus sectionalisers)
145 kV, 50 c/s, 1600 Amps,31.5 kA for one second, AC Motor Operated horizontal double break, outdoor type isolators with all accessories including solid core post insulators, auxiliaries, marshalling boxes, other essentials, complete in all respects as specified in the technical specification and its erection including its testing and commissioning.
3 pole without earth switches
3 pole with one earth switch
36 kV, 50 c/s, 2500 Amps, 25 kA for one second, Manually Operated horizontal double break, outdoor type isolators with all accessories including solid core post insulators, auxiliaries, marshalling boxes, other essentials, complete in all respects as specified in the technical specification and its erection including its testing and commissioning.
3 pole without earth switches
3 pole with one earth switch
Bus Post Insulator
145 KV Solid Core Post Insulators
36 KV Solid Core Post Insulators
INSTRUMENT TRANSFORMERS
CURRENT TRANSFORMERS
Single phase, 50 c/s Current Transformers including first fill of transformer oil plus 10% extra and all accessories, auxiliaries etc. complete in all respects as specified in the specification and its erection including its testing and commissioning.
33KV NCT(300/1)
SURGE ARRESTER
Single phase, 50 c/s, outdoor, metal oxide gapless type arresters including surge counters / monitors, insulating base and all associated accessories, auxiliaries, complete in all respects as specified in the technical specification and its erection including its testing and commissioning.
CONTROL & RELAY PANEL
Control, Relay & Protection panels duplex for the 132KV side of 50MVA, 132KV/33KV transformer completely equipped and wired as per the specification and ready for sub-station automation its erection including its testing and commissioning.
Control, Relay & Protection panels simplex for the 33KV side of 50MVA, 132KV/33KV transformer completely equipped and wired as per the specification and ready for sub-station automationits erection including its testing and commissioning.
Cable trays ,Cable Racks and accessories
Perforated galvanised cables trays and ladders including bends, tees, cross connections, reducers etc fixing arrangments such as coupler, bolts, nuts and washers, etc/ of various sizesand types as per design alongwith accessories complete in all respects and its erection including its testing and commissioning.
600mmx2500mm
300mmx2500mm
Lugs ,Ferrules,Welding material cotton wastes etc (Lump sum)
132KV main and equipment structures
Structures with stubs Column of C1 type-4Nos Column ofC2 - 4Nos Beam of B1 type- 4No, Beam B2 type- 4 Nos Equipment structures, Circuit breaker structure - 2 No., CT structure- 6 No., NCT structure - 1No. Surge Arrester structure - 6No. Isolator structure - 8 Nos P I Structure -6 Nos and its erection including its testing and commissioning.
Nuts and bolts
33KV main and equipment structures
Structures with stubs column C3 type -4 Nos column C4 type -4 Nos Beam B3 type - 4Nos Beam B4 type- 4Nos Equipment structures, Circuit breaker structure - 2 No., CT structure- 6 No, Isolator structure - 8No, Surge Arrester structure - 6No. and its erection including its testing and commissioning.
Nuts and bolts
Power and control cables
2 Core 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
5 Core 2.5 sq mm1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
8 Core 2.5 sq mm1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
12 Core 2.5 sq mm1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
16 Core 2.5 sq mm1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
20 Core 2.5 sq mm1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
Bay Marshalling Koisk(132KV)as per approved design
Bay Marshalling Koisk(33KV)as per approved design
Conductor and Hardware Fittings(As per STR) and its erection complete job done(As per STR)
0.5 ACSR Moose Conductor
Single Tension Fittings For Single Moose
Single Tension For Twin Moose
Double Tension for single moose
Double Tension for Double moose
Single suspension for double moose
Disc Insulators 120 KN
Disc Insulators 70 KN
T Clamps suitable for moose conductor
T Clamps Twin suitable for moose conductors
Spacers for Twin Moose
P I Clamps for Moose conductor
PG Clamps for Moose conductor
Earth Wire 7/3.15mm
Earth Wire Tension Clamps
Earthing Material for main earth mat with MS Flat 75x12 and equipment and structure earthing with GS Flat 50x8mm and embedding spikes as per earthmat design
MS Flat 75mmx12mm
GS Flat 50mm x 8mm
UPRATING OF BUSBARS WITH HTLS by way of Replacement of existing Bus bar conductor twin ACSR Moose with twin HTLS ACCC DRAKE along with necessary accessories such as long insulators,Tension and suspension fiitings, T clamps /isolator clamps / CT/PT clamps suitable for HTLS ACCC Drake as per approved design and Make (to be finalised during detailed engineering ) in respect of 220 KV. 132KV and 33 KV MAIN and TRANSFER BUS and INCOMING 132 KV TRANSFORMER BAYS
HTLS Conductor ACCC Drake
Bus Bar Tension fitting suitable for twin HTLS ACCC DRAKE as per approved design and Make (to be finalised during detailed engineering ) required for the complete job of required for the complete job of uprating of Main and transfer Bus bars in respect of 08 Nos 220KV Bays, 14 Nos 132KV bays,15 Nos 33KV Bays, and 03 Nos 220/132 KV incomer transformer bays
Bus bar suspension fitting suitable for twin HTLS ACCC DRAKE as per approved design and Make (to be finalised during detailed engineering ) required for the complete job of required for the complete job of uprating of Main and transfer Bus bars in respect of 08 Nos 220KV Bays, 14 Nos 132KV bays,15 Nos 33KV Bays, and 03 Nos 220/132 KV incomer transformer bays
220 KV long insulators suitable for twin HTLS ACCC DRAKE as per approved design and Make (to be finalised during detailed engineering ) required for the complete job of required for the complete job of uprating of Main and transfer Bus bars in respect of 08 Nos 220KV Bays and 03 Nos 220/132 KV incomer transformer bays
132 KV long insulators suitable for twin HTLS ACCC DRAKE as per approved design and Make (to be finalised during detailed engineering ) required for the complete job of required for the complete job of uprating of Main and transfer Bus bars in respect of 14 Nos 132KV bays, and 03 Nos 220/132 KV incomer transformer bays
33 KV long insulators suitable for twin HTLS ACCC DRAKE as per approved design and Make (to be finalised during detailed engineering ) required for the complete job of required for the complete job of uprating of Main and transfer Bus bars in respect of15 Nos 33KV Bays,
Equipment Clamps (such as CT, PT, PI, Isolator and LA) suitable for twin HTLS ACCC DRAKE as per approved design and Make (to be finalised during detailed engineering ) required for the complete job of required for the complete job of uprating of Main and transfer Bus bars in respect of 08 Nos 220KV Bays, 14 Nos 132KV bays,15 Nos 33KV Bays, and 03 Nos 220/132 KV incomer transformer bays
Other improvement works in the Existing bays of the Grid
Marshalling Kiosks suitable for 220 KV yard as per STR, drawing and Make (to be finalised during detailed engineering ) required for the complete replacement job
Marshalling Kiosks suitable for 132 KV yard as per STR, drawing and Make (to be finalised during detailed engineering ) required for the complete replacement job
Marshalling Kiosks suitable for 33 KV yard as per STR , drawing and Make (to be finalised during detailed engineering ) required for the complete replacement job
Control cables for the replacement of damaged cables in exisiting yard
2 Core 2.5 sq mm 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
5 Core 2.5 sq mm 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
8 Core 2.5 sq mm 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
12 Core 2.5 sq mm 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
16 Core 2.5 sq mm 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
Other Security related works in the Existing Grid station premises
Design installation testing and commisioning along with Annual maintenance contract for five years of the technoologically advanced /Updated CCTV surveillance with minimum 04 Nos IP-PTZ cameras 2.00MP 36X(Sony Starvis sensor),16 channel NVR,2 SATA,Surveillance Harddisk 4TB,OFC armoured 6 core,CAT6 UTP 23AWG outdoor cable,media converter Gigabit,4 port Gigabit switch,Rack 9U and Fixed Cameras for enhanced coverage of major yards, critical equipments and boundary walls as per the directions and satisfaction of the Engineer Incharge
(B)Handling, Storage, Preservation, Dismantling, Erection (except Civil Works), Testing & Commissioning
MAIN EQUIPMENTS
POWER TRANSFORMER
50 MVA 132/33 KV three phase power Xmer with OLTC ,SCADA compatible ,Digital RTCC,NIFPS,Common Marshalling Box, HV& LV connectors and other required accessories including mandatory spares .
De-erection of 20 MVA three phase power transformer for making space for 50 MVA and dragging the transformer from the foundation to the rail track
CIRCUIT BREAKERS
3 pole, SF6 Gas filled, out door circuit breakers with operating mechanism, all accessories, auxiliaries and marshalling boxes / kiosks, SF6 Gas (first filling plus 10 Kg. cylinder additional) alongwith supporting structures etc. complete in all respects as specified in the technical specification and its erection including its testing and commissioning.
145 kV, 1600 Amps of 3 Phase,50C/s,and 31.5 kA(rms) for 1sec
3 Pole , Vaccum Circuit Breaker (outdoor) 2500 Amp with offered operating mechanism all accessories auxillaries and marshalling boxes/ kiosks, etc complete in all respects with spare Vaccum bottle as specified in the technical specification. and its erection including its testing and commissioning.
36KV ,2500 Amps of 3 phase ,50 C/s and 25 KA(rms) for I sec
ISOLATORS (including bus sectionalisers)
145 kV, 50 c/s, 1600 Amps,31.5 kA for one second, AC Motor Operated horizontal double break, outdoor type isolators with all accessories including solid core post insulators, auxiliaries, marshalling boxes, other essentials, complete in all respects as specified in the technical specification and its erection including its testing and commissioning.
3 pole without earth switches
3 pole with one earth switch
36 kV, 50 c/s, 2500 Amps, 25 kA for one second, Manually Operated horizontal double break, outdoor type isolators with all accessories including solid core post insulators, auxiliaries, marshalling boxes, other essentials, complete in all respects as specified in the technical specification and its erection including its testing and commissioning.
3 pole without earth switches
3 pole with one earth switch
Bus Post Insulator
145 KV Solid Core Post Insulators
36 KV Solid Core Post Insulators
INSTRUMENT TRANSFORMERS
CURRENT TRANSFORMERS
Single phase, 50 c/s Current Transformers including first fill of transformer oil plus 10% extra and all accessories, auxiliaries etc. complete in all respects as specified in the specification and its erection including its testing and commissioning.
33KV NCT(300/1)
SURGE ARRESTER
Single phase, 50 c/s, outdoor, metal oxide gapless type arresters including surge counters / monitors, insulating base and all associated accessories, auxiliaries, complete in all respects as specified in the technical specification and its erection including its testing and commissioning.
CONTROL & RELAY PANEL
Control, Relay & Protection panels duplex for the 132KV side of 50MVA, 132KV/33KV transformer completely equipped and wired as per the specification and ready for sub-station automation its erection including its testing and commissioning.
Control, Relay & Protection panels simplex for the 33KV side of 50MVA, 132KV/33KV transformer completely equipped and wired as per the specification and ready for sub-station automationits erection including its testing and commissioning.
Cable trays ,Cable Racks and accessories
Perforated galvanised cables trays and ladders including bends, tees, cross connections, reducers etc fixing arrangments such as coupler, bolts, nuts and washers, etc/ of various sizesand types as per design alongwith accessories complete in all respects and its erection including its testing and commissioning.
600mmx2500mm
300mmx2500mm
Lugs ,Ferrules,Welding material cotton wastes etc (Lump sum)
132KV main and equipment structures
Structures with stubs Column of C1 type-6Nos Column ofC2 - 2Nos Beam of B1 type- 2No, Beam B2 type- 4 Nos Equipment structures, Circuit breaker structure - 1 No., CT structure- 3 No., NCT structure - 1No. Surge Arrester structure - 6No. Isolator structure - 5 Nos P I Structure -6 Nos and its erection including its testing and commissioning.
Nuts and bolts
33KV main and equipment structures
Structures with stubs column C3 type -2 Nos column C4 type -2 Nos Beam B3 type - 2Nos Beam B4 type- 4N0s Equipment structures, Circuit breaker structure - 1 No., CT structure- 3 No, Isolator structure - 5No, Surge Arrester structure - 3No. and its erection including its testing and commissioning.
Nuts and bolts
Power and control cables
2 Core 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
5 Core 2.5 sq mm1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
8 Core 2.5 sq mm1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor controlcable complete
12 Core 2.5 sq mm1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
16 Core 2.5 sq mm1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
20 Core 2.5 sq mm1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
Bay Marshalling Koisk(132KV)as per approved design
Bay Marshalling Koisk(33KV)as per approved design
Conductor and Hardware Fittings and its erection complete job done
0.5 ACSR Moose Conductor
Single Tension Fittings For Single Moose
Single Tension For Twin Moose
Double Tension for single moose
Double Tension for Double moose
Single suspension for double moose
Disc Insulators 120 KN
Disc Insulators 70 KN
T Clamps suitable for moose conductor
T Clamps Twin suitable for moose conductors
Spacers for Twin Moose
P I Clamps for Moose conductor
PG Clamps for Moose conductor
Earth Wire 7/3.15mm
Earth Wire Tension Clamps
Earthing Material for main earth mat with MS Flat 75x12 and equipment and structure earthing with GS Flat 50x8mm and embedding spikes as per earthmat design
MS Flat 75mmx12mm
GS Flat 50mm x 8mm
UPRATING OF BUSBARS WITH HTLS by way of Replacement of existing Bus bar conductor twin ACSR Moose with twin HTLS ACCC DRAKE along with necessary accessories such as long insulators,Tension and suspension fiitings, T clamps /isolator clamps / CT/PT clamps suitable for HTLS ACCC Drake as per approved design and Make (to be finalised during detailed engineering ) in respect of 220 KV. 132KV and 33 KV MAIN and TRANSFER BUS and INCOMING 132 KV TRANSFORMER BAYS
Replacement of existing Bus bar conductor twin ACSR Moose with twin HTLS ACCC DRAKE along with necessary accessories such as long insulators,Tension and suspension fiitings, T clamps /isolator clamps / CT/PT clamps suitable for HTLS ACCC Drake as per approved design and Make (to be finalised during detailed engineering ) in respect of 220 KV MAIN and TRANSFER BUS of 08 Nos 220KV Bays including dismantling of existing conductor and accessories and its write back of de-erected material to Divisional stores at Gladni
Replacement of exisitng Bus bar conductor twin ACSR Zebra with twin HTLS ACCC DRAKE along with necessary accessories such as long insulators,Tension and suspension fiitings, T clamps /isolator clamps / CT/PT clamps suitable for HTLS ACCC Drake as per approved design and Make (to be finalised during detailed engineering ) in respect of 132 KV MAIN and TRANSFER BUS of 14 Nos 132KV bays including dismantling of existing conductor and accessories and its write back of de-erected material to Divisional stores at Gladni
Replacement of exisitng Bus bar conductor twin ACSR Moose with twin HTLS ACCC DRAKE along with necessary accessories such as long insulators,Tension and suspension fiitings, T clamps /isolator clamps / CT/PT clamps suitable for HTLS ACCC Drake as per approved design and Make (to be finalised during detailed engineering ) in respect of 33 KV MAIN and TRANSFER BUS 15 Nos 33KV bays including dismantling of existing conductor and accessories and its write back of de-erected material to Divisional stores at Gladni
Replacement of exisitng Bus bar conductor twin ACSR Moose with twin HTLS ACCC DRAKE along with necessary accessories such as long insulators,Tension and suspension fiitings, T clamps /isolator clamps / CT/PT clamps suitable for HTLS ACCC Drake as per approved design and Make (to be finalised during detailed engineering ) in respect of INCOMER TRANSFORMER BAYS OF 400MVA BANK,160 MVA and 150 MVA 220/132KV AUTOTRANSFORMERS including dismantling of existing conductor and accessories and its write back of de-erected material to Divisional stores at Gladni
Other works at Existing bays of the Grid
Dismantling of existing Marshalling Kiosk in 220 KV yard and replacing it by new marshalling including identifying , record preparation ,laying and making connection with proper dressing and terminations as per the directions of the Engineer Incharge
Dismantling of existing Marshalling Kiosk in 132 KV yard and replacing it by new marshalling including identifying , record preparation ,laying and making connection with proper dressing and terminations as per the directions of the Engineer Incharge
Dismantling of existing Marshalling Kiosk in 33 KV yard and replacing it by new marshalling including identifying , record preparation ,laying and making connection with proper dressing and terminations as per the directions of the Engineer Incharge
Replacement of damaged control cables in respect of existing yards including identifying ,laying and making connection with proper dressing and terminations as per the directions of the Engineer Incharge
2 Core 2.5 sq mm 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
5 Core 2.5 sq mm 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
8 Core 2.5 sq mm 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
12 Core 2.5 sq mm 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
16 Core 2.5 sq mm 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
Reorientation of existing Control and relay panels in the Control room for making space for new C&R panels including electrical and civil works if any
Painting of existing 220/132 KV Auto transformers after proper cleaning and removal of grease / oil , with approved colour with minimum three coats for even and smooth finish and to the satisfaction of the Engineer Incharge
Painting of existing 132 /33 KV 20/50 MVA power transformers after proper cleaning and removal of grease / oil , with approved colour with minimum three coats for even and smooth finish and to the satisfaction of the Engineer Incharge
Dismantling of substation auxilliary for making space for 33 KV incomer and its re-erection of auxilliary transformer at new place .
Dismantling of existing Capacitor Bank for making space for the creation of 33 Kv feeder bays
Dismantling of uncharged 33 KV feeder in the proposed area of extension of the 132 KV yard and its re-erection outside the 132 yard boundary wall
Dismantling of lighting tower inside the land for the development of 132 KV line Bay.
Re-erection of dismantled Lighting tower in the 132 KV yard at another suitable place.
(C) Civil Works including design, supply, execution and preparation of drawings
DESIGN & PREPARATION OF CONSTRUCTION / STRUCTURAL DRAWINGS
Development of substation layout drawings(in AUTOCAD and PDF formats) of the complete 132/33KV Grid Station premises with existing bay arrangement and Design and Ddevelopment of layout of new 01 No 132KV and 01 No 33KV new indicating within the available space as per list in(Plan and Elevation),cable trench,layout,earthing and shielding layout,transformer firewall layout,transformer foundation layout and other allied works.Preparation of civil and structural designs and construction drawings for all foundation of Transformer, Gantries, equipment supporting structures, Cable trenches ,I beam or H beam / Joist columns for separation of 132 and 33KV Busbar in existing 3 no and new transformer bays , Earth mat and works not explicitly defined but reasonably implied and required for the construction of 1 no. 132 KVtransformer bay AND 1 No. 33 KV incomer bay for the successful commisioning of 50MVA 132/33KV transformer by obtaining approval of all the designs and drawings from the consultant/owner.
Development of land in the area (15MX50M), by way of filling excavated soil of yard foundations to be disposed and additional filling if required for creation of space for new 132 KV and 33 KV yards on the directions of Engineer Incharge or his representative
Dismantling of existing 132 and 33 KV yard retaining wall and mesh fencing(120 Meter length) for creation of space for new 132 KV and 33 KV yards
Construction of new retaining wall as per approved design after extension of 132 KV and 33 KV yard and placement of mesh fencing thereof .
FOUNDATION FOR TRANSFORMER GANTRIES AND EQUIPMENT SUPPORTING STRUCTURES (CIVIL WORKS) as per approved design drawings and specification for Civil works mentioned in SBD
132 KV Side
Column Foundation 08 Nos
Isolator Foundation 08 Nos
SF6 Breaker Foundation 02 Nos
CT Foundation 06 Nos
NCT Foundation 01 Nos
LA Foundation 06 Nos
Post Insulator 12 Nos
33 KV Side
Column Foundation 08 Nos
Isolator Foundation 08 Nos
VCB Foundation 02 Nos
CT /NCT Foundation 06 Nos
LA Foundation 06 Nos
Post Insulator 06 Nos
LIGHTING TOWER FOUNDATION AT ANOTHER SUITABLE PLACE EXTENSION OF YARD 1 no
Transformer Foundation suitable for 33/11KV 250 KVA Substation Auxilliary transformer 01 Nos
Construction of new retaining wall as per approved design after extension of 132 KV and 33 KV yard and placement of mesh fencing thereof .
Excavation in all type of soils including mixed soils (i.e. soils containing pebbles/boulders etc.) for any section including all labour, POL, hire charges of equipments and T&Ps etc. including shuttering & shoring, dewatering, lifting, handling and stock piling of excavated materials, back filling with excavated or borrowed earth and disposal of surplus excavated earth as directed for all leads & lifts complete as per specification, construction drawings and direction of Engineer-in-charge.
Providing & Laying of concrete including cost of all material, labour,T&P,leads & lifts shoring and shuttering, formwork,stock piling,carriage use of admixtures,curing and other associated works and fixing of foundation Bolts including two coats of cement plaster 12 mm thick cement plaster 1:5 (1 cement ;5 coarse sand) finished with top layer 6mm thick cement plaster on the exposed portion of all the foundations
Concrete of M-10 grade having cube strength of10N/ mm2 with 40mm nominal size & 25 N / mm2 with 20 mm nominal size respectively.
Concrete of M-25 grade having cube strength of10N/ mm2 with 40mm nominal size & 25 N / mm2 with 20 mm nominal size respectively.
Providing and laying Random Rubble masonary with hard stone from quarry in foundation & plinth( 1 cement : 6 coarse Sand :12 grade stone aggreage 20 mm nominal size ) at plinth level including all supply and Carriages ( Mechanical & Manual)
SUPPLY & PLACEMENT OF REINFORCEMENT/ RAIL ASSEMBLY
Mild steel reinforcement conforming to IS: 432 for R.C.C. or any other work including the cost of all materials, binding wire, labour, hire charges of equipments and T&P, POL etc for bending, binding, placing and tieing in position complete as per specification.
Earth mat
Excavation for Laying of Earthing Mat Main with MS Flat 75x12mm including equipment and structure earthing with GS Flat 50x12mm and back filling with good earth as per the directions of the Engineer incharge complete job
Laying of PCC sub base in 1:3:6 in 33 KV and 132 KV and transformer yard with expansion joints and spreading of Gravels thereof as per specification for the works mentioned in SBD
Construction of Cable duct along with its covers( including cost of excavation , formwork, concreting , fixing of angle making of angle framed cable duct covers as per approved lay out plan and cable trench crossectional drawing
132 KV yard
Main Duct of Size 1200mm x 1200mm with 75mm Concrete Covers grade M20 of size 1300x500 mmAS PER APPROVED DESIGN
Sub Main Duct of Size 600mm x 600mm with 75mm Concrete Covers grade M20 of size 700x500 mm AS PER APPROVED DESIGN
Tee off Duct: 150mm sand filled HDPE pipes from Sub main to Equipments in the outdoor area
33 KV yard
Main Duct of Size 900mm x 600mm with concrete grade M20 of size 500 x 1000 mm AS PER APPROVED DESIGN
Sub Main Duct of Size 600mm x 450mm with concrete grade M20 of size 700x500 mm AS PER APPROVED DESIGN
Tee off Duct: 150mm sand filled HDPE pipes from Sub main to Equipments in the outdoor area
Fixing/Placing of Perforated galvanised Cables trays and ladders including bends, tees, cross connections, reducers, etc., fixing arrangements such as coupler, bolts, nuts and washers, etc., of various sizes and types as per design alongwith accessories complete in all respects
132KV Cable duct
1200mm x 1200mm
600mmx 600mm
33KV Cable duct
900mm x 600mm
600mm x 450mm
300mm x 300mm
REPAIR OF DAMAGED CABLE DUCT OF DIFFERENT CROSSECTIONS AT DIFFERENT PLACES AND CABLE DUCT COVERS OF EXISTING 220 KV , 132KV and 33KV and TRANSFORMER YARDS AS PER THE DIRECTIONS OF ENGINEER INCHARGE
Making of frames of MS angle iron of size 45x45x6mm
Concrete of M-20 grade having cube strength of 20 N / sq mm with 20 mm nominal size coarse aggregate.
Mild steel reinforcement conforming to IS: 432 for R.C.C. or any other work including the cost of all materials, binding wire, labour, hire charges of equipments and T&P, POL etc for bending, binding, placing and tieing in position complete as per specification.
Other Civil works in the Existing Grid station premises
Removal of unserviceable equipment, material from yards , cleaning of unwanted growth, removal of existing stone metal, antiweed treatment and Repair of already laid PCC (1:3:6)and laying back of stone metal in an even manner in the existing 220 KV , 132KV and 33 KV yards ( approximate Area 25000 sqmtr)to the satisfaction of Engineer Incharge
Painting of existing 220/132 KV Auto transformers after proper cleaning and removal of grease / oil , with approved colour with minimum three coats for even and smooth finish and to the satisfaction of the Engineer Incharge
Painting of existing 132 /33 KV 20/50 MVA power transformers after proper cleaning and removal of grease / oil , with approved colour with minimum three coats for even and smooth finish and to the satisfaction of the Engineer Incharge
Other Security related works in the Existing Grid station premises
Raising the height of the boundary wall at identified places, fixing of angle posts and placing two layers of the concertina wires all along the ground and at the top of the boundary wall (length 1700 mtr)of Grid Station premises for security measure to the satisfaction of Engineer Incharge
Construction of storage shed( 100 sq mtrs)made out of CGI sheets and steel frame for the safeguard of the equipment (with residual life) against water ingress, dismantled under PSDF, within the Grid station Complex / Divisional Stores
Construction of borewell with pumping arrangement without reservoir within the complex in close vicinity of Grid station Control room Building for augmenting the water supply to the premises and pipe network feeding the fire protection system
KAILASH DEVBUILD (INDIA) PVT. LTD.
Suncity Enterprises
KANOHAR ELECTRICALS LIMITED
DAMODHARTECH INTERNATIONAL PVT. LTD.
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx