Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹5.0 LAccepted-Finance | ₹5.0 L | L1 | Accepted-Finance Accepted |
| 2 | L2₹6.0 L+₹96,595.37 (19.2%)Accepted-Finance | ₹6.0 L+₹96,595.37 (19.2%) | L2 | Accepted-Finance Accepted |
| 3 | L3₹6.1 L+₹1.0 L (20.3%)Accepted-Finance | ₹6.1 L+₹1.0 L (20.3%) | L3 | Accepted-Finance Accepted |
| 4 | L4₹6.7 L+₹1.7 L (33.3%)Accepted-Finance 272 VIKAS KUNJ VIKAS PURI NEW DELHI 110018 | WEST | DELHI | 110018 | ₹6.7 L+₹1.7 L (33.3%) | L4 | Accepted-Finance Accepted |
| 5 | L5₹7.3 L+₹2.3 L (44.8%)Accepted-Finance K 4 50 GALI NO 27 WEST GHONDA DELHI 110053 DELHI 110033 | NORTH | DELHI | 110033 | ₹7.3 L+₹2.3 L (44.8%) | L5 | Accepted-Finance Accepted |
Tender Value
₹8.4 L
EMD Value
₹16,785
Closing Date
10 Jun 2026, 3:00 pmClosed
Executive Engineer(E)
Judiciary Electrical Division-I, PWD, Yamuna Western Bank, Lok Nayak Setu, New Delhi-110002
RMO Specialized Electrical and Mechanical Services at Tis Hazari Court Complex, Delhi. (SH Supply and replacement of wornout/faulty Air Circuit Breaker (ACB) of the existing LT Panel and motorized Changer over switch.)
2026_PWD_292533_1
54/EE(E)/JED-1/PWD/2026-27
Open Tender
Electrical Works
Percentage
15 days
Tis Hazari Court Complex
Please refer Tender documents.
2 documents required · 2 mandatory
₹0
₹16,785
17 Jun 2026
2 Jun 2026
10 Jun 2026
2 Jun 2026
10 Jun 2026
2 Jun 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply, Installation, Testing and Commissioning of 2000 Amps, 415V, 50Hz, 3 Pole, Draw-out type Air Circuit Breaker (ACB) suitable for LT panel incomer from Transformer complete with the following:
Microprocessor-based release with adjustable protection for: Overload (L), Short Circuit (S) ,Instantaneous (I) Earth Fault (G), Rated breaking capacity not less than 50 kA, Motorized spring charging mechanism, Shunt trip and under-voltage release (UVR), Mechanical ON/OFF and trip indication, Electrical and mechanical interlocks, Auxiliary contacts, Safety shutters and arc chute assembly, Terminal spreaders, phase barriers, and all standard accessories, Compatible with existing LT panel having following item:-
2000A Three Pole 50 KA MDO ACB - 1 No.
Bus Bar Connections 2000A (2R x 100 x 10 mm TPN Al) - 1 No.
Heat Shrinking Sleeves for Bus-BAR - 1 No.
Nut-Bolt, Washers - LS
R/Y/B indication - 1 No.
6A SP Control MCB 10 KA (C Curve) - 4 Nos.
Retrofitting cost :- Installation of Breaker, Bus-Bar Fitting, Sleeves, Nut Bolt, Servicing of Main Bus-Bar and testing of Complete Panel) | 1 | Job | 7,34,437 | ₹7,34,437 |
| 2 | Supply, Installation, Testing and Commissioning of 400 Amps, 415V, 50Hz, 4 Pole Motorized Changeover Switch, suitable for LT distribution system, complete with the following:
On-load changeover with I–0–II (Source Selector) operation Suitable for switching between two power sources High short-circuit withstand capacity as per system fault level
Sheet steel enclosure with dust and vermin proof construction (IP-54 or better), Proper interlocking mechanism to prevent simultaneous closing of both sources, Clearly visible ON/OFF and source indication, Suitable busbar / terminal arrangement for 400A rating, Control wiring etc. complete as required. | 1 | No. | 1,04,793 | ₹1,04,793 |
stage.html
html • 0.05 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.74 MB
BOQ_388548.xls
BOQ • 0.33 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .