Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹11.3 CrAccepted-Finance | ₹11.3 Cr | 1 | Accepted-Finance TECHNICALLY RESPONSIVE |
| 2 | Rejected-Technical | - | - | Rejected-Technical Technically Not responsive |
Tender Value
₹11.3 Cr
EMD Value
₹11.3 L
Closing Date
7 Dec 2023, 3:00 pmClosed
Commissioner
Commissioner Tiruppur City Municipal Corporation office, Tiruppur.
Providing SCADA system for Raw Water Intake Pump House and feeder main Tapping points 5 Nos and 70 Nos OHT inlet supply in Tiruppur Corporation
2023_MAWS_387283_1
E1 / 4897 / 2023
Open Tender
Water Supply/Equipments/Meter/Drilling/Boring
365 days
Tiruppur
Please refer Tender documents.
5 documents required · 5 mandatory
₹0
₹11.3 L
Tiruppur City Municipal Corporation
22 Dec 2023
9 Nov 2023
7 Dec 2023
9 Nov 2023
7 Dec 2023
22 Nov 2023
22 Nov 2023
Amount
ELSR/ Tapping PRESSURE - FLOW MONITORING AND CONTROL - RTU/PLC PANEL
Supply & Erection of Remote Monitoring Panel - made of CRCA material with powder coated, Panel outer surface coated with anti-corrosive, heat resistant coating - suitable for outdoor installation, housing the RTU/PLC Controller, Flow meter Electronic Transmitter Unit, GSM-GPRS Communication unit, Signal Conditioner, Interposing relays, Power Relays, Changeover Relays, temperature, humidity sensor, heater, door limit switch, power, control, signal connectors, cable tray, DIN rail, etc. as per the application requirement, with suitable ventilation arrangement, vandalism sensor, and other components required as per the application requirements
The RTU panel shall have the Provision required for measuring the -flow rate (4 to 20mA) from the ELSR inlet & Outlet - Electromagnetic flow meter is connected with Signal/Communication Bus to the controller. Flow Quantity Pulse signal (for the flow quantity) from the electromagnetic flow meter, downstream pressure sensor cum transmitter interface, Pressure-flow control valve Interface, ELSR _ Level Sensor as per the technical specification & application requirements.
Panel door open/close limit switch, Panel Key and Lock arrangement, Surge arrestor for the AC/DC input to the charger, Connection, termination, Cable gland for the signal cables. Control, Power Cable, connectors, ferrules, lugs etc. as per the technical specification
COMMUNICATION BUS Flow meter shall communicate to the RTU/PLC controller through RS485 Interface to the Electromagnetic Flow Meter. For device configuration a Modbus shall be available, providing full access to all parameters.
Installation and Commissioning of RTU/PLC Remote Monitoring Panel with suitable accessories
PRESSURE TRANSDUCER/ TRANSMITTER
Supply, Fixing & Erection of pressure transducer/ transmitter with 4 to 20mA interface as per technical specification. - It shall be IP67/IP68 protected. - It shall be industrial grade - The measuring range according to the application requirement. - Elastomer-sealed - Process Connection material SS304 - Sensor Material – Ceramic type - Long-Term stability <0.2% - Accuracy ± 0.25%
- Operating temperature range 5 Deg.C to 100 Deg.C - The output shall be 4 to 20mA - It shall be energised by signal loop power - No display shall be required - The control voltage shall be 24VDC
Design, Manufacturing and supply & Commissioning of Pressure Transducer Hook-up system consists of suitable pipe, bend, coupling, Ball Valve with suitable accessories.
LEVEL TRANSMITTER
Supply & Erection of Level Transmitter with 4 to 20mA interface along with accessories
Level Transmitter fixing Plate/ Galvanised Sheet/canopy with fixing accessories
CABLE & Earthing Supply & Laying of Field Communication/Signal Cable and Power cable for the Electromagnetic Flow Transmitter, Pressure transmitter, Level Transmitter, Pressure-Flow Control Valve, Power Cable from the EB source, HDPE Conduit where ever required- as per the technical specification as per the application requirement.
GI coated perforated Cable tray 0f 150mm width X 50mm Height
GI conduit for field Instruments wiring (40 mm Dia)
Panel Battery Wiring
L.T. CABLES 4 CORE 2.5 Sqmm 1.1 KV GRADE ARMOURED COPPER CONDUCTOR CROSS LINKED POLY ETHYLENE INSULATED PVC SHEATHED & OVER SHIELDING CABLES CONFORMING TO IS 7098 (PART I)/1988 AND AS AMENDED THEREAFTER WITH ISI MARKING
L.T. CABLES 2 CORE 1.5 Sqmm 1.1 KV GRADE ARMOURED COPPER CONDUCTOR CROSS LINKED POLY ETHYLENE INSULATED PVC SHEATHED & OVER SHIELDING CABLES CONFORMING TO IS 7098 (PART I)/1988 AND AS AMENDED THEREAFTER WITH ISI MARKING
L.T. CABLES 3 CORE 1.5 Sqmm 1.1 KV GRADE ARMOURED COPPER CONDUCTOR CROSS LINKED POLY ETHYLENE INSULATED PVC SHEATHED & OVER SHIELDING CABLES CONFORMING TO IS 7098 (PART I)/1988 AND AS AMENDED THEREAFTER WITH ISI MARKING
L.T. CABLES 3 CORE 1.5 Sqmm 1.1 KV GRADE ARMOURED COPPER CONDUCTOR CROSS LINKED POLY ETHYLENE INSULATED PVC SHEATHED & OVER SHIELDING CABLES CONFORMING TO IS 7098 (PART I)/1988 AND AS AMENDED THEREAFTER WITH ISI MARKING For LT Panels
Junction & Instrument Box
Earthing Cable kit with array with following provisions
Supply of maintenance free Earthing system comprising of 17.2 mm dia 2 mtr long Earth electrode of low carbon steel electrode and other components as per the standard and suitable G. I clamp.. 1. By providing highly corrosion resistant Earthing Electrode. 2. By eliminating the corrosion causing elements in the salt. 3. By providing uniform non corrosive, low soil resistivity material around the electrode.
4. Highly conductive, improves earth’s absorbing power and humidity retention capability. 5. Non-corrosive in nature having low water solubility but highly hygroscopic. 6. Resistivity of less than 1.0 Ohms-meter. 7. Suitable for installation in dry form or in a slurry form. 8. Does not depend on the continuous presence of water to maintain its continuity. 9. Permanent and maintenance free and in its “set form”, maintains constant earth resistance with time. 10. Does not dissolve decompose or leach out with time. 11. Does not require periodic charging treatment nor replacement and maintenance.
Removing of soil, lowering of earth rod and refilling with required earth filling compounds, concrete top earthing chamber
Testing of maintenance free earthing system
Terminator
Ferrule & Consumables(end terminal)
Laying of Cables
Accessories Cable Ties. Crimping, Cutting, and Stripping Tools/ Cord Grips / Strain Relief Heat Shrink Tubing Markers & Marking Systems Sealing For Cable & Pipe Wire Connectors
Supply & Fixing of Steel DISMANTLING JOINTS, DI FLANGE SOCKET, DI FLANGE SPIGOT, DI FLANGE REDUCER/EXPANDER, DI Air valve TEE from DI main & DI Y strainer for Tapping points with Connecting Fasteners, Bolts, Nuts & Gaskets. The items shall be used for all the Pipe line components at ELSR inlet & tapping points
80 mm Dismantling joints
100 mm Dismantling joints
125 mm Dismantling joints
150 mm Dismantling joints
200 mm Dismantling joints
250 mm Dismantling joints
300 mm Dismantling joints
450 mm Dismantling joints
600 mm Dismantling joints
800 mm Dismantling joints
450 mm Y- Strainer
600 mm Y- Strainer
800 mm Y- Strainer
80 mm DI K9 Flange Spigot
100 mm DI K9 Flange Spigot
125 mm DI K9 Flange Spigot
150 mm DI K9 Flange Spigot
200 mm DI K9 Flange Spigot
250 mm DI K9 Flange Spigot
300 mm DI K9 Flange Spigot
450 mm DI K9 Flange Spigot
600 mm DI K9 Flange Spigot
800 mm DI K9 Flange Spigot
80x80x50 DI K9 Reduced TEE
100x100x50 DI K9 Reduced TEE
125x125x50 DI K9 Reduced TEE
150x150x50 DI K9 Reduced TEE
200x200x50 DI K9 Reduced TEE
250x250x100 DI K9 Reduced TEE
300x300x100 DI K9 Reduced TEE
450x450x150 DI K9 Reduced TEE
600x600x200 DI K9 Reduced TEE
800x800x200 DI K9 Reduced TEE
400X300 DI K9 Double Socket Concentric Reducer
400X250 DI K9 Double Socket Concentric Reducer
400X200 DI K9 Double Socket Concentric Reducer
350X250 DI K9 Double Socket Concentric Reducer
350X200 DI K9 Double Socket Concentric Reducer
300X250 DI K9 Double Socket Concentric Reducer
300X200 DI K9 Double Socket Concentric Reducer
300X150 DI K9 Double Socket Concentric Reducer
300X125 DI K9 Double Socket Concentric Reducer
300X100 DI K9 Double Socket Concentric Reducer
300X80 DI K9 Double Socket Concentric Reducer
200X125 DI K9 Double Socket Concentric Reducer
150X80 DI K9 Double Socket Concentric Reducer
125X100 DI K9 Double Socket Concentric Reducer
1100X800 DI K9 Double Socket Concentric Reducer
900X600 DI K9 Double Socket Concentric Reducer
600X450 DI K9 Double Socket Concentric Reducer
50 mm Rubber Insertion Gasket
80 mm Rubber Insertion Gasket
100 mm Rubber Insertion Gasket
125 mm Rubber Insertion Gasket
150 mm Rubber Insertion Gasket
200 mm Rubber Insertion Gasket
250 mm Rubber Insertion Gasket
300 mm Rubber Insertion Gasket
450 mm Rubber Insertion Gasket
600 mm Rubber Insertion Gasket
800 mm Rubber Insertion Gasket
Bolts & Nuts with Washer
Supply & Fixing of Manufacture, Supply and Delivery of Tamper proof DI Kinetic Air valve, triple function (ventilating, admitting and venting during operation) air release valves with pressure range from PN 1.0 to 2.5 with body and cover made of Ductile Iron of Grade GGG 40 or equivalent grade conforming to IS 1865 with Food Grade Epoxy Powder coating(EP-P) inside and for outside of colour blue RAL 5005. All internal parts such as float, shell etc., cover bolts, made of Austenitic alloy steel of SS AISI 304/316. The float shall be made of Polytetrafluroethylene/ Austenitic alloy steel of AISI 304/316. Gaskets and seals of EPDM / Neoprene rubber for TCMC Board works anywhere in Tamil Nadu and with 5 years
50mm for DN 125 & 300mm DI main pipe
100mm for DN 350 & 400mm DI main pipe
150mm for DN 600 DI main pipe
DN 200 for DN 900 & 1100 DI main pipe
Supply and Fixing of DI D/F Gate sluice valves (soft seated) resilient seated soft sealing Gate Valves(Sluice Valves) with body Bonnet of Ductile cast iron of Grade GGG 40 or equivalent grade, Wedge fully rubber lined with EPDM replaceable spindle nut without gland packing and with 3 O- Ring protection on the shaft and seals of NBR and the valves should be of Vacuum tight and 100% leak proof with face to face dimensions as per BS 5163- 89/ISI 14846-2000/DIN 3202 F4. All the valves should be with electrostatic powder coating both inside and out side with pocket less straight through body passage. All the valves are to be compatible for buried application with pressure rating PN 10/16 and with 5 years
50mm for DN 125 & 300mm DI main pipe
100mm for DN 350 & 400mm DI main pipe
150mm for DN 600 DI main pipe
DN 200 for DN 900 & 1100 DI main pipe
DI Flow rate Limit control Valve (PN10/16) with the function to limit the flow rate to a set point. In case the downstream demand increases beyond the set limit, the valve closes down to bring the flow back to set limit. The valve shall have an orifice plate and the orifice diameter is designed based on the set point as per the requirement and installed downstream of the control valve. A solenoid to set the limit of elevated service reservoir & to determine the level. “Manufacture supply and delivery of DI D/F Diaphragm type own medium controlled Flow rate Limit Control valve & se;enoid interfacing with cast body of ductile iron grade GGG-50 or equivalent grade or as per IS 3896-Part-2-1985 customized control cylinder for linear control behaviour or equivalent, performed diaphragm and pull out safe profile sealing ring of EPDM, threaded inserts (CORFIX - to prevent the coating from coming off in the connections area as well as corrosion and incrustations in the control circuit) or equivalent.
Flange connection dimensions according to EN 1092, Part 2/ ISO 7005[DIN]/ IS 1538, all parts (Epoxy coating, and diaphragm) in contact with medium are as per KTW and DVGW certified (harmless)/WRAS & NSF approved. The EPDM rubber & Epoxy coating (EP-P) should be approved by W270. (EP-P)/ WRAS & NSF.” Pilot valve system having Stainless Steel / Brass fittings with spring of stainless steel 304 as per standard parts according to DIN EN 12 266-1, orifice plate shall be as per the set point of flow rate and all the external control tubing of SS 304 / Copper/ reinforced plastic rated PN16, Tightness to DIN EN 12 266-1, leakage rate A (or) equivalent and the needle valve/ speed control device should be provided to vary opening speed of the main diaphragm with self-cleaning filter to avoid possibility of dirt build up inside the control tubing and with 5 years warranty
Supply and Erection of DI Diaphragm type Flow Control Valve with Flow Control Pilot & solenoid interfacing to the RTU Controller as per the technical specification
Supply, Erection & Commissioning of ELECTRO - MAGNETIC FLOW METER at ELSR Inlet & Tapping Points
Electromagnetic Flow Meter shall be a velocity sensing Electromagnetic type, microprocessor based signal converter, sealed housing, flanged tube meter for 1.0 Mpa working pressure, manufactured to highest standard available for mag-meters, equipped with minimum six digit digital totalizers, reading in different units (Kiloliters / Cubic meter) and shall be accurate within 0.5% of Measured value, shall operate within a range of 0.3 m/sec to 4 m/sec and be constructed as follows: Meter tube (Sensor) shall be fabricated from stainless steel tube and use class PN10 flat face carbon steel flanges in accordance with IS 1538. These flanges shall be welded to the flow tube. The internal and external of the meter tube shall be blasted to near white and lined with hard rubber/ Polyurethrene/ PTFE preferably by SBR or EPDM. Meter tube shall have a constant nominal inside diameter offering no obstruction to the flow.
The accuracy should be inclusive of linearity, hysteresis, repeatability, temperature and pressure effects. Coil Housing shall be fabricated from stainless steel (SS304)/ Die cast Aluminium/ Carbon steel with anticorriosive paint for corrosion resistance and welded to the tube providing a completely sealed environment for all coils, electrode connections and wiring harness capable of submerged or buried operation with IP68 Protection. Signal Converter shall be pulsed DC coil excitation type with auto zeroing. The signal converter shall be remotely mounted away from the meter. The converter shall indicate direction of flow and provide a flow rate indication and a total of flow volume for both forward and reverse directions. The converter shall provide an isolated 4-20 mA output into minimum 500-ohm load and a frequency output of a maximum of 0-10 KHZ and a scaled pulse output. The microprocessor based signal converter shall have a self-diagnostic test mode and a backlit display that continuously displays “Rate of Flow” and “Total Volume”. Converter shall be supplied with a programmable low flow drop out, higher flow and empty pipe zero return. The signal converter housing should be die-cast aluminum with glass window. The converter cum transmitter should be fully programmable from the front facia. The programming should be user friendly, self-prompting menu driven. Flow meter test calibration certificate from FCRI, flow test lab / NABL accredited lab to be furnished.
Supply & Erection of Electromagnetic flow Meters suitable for customer inlet pipeline with complete hardware accessories as per tender specification. - The Electromagnetic flow transmitter shall be IP68 protected. - The Electromagnetic flow transmitter shall be industrial grade - The measuring range according to the application requirement - Sensor electrode shall be SS316 material - Liner Material – Hard Rubber
Velocity requirement - (calibrated as per gravity flow (very low flow rate requirement.) Operating temperature range 5 Deg.C to 60 Deg.C Maximum withstanding pressure 10Bar Accuracy requirement ±0.5% 4 to 20mA Flow Rate Output Pulse output for flow quantity
UPS & BATTERY - LiFePO4/Lead Acid, SYSTEM with ACDB, 230 VAC, 24 Hour Backup OF PROCESS CONTROL PANEL, OTHER AUXILLARY DEVICES Study, Design, Supply of UPS System 2 kVA & with battery capacity 12V 150AH (2nos), 230 VAC, capacity consists of 8 Hour Backup with Junction Array Box and interconnecting cable as per the technical specification excluding GST.
Installation and commissioning of Power System with suitable mounting accessories as per the technical specification excluding GST.
Supply, Programming, Development, Testing & Commissioning for SCADA Software with Server & Work Station
SCADA Software with required number of Tags/Points, Faceplates with Historian, Firewall, Alarm Generation, Reporting, etc. Web SCADA upto 5 Clients, 2 PCs for Workstations. Accessories with required software & development of Graphical pages
Display of process parameters and status of the individual base stations To provide statistical information to assist management & maintenance programmes. To provide trend and analysis output for system performance analysis. To provide summary of hourly / daily throughput in each pumping main monitoring. Data Logging, History, Trend, Events, etc. should be supported The system software shall be of standard product. No programming shall be required beyond configuration and minor customization. The system software shall be designed to provide a big-data database. All of the programs are to be generalized in nature such that new functions can be added later.
The proposed system should be mostly designed based on open standards, to the extent feasible and in line with overall system requirements, in order to provide for good interoperability with multiple platforms and avoid any technology or technology provider lock-in.
Construction of RCC valve chamber of following inner size with the following specifications For flow meter and control valve chamber . A base concrete should be PCC 1:4:8 mix using 40mm metal to a thickness of 10cm. The base slab of the chamber should be 15cm thick and the side walls should be 15cm thick on all sides and the cover slab should be 23cm thick. The grade of concrete should be RCC M30. Necessary earthwork should be done with enough space (at least 15cm all-round) for outer cantering and fixing of 60cm x 60cm CI manhole cover with frame etc complete as directed by the engineers.
Inner Size: 3.5 x 2.3 x 2.2m
Inner Size: 2.2 x 2 x 2.2m
Construction of panel room for branch 1 and 3 (Refer Drawing enclosed) of size 2mx2m with RCC framed and room withGI Joineries including cost, conveyanceand labour charges etc., complete as per standard specifications
RAW WATER PUMP HOUSE - PUMP HOUSE MONITORING AND CONTROL - PROCESS CONTROL PANEL
Standalone/ Redundant PLC/ RTU System
Design, Assembly, Test and Supply of Remote Monitoring and control of Distribution - Pump House panel made of CRCA sheet material, powder coated with suitable ventilation arrangement-Cooling FANs, Space Heater and to house the process controller module, Digital/Analog input and output modules, Communication module, Battery Charge Controller with communication interface, Profibus/ Ethernet/ Modbus communication Interface to the Valve Actuators and VFD drives system, input power MPCB with signalling contact, Semi conductor fuses, input power disconnection Contactor, Low voltage and high voltage supply disconnector, Surge arrestor- gas discharge tube and other auxiliary devices, etc. excluding GST.
The Standalone/ Redundant PLC/ RTU System shall be complete with latest configuration, necessary programming software for PLC & SCADA and comprising of all accessories not limited to the following:- Programmable Logic Controller (PLC) with Redundant CPU, Power supply, Communication Module, IO & Processor rack (Standard DC), Back up Interface / Expansion Module, Rack (Backplane) 10 slots for IO and Processor. SCADA software shall have facility VPN, OPC, Smart Client, Web Enabled, Automation Report Generation, Archieving, Trends, Data Logging, etc., excluding GST
The Monitoring & Control Panel for measurement of the Pump House Inlet and Outlets water Flow Rate, cumulative flow, line Pressure and sump water level, Multifunction energy parameters. All the signal transmitters shall be connected through PROFIBUS /ETHERNET/ MODBUS communication bus to the process controller module.
The redundant GSM-GPRS communication unit shall be equipped with dual subscriber interface module card. Remote monitoring/ controlling of panel door open/close limit switch, Panel Temperature & Humidity sensor interface to the controller, Panel Heater ON/OFF, Solar Panel Disconnector, Battery Disconnector, Service Person Visit Confirmation Push Button, Field Device RESET from remote, Controller Reset from Remote, Panel Lock and Key arrangement, Surge arrestor protection for the solar voltage input to the charger, copper earth bus bar for signal and power, Cable glands for the signal cables. Control, Power Cables, terminations/connectors, ferrules, lugs etc. as per the tender technical specification,
The Sealed Maintenance free UPS shall be capable of 24 Hours power back-up to power the entire remote monitoring system including the panel components and field instruments/devices, etc. The Battery charger shall be directly connected to the Process Controller through communication bus to fetch the tender specified operational parameters - for effective monitoring of solar panel voltage, current, battery voltage & Current, load current, etc.
Installation and commissioning of PROCESS CONTROLLER panel for the Distribution - -PUMP HOUSE monitoring and control with suitable accessories excluding GST.
UPS SYSTEM with ACDB of 3 kVA, 230 VAC, 1 Hour Backup OF PROCESS CONTROL PANEL, OTHER AUXILLARY DEVICES
Study, Design, Supply of UPS System 3 kVA, 230 VAC, capacity consists of 1 Hour Backup solar panel, solar panel mounting structure, Solar Junction Array Box and Solar Panel interconnecting cable as per the technical specification excluding GST.
Installation and commissioning of Solar Panel Power System with suitable mounting accessories as per the technical specification excluding GST.
RADAR/ ULTRASONIC LEVEL SENSOR
Supply of RADAR/ Ultrasonic Level sensor and transmitter with PROFIBUS/ ETHERNET/ MODBUS Communication Bus interface and mounting arrangement, 0-30 m range, 4-20 mA, 24 VDC supply voltage as per the technical specification excluding GST.
Level Transmitter fixing Plate, Civil Concrete Casting/Galvanished Sheet/canopy, with fixing accessories excluding GST.
Installation and commissioning of RADAR/Ultrasonic Level Sensor with accessories as per the technical specification excluding GST.
PRESSURE TRANSMITTER WITH ISOLATION - Quotation
Supply of Individual Pressure transmitter with Isolation ball valve at Head of pumped water with mounting arrangements Thread Mounted, Diaphgarm sensor 2 wire type, Pressure 0 - 10 bar, 12/24VDC Powered. 4-20 mA Output for PLC, For water application
Installation and commissioning of Pressure Transmitter with accessories as per the technical specification excluding GST.
MOTOR - WINDING TEMPERATURE SIGNAL OUTPUT -ISOLATORS
Study, Design, Testing and Supply of Winding Temperature Signal Isolators suitable for the winding temperature sensors as per technical specification excluding GST.
Installation and commissioning of Winding Temperature Signal Isolators suitable for the winding temperature sensors with suitable mounting arrangement and commissioning accessories as per technical specification excluding GST.
MOTOR - VIBRATION SENSOR & TRANSMITTER in X - Y direction
Study, Design, Testing and Supply of Vibration Sensors/ pads and Transmitters suitable for wide frequency range of vibration as per technical specification excluding GST.
Installation and commissioning of vibration Sensors and Transmitter with suitable mounting arrangement with commissioning accessories as per technical specification excluding GST.
MOTOR - BEARING TEMPERATURE SENSOR
Study, Design, Testing and Supply of Motor Bearing Temperature Sensor and Transmitter suitable for wide Temperature range as per technical specification excluding GST.
Installation and commissioning of Motor Temperature Sensor and Transmitter with suitable mounting arrangement with commissioning accessories as per technical specification excluding GST.
PUMP - SEAL TEMPERATURE SENSOR
Study, Design, Testing and Supply of Pump Seal Temperature Sensor and Transmitter suitable for wide Temperature range as per technical specification excluding GST.
Installation and commissioning of Pump Seal Temperature Sensor and Transmitter with suitable mounting arrangement and commissioning accessories as per technical specification excluding GST.
MOTOR CUM PUMP- NOISE/SOUND-DECIBLE SENSOR
Study, Design, Testing and Supply of Motor- Pump-Noise/Sound- Decibel Sensor and Transmitter suitable for wide decibel range as per technical specification excluding GST.
Installation and commissioning of Motor -Pump-Noise/Sound- Decibel Sensor cum Transmitter with suitable mounting arrangement and commissioning accessories as per technical specification excluding GST.
ON-LINE WATER QUALITY ANALYSER
Study, Design, Testing and Supply of ON-LINE Water Quality Analyser for Turbidity measurement with PROFIBUS/ETHERNET / MODBUS Communication interface suitable for drinking water application as per technical specification excluding GST.
Design, Procure and supply of Hook -up system for the Water Quality Sensors - consists of suitable GI pipe, bend, coupling, valve manifold with suitable accessories excluding GST.
Installation and commissioning of ON-LINE Water Quality analyser with commissioning accessories as per technical specification excluding GST.
GSM - GPRS GATE WAY Recurring Charges
Supply of Subscriber interface module card from two network service providers with (for the Redunantant GSM-GPRS Communication Unit,) GSM-GPRS enabled and valid for one year period including the data cost for transmitting and receiving the data from the remote site to the central water distribution monitoring Centre excluding GST.
FIELD WORK
Signalling Earth Pit Digging, Installing of GI earth Pipe of 2m, and filling of earth pit with char coal of 5kg, salt of 5kg, sand and construction of suitable civil work with cover for the Signalling earth pit excluding GST.
Power Earth Pit Digging, Installing of GI earth Pipe of 2m, and filling of earth pit with char coal of 5kg, salt of 5kg, and construction of suitable civil work with cover for the Power earth pit excluding GST.
Lightening Arrestor Design, Procure and Supply of Lightening Arrestor Rod, Coupling, Flat fixing insulator, anchoring bolt excluding GST.
Lightening Arrestor Earth Pit Digging, Installing of GI earth Pipe of 2m, and filling of earth pit with char coal of 5kg, salt of 5kg, and construction of suitable civil work with cover for the lightening earth pit excluding GST.
GSM-GPRS External Antenna Supply of GSM-GPRS compatible External Antenna, suitable mounting structure, communication cable & Erection and commissioning of the system - when there is poor signal strength excluding GST.
FIELD CABLE
Supply of control, power, signal and communication cables suitable for the filed instruments like - level transducer, pressure transducer, Electromagnetic flow meter, Valve Actuator, Winding Temperature sensor, Vibration Sensor, Bearing Temperature Sensor, Pump Seal Temperature, Water Quality Analyser, Water Quality Sensor probe, Solar Panel, GSM-GPRS communication unit and battery bank etc.,excluding GST.
PVC Insulated 3 core x 1.5 sq.mm Copper Sheated cable for Resistance wiring for winding temperature sensor and motor bearing sensor
GI coated perforated Cable tray 0f 150mm width X 50mm Height
GI pipe electrode of 2m
GI conduit for field Instruments wiring (40 mm Dia)
Copper bus bar (25x3mm)
PVC Insulated 1 core x 6 sq.mm Copper Sheated cable for Panel wiring
L.T. CABLES 2 CORE 1.5 Sqmm 1.1 KV GRADE ARMOURED COPPER CONDUCTOR CROSS LINKED POLY ETHYLENE INSULATED PVC SHEATHED & OVER SHIELDING CABLES CONFORMING TO IS 7098 (PART I)/1988 AND AS AMENDED THEREAFTER WITH ISI MARKING
L.T. CABLES 3 CORE 1.5 Sqmm 1.1 KV GRADE ARMOURED COPPER CONDUCTOR CROSS LINKED POLY ETHYLENE INSULATED PVC SHEATHED & OVER SHIELDING CABLES CONFORMING TO IS 7098 (PART I)/1988 AND AS AMENDED THEREAFTER WITH ISI MARKING
L.T. CABLES 12 CORE 1 Sqmm 1.1 KV GRADE ARMOURED COPPER CONDUCTOR CROSS LINKED POLY ETHYLENE INSULATED PVC SHEATHED & OVER SHIELDING CABLES CONFORMING TO IS 7098 (PART I)/1988 AND AS AMENDED THEREAFTER WITH ISI MARKING
L.T. CABLES 3 CORE 1.5 Sqmm 1.1 KV GRADE ARMOURED COPPER CONDUCTOR CROSS LINKED POLY ETHYLENE INSULATED PVC SHEATHED & OVER SHIELDING CABLES CONFORMING TO IS 7098 (PART I)/1988 AND AS AMENDED THEREAFTER WITH ISI MARKING
Junction & Instrument Box
Terminator
Ferrule & Consumables(end terminal, glands, crimping & tools)
Laying of field control, power and signal Cable for the filed instruments like, level transducer, pressure transducer, Electromagnetic flow meter, Valve Actuator, Winding Temperature sensor, Vibration Sensor, Bearing Temperature Sensor, Pump Seal Temperature, Water Quality Analyser, Water Quality Sensor probe, Solar Panel, GSM-GPRS communication unit and battery bank etc., with suitable lugs, ferrules, tags, glands along with mounting accessories excluding GST.
Add GST @ 18%
stage.html
html • 0.04 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid