Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹54.9 LAccepted-Finance | L1 | Accepted-Finance L1 | |
| 2 | L2₹57.2 L+₹2.2 L (4.09%)Rejected-Finance | L2 | Rejected-Finance L2 | |
| 3 | L3₹63.7 L+₹8.7 L (15.9%)Rejected-Finance | L3 | Rejected-Finance L3 | |
| 4 | Rejected-Technical | - | Rejected-Technical Didnot Submit all the requisite documents as per NIT |
Tender Value
₹73.3 L
EMD Value
₹2.2 L
Closing Date
30 Jun 2025, 6:00 pmClosed
Niranjan Kumar, Manager(E-C), RHQ, NER
O/o RED, New Building, 1st Floor, RHQ, NER, Guwahati-15
Modification of Office Cubicles at RHQ, NER, Guwahati 2024 25 Civil and Electrical works
2025_AAI_235404_1
AAI/NER/SM(E-C)/Ghy/Office Cubicles/24-25
Open Tender
Civil Works - Buildings
Item Rate
180 days
RHQ, NER, Guwahati
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,180
₹2.2 L
29 Jul 2025
28 May 2025
2 Jul 2025
29 May 2025
30 Jun 2025
29 May 2025
29 May 2025 - 4 Jun 2025
Amount
Civil Work
Providing and fixing ISI marked flush door shutters conforming to IS : 2202 (Part I) non?decorative type, core of block board construction with frame of 1st class hard wood and well matched commercial 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters: 35 mm thick including ISI marked Stainless Steel butt hinges with necessary screws
Providing and fixing ISI marked flush door shutters conforming to IS : 2202 (Part I) non?decorative type, core of block board construction with frame of 1st class hard wood and well matched commercial 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters: 30 mm thick including ISI marked Stainless Steel butt hinges with necessary screws
Extra for providing vision panel not exceeding 0.1 sqm in all type of flush doors (cost of glass excluded) (overall area of door shutter to be measured)
Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete.
Providing and fixing bright finished brass hanging type floor door stopper with necessary screws, etc. complete.
Providing and fixing aluminium die cast body tubular type universal hydraulic door closer (having brand logo with ISI, IS : 3564, embossed on the body, door weight upto 35 kg and door width upto 700 mm), with necessary accessories and screws etc. complete.
Providing and fixing chromium plated brass 100 mm mortice latch and lock with 6 levers and a pair of lever handles of approved quality with necessary screws etc. complete.
Providing and fixing partition upto ceiling height consisting of G.I. frame and required plywood, including providing and fixing of frame work made of special section power pressed/ roll form G.I. sheet with zinc coating of 120 gms/sqm(both side inclusive), consisting of floor and ceiling channel 50mm wide having equal flanges of 32 mm and 0.50 mm thick, fixed to the floor and ceiling at the spacing of 610 mm centre to centre with dash fastener of 12.5 mm dia meter 50 mm length or suitable anchor fastener or metal screws with nylon plugs and the studs 48 mm wide having one flange of 34 mm and other flange 36 mm and 0.50 mm thick fixed vertically within flanges of floor and ceiling channel and placed at a spacing of 610 mm centre to centre by 6 mm dia bolts and nuts, including fixing of studs along both ends of partition fixed flush to wall with suitable anchor fastener or metal screws with nylon plugs at spacing of 450 mm centre to centre, and fixing of boards to both side of frame work by 25 mm long dry wall screws on studs, floor and ceiling channels at the spacing of 300 mm centre to centre. The boards are to be fixed to the frame work with joints staggered to avoid through cracks, M.S. fixing channel of 99 mm width (0.9 mm thick having two flanges of 9.5 mm each) to be provided at the horizontal joints of two boards, fixed to the studs using metal to metal flat head screws, including jointing and finishing to a flush finish with recommended jointing compound, jointing tape, angle beads at corners (25 mm x 25 mm x 0.5 mm), joint finisher and two coats of primer suitable for board as per manufacture’s specification and direction of engineer in charge all complete. 74 mm overall thickness partition with 12.0 mm thick double skin fire retardant plywood conforming to IS: 5509
Providing & Fixing decorative high pressure laminated sheet of plain / wood grain in gloss / matt/ suede finish with high density protective surface layer and reverse side of adhesive bonding quality conforming to IS : 2046 Type S, including cost of adhesive of approved quality. 1.0 mm thick
Deduct for not using 20 mm thick cement mortar 1:4 (1 cement : 4 coarse sand) bedding in laying of floor tiles and jointing with grey cement slurry @ 3.3 kg/ sqm
Fixing glazed/ Ceramic/ Vitrified floor tiles with cement based high polymer modified quick?set tile adhesive (Water based) conforming to IS: 15477, in average 3mm thickness.
Providing and laying full body vitrified tile in floor of minimum thickness 15 mm with water absorption less than 0.06% and conforming to IS:15622, of approved make, brand and manufacturer, laid on 20 mm thick base cement mortar 1:4 (1 cement: 4 coarse sand) jointing with grey cement slurry @3.30 kg / sqm including grouting the joints with white cement and matching pigments etc. The slab must be cut with the zero chipping diamond cutter only. Laying of slab will be done with the help of notch trowel, wedge, clips of required thickness, vacuum cups for lifting, leveling system and rubber mallet for placing the slab gently and easily. Size of tile 800x2400mm of all colours and shades.
Providing and fixing tiled false ceiling of specified materials of size 595x595 mm in true horizontal level, suspended on inter locking metal grid of hot dipped galvanized steel sections ( galvanized @ 120 grams/ sqm, both side inclusive) consisting of main “T” runner with suitably spaced joints to get required length and of size 24x38 mm made from 0.30 mm thick (minimum) sheet, spaced at 1200 mm center to center and cross “T” of size 24x25 mm made of 0.30 mm thick (minimum) sheet, 1200 mm long spaced between main “T” at 600 mm center to center to form a grid of 1200x600 mm and secondary cross “T” of length 600 mm and size 24x25 mm made of 0.30 mm thick (minimum) sheet to be interlocked at middle of the 1200x600 mm panel to form grids of 600x600 mm and wall angle of size 24x24x0.3 mm and laying false ceiling tiles of approved texture in the grid including, required cutting/making, opening for services like diffusers, grills, light fittings, fixtures, smoke detectors etc. Main “T” runners to be suspended from ceiling using GI slotted cleats of size 27 x 37 x 25 x1.6 mm fixed to ceiling with 12.5 mm dia and 50 mm long dash fasteners, 4 mm GI adjustable rods with galvanised butterfly level clips of size 85 x 30 x 0.8 mm spaced at 1200 mm center to center along main T, bottom exposed width of 24 mm of all T-sections shall be pre-painted with polyester paint, all complete for all heights as per specifications, drawings and as directed by Engineer-in-charge. GI Metal Ceiling Lay in plain Tegular edge Global white colour tiles of size 595x595 mm, and 0.5 mm thick with 8 mm drop; made of G I sheet having galvanizing of 100 gms/sqm (both sides inclusive) and electro statically polyester powder coated of thickness 60 microns (minimum), including factory painted after bending.
Providing and Fixing 15 mm thick densified tegular edged eco friendly light weight calcium silicate false ceiling tiles of approved texture of size 595 x 595 mm in true horizontal level, suspended on inter locking metal grid of hot dipped galvanised steel sections (galvanising @ 120 grams per sqm including both side) consisting of main ‘T’ runner suitably spaced at joints to get required length and of size 24x38 mm made from 0.33 mm thick (minimum) sheet, spaced 1200 mm centre to centre, and cross “T” of size 24x28 mm made out of 0.33 mm (Minimum) sheet, 1200 mm long spaced between main’T’ at 600 mm centre to centre to form a grid of 1200x600 mm and secondary cross ‘T’ of length 600 mm and size 24 x28 mm made of 0.33 mm thick (Minimum) sheet to be inter locked at middle of the 1200x 600 mm panel to from grid of size 600x600 mm, resting on periphery walls /partitions on a Perimeter wall angle pre-coated steel of size(24x24X3000 mm made of 0.40 mm thick (minimum) sheet with the help of rawl plugs at 450 mm centre to centre with 25 mm long dry wall screws @ 230 mm interval and laying 15 mm thick densified edges calicum silicate ceiling tiles of approved texture in the grid, including, cutting/ making opening for services like diffusers, grills, light fittings, fixtures, smoke detectors etc., wherever required. Main ‘T’ runners to be suspended from ceiling using G.I. slotted cleats of size 25x35x1.6 mm fixed to ceiling with 12.5 mm dia and 50 mm long dash fasteners, 4 mm G.I. adjustable rods with galvanised steel level clips of size 85 x 30 x 0.8 mm, spaced at 1200 mm centre to centre along main ‘T’, bottom exposed with 24 mm of all Tsections shall be pre-painted with polyster baked paint, for all heights, as per specifications, drawings and as directed by Engineer-in-Charge.
Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete.
Wall painting with acrylic emulsion paint, having VOC (Volatile Organic Compound) content less than 50 grams/ litre, of approved brand and manufacture, including applying additional coats wherever required, to achieve even shade and colour. Two coats
Renewing glass panes, with wooden fillets wherever necessary: Float glass panes of nominal thickness 4 mm (weight not less than 10kg/sqm)
Providing and laying APP (Atactic Polypropylene Polymer) modified prefabricated five layer 3 mm thick water proofing membrane, black finished reinforced with non-woven polyester matt consisting of a coat of bitumen primer for bitumen membrane @ 0.40 litre/sqm by the same membrane manufacture of density at 25°C, 0.87-0.89 kg/ litre and viscocity 70-160 cps. Over the primer coat the layer of membrane shall be laid using Butane Torch and sealing all joints etc, and preparing the surface complete. The vital physical and chemical parameters of the membrane shall be as under : Joint strength in longitudinal and transverse direction at 23°C as 650/ 450N/ 5cm. Tear strength in longitudinal and transverse direction as 300/250N. Softening point of membrane not less than 150°C. Cold flexibility shall be upto -2°C when tested in accordance with ASTM, D - 5147. The laying of membrane shall be got done through the authorised applicator of the manufacturer of membrane : 3 mm thick
Dismantling aluminium/ Gypsum partitions, doors, windows, fixed glazing and false ceiling including disposal of unserviceable material and stacking of serviceable material with in 50 meters lead as directed by Engineer-in-charge
Providing and fixing glazing in wooden door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket/grooves/rebate etc. complete as per the architectural drawings and the directions of engineer-in-charge . With toughened glass panes of 12 mm thickness
Providing and fixing double action hydraulic floor spring of approved brand and manufacture conforming to IS : 6315, having brand logo embossed on the body / plate with double spring mechanism and door weight upto 125 kg, for doors, including cost of cutting floors, embedding in floors as required and making good the same matching to the existing floor finishing and cover plates with brass pivot and single piece M.S. sheet outer box with slide plate etc. complete as per the direction of Engineer-in-charge. With stainless steel cover plate minimum 1.25 mm thickness
Grading roof for water proofing treatment with With float glass panes of 5 mm thickness (weight not less than 12.50 kg/sqm) Cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size)
ELECTRICAL WORKS
SH: I Internal Wiring and Light Fixtures
Wiring for circuit/submain wiring along with earth wire with the following sizes of FRLSH PVC insulated copper conductor, single core cable in surface/recessed medium class PVC conduit as required.
a) 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire
b) 2 X 2.5 sq.mm + 1 X 2.5 sq.mm earth wire
c) 2 X 4sq.mm + 1 X 4sq.mm earth wire
Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated cooper conducter single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5sq.mm FRLS PVC insulted cooper conductor single core cable etc. as required. Group C
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. (For LAN & Telephone circuit)
Supplying and fixing of 6 Module (200mmX75mm) , GI box alongwith modular base & cover plate for modular switches in recess etc. as required.
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.
a) 5/6 A switch
b) 15/16 A switch
c) 3 pin 5/6 A socket outlet
d) 6 pin 15/16 A socket outlet
e) Telephone socket outlet
Supplying and fixing 6 amps to 32 amps rating, single pole, 240 volts/415V,10KA "C" series, miniature circuit breaker suitable for inductive loads of Single pole in the existing DB complete with connections, testing and commissioning etc. as required.
Supplying and fixing of single pole blanking plate in the existing MCB DB complete as required.
Supply of recess mounted 18/20W, round LED luminaries having minimum efficacy of 100 lumens/watt, minimum CRI of 80, T.H.D.of less than 10%, IP20 or higher, inbuilt surge protection of more than 2kV, power factor of more than 0.95, efficiency of driver should be greater than 85%, IK rating should not be less than 04, Unified Glare index should be lesser than or equal to 19, CCT of 5000-6500K made out of powder coated CRCA/Extruded Aluminium housing suitable to operate on voltage range 140V-270V, 50Hz single phase AC supply etc. complete with all accessories as required
Supply of 2ft X 2ft, 36Watts, Recess mounted LED luminaries having minimum efficacy of 100 lumens/watt, CRI of 80, T.H.D.of less than 10%, IP20 or higher, inbuilt surge protection of more than 2kV, power factor of more than 0.95, efficiency of driver should be greater than 85%, IK rating should not be less than 04, Unified Glare index should be lesser than or equal to 19, CCT of 5000-6500K made out of powder coated CRCA/Aluminium housing with opal/acrylic diffuser suitable to operate on voltage range 140V-270V, 50Hz single phase AC supply etc. complete with all accessories as required
Supply and fixing of 2 ft. LED batten with 20 W LED tube, premium metallic grey finish for glare free soothing light minimum efficacy of 100 lumens/watt, CRI of 80, T.H.D.of less than 10%, IP20 or higher, inbuilt surge protection of more than 2kV, power factor of more than 0.95, efficiency of driver should be greater than 85%, IK rating should not be less than 04, CCT of 5000-6500K made out of powder coated CRCA/Aluminium housing with opal/acrylic diffuser suitable to operate on voltage range 140V-270V, 50Hz single phase AC supply etc. complete with all accessories as required as per actual site requirements.
Installation, testing and commissioning of 2ft X 2ft 36Watts- Recess mounted LED complete with all accessories including modification/cutting/finishing of existing cutouts of gysum false ceiling to install the new fittings, also provide GI wire/chain to each corner to ceiling for safety purpose, connection with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. complete as required as per actual site requirements.
Installation, testing and commissioning of recess mounted 18/20W- round LED complete with all accessories including modification/cutting/finishing of existing cutouts of gysum false ceiling to install the new fittings, connection with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. complete as required as per actual site requirements.
Supply and fixing of Wall mounted fan of 400mm sweep size with Aerodynamically designed & balanced blades, heavy duty motor with inbuilt thermal overload protection with tilting facility and speed control provision, power cord (standard length) with 5/6A plug top etc suitable for operation on 230V, 50Hz, AC supply
Supplying and fixing suitable size GI box with modular plate and cover on surface or in recess, including providing and fixing of RJ-45 flush mounted information outlets connection etc. as required.
Supply of following sizes LT power cables of 1.1 KV grade aluminium conductor XLPE insulated and PVC sheathed armoured cable confirming to IS 7098 Part I-1988 with upto date amendment as required.
3.5C x 50 sq. mm.
Supply of following sizes of HDPE (High Density Polyethylene) pipe of grade PE80, PN6 ISI marked conforming to IS 4984:1995, complete as required.
Laying of DWC/HDPE (High Density Polyethylene) upto 110mm dia duct direct in ground up to a depth of 75 cm including cutting, providing accessories like couplers and adhesive/solvent for jointing, excavation and refilling the trench etc. complete as required.
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray / wall surface as required.
Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp)
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required.
3.5 x 50 Sqmm.
Dismantling of existing 1.5 TR / 2.0 TR/ 3.0 TR Capacity, Single Phase Split type Air Conditioner units from different locations at old RHQ building including dismantling the indoor, outdoor unit, other accessories, piping etc. safely and shifting to AAI Store etc. as required.
Dismantling of existing light point/fan point/exhaust fan point/ call bell point from different locations at old RHQ building including other accessories etc safely and shifting to AAI Store etc. as required.
Dismantling of existing light /fan /exhaust fan / call bell from different locations at old RHQ building including other accessories etc safely and shifting to AAI Store etc. as required.
SH:II VRF/VRV air conditioning system
OUTDOOR UNIT Design, Supply, Installation, Testing & Commissioning of modular type Variable Refrigerant Flow/ Variable Refrigerant Volume air cooled Outdoor units suitable for cooling and heating, having all hermetically sealed inverter type Scroll Compressor(s), minimum two compressors for above 14 HP modules, microprocessor based Controller, top discharge type condensing unit(s), with R 410 A Refrigerant, vibration isolators, with suitable foundation etc. complete as required. The unit shall deliver the rated capacity at AHRI Conditions and work even at 50°C ambient temperature without tripping. The unit shall be suitable to work on 400V +/- 10%, 3 Phase, 50Hz AC power supply. The unit shall be filled with first charge of the refrigerant and ready for use as required. The COP at AHRI conditions shall not be less than 3.1 and IEER not less than 6.5, item includes providing suitable MS supports/base frame including vibration pads, cutting, fabrication, painting as per approved manufactures drawing complete as required.
not less than 28 HP ODU
INDOOR UNIT-CASSETTE TYPE Supply, installation, testing and commissioning of following minimum capacity 4-way flow VRV/VRF Cassette Type Indoor ceiling mounted unit equipped with synthetic washable media pre-filter, fan section with low noise fan/dynamically balanced blower, multispeed motor, coil section with DX Copper coil, electronic expansion valve, outer cabinet, drain pump, grill, necessary supports, vibration isolation, cord less remote control etc., suitable for operation on single phase 230 V ± 10%, 50Hz AC supply, complete, as required. The unit shall have automatic force shut down provision in case of fire on receiving signal from BMS System. The cooling capacity of indoor unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature. (Arrangement for providing MS supports where RCC roof is not available shall be executed in separate item)
not less than 2 TR
INDOOR UNIT-HIGH WALL TYPE Supply, installation, testing and commissioning of following minimumcapacityVRV/VRFHighwall type Indoor unit equipped with wash able synthetic media pre-filter, fan section with low noise fan/dynamically balanced blower, multispeedmotor, coil section with DX copper coil, electronic expansion valve, outer cabinet, cord less remote control, drainpan, necessary accessories etc., suitable for operation on 230 V ± 10%, 50Hz, single phase AC supply, complete as required. The unit shall have automatic force shut down provision in case of fire on receiving signal from BMS System.The cooling capacity of indoor unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature.
Supply, Installation, testing and commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft/hard drawn copper refrigerant piping for VRV/VRF system, complete with fittings, with suitable adjustable ring type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O tubular insulation/with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of specified thickness as given below for Suction and Liquid lines, all accessories as per specifications etc. as required-
6.4 mm dia soft drawn with 19 mm dia tube insulation
9.5 mm dia soft drawn with 19 mm dia tube insulation
12.7 mm dia soft drawn with 19 dia mm tube insulation
15.9 mm dia soft drawn with 19 dia mm tube insulation
19.1 mm dia Hard drawn with 19 mm dia tube insulation
22.2 mm dia Hard drawn with 19 dia mm tube insulation
28.6 mm dia Hard drawn with 19 dia mm tube insulation
31.8 mm dia Hard drawn with 19 dia mm tube insulation
34.9 mm dia Hard drawn with 19 dia mm tube insulation
Supply,installation,testing and commissioning of 2C x 1.5 sqmm copper conducter flexible cable laying in PVCcunduit with bent, tee as require for communication beetween VRV IDU and ODU and also for Central remote controlling system.
Refrigerant gas R410 Supply, charging of Refrigerant gas- R410a in additional Cu-piping as required.
Supply,installation,testing and commissioning of PVC drain pipes density 10Kg/m3 complete with fittigs like elbows, tees, reducers, bends, flanges, supports with 6 mm thick class - O nitrile rubber insulatiions complete with supports as per drawings and specifications of below sizes make - as per ability.
32 mm dia
15.9 mm dia PVC nylon braided pipe
Supply, Fabrication, and Welding of Suitable-Size MS Structural Support for VRV IDU Installation. MS sections of appropriate size and grade, including angles, channels, and plates.Fabrication of MS structural support, ensuring accurate cutting, shaping, and drilling to meet project requirements. (For CASSETTE TYPE AC)
M/S Arya Enterprise (BID ID -867414)
Jagat jyoti Chetia (BID ID -864993)
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .